CE Series
CE Series
Table of Contents
Table of Contents
Model Nomenclature..................................................................................... 3
Initial Inspection........................................................................................... 4
General Description...................................................................................... 4
Moving and Storage...................................................................................... 4
Safety Considerations................................................................................... 4
Location........................................................................................................ 4
Installation.................................................................................................... 4
Condensate Drain......................................................................................... 5
Duct System.................................................................................................. 6
Piping ........................................................................................................... 6
Electrical....................................................................................................... 7
Thermostat Connections.............................................................................. 7
Safety Devices & the UPM Controller............................................................ 9
Electric Heater Package Option.................................................................. 12
Sequence of Operation Two-Stage Units..................................................... 13
Well Water Systems..................................................................................... 13
Installation of Pressure Regulating Valves................................................... 13
Cooling Tower / Boiler Application.............................................................. 13
Earth Coupled Systems............................................................................... 14
System Checkout........................................................................................ 14
Unit Start-Up............................................................................................... 14
Heat Recovery Package .............................................................................. 15
Hot Gas Reheat........................................................................................... 16
Maintenance............................................................................................... 16
Well Water Application................................................................................ 17
Cooling Tower/Boiler Application............................................................... 18
Earth Coupled Application.......................................................................... 19
Wiring Diagrams.......................................................................................... 20
Operating Pressures & Temperatures......................................................... 23
Unit Check Out............................................................................................ 27
Trouble Shooting......................................................................................... 28
Model Nomenclature
CE 049 - 1 VT C - F L T
SERIES:
CE
NOMINAL CAPACITY:
VOLTAGE DESIGNATION:
1 - 208/1/60 & 230/1/60
CABINET CONFIGURATION:
VT - VERTICAL
HZ - HORIZONTAL
CF - COUNTERFLOW
WATER CONNECTION
LOCATION
F - FRONT
C - COPPER
N - CUPRO-NICKEL
Revised 05-13
Initial Inspection
Ce series
InITIal InsPeCTIon
Be certain to inspect all cartons or crates on each
unit as received at the job site before signing the
freight bill. Verify that all items have been received
and that there are no visible damages; note any
shortages or damages on all copies of the freight
bill. In the event of damage or shortage, remember
that the purchaser is responsible for filing the
necessary claims with the carrier. Concealed
damages not discovered until after removing the
units from the packaging must be reported to the
carrier within 24 hours of receipt.
General desCrIPTIon
These Water-to-Air Heat Pumps provide
the best
Caution
combination of performance and efficiency
available. Safety devices are built into each unit to
provide the maximum system protection possible
when properly installed and maintained.
The CE Water-to-Air Heat Pumps are Underwriters
Laboratories (UL) and (cUL) listed for safety. The
water-to-Air Heat Pumps are designed to operate
with entering fluid temperature between 25F to
75F in the heating mode and between 50F to
110F in the cooling mode.
50F Min. EWT for well water applications with
sufcient water ow to prevent freezing.
Antifreeze solution is required for all closed
loop applications. Cooling Tower/Boiler and
Earth Coupled (Geo Thermal) applications
should have sufcient antifreeze solution to
protect against extreme conditions and
equipment failure. Frozen water coils are not
covered under warranty.
This product should not be used for temporarily heating/cooling during construction. Doing
so may effect the units warranty.
safeTY ConsIderaTIons
Installation and servicing of this equipment can be
hazardous due to system pressure and electrical
components. Only trained and qualified personnel
should install, repair, or service the equipment.
Untrained personnel can perform basic functions of
maintenance such as cleaning coils and replacing
filters.
Before performing service or maintenance
operations on the system, turn off main power
to the unit. Electrical shock could cause
personal injury or death.
loCaTIon
Locate the unit in an indoor area that allows easy
removal of the filter and access panels, and has
enough room for service personnel to perform
maintenance or repair. Provide sufficient room to
make fluid, electrical, and duct connection(s). If the
unit is located in a confined space such as a closet,
provisions must be made for return air to freely enter
the space. On horizontal units, allow adequate room
below the unit for a condensate drain trap and do
not locate the unit above supply piping. These units
are not approved for outdoor installation; therefore,
they must be installed inside the structure being
conditioned. Do not locate in areas that are subject
to freezing.
InsTallaTIon
Remove all shipping blocks under blower
housing. Loosen compressor mounting bolts.
Revised 05-13
Ce series
CondensaTe draIn
If equipped with oat style condensate
overow switch, nal adjustment must be
made in the eld.
Caution
VIBRATION
figure #1
PAD
FULL SIZE
figure #2
Revised 05-13
figure #3
Duct System
CE Series
PIPING
Figure #4
DUCT SYSTEM
A supply air outlet collar and return air duct flange
are provided on all units to facilitate duct
connections. Refer to the individual data
specification sheet for physical dimensions of the
collar and flange.
A flexible connector is recommended for supply and
return air duct connections on metal duct systems.
All metal ducting should be insulated with a
minimum of one inch duct insulation to avoid heat
loss or gain and prevent condensate forming during
the cooling operation. Application of the unit to
uninsulated duct work is not recommended as the
units performance will be adversely affected. Do not
connect discharge ducts directly to the blower
outlet. The factory provided air filter must be
removed when using a filter back return air grill. The
factory filter should be left in place on a free return
system.
If the unit will be installed in a new installation which
includes new duct work, the installation should be
designed using current ASHRAE procedures for duct
sizing. If the unit is to be connected to existing
ductwork, a check should be made to assure that the
duct system has the capacity to handle the air
required for the unit application. If the duct system
is too small, larger ductwork should be installed.
Check for existing leaks and repair.
The duct system and all diffusers should be sized to
handle the designed air flow quietly. To maximize
sound attenuation of the unit blower, the supply and
Revised 05-13
electrical
Ce series
eleCTrICal
figure #5
Revised 05-13
THerMosTaT ConneCTIons
Thermostat wiring is connected to the 10 pin screw
type terminal block on the lower center portion of
the ECM Interface Board. In addition to providing a
connecting point for thermostat wiring, the
interface board also translates thermostat inputs
into control commands for the variable speed
programmable ECM DC fan motor and displays an
LED indication of operating status. The thermostat
connections and their functions are as follows:
Y2
Y1
Fan
W1
EM/W2
NC
C1
HUM
Ce series
Emergency Heat On
W1 (red)
Auxiliary Heat On
O (green)
Y2 (green)
Y1 (green)
G (green)
Fan On
fan
only
Y1
Cool/
HeaT
Y2
Cool/
HeaT
auX
HeaT
eMerG
HeaT
Plus
adJ
MInus
adJ
TaP Cool/
HeaT/delaY
CE025
450
500
800
800
800
900
700
CE035
700
800
1200
1200
1200
1400
1000
CE049
900
1000
1600
1600
1600
1800
1400
CE061
1200
1400
2000
2000
2000
2100
1900
CE071
1600
1600
2200
2200
2200
2300
1900
Revised 05-13
Ce series
Freeze
Protection
Sensor
Revised 05-13
10
Ce series
Revised 05-13
CE Series
UPM Sequence of Operation (SOO) Flow Chart
Y1=1
NO
YES
Power/Switchs/Sensor
Status Check
V > 18VAC
NO
YES
HPC = 1
NO
YES
LPC = 1
NO
Start Timer
Start Timer
TIME > 30
SEC
YES
CC Output = Off
NO
YES
NO
YES
INITIAL NO
POWER UP
Revised 05-13
NO
YES
NO
YES
YES
YES
CON > 0
COUNT = 2
Start
Anti Short Cycle
Start
Random Start Up
NO
T > ASC OR
RS SEC
YES
CC Output = On
11
12
CE Series
Temp30F
Lockout2
ResetY
AlarmPulse
TestNO
Caution
Hot/Dry Alarm Normally Open (NO)
Considerations
1. Always check incoming line voltage power supply
and secondary control voltage for adequacy.
Transformer primaries are dual tapped for 208
and 230 volts. Connect the appropriate tap to
ensure a minimum of 18 volts secondary control
voltage. 24 volts is ideal for best operation.
2. Long length thermostat and control wiring leads
may create voltage drop. Increase wire gauge or
up-size transformers may be required to insure
minimum secondary voltage supply.
3. FHP recommends the following guidelines for wiring
between a thermostat and the unit: 18 GA up to 60
foot, 16 GA up to 100 ft and 14 GA up to 140 ft.
Heater Model
KW
Heater AMPS
208V
240V
Circuit
MCA
Max. Fuse
208V
240V
208V
240V
AWG
Min.
HP050-1XS
4.8
17.3
20.0
L1/L2
27.1
30.4
30
30
HP050-1XM
4.8
17.3
20.0
L1/L2
27.1
30.4
30
30
HP075-1XS
7.2
23.6
30.0
L1/L2
34.9
42.9
40
45
HP075-1XM
7.2
23.6
30.0
L1/L2
35.7
43.8
40
45
HP100-1XS
9.6
34.7
40.0
L1/L2
48.8
55.4
50
60
HP100-1XM
9.6
34.7
40.0
L1/L2
49.5
56.3
50
60
HP150-1XM
HP150-1XM
14.4
14.4
52.0
34.7
17.3
60.0
40.0
20.0
SINGLE
L1/L2
L3/L4
71.2
49.5
21.7
81.3
56.3
25.0
80
60
25
90
60
25
4
6
10
HP200-1XM
HP200-1XM
19.2
19.2
69.3
34.7
34.7
80.0
40.0
40.0
SINGLE
L1/L2
L3/L4
92.9
49.5
43.4
106.3
56.3
50.0
100
50
45
110
60
50
2
6
6
All heaters rated single phase 60 Hz, and include unit fan load. All fuses type D time delay or HACR type breaker or
HRC FORM 1. Wire size based on 60 deg. C copper conductors.
Revised 05-13
Ce series
13
seQuenCe of oPeraTIon
TWo sTaGe unITs
InsTallaTIon of Pressure
reGulaTInG ValVes
CoolInG Mode
HeaTInG Mode
The first two stages of heating (Y1 & Y2) operate in the
same manner as cooling, but with the reversing valve
de-energized. On a call for auxiliary heat (W1), the fan
ramps up to auxiliary heat air flow immediately and the
electric heater package is energized along with the
compressor. As the thermostat is satisfied, the heaters
will shut off as soon as W1 is de-energized, and the
compressors will remain on until the thermostat stages
are satisfied. Note that if the unit compressor lock out
for any reason at this time, the electric heaters will
continue to function normally.
Once the thermostat is satisfied, the compressor
shuts down and the fan ramps down either fan only
mode or off over a span of 30 seconds. If emergency
heat (W2/EM) is called for, the fan will ramp up to
emergency heat air flow immediately and the heater
package will energize in emergency heat mode, all
heater elements coming on. On shut down the fan
will ramp down over a period of 30 seconds.
Revised 05-13
(Figure #10)
14
CE Series
SYSTEM CHECKOUT
After completing the installation, and before
energizing the unit, the following system checks
should be made:
Verify that the supply voltage to the heat pump is
in accordance with the nameplate ratings.
Make sure that all electrical connections are tight
and secure.
Check the electrical fusing and wiring for the
correct size.
Verify that the low voltage wiring between the
thermostat and the unit is correct.
Verify that the water piping is complete and correct.
Check that the water flow is correct, and adjust if
necessary.
Check the blower for free rotation, and that it is
secured to the shaft.
Verify that vibration isolation has been provided.
Unit is serviceable. Be certain that all access
panels are secured in place.
UNIT START-UP
1. Set the thermostat to the highest setting.
2. Set the thermostat system switch to COOL,
and the fan switch to the AUTO position. The
reversing valve solenoid should energize. The
compressor and fan should not run.
3. Reduce the thermostat setting approximately 5
degrees below the room temperature.
4. Verify the heat pump is operating in the cooling mode.
5. Turn the thermostat system switch to the OFF
position. The unit should stop running and the
reversing valve should de energize.
EARTHCOUPLED SYSTEMS
(Figure #12)
Revised 05-13
CE Series
15
HR WATER PIPING:
All hot water piping should be a minimum of 3/8t O.D.
copper tube to a maximum distance of fifteen (15)
feet. For distances beyond fifteen feet but not
exceeding sixty (60) feet use 1/2 copper tube.
Separately insulate all exposed surface of both
connecting water lines with 3/8 wall closed cell
insulation. Install isolation valves on supply and return
to the heat recovery.
16
Initial Start-Up
CE Series
INITIAL START-UP:
1. Make sure all valves in heat recovery water piping
system are open. NEVER OPERATE HR PUMP DRY.
2. Turn on the heat pump. The HR pump should not
run if the compressor is not running.
MAINTENANCE
1. Filter changes or cleanings are required at regular
intervals. The time period between filter changes
will depend upon type of environment the
equipment is used in. In a single family home, that is
not under construction, changing or cleaning the
filter every 60 days is sufficient. In other applications
such as motels, where daily vacuuming produces a
large amount of lint, filter changes may be need to
be as frequent as biweekly.
Equipment should never be used during
construction due to likelihood of wall board dust
accumulation in the air coil of the equipment
which permanently affects the performance
and may shorten the life of the equipment.
Revised 05-13
Revised 05-13
2.
3.
4.
5.
6.
7.
8.
9.
CE Series
1.
BALL VALVES
3.
4.
5.
6.
7.
8.
THREADED ROD
2.
9.
CE Series
1.
18
Cooling Tower/Boiler Application
Revised 05-13
Revised 05-13
3.
4.
5.
6.
CE Series
CONDENSATE DRAIN
2.
7.
1.
20
CE Series
Revised 05-13
CE Series
Revised 05-13
21
22
CE Series
Revised 05-13
CE Series
23
17
Entering
Water
Temp. F
30
40
50
CE025
First
Step
60
70
80
90
100
30
40
50
CE025
Full
Capacity
60
70
80
90
100
30
40
50
CE035
First
Step
60
70
80
90
100
Water
Flow
GPM
2
4
2
4
2
4
2
4
2
4
2
4
2
4
2
4
4
6
4
6
4
6
4
6
4
6
4
6
4
6
4
6
2.5
4.5
2.5
4.5
2.5
4.5
2.5
4.5
2.5
4.5
2.5
4.5
2.5
4.5
2.5
4.5
Suction
Pressure
PSIG
120-146
115-140
129-157
124-151
134-163
128-156
138-168
133-161
143-174
137-167
147-179
141-172
151-185
146-177
125-151
120-146
134-163
129-157
139-169
134-163
144-175
138-168
148-181
143-174
153-186
147-179
158-191
152-185
117-143
112-137
126-154
121-148
131-160
125-153
135-165
130-158
140-171
134-164
144-176
138-169
149-182
143-174
Discharge
Pressure
PSIG
186-228
175-214
218-267
204-250
249-305
233-287
281-341
263-323
317-388
297-366
357-437
335-411
402-492
378-459
180-221
169-207
211-258
198-242
241-295
227-278
272-333
255-313
307-375
288-353
346-423
325-398
389-477
366-448
189-231
178-217
221-270
207-253
252-308
237-290
284-347
266-326
320-391
300-367
360-440
338-414
405-495
381-465
Water
Temp
Rise F
14-17
8-9
14-17
8-9
13-16
8-9
13-16
7-9
13-16
7-9
13-16
7-9
13-15
7-9
14-18
8-10
14-18
8-10
14-17
8-10
14-17
8-10
14-17
8-10
14-17
8-9
13-16
8-9
14-17
8-9
14-17
8-9
13-16
8-9
13-16
7-9
13-16
7-9
13-16
7-9
13-15
7-9
HEATING (+)
Air
Temp
Drop F
18-21
19-23
18-20
19-22
17-20
18-21
17-19
18-21
16-19
17-20
16-18
17-20
15-18
16-19
19-22
20-23
18-21
19-23
18-21
19-22
17-20
18-21
17-19
18-21
16-19
17-20
16-18
17-20
18-22
19-24
18-21
19-23
17-21
18-22
17-20
18-22
16-20
17-21
16-19
17-21
15-19
16-20
Suction
Pressure
PSIG
Discharge
Pressure
PSIG
Water
Temp
Drop F
Air
Temp
Rise F
75-91
79-96
88-107
92-112
98-122
110-130
112-136
117-143
124-152
131-159
136-166
143-174
149-181
156-190
264-322
270-331
277-339
284-348
291-356
298-364
304-372
312-381
318-389
325-398
331-405
339-415
345-422
352-432
5-6
3-4
6-7
4-5
7-8
5-6
8-10
6-7
9-11
6-8
11-13
7-9
12-14
8-10
15-17
16-18
17-20
18-21
20-23
21-24
22-26
23-28
24-29
26-31
27-32
28-33
29-35
31-37
76-92
80-97
89-108
93-113
106-118
104-112
113-138
119-145
126-155
133-162
138-168
145-177
151-184
158-193
242-297
249-304
255-312
261-320
267-327
274-335
280-342
287-351
292-358
300-367
305-373
312-382
317-388
325-398
3-4
2-3
4-5
3-3
5-6
3-4
6-7
4-5
7-8
5-6
8-9
5-6
8-10
6-7
13-14
13-15
15-17
16-18
17-19
18-21
19-22
20-23
21-24
22-26
23-27
24-29
25-29
26-31
73-89
77-94
86-105
90-110
162-198
170-208
110-134
115-141
122-150
129-157
134-164
141-172
147-179
154-188
266-325
272-333
279-341
286-350
293-358
300-366
306-374
314-383
320-391
327-400
333-407
341-417
347-424
355-434
5-6
3-4
6-7
4-5
7-8
5-6
8-10
6-7
9-11
6-8
11-13
7-9
12-14
8-10
15-18
16-19
17-21
18-22
20-24
21-25
22-27
23-29
24-30
26-32
27-33
28-35
29-36
31-38
This chart shows approximate temperatures and pressures for a unit in good repair. The values shown are meant as a guide only and
should not be used to estimate system charge. This chart assumes rated air flow and 80 d.b./67 w.b. entering air temperature in
cooling, 70 d.b. entering air temperature in heating. Heating data at entering fluid temperatures below 50 assumes the use of
antifreeze. As a result of continuing research and development, specifications are subject to change without notice.
Revised 05-13
24
18
CE Series
Entering
Water
Temp. F
30
40
50
CE035
Full
Capacity
60
70
80
90
100
30
40
50
CE049
First
Step
60
70
80
90
100
30
40
50
CE049
Full
Capacity
60
70
80
90
100
Water
Flow
GPM
4.5
9.0
4.5
9.0
4.5
9.0
4.5
9.0
4.5
9.0
4.5
9.0
4.5
9.0
4.5
9.0
4.0
6.0
4.0
6.0
4.0
6.0
4.0
6.0
4.0
6.0
4.0
6.0
4.0
6.0
4.0
6.0
6.0
12.0
6.0
12.0
6.0
12.0
6.0
12.0
6.0
12.0
6.0
12.0
6.0
12.0
6.0
12.0
Suction
Pressure
PSIG
122-149
117-143
131-160
126-154
136-166
131-160
141-172
135-165
145-178
140-171
150-183
144-176
155-189
149-182
109-134
105-128
118-144
113-138
122-149
117-143
126-154
121-148
130-159
132-153
134-164
129-158
139-170
133-163
118-144
113-138
127-155
122-149
131-160
126-154
136-166
130-159
140-171
135-165
145-177
139-170
149-183
143-175
Discharge
Pressure
PSIG
183-224
172-210
214-261
201-245
244-298
230-281
275-336
258-316
310-378
291-356
349-426
328-401
392-480
369-451
183-224
172-210
214-261
201-245
244-298
230-281
275-336
258-316
310-378
291-356
349-426
328-401
392-480
369-451
194-237
182-223
226-276
213-260
259-316
243-297
291-355
273-334
328-401
308-377
369-451
347-424
415-508
391-477
Water
Temp
Rise F
14-18
8-10
14-18
8-10
14-17
8-10
14-17
8-10
14-17
8-10
14-17
8-9
13-16
8-9
18-22
10-12
18-22
10-12
17-21
10-12
17-21
10-12
17-21
10-12
17-20
9-12
16-20
9-11
21-25
12-14
21-25
12-14
21-25
12-14
20-25
12-14
20-24
11-14
20-24
11-14
19-24
11-14
HEATING (+)
Air
Temp
Drop F
19-23
20-24
18-22
19-24
18-22
19-23
17-21
18-22
17-20
18-22
16-20
17-21
16-19
17-21
19-23
20-25
19-23
20-24
18-22
19-24
18-22
19-23
17-21
18-22
17-20
18-22
16-20
17-21
19-23
20-24
18-22
19-24
18-22
19-23
17-21
18-22
17-20
18-22
16-20
17-21
16-19
17-21
Suction
Pressure
PSIG
Discharge
Pressure
PSIG
Water
Temp
Drop F
Air
Temp
Rise F
74-90
78-95
87-106
91-111
164-201
173-211
111-136
117-143
124-152
131-160
136-166
143-175
149-182
156-191
244-299
251-306
257-314
263-322
269-329
276-337
282-344
289-353
294-360
302-369
307-375
314-384
319-390
327-400
3-4
2-3
4-5
3-3
5-6
3-4
6-7
4-5
7-8
5-6
8-9
5-6
8-10
6-7
13-15
13-16
15-18
16-19
17-20
18-22
19-23
20-24
21-25
22-27
23-28
24-30
25-30
26-32
64-78
67-82
75-91
79-96
142-173
149-182
96-117
101-123
107-131
113-138
117-143
123-151
128-157
135-165
248-303
254-311
261-319
267-327
273-334
280-342
286-349
293-358
299-365
306-374
311-380
319-390
324-396
332-406
5-6
3-4
6-8
4-5
8-10
5-7
9-11
6-8
11-13
7-9
12-15
8-10
13-16
9-11
15-18
16-19
17-21
18-23
20-24
21-26
22-27
24-29
25-30
26-32
27-33
29-35
29-36
31-38
71-87
75-92
84-102
88-108
159-194
167-204
108-132
113-138
120-147
126-154
131-161
138-169
144-176
151-185
277-339
284-347
291-356
299-365
305-373
313-383
320-391
328-400
334-408
342-418
348-425
356-436
362-442
371-453
6-7
4-5
7-9
5-6
9-11
6-7
10-13
7-9
12-15
8-10
14-17
9-11
15-18
10-12
15-19
16-20
18-22
19-23
20-25
21-26
23-28
24-29
25-31
27-32
27-34
29-36
30-37
32-39
This chart shows approximate temperatures and pressures for a unit in good repair. The values shown are meant as a guide only and
should not be used to estimate system charge. This chart assumes rated air flow and 80 d.b./67 w.b. entering air temperature in
cooling, 70 d.b. entering air temperature in heating. Heating data at entering fluid temperatures below 50 assumes the use of
antifreeze. As a result of continuing research and development, specifications are subject to change without notice.
Revised 05-13
CE Series
25
Entering
Water
Temp. F
30
40
50
CE061
First
Step
60
70
80
90
100
30
40
50
CE061
Full
Capacity
60
70
80
90
100
30
40
50
CE071
First
Step
60
70
80
90
100
Water
Flow
GPM
5.0
7.0
5.0
7.0
5.0
7.0
5.0
7.0
5.0
7.0
5.0
7.0
5.0
7.0
5.0
7.0
7.0
14.0
7.0
14.0
7.0
14.0
7.0
14.0
7.0
14.0
7.0
14.0
7.0
14.0
7.0
14.0
10.0
16.0
10.0
16.0
10.0
16.0
10.0
16.0
10.0
16.0
10.0
16.0
10.0
16.0
10.0
16.0
Suction
Pressure
PSIG
113-138
110-134
116-142
112-137
118-145
115-140
121-148
117-143
123-151
120-146
126-154
122-149
128-157
125-152
117-143
114-139
120-147
117-143
123-150
119-146
126-154
122-149
129-157
125-153
132-161
128-156
134-164
131-160
116-141
113-137
119-145
115-140
121-148
118-143
124-151
120-146
126-154
123-149
129-157
125-152
131-160
128-155
Discharge
Pressure
PSIG
172-210
161-196
206-252
193-236
241-294
225-275
275-336
257-314
309-378
289-353
344-420
321-392
378-462
353-432
182-222
170-208
215-263
201-246
248-304
232-284
282-344
263-322
315-385
294-360
348-426
326-398
382-466
357-436
175-213
164-199
209-255
196-239
244-297
228-278
278-339
260-317
312-381
292-356
347-423
324-395
381-465
356-435
Water
Temp
Rise F
18-22
12-14
17-21
12-14
17-21
11-14
17-21
11-14
16-20
11-13
16-20
11-13
16-19
11-13
15-19
11-14
15-18
11-14
14-17
11-13
14-17
10-13
13-16
10-12
13-16
10-12
12-15
9-11
18-22
12-14
17-21
12-14
17-21
11-14
17-21
11-14
16-20
11-13
16-20
11-13
16-19
11-13
HEATING (+)
Air
Temp
Drop F
19-23
20-24
19-23
19-24
18-23
19-23
18-22
19-23
18-22
19-23
18-22
18-22
17-21
18-22
21-26
22-27
20-25
21-26
20-24
21-25
19-24
20-25
19-23
19-24
18-22
19-23
17-21
18-22
19-23
20-24
19-23
19-24
18-23
19-23
18-22
19-23
18-22
19-23
18-22
18-22
17-21
18-22
Suction
Pressure
PSIG
Discharge
Pressure
PSIG
Water
Temp
Drop F
Air
Temp
Rise F
68-84
73-89
81-99
86-105
93-114
99-121
106-129
113-138
118-145
126-154
131-160
139-170
143-175
152-186
256-313
261-319
277-339
283-346
299-365
305-373
321-392
327-400
342-418
349-427
364-444
371-454
385-471
393-480
5-7
4-5
7-8
5-6
8-9
6-7
9-11
7-8
10-12
8-9
11-14
8-10
12-15
9-11
19-23
20-25
22-26
23-28
24-29
25-31
26-32
28-34
29-35
30-37
31-38
33-40
33-41
35-43
68-84
73-89
81-99
86-105
93-114
99-121
106-129
113-138
118-145
126-154
131-160
139-170
143-175
152-186
256-313
261-319
277-339
283-346
299-365
305-373
321-392
327-400
342-418
349-427
364-444
371-454
385-471
393-480
5-7
4-5
7-8
5-6
8-9
6-7
9-11
7-8
10-12
8-9
11-14
8-10
12-15
9-11
19-23
20-25
22-26
23-28
24-29
25-31
26-32
28-34
29-35
30-37
31-38
33-40
33-41
35-43
71-87
76-92
84-102
89-108
96-117
102-124
109-132
116-141
121-148
129-157
134-163
142-173
146-178
155-189
259-316
264-322
280-342
286-349
302-368
308-376
324-395
330-403
345-421
352-430
367-447
374-457
388-474
396-483
5-7
4-5
7-8
5-6
8-9
6-7
9-11
7-8
10-12
8-9
11-14
8-10
12-15
9-11
19-23
20-25
22-26
23-28
24-29
25-31
26-32
28-34
29-35
30-37
31-38
33-40
33-41
35-43
This chart shows approximate temperatures and pressures for a unit in good repair. The values shown are meant as a guide only and
should not be used to estimate system charge. This chart assumes rated air flow and 80 d.b./67 w.b. entering air temperature in
cooling, 70 d.b. entering air temperature in heating. Heating data at entering fluid temperatures below 50 assumes the use of
antifreeze. As a result of continuing research and development, specifications are subject to change without notice.
Revised 05-13
26
CE Series
Entering
Water
Temp. F
30
40
50
CE071
60
Full
Capacity
70
80
90
100
Water
Flow
GPM
10.0
16.0
10.0
16.0
10.0
16.0
10.0
16.0
10.0
16.0
10.0
16.0
10.0
16.0
10.0
16.0
Suction
Pressure
PSIG
120-146
117-142
123-150
120-146
126-153
122-149
129-157
125-152
132-160
128-156
135-164
131-159
137-167
134-163
Discharge
Pressure
PSIG
185-225
173-211
218-266
204-249
251-307
235-287
285-347
266-325
318-388
297-363
351-429
329-401
385-469
360-439
Water
Temp
Drop F
15-19
11-14
15-18
11-14
14-17
11-13
14-17
10-13
13-16
10-12
13-16
10-12
12-15
9-11
HEATING (+)
Air
Temp
Drop F
21-26
22-27
20-25
21-26
20-24
21-25
19-24
20-25
19-23
19-24
18-22
19-23
17-21
18-22
Suction
Pressure
PSIG
Discharge
Pressure
PSIG
Water
Temp
Drop F
Air
Temp
Rise F
71-87
76-92
84-102
89-108
96-117
102-124
109-132
116-141
121-148
129-157
134-163
142-173
146-178
155-189
259-316
264-322
280-342
286-349
302-368
308-376
324-395
330-403
345-421
352-430
367-447
374-457
388-474
396-483
5-7
4-5
7-8
5-6
8-9
6-7
9-11
7-8
10-12
8-9
11-14
8-10
12-15
9-11
19-23
20-25
22-26
23-28
24-29
25-31
26-32
28-34
29-35
30-37
31-38
33-40
33-41
35-43
This chart shows approximate temperatures and pressures for a unit in good repair. The values shown are meant as a guide only and
should not be used to estimate system charge. This chart assumes rated air flow and 80 d.b./67 w.b. entering air temperature in
cooling, 70 d.b. entering air temperature in heating. Heating data at entering fluid temperatures below 50 assumes the use of
antifreeze. As a result of continuing research and development, specifications are subject to change without notice.
Revised 05-13
Unit Checkout
CE Series
27
Date ____________________________________
Address ___________________________________________________________
____________________________________________________________________
Phone _____________________________________________________________
Serial Number_______________________________
Operating Conditions
Cooling Mode
Heating Mode
_______________________________ ______________________________
_______________________________ ______________________________
______________________________
_______________________________ ______________________________
______________________________
______________________________
______________________________
______________________________
Suction Superheat*
_______________________________ ______________________________
_______________________________ _________________________________
Liquid Subcooling*
_______________________________ _________________________________
______________________________
Auxiliary Heat
Unit Make ________________________________________________
Model Number ___________________________________________
Serial Number_______________________________
Revised 05-13
28
Troubleshooting
CE Series
Troubleshooting
Problem
Possible Cause
Entire unit
does not run
Blown Fuse
Thermostat
Set the fan to ON, the fan should run. Set thermostat to COOL and
lowest temperature setting, the unit should run in the cooling mode
(reversing valve energized). Set unit to HEAT and the highest temperature setting, the unit should run in the heating mode. If neither the blower
or compressor run in all three cases, the thermostat could be miswired or
faulty.To ensure miswired or faulty thermostat verify 24 volts is available
on the condensing section low voltage terminal strip between R and
C, Y and C, and O and C. If the blower does not operate, verify
24 volts between terminals G and C in the air handler. Replace the
thermostat if defective.
Thermostat
Wiring
Safety Controls
Compressor
overload open
If the compressor is cool and the overload will not reset, replace compressor.
Compressor motor
grounded
Compressor
windings Open
Discharge pressure
too high
Refrigerant charge
High pressure
Suction pressure
too low
Refrigerant charge
Low pressure
switch
Unit oversized
Thermostat
Blower
operates but
compressor
does not
Unit off on
high pressure
control
Unit off on
low pressure
control
Unit short
cycles
Revised 05-13
Troubleshooting
Insufficient
cooling or
heating
UPM board
trouble
shooting
CE Series
Unit undersized
Loss of conditioned Check for leaks in duct work or introduction of ambient air through
air by leakage
doors or windows
Airflow
Refrigerant charge
Compressor
Reversing Valve
Operating
pressures
TXV
Moisture,
noncondensables
Compressor will
not run, no fault
blink code
Yes
Yes
Yes
Is there
power to
the Y Call
(C-Y)?
Is Green
Power LED
light on and
no Red
Blink Code?
Check
thermostat
settings and
configurations
for heat
pumps, and
wiring
- Check all
power supplies
- Check all
safety switches
UPM Board
is Good
Is there 24 V
power from
C to CC?
No
No
No
Revised 05-13
29
30
Notes
CE Series
Revised 05-13
Notes
Revised 05-13
CE Series
31
or