Escolar Documentos
Profissional Documentos
Cultura Documentos
fully edited. Content may change prior to final publication. Citation information: DOI
10.1109/TPWRD.2014.2372045, IEEE Transactions on Power Delivery
I. INTRODUCTION
0885-8977 (c) 2013 IEEE. Personal use is permitted, but republication/redistribution requires IEEE permission. See
http://www.ieee.org/publications_standards/publications/rights/index.html for more information.
This article has been accepted for publication in a future issue of this journal, but has not been fully edited. Content may change prior to final publication. Citation information: DOI
10.1109/TPWRD.2014.2372045, IEEE Transactions on Power Delivery
(1)
where;
[d ( ) ] [U ] 0.5 2 [ Z ][Ysh ]
(2)
[b( ) ] [Z ]
(3)
[Z ]
S F [VF ]t [ I F ]
(4)
(5)
0885-8977 (c) 2013 IEEE. Personal use is permitted, but republication/redistribution requires IEEE permission. See
http://www.ieee.org/publications_standards/publications/rights/index.html for more information.
This article has been accepted for publication in a future issue of this journal, but has not been fully edited. Content may change prior to final publication. Citation information: DOI
10.1109/TPWRD.2014.2372045, IEEE Transactions on Power Delivery
3
Bus-i
Segment-p
Segment-q
[Vr-p]
[Ir-p]
[Vs-p]
[Is-p]
[Vs-q]
[Is-q]
Bus-j
[Vr-q]
[Ir-q]
G
(1 )
( )
SF
[ I r p ] [C( ) ][Vs p ] [d ( ) ][ I s p ]
(12)
(13)
where;
(6)
Equation (6) can be rearranged as a second-order polynomial with respect to a per-unit fault distance ( ) as in (7):
X 0 X1 X 2 2 0
(7)
X 0 Im{[Vs p ]t [ I F ]}
(8)
X 1 Im{[ I s p ]t [ Z ][ I F ]}
(9)
(10)
where;
[I F ] [I r p ] [I s q ]
(11)
[ I r q ] [ Z d ]j [Vr q ] [ I G ] j [ Z d ]j
[Z
T ] j , k [ I G ]k
(14)
k 1, k j
(15)
[ I r q ] [d (1 ) ][ I s q ] [C(1 ) ][VF ]
(16)
[ I s q ] [ A3 ] [ A1 ][Vs p ] [ A3 ] [ A2 ][ I s p ]
[ A3 ] [ I G ] j [ A3 ] [ Z d ]j
[ Z
T ] j ,k [ I G ]k
(17)
k 1, k j
where;
[ A1 ] ([ Z d ]j [d (1 ) ] [C(1 ) ])[d ( ) ]
(18)
[ A2 ] ([ Z d ]j [d (1 ) ] [C(1 ) ])[b( ) ]
(19)
[ A3 ] [d (1 ) ] [ Z d ]j [b(1 ) ]
(20)
0885-8977 (c) 2013 IEEE. Personal use is permitted, but republication/redistribution requires IEEE permission. See
http://www.ieee.org/publications_standards/publications/rights/index.html for more information.
This article has been accepted for publication in a future issue of this journal, but has not been fully edited. Content may change prior to final publication. Citation information: DOI
10.1109/TPWRD.2014.2372045, IEEE Transactions on Power Delivery
[Vi]
[Ir]u
[Vs]u
[Is]u
[Vs]k
[Is]k
Line Section-k
Line Section-u
Load-i
Bus-i
[Vi]
[ILt]i
G
Line Section-u
Line Section-k
(21)
where [Vs]u and [Is]u are the sending-end voltages and currents
of the line section-u. [d(1)] and [b(1)] are determined by
substituting =1 in (2) and (3), respectively.
The sending-end voltages of the line section-k can then be
calculated using (22):
[Vs ]k [T ]k [V ]i
G
Bus-j
Bus-i
Load-i
Fig. 3. Distribution feeder with separation of the load and laterals connected
to bus-i from the rest of the system.
[ I Lt ]i [ Z d ]i [Vi ] [ I G ]i [ Z d ]i
[Z
T ]i , k [ I G ]k
(25)
k 1, k i
(22)
[ I s ]k [T ]k ([ I r ]u [ I Lt ]i )
(23)
(24)
[ Z d ]i [Vi ] [ I G ]i [ Z d ]i
[Z
T ]i , k [ I G ]k )
(26)
k 1, k i
[ I F ] [ I s p ] [ I s p ]
(27)
where [Is-p] and [Is-p] are the measured currents at the sendingend of the segment-p during the fault and before the fault,
respectively.
Step 4) Solve the FL equation to determine the per-unit fault
distances ( 1 ) and ( 2 ), respectively, using (28) and
(29):
X 1 X 12 4 X 2 X 0
2 X2
0885-8977 (c) 2013 IEEE. Personal use is permitted, but republication/redistribution requires IEEE permission. See
http://www.ieee.org/publications_standards/publications/rights/index.html for more information.
(28)
This article has been accepted for publication in a future issue of this journal, but has not been fully edited. Content may change prior to final publication. Citation information: DOI
10.1109/TPWRD.2014.2372045, IEEE Transactions on Power Delivery
X 1 X 12 4 X 2 X 0
(29)
2 X2
norm([V
sc ]i
[Vsm ]i )
(33)
i 1
where X0, X1 and X2 are determined by using (8), (9) and (10),
respectively.
Step 5) Check the convergence of 1 and 2 by using (30)
and (31), respectively:
1 (i) 1 (i 1)
(30)
2 (i) 2 (i 1)
(31)
[Vsc ]i [ Z d ]i [ I G ]i [ I F ][ Z T ]i , N 1
Error
[ Z
T ]i ,k [ I G ]k
(32)
k 1, k i
% Error
Actual FL - Estimated FL
100
Total Length
0885-8977 (c) 2013 IEEE. Personal use is permitted, but republication/redistribution requires IEEE permission. See
http://www.ieee.org/publications_standards/publications/rights/index.html for more information.
(34)
This article has been accepted for publication in a future issue of this journal, but has not been fully edited. Content may change prior to final publication. Citation information: DOI
10.1109/TPWRD.2014.2372045, IEEE Transactions on Power Delivery
6
TABLE I
MAXIMUM AND AVERAGE ERRORS
848
800
822
802
846
820
806
844
864
818
812
814
850
824
808
DG1
842
860
826
836
840
858
834
816
832
DG2
810
852
828
830
854
862
838
856
Fig. 4. Single line diagram of the modified IEEE 34-bus test feeder with DG
units.
A-g
0.01
0.04
0.05
B-g
0.01
0.03
0.04
C-g
0.02
0.03
0.04
AB
0.01
0.05
BC
0.02
0.05
CA
0.01
0.03
AB-g
0.01
0.02
0.04
BC-g
0.01
0.02
0.03
CA-g
0.01
0.02
0.04
ABC
0.01
0.01
ABC-g
0.01
0.02
0.03
AB & C-g
0.01
0.01
0.02*
BC & A-g
0.01
0.02
0.03*
CA & B-g
0.01
0.01
0.02*
*
The phase-to-phase fault resistance is 10 ohm.
0.03
0.08
0.10
0.03
0.08
0.09
0.03
0.09
0.10
0.03
0.09
0.04
0.08
0.02
0.06
0.01
0.03
0.07
0.01
0.03
0.06
0.01
0.03
0.07
0.01
0.02
0.01
0.02
0.04
0.01
0.02
0.05*
0.02
0.03
0.05*
0.01
0.02
0.04*
Fig. 5. Fault location error for the case of single-phase-to-ground faults with
RF = 10 and 25 .
0885-8977 (c) 2013 IEEE. Personal use is permitted, but republication/redistribution requires IEEE permission. See
http://www.ieee.org/publications_standards/publications/rights/index.html for more information.
This article has been accepted for publication in a future issue of this journal, but has not been fully edited. Content may change prior to final publication. Citation information: DOI
10.1109/TPWRD.2014.2372045, IEEE Transactions on Power Delivery
Fig. 7. Fault location error for the case of individual load variations.
Fig. 8. Fault location error for the case of compound load type.
TABLE II
RANKING RESULTS FOR THE POSSIBLE FAULT LOCATIONS
Case
Fault
type
Faulty
line
section
Normal
load
A-g
846-848
Individual
load change
BC
Load type
change
ABC-g
Normal
load
AB-g
Individual
load change
AB&Cg
Load type
change
ABC
836-862
Line sections
that include the
most possible
locations
846-848
846-848
846-848
836-862
836-840
836-862
836-840
836-862
836-840
0885-8977 (c) 2013 IEEE. Personal use is permitted, but republication/redistribution requires IEEE permission. See
http://www.ieee.org/publications_standards/publications/rights/index.html for more information.
This article has been accepted for publication in a future issue of this journal, but has not been fully edited. Content may change prior to final publication. Citation information: DOI
10.1109/TPWRD.2014.2372045, IEEE Transactions on Power Delivery
8
TABLE III
FAULT ERROR COMPARISON
Fault
Distance
(km)
0.4
1.05
6.3
17
27.2
0.001
0.001
0.001
0.003
0.006
RF = 0
Nuness
Method
0.005
0.013
0.014
0.015
0.022
Bretass
Method
Proposed
Method
0.016
0.044
0.333
1.575
3.718
0.005
0.005
0.005
0.008
0.014
methods use the short line model where the capacitive effect is
not considered. This model can provide good accuracy for
locating the fault in the short distribution lines. However, it is
not suitable for long distribution feeder [20]. Moreover,
Bretass method neglects the mutual impedance effect of the
distribution line by assuming the loads are balanced and the
distribution lines are perfectly transposed. From the practical
view, this assumption is not valid and decreases the accuracy
of FL estimate as shown in the results presented in Table III.
This observation led to the conclusion that the proposed
method presents great improvements to the FL accuracy by
considering the characteristics of the distribution system.
Besides the consideration of distribution system characteristics, the proposed impedance-based method uses only one FL
equation that is applicable for all fault types occurrence in
single phase, two phase and three phase line sections. Hence,
the identification of fault type is not required. Only the
fundamental values of voltages and current measured at the
substation and each DG unit bus are required for the proposed
method. The currents measured at each DG unit bus are treated
as current injection to consider the participation of each DG
unit to the fault current. This idea avoids the modeling effort to
represent the behavior of the generation unit and its interface
during the fault conditions. Hence, the proposed method is
applicable to any DG unit type and has similar behavior for
different types.
On the other hand, Bretas and Nuness methods use FL
equation for each fault type. The identification of fault type is
required. Therefore, the accuracy of these methods not only
depends on the FL methodology but it also depends on the
accuracy of the adopted fault classification method. These
methods are formulated for three-phase distribution systems
with a synchronous generator unit. Due to the complexity to
obtain FL equations for different fault type configurations,
these methods are formulated in [15-17] for single-phase to
ground fault and in [18] for three-phase to ground fault. These
papers did not consider all possible fault types.
Finally, impedance-based methods such as the methods
presented in [15-18] determine the FL that is given by the fault
distance. Due to the tree topological structure of distribution
systems, multiple fault locations are frequently obtained. In
practice, other techniques and devices, such as fault indicators,
and information from protection devices may be used to
determine the exact FL or the most likely FL. However, the
proposed scheme in this paper identifies the exact FL among
RF = 25
Nuness
Method
0.410
0.417
0.466
0.601
0.776
Bretass
Method
0.415
0.431
0.727
2.02
4.238
[2]
[3]
0885-8977 (c) 2013 IEEE. Personal use is permitted, but republication/redistribution requires IEEE permission. See
http://www.ieee.org/publications_standards/publications/rights/index.html for more information.
This article has been accepted for publication in a future issue of this journal, but has not been fully edited. Content may change prior to final publication. Citation information: DOI
10.1109/TPWRD.2014.2372045, IEEE Transactions on Power Delivery
[4]
[5]
[6]
[7]
[8]
[9]
[10]
[11]
[12]
[13]
[14]
[15]
[16]
[17]
[18]
[19]
[20]
[21]
[22]
systems," Electric Power Systems Research, vol. 78, no. 4, pp. 657-666,
Apr. 2008.
S. Chaitusaney, and A. Yokoyama, "Prevention of reliability
degradation from recloserfuse miscoordination due to distributed
generation," IEEE Trans. Power Delivery, vol. 23, no. 4, pp. 25452554, Oct. 2008.
S. M. Brahma, and A. A. Girgis, "Microprocessor-based reclosing to
coordinate fuse and recloser in a system with high penetration of
distributed generation," in Proc. IEEE Power Eng. Soc. Winter
Meeting, 2002, vol. 1, pp. 453458.
S. M. Brahma, and A. A. Girgis, "Development of Adaptive protection
scheme for distribution systems with high penetration of distributed
generation," IEEE Trans. Power Delivery, vol. 19, no. 1, pp. 56-63, Jan.
2004.
A. F. Naiem, Y. Hegazy, A. Y. Abdelaziz, and M. A. Elsharkawy, "A
classification technique for recloser fuse coordination in distribution
systems with distributed generation," IEEE Trans. Power Delivery, vol.
27, no. 1, pp. 176-185, Jan. 2012.
K. Tuitemwong, and S. Premrudeepreechacharn, "Expert system for
protection coordination of distribution system with distributed
generators," International Journal of Electrical Power and Energy
Systems, vol. 33, no. 3, pp. 466-471, March 2011.
H. Zayandehroodi, A. Mohamed, and H. Shareef, "Determining exact
fault location in a distribution network in presence of DGs using RBF
neural networks," in proc. 2011 IEEE International Conference on
Information Reuse and Integration (IRI), pp. 434-438.
S. A. M. Javadian, A. M. Nasrabadi , M. R. Haghifam, and J.
Rezvantalab, "Determining fault's type and accurate location in
distribution systems with DG using MLP neural networks," in proc.
2009 IEEE Int. Conf. on Clean Electrical Power, pp. 284-289.
S. A. M. Javadian, M. R. Haghifam, S. M. T. Bathaee, and M. F.
Firoozabad, "Adaptive centralized protection scheme for distribution
systems with DG using risk analysis for protective devices placement,"
International Journal of Electrical Power and Energy Systems, vol. 44,
no. 1, pp. 337-345, Jan. 2013.
M. Zayandehroodi, A. Mohamed, H. Shareef, and M. Farhoodnea, "A
novel neural network and backtracking based protection coordination
scheme for distribution system with distributed generation,"
International Journal of Electrical Power and Energy Systems, vol. 43,
no. 1, pp. 868-879, Dec. 2012.
M. M. Saha, J. Izykowski, and E. Rosolowski, Fault Location on Power
Networks, London: Springer, 2009.
S. M. Brahma, "Fault location in power distribution system with
penetration of distributed generation," IEEE Trans. Power Delivery,
vol. 26, no. 3, pp. 1545-1553, July 2011.
A.S. Bretas, and R.H. Salim, "Fault Location in Unbalanced DG
Systems using the Positive Sequence Apparent Impedance," in proc.
2006 IEEE Transmission and Distribution Conference and Exposition:
Latin America, pp.1-6.
J.U.N. Nunes, and A.S. Bretas, "An extended fault location formulation
for unbalanced distribution feeders with distributed generation," in 2010
Proceedings of the International Symposium, Modern Electric Power
Systems (MEPS), pp.1-6.
J. U. N. Nunes, and A. S. Bretas, "A impedance-based fault location
technique for unbalanced distributed generation systems," in proc. 2011
IEEE Trondheim PowerTech, pp. 1-7.
J.U.N. Nunes, and A.S. Bretas, "Impedance-based fault location
formulation for unbalanced primary distribution systems with
distributed generation," in proc. 2010 International Conference on
Power System Technology (POWERCON), pp.1-7.
D. Penkov, B. Raison, C. Andrieu, J. P. Rognon, and B. Enacheanu,
"DG impact on three phase fault location. DG use for fault location
purposes," in proc. 2005 Int. Conf. on Future Power Systems.
R. H. Salim, K. C. O. Salim, A. S. Bretas, "Further improvements on
impedance-based fault location for power distribution systems," IET
Generation, Transmission and Distribution, vol. 5, no. 4, pp. 467-478,
April 2011.
B. Das, "Fuzzy logic-based fault-type identification in unbalanced radial
power distribution system," IEEE Trans. Power Delivery, vol. 21, no. 1,
pp. 278-285, Jan. 2006.
S. F. Alwash, and V. K. Ramachandaramurthy, "Novel fault location
method for overhead electrical distribution systems," IEEJ Transactions
[23]
[24]
[25]
[26]
[27]
[28]
[29]
[30]
[31]
[32]
[33]
[34]
0885-8977 (c) 2013 IEEE. Personal use is permitted, but republication/redistribution requires IEEE permission. See
http://www.ieee.org/publications_standards/publications/rights/index.html for more information.