Escolar Documentos
Profissional Documentos
Cultura Documentos
1431
ABSTRACT
The soundness of a power transformer under an operating voltage is evaluated in partial
discharge (PD) test of long-duration induced ac voltage test. The acceptance criterion for
this PD test is 500 pC according to IEC standard; however, few basic data backing this
criterion are available. To establish a clear criterion for this PD test, the authors initially
conducted a study on the harmful PD level of materials themselves constituting the
insulation of an oil-immersed transformer and a gas-filled transformer. This PD level was
evaluated based on the rate of decline in the lightning impulse breakdown voltage using the
insulating materials themselves and the element models simulating the insulating structure
which had been exposed to a PD. Consequently, it emerged that insulations of both types of
transformers were degraded if exposed to a PD of 7,000 pC to 10,000 pC. With the safety
factor for this PD value taken into account considering the long-term operation and the
structural difference of an actual transformer, 5,000 pC was deemed as the harmful PD
level at the PD occurrence position. Subsequently, using a winding model of a transformer,
PD signal propagation characteristics inside the winding were investigated through actual
measurement and analysis. As a result, it was found that the PD having occurred inside the
winding is measured as the signal significantly damped depending on the position of
occurrence. The transmission rate was 2.2% for an oil-immersed transformer and 2.8%
for a gas-filled transformer in the respective lowest cases. What should be controlled in the
PD test of an actual transformer is the value of the harmful PD level at the PD occurrence
position multiplied by the transmission rate at the PD detection position. Therefore, the
conclusion was reached that the acceptance criterion in the test should be set to 5,000 pC
2.2% = 110 pC or less for an oil-immersed transformer and 5,000 pC 2.8% = 140 pC or
less for a gas-filled transformer, respectively.
Index Terms Oil-immersed power transformer, gas-filled power transformer, ac test,
partial discharge, insulation degradation, signal transmission rate, harmful partial
discharge level, acceptance criterion.
1 INTRODUCTION
THE insulation performance of a power transformer is
verified by a lightning impulse withstand voltage test and a
long-duration induced ac voltage test [1, 2]. The lightning
impulse withstand voltage test mainly verifies the surge
overvoltage whereas the ac test verifies the normal operating
voltage and temporary overvoltage during operation. Of these,
in the ac test, the partial discharge (hereafter, PD) magnitude is
generally measured [3]. The acceptance criterion for this PD test
is 500 pC according to the IEC standard [1, 2] and 100 pC
according to JEC standard [4, 5], differing from each other with
Manuscript received on 4 October 2011, in final form 14 May 2012.
1432
S. Okabe and G. Ueta: Partial Discharge Criterion in AC Test of Oil-immersedTransformer and Gas-filled Transformer
C2
Insulating bolt
=2 mm
R1 mm
Oil gap
approx. 1 mm
6 mm (bottom in 2 mm
+ 5 sheets in 0.8 mm)
Insulating support
Pressure plate
=80 mm
PD measurement
system
C1
Bushing
Securing ring
Test PB
=100 mm
High voltage plane electrode
ac high voltage
300
5000 pC
10000 pC
15000 pC
20000 pC
50000 pC
250
200
150
100
50
1h2h4h
0
0.1
10
100
1000
80
PD measurement
system
60
C2
PB insulating spacer
2 mm 2 sheets
Bushing
Test PB
ac high voltage
5000 pC
10000 pC
15000 pC
20000 pC
50000 pC
40
20
1h2h4h
0
0.1
10
100
PB spacer
4 mm Oil gap
100
250 mm square
23 mm
3 mm
1433
1 mm
1000
Side view
Particle (copper wire)
1434
S. Okabe and G. Ueta: Partial Discharge Criterion in AC Test of Oil-immersedTransformer and Gas-filled Transformer
100
80
10000 pC
20000 pC
50000 pC
5000 pC
10000 pC
15000 pC
20000 pC
50000 pC
60
40
20
Structure
model
Material
model
1h2h4h
0
0.1
10
100
1000
No damage
120
Black
discoloration
Clouding
100
80
Clouding
Harmful partial discharge
level (7600 pC)
60
40
Black
discoloration
No damage
or clouding
Black
discoloration
20
0
0
Rectangular
copper wire
Not damaged
120
100
100 mm
80
60
Both damaged
40
No spacer damage
(PET damaged)
Black discoloration
on spacer
0
0
PET
damaged
20
Key spacer
Either
Both damaged
damaged
None damaged
1435
4000
8000 12000 16000
Maximum partial discharge (pC)
20000
35 mm
To PD measurement system
Key spacer
4.0 mm
10 mm
Particle of
copper wire
2.2 mm
A-A view on arrow
0.6 mm
PET: 50 m
10 turns (lap winding)
Magnified view
S. Okabe and G. Ueta: Partial Discharge Criterion in AC Test of Oil-immersedTransformer and Gas-filled Transformer
300 pF
Series winding
8300 pF
Shunt winding
Tertiary winding
Core
ERA
or GND
300 pF
ERA
or GND
16500 pF
ERA
or GND
300 pF
Neutral point terminal
(NPT)
400
300
Between windings
Between sections
Against ground
80
60
200
40
100
20
Between sections
1436
PD occurrence position
Figure 11. Relationship between the PD occurrence position and the
transmission rate. The transmission rate is evaluated using both the peak value
at the first peak and the crest value during the period up to 200 s referred to
as full wave. (Left axis: Against ground and between windings, Right axis:
Between sections)
Coupling
terminal
Section 1
NPG-1
300 pF
300 pF
Section 20
Section 40
300 pF
ERA
16500 pF
ERA
Neutral point
terminal, NPT
ERA
1437
Analysis, BgTT
Experiment, BgTT
Analysis, NPT
Experiment, NPT
100
80
60
40
20
0
U-ground
1-2
19-20
39-40
PD occurrence position
Figure 14. Transmission rate of the PD signal occurrence between sections.
1438
S. Okabe and G. Ueta: Partial Discharge Criterion in AC Test of Oil-immersedTransformer and Gas-filled Transformer
Table 1. Harmful PD level at the PD occurrence position and transmission rate of the PD signal to the measurement terminals of an oil-immersed transformer
and a gas-filled transformer.
Type of power
Insulation part
transformer
Main insulation
Oil-immersed
power
transformer
Structure model
10,000 pC
10% or more
Minimum values
H-BgTT: 3.6%
M-BgTT: 2.2%
Section-tosection
Medium
Turn-to-turn
10,000 pC
10,000 pC or more
Minimum value
BgTT: 2.8%
Less than 1.0% in some
cases
REFERENCES
[1]
5 SUMMARY
[2]
[3]
[4]
[5]
[6]
[7]
[8]
[9]
1439