Input Data
system
( U ) No Load Voltage
Power Factor ( P.F )
Rated Voltage ( Vn )
Ampient Temperature
Max.conductor Temperature
Route length of Cable ( L )
Load Power ( PL )
o
Rated Current ( I L ) = PL / ( 3 x Vn x PF )
Cable selection is:
1
x ( 4 Core
Cable Ampacity =
Iz
=
=
=
=
=
=
=
=
=
3
415
0.80
415
40
90
300
60,000
=
x
165
104
70
A
INSTALLATION METHOD
INSTALLATION DETAILS
Multi-Core Cable
No Adjacent Circuit
Overhead
Unburied Circuit
150 A
>
>
=
=
=
=
0.91
1.00
165
1.25
150
130
=
=
=
=
P.F = cos()
Sin ()
0.321
0.08
0.80
0.600
0.53
( V D% ) = (V D cable *100 / V n)
3.99
<
V/Amp/Km
(V D x I L
16.54
3.99
4.0
Iz
=
=
104
165
A
Three pole rated current
(Iz)
phase
V
V
c
c
m
Watt
A
mm )
A
A
/Km
/Km
= 3 ( R
V/Amp/Km
(V D x I L x L)
(Iz)
V
%
A
A
S. No
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
Cross Section
Current
1.5
2.5
4
6
10
16
25
35
50
70
95
120
150
185
240
300
19.5
27
36
48
63
85
112
138
150
165
258
299
344
392
461
530
S. No
1
2
3
4
5
6
7
8
9
10
Temperatures
10
15
20
25
30
35
40
45
50
55
derating factor
1.15
1.12
1.08
1.04
1
0.96
0.91
0.87
0.82
0.76
Unburid Circuit
S. No
1
2
3
4
5
6
7
8
9
10
Temperatures
10
15
20
25
30
35
40
45
50
55
derating factor
1.07
1.04
1
0.96
0.93
0.89
0.85
0.8
0.76
0.71
1 Insaultated Conductor
2 Single-Core Cable
3 Multi-Core Cable
1
2
3
4
5
6
7
S. No
1
2
3
4
5
6
7
8
S. No
1
2
3
4
5
6
Embedded in structure
In Accessible Building Void
In Cable Chanel
In not Accessible Building Void
In The Ground
Overhead
Surface Mounted
Method of Installation
In Conduit
Conduit installed in thermal installation material
Cables Installed directly in thermal installation materials
Construction cavities and closed cable trenchs
Surface Mounted on Ceiling
placed in earthenware ducts; in conduits or in decorative Moulding
On Cable Ladder Or Perforated Cable Tray
Method of Installation
Unburied Circuit
Very wet soil
Wet Soil
Damp Soil
Dry Soil
Very Dray Soil
derating factor
0.9
0.77
0.7
0.95
0.95
0.8
1
1
derating factor
1
1.21
1.13
1.05
1
0.86
Cables Insta
0.7
S. No
1
2
3
4
5
6
7
Method of Installation
No Adjacent Circuit
1 Adjacent Circuit
2 Adjacent Circuit
3 Adjacent Circuit
4 Adjacent Circuit
5 Adjacent Circuit
6 Adjacent Circuit
derating factor
1
0.8
0.7
0.65
0.6
0.57
0.54
10
Temp
CSA
S. No
rating amp
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
10
16
20
25
30
40
50
60
80
100
125
160
200
250
320
400
500
630
800
6
5
1
1
Ins Meth 1 Ins Meth 2 Ins Det1 Ins Det2 C.B
14