Escolar Documentos
Profissional Documentos
Cultura Documentos
Authorized licensed use limited to: UNIVERSITATSBIBLIOTHEK DORTMUND. Downloaded on September 10, 2009 at 15:49 from IEEE Xplore. Restrictions apply.
2 COORDINATION CONTROLLER
Figure 1 shows the scheme of the proposed controller.
After a load change as a disturbance, the STATCOM
supplies/absorbs required reactive power very quickly
(nearly within 3 msec) to keep the load bus voltage at
the specified value, and then stabilizes at a steady-state
operating point.
In order to make the STATCOM available for further
system changes, the coordination controller forces the
ULTC to activate and be set at a tap position appropriate
to nearly zero STATCOM output, while keeping the
load bus voltage at the desired value.
Figure 2 shows the coordination controller flow
diagram. As can be seen from this figure, a dead zone
block is used to prevent oscillatory operation around the
desired operating point. The Dead Zone block generates
zero output within a specified region, called its dead
zone. The lower and upper limits of the dead zone are
specified as the Start of dead zone and End of dead zone
parameters. The block output depends on the input and
dead zone:
If the input is within the dead zone (greater than
the lower limit and less than the upper limit),
the output is zero.
If the input is greater than or equal to the upper
limit, the output is the input minus the upper
limit.
If the input is less than or equal to the lower
limit, the output is the input minus the lower
limit.
The reference voltage of the power transformer is the
load bus voltage that needs to be kept at a desired value,
for example 1 p.u.. When STATCOM output is nearly
zero, the reference voltage is the load bus voltage,
otherwise, the reference voltage is higher or lower than
the load bus voltage, and hence the ULTC is forced to
compensate the reactive power already supplied by
STATCOM. By each tap changing, STATCOM
decreases its output, so the final reference value
approaches the load bus voltage.
Tap
Coordination
Controller
STATCOM
Load
STATCOM Reactive Power
Authorized licensed use limited to: UNIVERSITATSBIBLIOTHEK DORTMUND. Downloaded on September 10, 2009 at 15:49 from IEEE Xplore. Restrictions apply.
ULTC
Reference
Voltage
Yg/Delta (D1)
47 MVA 120/25 kV
cC
1000 MVA
B3
A
B
C
aA
bB
cC
B4
Three-Phase OLTC
Regulating Transformer
(Phasor Type)
[V1_B4]
V_REF
Phasors
100 MVA
STATCOM1
STATCOM
A
B
C
pow ergui
Trip
Three-Phase
Breaker
Scope1
[m1]
25 kV
18 MW
5 Mvar 1
<Qm (pu)>
m1
Dead Zone
Authorized licensed use limited to: UNIVERSITATSBIBLIOTHEK DORTMUND. Downloaded on September 10, 2009 at 15:49 from IEEE Xplore. Restrictions apply.
A
B
C
120 kV
bB
aA
B
C
25 kV
10 Mvar 1
Tap2
<Tap>
A
B
A
N
Vm (pu)
[V_REF]
Tap2
25 kV
36 MW
10 Mvar
Tap #
-4
-6
-8
20
40
60
Q_STATCOM
80
100
120
20
40
60
V B4 (pu)
80
100
120
20
40
60
V B3 (pu)
80
100
120
20
40
60
Time
80
100
120
1
0
-1
2
1
0
1
0.95
0
-5
-10
20
40
60
Q_STATCOM
80
100
120
20
40
60
V B4 (pu)
80
100
120
20
40
60
V B3 (pu)
80
100
120
20
40
60
Time (Sec)
80
100
120
1
0
-1
2
1
0
1
0.95
Authorized licensed use limited to: UNIVERSITATSBIBLIOTHEK DORTMUND. Downloaded on September 10, 2009 at 15:49 from IEEE Xplore. Restrictions apply.
Tap #
-1
-2
-3
20
40
60
Q_STATCOM
80
100
120
20
40
60
V B4 (pu)
80
100
120
20
40
60
V B3 (pu)
80
100
120
20
40
60
Time
80
100
120
1
0
-1
2
1
0
1
0.95
Figure 6 Operation of STATCOM and ULTC without coordination (with fixed capacitor)
Figure 7 shows the independent operation of
STATCOM and ULTC of the sample network without
the fixed capacitor bank. The initial tap is -4 in order to
provide the required reactive power. At t=20 Sec. the
breaker closes and the bus load increases, and
motivating the STATCOM to operate. STATCOM can
not supply the required reactive power, so ULTC
operates and moves to tap -6. STATCOM output
Tap #
-4
-5
-6
20
40
60
Q_STATCOM
80
100
120
20
40
60
V B4 (pu)
80
100
120
20
40
60
V B3 (pu)
80
100
120
20
40
60
Time
80
100
120
1
0
-1
2
1
0
1
0.95
Figure 7 Operation of STATCOM and ULTC without coordination (without fixed capacitor)
Authorized licensed use limited to: UNIVERSITATSBIBLIOTHEK DORTMUND. Downloaded on September 10, 2009 at 15:49 from IEEE Xplore. Restrictions apply.
Tap #
-4
-4.5
-5
20
40
60
Q_STATCOM
80
100
120
20
40
60
V B4 (pu)
80
100
120
20
40
60
V B3 (pu)
80
100
120
20
40
60
Time (Sec)
80
100
120
0.5
0
-0.5
1.5
1
0.5
1
0.98
0.96
Figure 8 Coordination of STATCOM and ULTC for a light load change (without fixed capacitor)
4 CONCLUSIONS
This paper proposes a new control scheme for the
coordination of a ULTC transformer and a STATCOM
installed at the same bus and has the merit of reserving
the STATCOM operating margin for emergencies. The
proposed coordination controller controls the ULTC in
maximizing the capacity margin of the STATCOM
without increasing the tap operation and improving the
load voltage profile and quality. The coordinated control
avoids ULTC oscillatory operation by applying a dead
zone block.
5 REFERENCES
1. Calovic, M. S., Modeling and analysis of underload tap-changing transformer control system,
IEEE Trans. on Power Apparatus and Systems, vol.
PAS-103, no. 7, pp. 19091915, 1984.
2. Hingorani, N. G. and Gyugy, L., "Understanding
FACTS", Concepts and Technology of Flexible AC
Transmission System. New York: Inst. Elect.
Electron. Eng., Inc., 2000.
3. Paserba, J. J., Leonard, D. J., Miller, N. W.,
Naumann, S. T., Lauby, M. G., and Sener, F. P.,
"Coordination of a distribution level continuously
controlled compensation device with existing
substation equipment for long term var
AUTHOR'S ADDRESS
Dr. Mojtaba Khederzadeh can be contacted at
Electrical Engineering Department,
Power & Water University of Technology,
Tehranpars, Vafadar Bldv.,
P. O. Box: 16765-1719,
Tehran,
IRAN.
Email: khederzadeh@pwut.ac.ir
Authorized licensed use limited to: UNIVERSITATSBIBLIOTHEK DORTMUND. Downloaded on September 10, 2009 at 15:49 from IEEE Xplore. Restrictions apply.