Michigan Street
P.O. Box 423, Milwaukee, WI 53202
Code No. LIT-1900038
tmx1600
1900038
9thcc:na
FMS
pending
Rev:
020100
logo:
TMx
left ft:
Room Sensor
right ft:
standard
Sect# = 0
seQ# = 28
Tmx.tif
receive data over a communication network
from a remote controller. All controllers used
with the TMx1600 must be configured using
HVAC PRO Release 8.01 or later.
Applications
TMZ models:
- UNT controllers
- VAV controllers, Revision D or later
Features
- VMA1200
Description
The TMx1600 is a user-friendly room sensor
with an easy-to-read display and compact
styling. It features room comfort at the touch of
a button, and a Liquid Crystal Display (LCD)
for convenient feedback on changing room
conditions. The TMx1600 is available in two
separate models:
TMZ1600: communicates on the Zone Bus,
and connects to Unitary (UNT), Variable Air
Volume (VAV), and VAV Modular
Assembly (VMA) controllers via phone jack
connections
TMS1600: communicates on the Service
Bus and connects to TC-9102 fan coil
controllers via screw terminal connections
To Order
Specify the code number from the following
selection chart.
Selection Chart
Code
Number
Description
AP-TMZ1600-0
AP-TMS1600-0
Accessories
Code Number
Description
ACC-INSL-0 (a)
Specifications
ACC-INSL-1 (a)
TE-6400-603
T-4000-119
Storage Environment
10 mA maximum
Housing Material
Housing Protection
IP 30 (IEC 529)
Dimensions
Override Button
Momentary contact
Mode Indicator
Red LED
Temperature
Sensor
Sensor Type:
Fenwal NTC
Range:
0 to 37.7C (32 to 99.9F)
TMS1600 Reference Resistance: 30000 ohm at 25C (77F)
Accuracy:
+/-0.2C (0.3F) at 21.1C (70F)
+/-0.6C (1F) at 0C to 50C (32 to 122F)
HVAC PRO for Windows Release 8.01 or later (part of M-Tool Rel. 2.0
[MW-MTool-0])
Interface (TMZ1600 only) AS-CBLPRO-1 or later (use with Zone Terminal Unit)
Agency Compliance
Description
Preconfigured Cables
Sensor Type:
Nickel PTC
Range:
0 to 50C (32 to 122F)
TMZ1600 Reference Resistance: 1000 ohm at 21.1C (70F)
Accuracy:
+/-0.2C (0.3F) at 21.1C (70F);
+/-0.6C (1F) at 0C to 50C (32 to 122F)
Software
CBL-STAT25-SW/WC (a)
Preconfigured 8-pin
cable, 7.62 m (25 ft)
CBL-STAT50-SW/WC (a)
Preconfigured 8-pin
cable, 15.24 m (50 ft)
CBL-STAT75-SW/WC (a)
Preconfigured 8-pin
cable, 22.86 m (75 ft)
CBL-STAT100-SW/WC (a)
Preconfigured 8-pin
cable, 30.48 m (100 ft)
Cable Components
CBL-24/8NAT-SW/WC (a)
S100710
S104012
Premium/economy
crimp tool
S104020
The performance specifications are nominal and conform to acceptable industry standards. For applications at conditions beyond t hese specifications, consult the local Johnson
06/01 Johnson Controls, Inc
Controls office. Johnson Controls, Inc. shall not be liable for damages resulting from misapplication or misuse of its products.