Knock Monitoring
System
DetCon2
MOTORTECH GmbH
Hogrevestr. 21-23 D-29223 Celle
Telefon: +49 5141 9399-0 Fax: +49 5141 9399-98 / -99
eMail: motortech@motortech.de Internet : www.motortech.de
Table Of Contents
Page
1 Features
2 Function Description
3 Installation
3.1 Hardware Configuration
3.2 Software Configuration
4
4
4
5
5
5
6
6
6
4 Technical Specifications
10
10
10
10
5 Wiring
5.1 Wiring Diagram Control Unit
5.2 Circuit Board / Description of LEDs
5.3 Wiring Diagram Ignition Sensor
6 Dimensions / Mounting
6.1 Control Unit
6.2 Knock Sensor
6.3 Ignition Sensor
11
11
12
12
13
13
13
14
1 Features
Knock monitoring
Panel mounting
Warning!!!
Caution High Voltage!!! Danger to life!!!
When engine is running, ignition sensor should
not be touched, disconnected or removed.
ATTENTION!!!
The knock monitoring system detects engine
knocking as far as possible but not guaranteed.
ATTENTION!!!
With V-engines it is only possible to run the
system, when only single-firing ignition systems
are mounted, not double-firing systems.
ATTENTION!!!
High tension leads with integrated 5 k resistor
are required to run the knock monitoring
system.
2 Function Description
2.1 Principle Of Knock Detection
During detonation combustion, a frequency is generated, which is typical for each engine type. detcon
measures the vibration energy in the narrow frequency band, where knocking can be expected. This
energy is equivalent to a knocking level. Measurements are executed during that specific section of
working cycle, where detonating is possible. This increases the sensitivity of the knock monitoring
system and improves immunity against random noise.
3 Installation
Customer installation is possible only for those engine types, for which the knocking frequencies
already have been measured.
For wiring of the control units, please refer to sections 5.1 - 5.3 on pages 12 - 14.
Binary outputs can be connected in both polarity as they are galvanicly seperated.
For wiring of the ignition sensor, please refer to section 5.3 on page 14.
For installation of the knock sensor(s), please refer to section 6.2 on page 16.
First install the software program (included in scope of supply) on your PC or Laptop. Minimum
system requirements are MS-DOS.
Copy all files out of the folder "detcon2" on your hard disc. A destination folder has to be created
before.
Now please connect your detcon control unit to your PC/Laptop. Therefore please take a "NullModem" cable and connect it from COM1 or COM2 of your PC/Laptop to the control unit. Cable is
included in scope of supply. When using a different kind of cable, both detcon control unit and
your PC/Laptop could be damaged.
To start the program from MS DOS box, please type "denox" (connection with COM 1) or "denox2"
(connection with COM 2).
Computers, connected to detcon, must be galvanicly speperated from grid potential and any other
potential of the genset. We recommend to use a notebook with internal batteries during detcon
configuration. During communication the detcon control unit must be powered up.
After program is loaded, you will see "detcon DEBUGER/LOADER, Version x" on the screen.
Communication window shows all user changeable values and also contents a program help file
(press [F1]).
Function of keys [F2], [F3], [F7] and [F8] see above.
When connection to control unit is established following message will appear:
COM 1 (COM 2) linked to: detcon (version x) OK.
In the last two lines you can see actually set values (please see table below for their meaning).
To leave the program press [ALT + X].
Parameter
Range
Description
Function control
Balance control
Number of measurements
10
11
0 100%
12
DECREASE RAMP
0 31,5%
per sec.
13
0 235
14
0 255
0,1 sec.
15
0 235
Parameter
Range
Yes / No
Yes / No
0 100%
Open /
Close
Yes / No
Yes / No
Description
Changes 4 20 mA to 20 4 mA if
YES.
Enables point 1 if chosen YES.
Maximum analog output value (if
enabled), 100% = 20 mA.
Enables alarm features for signal
loss of ignition sensor:
Open = no alarm
Close = alarm if signal failure.
Enables alarm feature for signal loss
of knock sensor 1.
Enables alarm feature for signal loss
of knock sensor 2.
Parameter
Range
KNOCKING INTENSITY
0 235
0 100%
Description
Instantaneous measured value of
knocking energy.
Instantaneous value of detcon
regulation output
(analog output for ignition timing
control).
4 Technical Specifications
4.1 Knock Sensor
Parameter
Knock sensor
Frequency range
Resonance frequency
Temperature range
Dimensions
Mounting
Specification
Piezoelectric acceleration transducer
1 20 kHz
> 20 kHz
-40 - +130C
45 x 20 x 21 mm
Screw M8 x 25 (Cylinder head cast iron)
Screw M8 x 30 (Cylinder head aluminium)
Specification
All three outputs have one common terminal, max.
voltage 33 V, max. load current 50 mA
1) 0 - 5 V (+0, 0,5 V), max. load current 2mA
2) current loop 4 20 mA, max. voltage 30 V
-25 - +70C
9 - 36 VDC
IP20
160 x 200 x 46 mm (incl. rail)
approx. 1,0 kg
Panel mounting
Analog ouput
Temperature range
Power supply
Protection class
Dimensions
Weight
Mounting
Specification
Ignition coil current sensor
-25 - +70C
70 x 46 x 48 mm (incl. rail)
approx. 0,1 kg
Rail
5 Wiring
5.1 Wiring Diagram Control Unit
DetCon
6 Dimensions / Mounting
6.1 Control Unit