GOVERNMENT OF INDIA
MINISTRY OF RAILWAYS
SPECIFICATION
FOR
220KV /132KV /110KV /100 KV /66KV
DOUBLE POLE, TRIPLE POLE, OUTDOOR
SF6 CIRCUIT BREAKERS
FOR
INDIAN RAILWAY
SPECIFICATION NO TI/SPC/PSI/HVCB/0120
(DECEMBER, 2013)
(REVISION-0)
TRACTION INSTALLATION DIRECTORATE
RESEARCH DESIGNS AND STANDARDS ORGANISATION
MANAK NAGAR LUCKNOW-226011(INDIA)
Prepared By
Checked By
Approved By
Signature
Designation
SSE(SWGR)
ADETI(PSI)
DTI(PSI)
Effective
from
16.04.2014
Page
2 of 44
Table of Contents
Sl.No.
1.
2.
3.
4.
5.
6.
7.
8.
09.
10.
11.
12.
13.
14.
15.
16.
17.
18.
Clause
No.
1.0
2.0
3.0
4.0
5.0
6.0
7.0
8.0
9.0
10.0
11.0
12.0
13.0
14.0
15.0
16.0
17.0
18.0
Description
Scope
Governing Documents
Duties of Circuit Breaker(CB)
Technical Specification
Type and General Condition
Steel Supporting Frame
Foundations
Corrosion Prevention
Parts, Fittings and Accessories
Testing
Deviations
Drawing/Documents
Technical Data and Drawings
Erection, Testing and Commissioning
Spares
Training of Indian Railways Engineers
After Sales Service
Packing and Dispatch
Annexure
NNEXURE-A
ANNEXURE-B
Effective
from
16.04.2014
Page
3 of 44
1. SCOPE
1.1.
This Specification applies to Outdoor Type, Double Pole & Triple Pole
SF6 HV Circuit Breakers for use in Indian Railways Traction Sub
Stations for controlling Power Supply to the 25kV AC 50 Hz single
phase Traction Overhead Equipment and 2x25 kV AC 50 Hz AT
Feeding System for Traction Overhead Equipment (OHE)
1.2.
Specification No.
Description
1.3.
1.4.
IS/IEC/RDSO
Specification
IEC: 62271-100
IEC: 60376(2005)
(iii)
IEC:62271-1(2007)
Description
High voltage Alternating Current Circuit Breakers
Specification and acceptance of new Sulfur
Hexafluoride (SF6) Gas.
Common clauses for High
Voltage Switchgear and Control
Gear standards.
Effective
from
16.04.2014
(iv)
(v)
IS: 456(2000)
IS: 996(2009)
(vi)
IS: 2099(1986)
(vii)
IS: 2544(1973)
(viii)
IS: 5561(1970)
(ix)
IS: 5621(1980)
(x)
IS:13947-Part V :
Sec.1:2004
(xi)
IS:7906(Pt.I-1997)
(xii)
(xiii)
IS:7907(Pt.I-2004)
IS:13118(1991)
(xiv)
IS:1554
(Pt. I-1988)/
IS 694 (2010)
(xv)
IS: 808(1989)
(xvi)
IEC-60529-2001/
IS:13947(Part-1)-1993
& latest
(xvii) RDSO Specification
No. TI/OHE/13 (4/84)
with A & C Slip No.1 to
3
(xviii) RDSO
Specification
No.ETI/OHE/18 (4/84)
with A & C Slip No.1 to
4
(xix) RDSO
Specification
No.M&C/PCN/102/2009
(xx) RDSO
Specification
No.M&C/PCN/110/2006
(xxi) AC Traction manual
2.2.
Page
4 of 44
Effective
from
16.04.2014
Page
5 of 44
3.1.
3.2.
4. TECHNICAL SPECIFICATION
4.1.
(i)
(ii)
(iii)
(iv)
(v)
(vi)
(vii)
(viii)
Particulars
66
100 /110
132
220
Number of poles
Nominal system
voltage(kV)
Highest System
voltage(kV)
Rated insulation level
(a)Rated 1min Dry/wet
power frequency
withstand voltage
2 /3
66
2 /3
100/110
2 /3
132
2 /3
220
72.5
123
145
245
140kV
(rms)
230 kV
(rms)
275 kV
(rms)
460 kV
(rms)
(b)Rated impulse
(1.2/50s) withstand
voltage
Rated
frequency
Rated Normal Current
Rated
short
Circuit
Breaking Current
Rated breaking capacity
(symmetrical)
(i) Two Pole
325 kV
(peak)
550 kV
(peak)
650 kV
(peak)
1050 kV
(peak)
(iii)Three Pole
(ix)
(x)
(xi)
50Hz 3%
1250 A
31.5 kA
1600 A
40.0 kA
1600 A
40.0 kA
2000 A
40.0 kA
2284
MVA
4920
MVA
5800
MVA
9800
MVA
3956
MVA
8522
MVA
10046
MVA
16974
MVA
7.9 kA
(rms)
10 kA (rms)
400 A
10 A
31.5 A
50 A
125 A
Effective
from
16.04.2014
(xii)
(xiii)
(xiv)
(xv)
(xvi)
(xvii)
4.2.
(xviii)
Corona Extinction
Voltage
(xix)
Rating
of
Auxiliary
Switch Contacts
(a) Rated Voltage
Page
6 of 44
10 A
78.8 kA
( peak)
100 kA(peak)
O 0.3 sec CO 3 min CO
Not more than 60 ms
40 kA for 1 sec
31.5 kA
for 1 sec
1.5 for 2
1.5 for 2
1.3 for 4
1.3 for 4
parameters
parameters
parameters
parameters
53 kV
88 kV
106 kV
176 kV
110 V DC
10 A
CLEARANCES
The design of the Circuit Breaker shall be such that when it is erected
on the supporting Structure, the following clearances / distance of
lowest live part of the Circuit Breaker from the ground level or earth
are achieved:
Sl.
No.
1.
2.
3.
100/110
132
220
5500
3500
4000
5000
2500
4.
900
1100
1300
2100
5.
2000
3000
3000
4000
Effective
from
16.04.2014
5.1.
Page
7 of 44
Effective
from
16.04.2014
Page
8 of 44
100/110 132
220
3075
3625
6125
2460
2900
4900
TERMINAL CONNECTORS
(i) The Circuit Breaker shall have Aluminum Terminal pads and
shall be supplied with the Flexible Terminal Connectors as
per RDSO Drawing No. ETI/PSI/1/11030 (Mod G) suitable
for connecting to ZEBRA 28.62 mm ACSR conductors for
66kV, 100/110kV, 132kV and 220kV Circuit Breaker.
(ii) The connectors shall conform to IS:5561 (1978) and design
shall be such, so as to be connected to the equipment
Terminal pads with minimum four 12 mm diameter Bolts,
Nuts, Lock-Nut of Stainless Steel conforming to IS:1570 (Pt.)
(1978) grade 04Cr,17Ni and Mo2 each of these bolts shall
have two flat washers.
Effective
from
16.04.2014
Page
9 of 44
Effective
from
16.04.2014
Page
10 of 44
Effective
from
16.04.2014
Page
11 of 44
any
Effective
from
16.04.2014
Page
12 of 44
5.1.2.20. The Terminal end of all wires shall be provided with numbered
interlock type ferrules which shall be of PVC or other durable
material with markings (numbers) either engraved or punched so as
to be indelible. The ferrules shall be of white color with lettering
thereon black. All wiring shall be properly supported and suitably
protected to avoid rubbing against any metallic part.
5.1.2.21. Terminal blocks of standard type shall be provided in the
operating mechanism cubicle. There shall be insulating barriers
between adjacent terminals. The terminals shall be stud type with
spring washers/self-locking spring loaded type. Suitable dust proof
shrouds of unbreakable transparent material shall be provided on
each Terminal block. The Terminal blocks used for DC and AC
circuits shall be clearly distinguished and separated from each other.
Similarly positive and negative Terminations of the wiring of the DC
Circuit shall be segregated and separated by insulating barriers.
5.1.2.22. The following gauges/switches shall be provided for monitoring
the pressure/density of SF6 gas. The pressure gauge shall have no
oil to avoid leakage. The gauges shall b so positioned as to clearly
and conveniently readable from ground/platform (1500mm to 2000
mm from ground/platform). The density (s) monitor and pressure
gauges shall be common for all the poles of the breaker and these
shall indicate and actuate for any loss of pressure in the Circuit
Breaker.
(i)
(ii)
The steel supporting frame for Circuit Breaker shall be designed with a
factor of safety not less than 2.5 with respect to the yield point under
conditions of maximum loading for a basic wind pressure of 200 kg/m
on 1.5 times the projected area of each member of one face and
taking into account to IS: 808 (1989) and Test certificate shall be
furnished to RDSO.
6.2.
6.3.
Effective
from
16.04.2014
Page
13 of 44
GALVANIZING
The Operating Mechanism Cubical and Steel Supporting Frame shall
be Hot Dip Galvanized in accordance with RDSO Specification
No.ETI/OHE/13 (4/84)with A & C Slip No.1 to 3 and the weight of zinc
coating shall not be less than 1000 gm/m.
8.2.
PAINTING
If the successful Tenderer/Manufacturer is not able to Hot Dip
Galvanize the operating mechanism cubicle and the Steel Supporting
frame as per Clause 8.1, it shall be painted conforming to RDSOs
Specification No. M&C/PCN/ 110/2006 for polyurethane based
aluminum
paint
(three
packs)
and
specification
no.
M&C/PCN/102/2009 for epoxy based zinc phosphate primer (two
packs).
8.3.
FASTENERS
All fasteners of 12 mm diameter and less exposed to atmosphere shall
be of Stainless Steel and those above 12 mm diameter shall be of
preferably Stainless Steel or of Mild Steel Hot Dip Galvanized, to
RDSOs Specification No. ETI/OHE/18(4/84) with A & C Slip No.1 to 4.
The following parts, fittings and accessories shall be provided for each
Circuit Breaker:
i.
ii.
Effective
from
16.04.2014
Page
14 of 44
iii.
iv.
v.
vi.
vii.
viii.
Operation Counters.
ix.
x.
Terminal connectors.
xi.
Earthling Terminals
xii.
xiii.
xiv.
xv.
xvi.
xvii.
Anti-pumping device.
xviii.
Foundation Bolts.
xix.
9.2.
Effective
from
16.04.2014
ii.
iii.
Serial number.
iv.
Rated voltage.
v.
vi.
Rated frequency.
vii.
viii.
ix.
x.
xi.
xii.
xiii.
xiv.
xv.
xvi.
xvii.
xviii.
Maximum
Normal
Alarm
Lock out
xix.
Order reference
xx.
Month/Year of Manufacture
10.TESTING
Page
15 of 44
Effective
from
16.04.2014
Page
16 of 44
10.1. GENERAL
10.1.1.
BEFORE MANUFACTURE OF PROTOTYPE
The successful Tenderer has to offer drawing & design for approval of
RDSO including Quality Assurance Plan (QAP), Schedule of Guaranteed
Performance (SOGP) and Design Calculations as required and
mentioned in the relevant Clauses of Specification.
Only after all submitted documents have been approved and
clearance given to this effect by RDSO, the manufacturer shall take up
manufacture of the prototype for inspection/testing by RDSO. It is to
be clearly understood that if, there are any changes to be done on the
prototype as required by RDSO, same shall be done expeditiously.
10.1.2.
Effective
from
16.04.2014
Page
17 of 44
/DG/TI/ RDSO the cost for the representative(s) having to visit the
works or other place(s) for the tests more than once. The cost as
claimed by the Purchaser /DG/TI/ RDSO ,Lucknow shall be paid
thorough a Demand Draft to the concerned Accounts Officer of the
Purchaser/ Purchaser /DG/TI/ RDSO, Lucknow as shall be advised to
the successful Tenderer/manufacturer.
10.1.4.
The tests shall be conducted on the prototype of the Circuit
Breaker at the works of the successful Tenderer/ manufacturer or at
any reputed testing laboratory in the presence of Purchaser /DG/TI/
RDSO, Lucknow or his authorized representative. The prototype shall
be complete in all respects, including the terminal connectors as would
be supplied if it had passed the tests. The tests shall be conducted as
per relevant governing Specification and as modified or amplified
herein. In case of test being conducted at government test laboratory,
the presence of Purchasers representative for witnessing the test may
be waived off subject to the discretion of the Purchaser /DG/TI/ RDSO,
Lucknow.
10.1.5.
For the tests which are conducted in the laboratories of Central
Power Research Institute, Bhopal/Bangalore, Electrical Research
Development Association, Vadodara or any such testing house or
laboratory a clear certificate to the effect that the equipment has
passed the tests as per the Specification shall be obtained by the
manufacturer and submitted to the Purchaser/DG (TI)/RDSO,
Lucknow. Full details of the tests and the test parameters shall be
furnished along with the test reports.
10.2. Type Tests
The type Tests comprises of:
Sl.No.
i.
ii.
iii.
iv.
v.
vi.
vii.
Description of Test
Mechanical Operation Test
Temperature Rise Tests
Dielectric Tests
a. Rated Lightning Impulse Voltage withstand
Test.
b. Rated One Minute Dry Power Frequency
withstand Voltage Test
c. Rated One Minute wet Power Frequency
withstand Voltage Test
Rated Short Circuit Making and Breaking Capacity
Test (Basic Short Circuit Test duties)
Rated Short Time Withstand Current & Peak
Withstand Current Test
Line Charging Breaking Current Test
Test to prove the rated transient recovery voltage
Refer in
10.2.1
10.2.2
10.2.3
10.2.3.1
10.2.3.2
10.2.3.3
10.2.4
10.2.5
10.2.6
10.2.7
Effective
from
16.04.2014
viii.
ix.
x.
xi.
Page
18 of 44
10.2.8
10.2.9
10.2.10
10.2.11
10.2.1.
10.2.1.1.
10.2.1.2.
Following
checks/
Tests
shall
commencement of operation Test.
be
done
before
the
(i)
(ii)
(iii)
(iv)
(v)
(vi)
(vii)
Effective
from
16.04.2014
(b)
(c)
(d)
Page
19 of 44
10.2.1.3.
10.2.1.4.
(ii)
(iii)
(iv)
(v)
(vi)
(vii)
Effective
from
16.04.2014
Page
20 of 44
10.2.2.1.
On main contact
The temperature rise Test on the main circuit (contacts) and
Terminal Connectors shall be carried out as per clause 4.4.2
Table III of IEC62271-1(2007) or latest. Contact resistance of
the main circuit shall be determined by DC Voltage Drop and
recorded before and after this Test.
10.2.2.2.
Procedure
Unless otherwise specified, temperature rise test on the main
circuit shall be carried out on a new Circuit Breaker in closed
position with clean contacts. The Test shall be carried out with
rated normal current in indoor environment substantially free
from air currents, except those generated by heat from the
Circuit Breaker being tested. Temporary connections to the
Circuit Breaker shall be such that no significant amount of heat
is conducted away from, or conveyed to the Circuit Breaker
during the Test. The temperature rise at the Terminal of main
circuit and the temporary connections at a distance of 1 meter
away from the Terminal shall be measured. The difference of
temperature rise shall not exceed 5C. The type and sizes of
temporary connections shall be recorded in the Test report.
10.2.2.3.
10.2.2.4.
10.2.2.5.
The temperature rise Test on the coils shall be carried out as per
clause 4.4.2 of IEC: 62271-1(2007) or latest.
10.2.2.6.
Procedure
Effective
from
16.04.2014
Page
21 of 44
10.2.3.
Dielectric Tests
Dielectric Tests shall be carried out generally in accordance with
Clause 6.1 of IEC: 62271-1 (2007) or Latest. Humidity and air
density correction factor if less than 1.0 shall not be applied.
The Tests shall be carried out at minimum SF6 Gas
pressure. The Test shall comprise of:
10.2.3.1.
APPLIED
VOLTAGE (kVp)
10.2.3.2.
66
325
APPLIED
VOLTAGE
(KVrms)
10.2.3.3.
Effective
from
16.04.2014
APPLIED
VOLTAGE
(KVrms)
10.2.4.
66
140
100/110
230
&
132
275
Page
22 of 44
220
460
Breaking
Capacity
Test
Withstand
Value of
current &
duration
10.2.6.
31.5 kA (rms)
for 1 second
78.75 kA (peak)
100/110
132
220
10.2.7.
10.2.8.
10.2.9.
Effective
from
16.04.2014
Current
Recovery
Voltage
10.2.10.
66
7.9 kA
rms
144 kV
rms
Page
23 of 44
290 kV rms
490 kV rms
10.2.11.
10.3. Condition of Circuit Breaker during the Tests conducted as per clause
no. 10.2.4, 10.2.5, 10.2.6, 10.2.7, 10.2.8, 10.2.9, 10.2.10 & 10.2.11
of this Specification shall conform as under:
10.3.1.
During these tests the Circuit Breaker shall neither show signs
of excessive distress nor endanger the operator. No disruptive
discharge between energised parts and earth shall occur during
the test. There shall be no indication of significant leakage
current to the earth structure or screens whenever fitted during
the test. The earthed part shall be connected to earth through a
fuse consisting of copper wire of 0.11 mm diameter and 5 cm
length. The fuse wire shall be intact after the test.
10.3.2.
Power frequency
withstand voltage
10.4. The tenderer may quote separately the charges for Short Circuit Test
Duties, Short Time Withstand Current and Peak Current Withstand
Test, Line Charging Breaking Current Tests, Test to Prove Rated TRV,
Effective
from
16.04.2014
Page
24 of 44
Short Line Fault Tests, Out Of Phase Making And Breaking Tests,
Capacitor Bank Breaking Current Test, Measurement of RIV level as
per clause 10.2.4, 10.2.5, 10.2.6, 10.2.7, 10.2.8, 10.2.9, 10.2.10 &
10.2.11. No Test charge shall be payable for any other Test.
10.5. If the prototype of the Circuit Breaker conforming to the Specification
has been approved for earlier supplies to Indian Railways, testing of
prototype again may be waived provided that no changes in the design
and Materials have been made. For this purpose the successful
Tenderer/manufacturer shall approach Purchaser/DG (TI), RDSO
Lucknow with complete documents to ascertain whether the
equipment is identical to the prototype approved earlier. Once
prototype approval is accorded after conducting all or part of the type
tests by RDSO, the prototype approval shall normally be valid subject
to the no changes in the design and Materials.
At the time of renewal of registration, Mechanical Operation Test
as per Clause 10.2.1 shall be carried out.
10.6. Only after written approval of the prototype by Purchaser/DG/TI/,
RDSO Lucknow to the successful tenderer/Manufacturer, they shall
take up bulk manufacture of the Circuit Breaker which shall be strictly
with the same design, material and process as adopted for the
prototype. In no circumstances the material from sources other than
those approved in the design/drawings shall be used for bulk
manufacture.
10.7. During Prototype Inspection, the successful Tenderer/Manufacturer
shall furnish copies of Test Certificate for all the important items
including items listed at Annexure B.
Suitable monogram in the form of engraving/embossing or other
similar means shall be provided on each of these items to identify their
Manufacturer/ source and shall also be verified during inspection.
10.8. Details of the important parts/sub-assemblies and accessories listed at
Annexure B shall be furnished by the successful tenderer/Manufacturer
to DG/(TI), RDSO Lucknow for approval.
Copy of the same shall also be furnished to purchaser along with
SOGP.
10.9. Routine Tests
Every Circuit Breaker shall be subjected to the routine Tests at the
Manufacturers works as per Clause 7 of IEC 62271-100 or latest.
Routine Test reports of items / components used shall be made
available to the inspecting authority whenever required. The routine
Tests comprise
Sl.No.
Refer
Effective
from
16.04.2014
(i)
(iv)
(v)
(ii)
(iii)
10.9.1.
Page
25 of 44
Clause
11.8.1
11.8.2
11.8.3
11.8.4
11.8.5
10.9.2.
10.9.3.
10.9.4.
10.9.5.
Effective
from
16.04.2014
(ii)
Page
26 of 44
of
Electrical
Command
Local
Remote
Local
Remote
should
should
should
should
operate
not operate
not operate
operate
Effective
from
16.04.2014
Page
27 of 44
(ii)
Schematic drawing.
(iii)
Effective
from
16.04.2014
Page
28 of 44
(iv)
ISO certification.
(v)
(vi)
(vii)
(viii)
(ii)
(iii)
(iv)
(v)
(vi)
(vii)
Effective
from
16.04.2014
Page
29 of 44
(viii)
(ix)
(x)
(xi)
(xii)
Plain mass
calculations.
(xiii)
(xiv)
(xv)
(xvi)
concrete
foundation
drawing
and
design
Effective
from
16.04.2014
Page
30 of 44
Effective
from
16.04.2014
Page
31 of 44
The total duration of training for each engineer shall be two weeks of
which approximately one week will be at Manufacturers works and one
week on a railway system or other public utility. If the country of
Manufacturer is not India, the cost to travel to that country and back will
be borne by the Indian Railways. Other details shall be settled at the time
of finalizing the contract/ Purchase order.
17.After sales - service
17.1. The successful tenderer shall make necessary arrangements for closely
monitoring the performance of the Circuit Breaker through periodical
(preferably once in two months during warranty period) visit to the
locations where they are erected for observations and interactions with
operating
and
maintenance
personnel
of
Indian
Railways.
Arrangements shall also be made by the successful tenderer/
Manufacturer for emergency/ stand by spare parts being kept readily
available. To meet exigencies warranting replacements so as to keep
the Circuit Breaker in service with listed on time.
17.2. Successful tenderer/ Manufacturer shall respond promptly to any call
given by Indian Railway for any assistance by way of attending to
failures, investigations into the causes of failures including the Tests, if
any, to be done and such other items with a view to see that the
Circuit Breaker serves for the purpose for which it is procured.
Besides, technical guidance to ensure proper operation and
maintenance of the Circuit Breaker shall be constantly rendered.
18.Packing and dispatch
18.1. The various components of each Circuit Breaker shall be securely
packed in wooden crates/ boxes. General packing list, together with
weight and overall dimensions of each packing case shall be furnished
to purchaser for each Circuit Breaker indicating the following.
Crate/
No.
Box Description
component
crate/ box
of item/ Gross
in
the in kg
weight Approximate
outside
dimensions
Effective
from
16.04.2014
-------------
Page
32 of 44
Effective
from
16.04.2014
Page
33 of 44
Annexure A
Schedule of Guaranteed Performance Technical and other particulars for
66kV, 100kV, 110kV, 132kV, 220kV, Outdoor type, Double Pole/Triple Pole
SF6 Gas Circuit Breakers, guaranteed particulars are to be established by
Test reports/ actual Tests.
S.No.
1.
2.
3.
A.
4.
5.
6.
7.
8.
9.
10.
11.
12.
13.
14.
15.
Description
Unit
Values to
be
supplied
by
tenderer
Makers Name
Country of Manufacture
Manufacturers type Designation & Operating
Mechanism
Rating
Number of poles
Rated voltage
Voltage rating class as per standard
Rated normal current
Rated frequency
Rated insulation level of the Circuit Breaker
(i)
One minute dry and wet power
frequency
withstand voltage
No.
kV
kV
A
Hz
kV (rms)
(ii)
kV (p)
(iii)
kV (p)
(iv)
kV (rms)
kA
(ii)
kA
(iii)
Breaking capacity (symmetrical)
Rated making current
Rated line charging breaking current
Rated cable charging breaking current
Rated small inductive breaking current
Rated capacitor bank breaking current
MVA
kA peak
A
A
A
A
Effective
from
16.04.2014
16.
17.
18.
19.
B
20.
21.
22.
26.
27.
28.
29.
30.
31.
32.
33.
34.
for 1 s
(ii)
for 3 s
Rated operating sequence
Rated transient recovery voltage
Breaking current on out of phase condition
35.
36.
kA
kA
kV
kA (rms)
CONSTRUCTIONAL FEATURES
(i)
(ii)
(iii)
(iv)
23.
24.
25.
mm
m/s & ms
m/s & ms
mm (max)
s (max)
kg/cm
kg/cm
kg/cm
kg/cm
kg/cm
%
Yes/ No
Kg
Kg
kg
kg
Kg
kg
mm
mm
mm
mm
Page
34 of 44
Effective
from
16.04.2014
37.
38.
C.
39.
mm
(i)
Length
mm
(ii)
Width
mm
(iii)
Height
mm
ms
40.
ms
41.
42.
ms
43.
(i)
(ii)
44.
46.
47.
ms
ms
ms
ms
ms
45.
ms
ms
Amplitude factor
Rate of rise at natural frequency
Type and device used to limit rate of
rise of re-striking voltage
Minimum time interval (t) permissible between
successive CO operations after first auto
reclosures.
Number of operations (close and open) the
Circuit Breaker can perform with the available
stored energy
Number of operations permissible without
change of SF6 gas
(i)
At 50% of rated current
kV
Page
35 of 44
Effective
from
16.04.2014
(ii)
(iii)
(iv)
48.
49.
D
50.
(ii)
(iii)
(iv)
51.
52.
53.
54.
C
C
C
C
C
C
watts
Closing coil
V dc %
Tripping coil
V dc %
Contactors ( if any)
V dc %
V dc %
Page
36 of 44
Effective
from
16.04.2014
55.
56.
57.
kW
V
kV (rms)
s
watts
IS/ IEC
No. of springs
Type (Compression/tension)
Specification of Testing and design
Insulators
Support Insulator
(a) Makers name and type
designation
IS/IEC
62.
63.
Total Spare
Total Spare
A
A
No.
A
A
No
Page
37 of 44
Effective
from
16.04.2014
64.
E
65.
66.
67.
68.
69.
70.
71.
72.
73.
74.
75.
76.
77.
78.
79.
80.
81.
82.
83.
84.
85.
86.
87.
IS/IEC
Yes/No
Yes/No
Yes/No
Yes/No
Yes/No
Yes/No
Yes/No
Yes/No
Yes/No
Yes/No
Yes/No
Yes/No
Yes/No
Yes/No
Yes/No
Yes/No
Dia
No
Dia
No
V
Yes/No
Yes/No
Yes/No
Page
38 of 44
Effective
from
16.04.2014
88.
89.
90.
91.
92.
93.
94.
95.
96.
97.
98.
99.
-------
Yes/No
Yes/No
Yes/No
Yes/No
Yes/No
Yes/No
Yes/No
Yes/No
Yes/No
Yes/No
Clause No.
Yes/No
Yes/No
Kg/m2
Page
39 of 44
Effective
from
16.04.2014
Page
40 of 44
Annexure- B
The following information shall be furnished by the Manufacturer/ supplier.
Sl. No.
1.
2.
3.
4.
5.
6.
Description
Fixed main contact
(i) Description and type Designation
(ii) Make
(iii)Identification mark
(iv)Item drawing No.
(v)Material Specification No.
Moving main contact
(i) Description and type Designation
(ii) Make
(iii)Identification mark
(iv)Item drawing No.
(v)Material Specification No.
Fixed arcing contact
(i) Description and type Designation
(ii) Make
(iii)Identification mark
(iv)Item drawing No.
(v)Material Specification No.
Moving arcing contact
(i) Description and type Designation
(ii) Make
(iii)Identification mark
(iv)Item drawing No.
(v)Material Specification No.
Nozzle- Main and Auxiliary (if any)
(i) Description and type Designation
(ii) Make
(iii)Identification mark
(iv)Item drawing No.
(v)Material Specification No
Auxiliary contact
(i) Description and type Designation
(ii) Make
(iii)Identification mark
(iv)Item drawing No.
(v)Governing Specification No.
(vi)Rating
(a)Voltage
(b)Continuous Current
(c)Breaking and making Current
(d)Electrical & life (No. of operations)
Unit of measurement
Effective
from
16.04.2014
7.
8.
MCBs
(i)Description and type
(ii)Type designation
(iii)Make
(iv)Identification mark
(v)Governing Specification No.
(vi) Rating
(a) Voltage
(b) Continuous Current
(c) Breaking and making Current
(d) Electrical & life(No. of operations)
9.
10.
Page
41 of 44
Effective
from
16.04.2014
12.
13.
14.
15.
Pressure
Pressure
indication
switch
Page
42 of 44
Effective
from
16.04.2014
16.
17.
18.
(iv)Identification mark
(v)Governing Specification No
(vi)Electrical rating of switch used
Terminal connector
(i)Description and type
(ii)Type designation
(iii)Make
(iv)Identification mark
(v)Governing Specification No
(vi)Rating
(a) Voltage
(b) Current
Registers
(i)Description and type
(ii)Type designation
(iii)Make
(iv)Identification mark
(v)Governing Specification No
(vi) Rating:
(a) Voltage
(b) Current/Power
Relays and contactors( please furnish details
for all the types of relays/ contactors used)
(i)Description and type
(ii)Type designation
(iii)Make
(iv)Identification mark
(v)Governing Specification No
(vi)Rating:
19.
20.
Page
43 of 44
Effective
from
16.04.2014
21.
Shock absorber
(i)
Description and type
(ii)
Type designation
(iii)
Identification mark
(iv)
Governing Specification
(v)
Type brand and Specification of
fluid used (if any)
-------
Page
44 of 44