Escolar Documentos
Profissional Documentos
Cultura Documentos
Vortex Tube
Edited by
Ihsan
Dogramac Bilkent
University
Contents
1 Introduction
3.1
Dimension Effects . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3.2
3.3
Resulting Design . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4 References
12
Introduction
The vortex tube also known as the Ranque-Hilsch vortex tube separates a compressed gas
into hot and cold streams adiabatically. Tube consist of two arms, one is short for cold
stream, other is long with a conical valve for hot stream at the end. Compressed air enters
the tube through a tangential nozzle, goes along the longer arm, hits on the conical valve.
[1]After this instance, some part of the flow exits the tube as cold stream and rest is returns
along longer side of he tube to shorter side and exits the tube as hot stream.
The most advantageous side of the tube is, not containing any moving part, it is a
stationary structure which gives it a high reliability and long life in operation. Heat transfer
to or from the tube is negligible due to well insulation. Irreversibilities and thus exergy
destruction is inevitable due to pressure drops and friction effects within the tube.
Its aim is spot cooling and usage areas can vary from industry to space applications.
Below you can examine an illustration of vortex tube. Blue is hot stream, red is cold stream
and yellow one is the entering compressible air passing from a tangential nozzle.
In this example, operation of the system will be modeled with first and second laws of
engineering thermodynamics.[7]. This will be done on an exemplary vortex tube.
Temperatures
p1 = 5 bar
T1 = 21C
p2 = 1 bar
T2 = 79C
0.4m
kg
s
p3 = 1 bar
T3 =-18C
0.6m
kg
s
kg
s
X
X
dEcv
V2
V2
+
= Q W
m
i (hi + i + gzi )
m
e (he + e + gze )
dt
2
2
(1)
Kinetic energy and potential energy contributions are neglected. As stated above system
is adiabatic, no work is done by or on the system, and system operates at steady state. After
these notices, first law reduces to:
0=
m
i hi
m
e he
mh
1 = 0.6mh
3 + 0.4mh
2
(2)
(Assuming constant specific heats because of incompressible flow with taking cp = 1.0kJ/kg.K
and applying formula cp 4T can also be used as the book does. We choose to get values of
entalphys from the table.) When the values are put to entalphys, LHS and RHS of the first
law results in zero which shows us that the obeys the law.
Second Law Analysis of the System:
Second law for open systems in differential form is as follows:
X
dScv X Q i X
=
+
m
i si
m
e se +
dt
Tbi
(3)
System operates at steady state, no heat transfer to the surroundings, no work is done on
or by the system, so that equation reduces to:
0=
m
i si
m
e se +
(4)
Now take m1 as inlet, m2 as hot mass flow rate, m3 as cold mass flow rate, rewrite the
equation as :
3
0 = (m
2+m
3 )s1 m
2 s2 m
3 s3 +
(5)
0 = 0.4m
1 (s 1 s 2 ) + 0.6m
1 (s 1 s 3 ) +
(6)
m
1
T2
p2
T3
p3
(7)
After the given values in the table inserted in to the equation, result is as below:
m
1
= 0.454 kJ/kg.K > 0 as it should be, since otherwise would be a violation of the
second law.
Thus, in conclusion, given the values of pressure, temperature and mass flow rates, such
a device does exists since it obeys first and second law of thermodynamics. Apart from that,
given values also give idea about the operational data of the vortex tube. Such manipulations
can be done on the thermodynamic properties of the inlet and exit flows. In the rest of the
report the design of a custom vortex tube done by literature scan will be given.[2]
The analytical solution to radial temperature distribution within tube is still a vivid research
area. There is not any analytical solution to the phenomenon exists, and only the most
advanced CFD analyses can give good approximations. Main design parameters that effect
the performance of a vortex tube are inlet pressure, diameter of inlet orifice, diameter of
nozzle, length to diameter (L/D) ratio and cold mass fraction. These parameters are not
independent but also affect each other. According to the researches, the choice of these
factors that are used in the design will be given with reasons.
3.1
Dimension Effects
Performance of the vortex tube changes according to the chosen length and length to the
diameter ratio, however there is not any best performance parameter before design. Researches on this area are on a chosen length and diameter of the tube, then optimizing the
other parameters for best performance for these two parameters. There is no best diameter
for the system, however there is a best L/D ratio for every chosen tube diameter. According
to the Prabakaran[3] et al and considering the manufacturing of tube within the machine
shop, tube diameter is chosen as 12mm, corresponding best L/D according to the Prabakaran
et al came up to be 15 for this diameter, therefore corresponding hot arm length is 180mm.
Corresponding nozzle and orifice diamater, inlet pressure and their corresponding temperature difference between inlet temperature and cold exit is given below with their graphs
versus each other:
C. [1]
(a) Contour Plot of Pressure, Orifice Diameter and (b) Contour Plot of Pressure, Nozzle Diamater and
Temperature Gradient
Temperature Gradient
Figure 3: Contour Plot of Orifice Diamater, Nozzle Diameter and Temperature Gradient
Remark: All the plots include temperature gradient since the main purpose of the
vortex tube is spot cooling which can only be achieved by having a high temperature difference between inlet stream and cold stream. With the chosen design parameters, maximum
6
3.2
As a result of the cooling process, temperature difference between the inlet and the cold
exit is 16 C. With the dimensions of the design and based on the experimental results
from Pongjet Promvonges [2] research as seen in the plots below corresponding cold mass
fraction for 16 C is approximately 0.3 with ratio of orifice diameter to tube diameter (d/D)
is (5mm/12mm) 0.42.(where d is orifice diameter.) Despite of the fact that d/D ratio of 0.5
gives more efficient result according to the plot below, based on Prabakarans research which
claims d/D ratio is 5/12 gives the most efficient result.
(a) Cold Mass Fraction versus Temperature Differ- (b) Cold Mass Fraction versus Temperature Difference According to Orifice Diameter to tube Diameter ence According to Inlet Number
Ratio
Given temperature difference in the graphs is the difference between inlet stream temperature and cold stream temperature. According to our chosen parameters, temperature
difference came up to be 16 C, thus corresponding cold stream temperature would be 9 C
when the inlet stream temperature is room temperature.
Additionally, number of inlets affects the corresponding cold mass fraction. Considering manufacturability, design was made for 1 inlet even more inlet provides more efficient
performance according to plot above.
3.3
Resulting Design
According to the examination that is shown above of parameters and their effects on each
other, final design and its technical drawing is provided below.
10
17
12
KESKN KENARLARI
PAHLAYIN VE
KIRIN
BTRME:
MZA
TARH
REVZYON
BALIK:
ZEN
DENET.
ONAY.
RET.
KALTE
MALZEME:
RESM NO.
AIRLI:
LEK:1:5
vortextubedraw
SAYFA 1 / 1
10
A4
12
5
15
18
5
15
162.5
50
18
12
5
15
10
18
2
3
4
18
15
15
18
18
12
7,50
15
11
References
12