37180G
APPLICATIONS
The 2nd Generation of genset controls is designed to
provide a maximum of flexibility in a user friendly and
intuitive design with a large graphical display for various
applications. This controller is one of a series of new and
powerful genset controls (easYgen). This trend-setting
technology offers a maximum of flexibility for each user.
New technologies included are:
FlexAppTM - This intelligent and flexible feature provides
the tools to easily configure for multiple applications. The
user can configure the easYgen-1000 Series for use as
Measuring transducer/engine control [0-CB-Mode {0}]
for start/stop and measuring conversion
1-breaker-control [GCB open, {1o}]
above plus engine/generator protection
1-breaker-control [GCB open/close, {1oc}]
above plus stand-by power applications
2-breaker-control [GCB/MCB open/close, {2oc}]
above plus AMF, and open transition applications
DynamicsLCDTM - The graphical LCD provides softkeys
that vary depending on application and operation.
FlexInTM - The two analog inputs can be freely configured
(adaptable for each type of sensor) by the user as:
VDO (0 to 180Ohm [0 to 5bar/0 to 10bar]; 0 to 380Ohm [40 to
120C/50 to 150C]; 0 to 180 Ohm [0 to 100% level]; isolated (2pole) and non-isolated (1-pole) ground senders only)
Resistive input (Pt100 / linear 2point / user-defined 9point)
FlexAppTM Technology
Flexible and
multifunctional
DynamicsLCDTM
DESCRIPTION
AMF/loss of mains
auto start/stop
I/Os
Complete engine,
generator, and mains
protection in one unit
Protection
Features
FlexAppTM Technology (4 application modes)
DynamicsLCDTM - 12864 pixel graphical interactive LC display with softkeys
Start/stop logic for Diesel/Gas engines
Engine pre-glow or purge control
kWh meter, kvarh meter
Operating hours/start/maintenance counters
Configurable trip levels/delays/alarm classes
Push-buttons (softkeys) for direct control
PC and/or front panel configurable
Multi-level password protection
Multi-lingual capability (10 languages in 1 unit configurable: English, German, French, Italian, Spanish, Portuguese, Russian, Turkish, Chinese, Japanese)
Differentiation
Current input as ../5 A (standard) or ../1 A
SPECIFICATIONS
Power supply.................................................. 12/24 Vdc (6.5 to 40.0 Vdc)
Intrinsic consumption ................................................................max. 15 W
Ambient temperature (operation) ..................... -20 to 70 C / -4 to 158 F
Ambient temperature (storage) ...................... -30 to 80 C / -22 to 176 F
Ambient humidity.................................................... 95 %, non-condensing
Voltage .............. (both ranges within one unit on different terminals, /)
100 Vac [1]
Rated (Vrated)..........................................69/120 Vac
Max. value (Vmax)..........................................86/150 Vac
Rated (Vphase-ground)...............................................150 Vac
Rated surge volt.(Vsurge)..................................................2.5 kV
and 400 Vac [4]
Rated (Vrated)........................................277/480 Vac
Max. value (Vmax)........................................346/600 Vac
Rated (Vphase-ground)...............................................300 Vac
Rated surge volt.(Vsurge)..................................................4.0 kV
Accuracy ........................................................................................ Class 1
Measurable alternator windings ....................3p-3w, 3p-4w, 1p-2w, 1p-3w
Setting range..................... primary...............................50 to 650,000 Vac
Linear measuring range ..............................................................1.25Vrated
Measuring frequency..............................................50/60 Hz (40 to 70 Hz)
Input resistance per path................................... [1] 0.498 M, [5] 2.0 M
Max. power consumption per path ...............................................< 0.15 W
Current
Rated (Irated)............................ [1] ../1 A or [5] ../5 A
Linear measuring range .............................Igen = 3.0Irated, Imains = 1.5Irated
Burden........................................................................................ < 0.15 VA
Rated short-time current (1 s) .................................[1] 50Irated, [5] 10Irated
DIMENSIONS
219 mm
185 mm
171 mm
136 mm
58 57 56 55 54 53 52 51 50
61 mm
50 mm
49 48 47 46 45 44 43 42 41 40 39 38 37 36 35 34 33 32 31 30
NOTE
Connected inductances (e.g. coils of operating current
or undervoltage tripping devices, auxiliary contactors
and power contactors) must be wired with an appropriate
interference protection.
WARNING
Before disconnecting the current transformer/CT secondary
connections or the connections of the current transformer/CT
at the device, ensure that the current transformer/CT
is short-circuited.
Dimensions
Cutout [WxH]:186 x 138 mm
Total [WxHxD]: 219 x 171 x 61 mm
1 2 3 4 5 6 7 8 9
PC
Configuration
Port
Back view
2006-09-05 | easYgen-300 Dimensions eYg300ww-3606-ab.skf
10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29
Rated PT secondary
FlexRangeTM
69/120 Vac
and
277/480 Vac
Rated CT
secondary
../5 A
Part Number
(P/N)
8440-1809
../1 A
8440-1810
Description
EASYGEN-1500-55B
EASYGEN-1500-51B
Right view
Drive
Sensor
48
Sensor
CAN-H
FlexCAN
FlexApp / DynamicsLCD
CAN bus
CAN-L
Pickup
switching/inductive
FlexIn
only connection
for two-pole
sensors is
shown below:
11 12 13 9 10 3 4
WIRING DIAGRAM
Model easYgen-1500
- P/N 8440-1750 = ../5 A
- P/N 8440-1751 = ../1 A
3
1
Relay [R11]
- LogicsManager or
- Ready for operation
Generator voltage N
Relay [R10]
- LogicsManager or
- "Command: close GCB"
120 Vac
FlexApp
GCB
Relay [R7]
- LogicsManager or
- "Command: open GCB"
{2oc}
Mains voltage L1
120 Vac
120 Vac
480 Vac
FlexRange
14 15 16 17 18 19 20 21 1 2
Mains current L1 or
Ground current
120 Vac
480 Vac
120 Vac
{2oc}
Mains voltage L2
{2oc}
Mains voltage L3
{2oc}
Mains voltage N
MCB
FlexApp
480 Vac
S/S
{2oc}
GND
{1oc}
Relay [R8]
- LogicsManager or
- "Command: close MCB"
G
S/S
Relay [R9]
- LogicsManager or
- "Command: open MCB"
Common
../1 A or ../5 A
{1o}
Generator voltage L3
480 Vac
GND
G
S/S
LogicsManager
FlexRange
{0}
120 Vac
480 Vac
G
S/S
8
7
6
5
4
3
2
1
NO/NC#1
NO/NC#1
NO/NC#1
NO/NC#1
Generator current L3
480 Vac
GCB
48 49 50 51 52 53 54 55 56 57 58 30 31 32 33 34 35 36 37 38 39 40 41 42 43 44 45 46 47
Generator current L2
../1 A or ../5 A
open/close
../1 A or ../5 A
G
120 Vac
open/close
Generator current L1
120 Vac
Generator voltage L2
GCB
LogicsManager
../1 A or ../5 A
Generator voltage L1
480 Vac
open
8 22 23 24 25 26 27 28 29
GCB
480 Vac
5 6 7
1 2
MCB
NO/NC#1
NO/NC#1
NO/NC#1
NO/NC#1
#2Battery
Battery
FEATURES OVERVIEW
International
Woodward
PO Box 1519
Fort Collins CO, USA
80522-1519
1000 East Drake Road
Fort Collins CO 80525
Ph: +1 (970) 482-5811
Fax: +1 (970) 498-3058
Europe
Woodward GmbH
Handwerkstrasse 29
70565 Stuttgart, Germany
Ph: +49 (0) 711 789 54-0
Fax: +49 (0) 711 789 54-100
email: stgt-info@woodward.com
Distributors & Service
Woodward has an international
network of distributors and
service facilities. For your nearest representative, call the Fort
Collins plant or see the Worldwide Directory on our website.
www.woodward.com/power
Woodward
All Rights Reserved
37180G - 2007/5/Stuttgart
easYgen-1500
Configured as ...
{0}
{1o}
No CB
control
Measuring
Generator voltage (3phase/4-wire)
- true rms
- FlexRangeTM
{1oc}
{2oc}
1 CB control 2 CB control
1 CB control
(GCB
(GCB / MCB
(GCB open)
open / close) open / close)
9
9
9
9
9
(9)#2
(9)#2
(9)#2
(9)#2
(9)#2
9
9
9
9
9
(9)#2
(9)#2
(9)#2
(9)#2
(9)#2
9
9
9
9
9
(9)#2
(9)#2
(9)#2
(9)#2
(9)#2
9
9
9
9
9
9
9
9
9
9
0
9
1
9
9
9
2
9
9
9
9
9
9
9
9
9
9
9
9
9
300
9
9
9
9
9
9
300
9
9
9
9
9
9
300
9
9
9
9
9
9
300
9
(9)#6
(9)#6
(9)#6
(9)#6
(9)#6
(9)#6
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
8
8
2
9
9
9
8
7
2
9
9
9
7
6
2
9
9
9
5
4
2
9
9
9
9
9
9
9
9
9
9
9
9
9
9