RA12-100SDG (12V100Ah)

Specification

RA12-100SDG is GEL Deep cycle battery, with 12 years floating design life,
superiorly designed for frequent cyclic discharge applications under
extreme temperature. By using strong grid to insure reliable performance
under frequent cyclic discharge use. 400 cycles could be available at 100%
DOD. Offering extra-durable cyclic performance, high efficiency of recovery
,that is more suitable for solar, mobility, E-toll, marine , deep discharge UPS
etc..

Cells Per Unit

Voltage Per Unit

12

Capacity

100Ah@20hr-rate to 1.75V per cell @25 oC

Weight

Approx. 29.0 Kg

Max. Discharge Current

1000 A (5 sec)

Internal Resistance

Approx. 5.0 m

Operating Temperature Range

Discharge: -40 C ~60 C


Charge:-20 oC~50 oC
Storage: -40 oC~60 oC

Normal Operating Temperature Range

25 oC5 oC

Float charging Voltage

13.6to 13.8 VDC/unit Average at 25 oC

Recommended Maximum Charging


Current Limit

20A

Equalization and Cycle Service

14.2 to 14.4VDC/unit Average at 25 oC

Self Discharge

RITAR batteries can be stored for more than 6 months


at 25 oC. Self-discharge ratio less than 3% per month
at 25 oC. Please charge batteries before using.

Terminal

Terminal F15/F12

Container Material

A.B.S. (UL94-HB), Flammability resistance of UL94-V1


can be available upon request.

Dimensions
Unit: mm

Dimension: 306.5(L)168.5(W)235(H)

Terminal F12

Constant Current Discharge Characteristics: A (25 oC)


F.V/Time

5MIN

10MIN

15MIN

30MIN

9.60V
10.0V
10.2V
10.5V
10.8V
11.1V

315.4
306.9
289.2
259.7
234.4
204.1

226.0
215.0
207.4
191.4
174.6
156.0

164.4
161.1
158.5
150.9
139.1
124.8

103.2
101.5
100.6
98.11
93.80
87.88

1HR

2HR

3HR

4HR

5HR

8HR

10HR

20HR

58.34
58.07
57.54
57.00
55.65
52.87

33.31
33.06
32.81
32.56
31.97
30.55

23.43
23.34
23.16
23.07
22.44
21.45

19.39
19.30
19.21
19.03
18.58
17.68

16.33
16.23
16.14
15.94
15.66
14.98

11.27
11.18
11.09
10.99
10.81
10.35

9.53
9.44
9.35
9.25
9.16
8.89

5.04
4.95
4.86
4.76
4.67
4.40

Constant Power Discharge Characteristics: W (25 oC)


F.V/Time

5MIN

10MIN

15MIN

30MIN

1HR

2HR

3HR

4HR

5HR

8HR

10HR

20HR

9.6V
10.0V
10.2V
10.5V
10.8V
11.1V

3286.4
3219.3
3038.9
2736.5
2461.5
2124.8

2403.2
2295.4
2218.9
2050.3
1861.6
1653.3

1769.4
1732.7
1709.1
1629.7
1497.4
1337.1

1164.9
1150.4
1136.9
1111.0
1060.4
993.64

667.3
664.0
659.2
652.7
636.6
603.2

383.2
381.7
378.1
374.6
369.1
352.1

270.4
269.8
268.2
266.6
260.1
247.2

224.0
223.5
222.4
220.8
214.9
204.7

189.0
187.9
187.3
185.6
182.7
173.5

130.8
130.2
129.1
128.0
125.3
120.9

107.1
106.0
105.5
104.4
103.3
100.0

56.59
56.04
55.49
54.94
54.39
52.20

All mentioned values are average values.

RA12-100SDG

12V100Ah
Storage characteristic

Li fe ch ar ac ter ist ics of cy cl ic us e

100

120

Su ppleme ntary ch arge required


(Ca rry ou t suppleme ntary ch arge
before us e if 100% ca pacity is
requires)

Capacity (%)

Capacity(%)

100
80
60
100% 80%
D.O.D D.O.D

50%
D.O.D

30%
D.O.D

15%
D.O.D

40

80
10

Su ppleme ntary ch arge required


before us e.
This su ppleme ntary ch arge wi ll help
to recover the ca pacity an d sh ould
be ma de as ea rly as po ssible.

60
20

40

30

40

Su ppleme ntary ch arge ma y of ten


fail to recover the ca pacity.
The ba ttery sh ould ne ver be left
standing till this st ate is reached

20
20

0
400

800

1200

1600

2000

2400

Number of Cycle(Times)

Charge characteristic Curve for standby use


15 7.5

Discharge characteristic Curve

5.0

0.24

120

4.3

12 6.0

80
Discharge
100%0.05CA20h
50%0.05CA10h
Charge
Chcrge Voltage2.275V/C
Charge Current0.1CA
Temperature 25

4.0

11 5.5

3.7

10 5.0

3.3

60

40

0.16

0.12

0.08

T erm inal V oltage (V )

13 6.5

13

6.5

4.3

12

6.0

4.0

11

5.5

3.7

0.20

100

Chcrge Voltage

C h a rg e C u rre n t (C A )

4.7

C h a rg e V o lu m e (% )

C h a rg e V o lta g e V

Chcrge Volume

14 7.0

Su ppleme ntary ch arge an d st orage


guidelines

8 10 12 14 16 18 20 22 24

Storage Time (months)

0.05C
0.16C 0.093C

10

5.0

3.3

4.5

3.0

0.35C
0.62C
3C

20

0.04

1C

Charge Current

4.5

3.0
0

0.6

1.2

12

30

10 12 14 16 18 20 24 28

10

20

24

Hr

min
Discharge Time

Charge Timeh

Capacity Factors With Different Temperature


Battery Type

-20

-10

10

20

25

30

40

45

GEL
6V&12V
Battery
2V

50%

70%

83%

85%

90%

98%

100%

102%

104%

105%

60%

75%

85%

88%

92%

99%

100%

103%

105%

106%

AGM
6V&12V
Battery
2V

46%

66%

76%

83%

90%

98%

100%

103%

107%

109%

55%

70%

80%

85%

92%

99%

100%

104%

108%

110%

Maintenance & Cautions

Discharge Current VS. Discharge Voltage


Final Discharge
Voltage V/cell

1.75V

Discharge
Current (A)

A0.2C

1.60V

1.70V

Cycle service
Avoid battery over discharge, especially battery sereis connection use.

0.2CA1.0C

A1.0C

Charged with recommend voltage, ensure battery can be full recharged.

In general, recharge capacity should be 1.1-1.15 times discharge capacity.


Charge the batteries at least once every six months,
o
if they are stored at 25 C.
Effect of temperature on cycle charge voltage: -4mV//Cell.

Charging Method:

There are a number of factors that will affect the length of cyclic service.

Constant Voltage

-0.2Cx2h+2.4~2.45V/Cellx24h,Max. Current 0.3CA

Constant Current

-0.2Cx2h+0.1CAx12h

discharge rate, and the manner in which the battery is recharged.

Fast

-0.2Cx2h+0.3CAx4.0h

Generally specking, the most important factors is depth of discharge.