Você está na página 1de 1

Short-circuit Coordination

Starter Type:

Direct-On-Line & Reversing, Trip Class 10


3C Starter: MCP + Contactor + OLR
140M-..N Magnetic Only
140MG UL 489 MCP
100-C, 100S-C, 100-D, 100S-D
193-E1 Plus, 193-E3, E3 Plus & E300
380-400 V, 50 Hz
436V 50 Hz, 483V 60 Hz
65 kA (rms sym.)
Type ''2'' (Type "1") per IEC 60947-4-1

Circuit Breaker:
Contactor:
Overload Relay:
Rated Operational Voltage:
Test voltage:
Rated Conditional S.C. Current (Iq):
Level of S.C. Coordination:

Motor Ratings
Rated
Operational
Current Ie
[kW]
[A] 1)

Circuit Breaker (MCP)


Catalog
Number
2)

Contactor

Magnetic
Trip Current
[A]

Catalog
Number
3)

O/L Relay 193-EE..


Current
Catalog
Setting
Number
Range
4)
[A]

O/L Relay 193-EC..


Current
Catalog
Setting
Number
Range
5)
[A]

S.C. Coordination
Test
Coordination Summary
Type
Letter
Remark

0.06

0.20

140M-C2N-B10

13

100-C09...

193-EEAB

0.1 - 0.5

---

0.09

0.30

140M-C2N-B10

13

100-C09...

193-EEAB

0.1 - 0.5

---

0.12

0.44

140M-C2N-B10

13

100-C09...

193-EEAB

0.1 - 0.5

193-EC1PB

0.4 - 2

---

0.18

0.60

140M-C2N-B10

13

100-C09...

193-EEBB

0.2 - 1.0

193-EC1PB

0.4 - 2

---

0.25

0.85

140M-C2N-B10

13

100-C09...

193-EEBB

0.2 - 1.0

193-EC1PB

0.4 - 2

---

0.37

1.1

140M-C2N-B16

20

100-C09...

193-EECB

1.0 - 5.0

193-EC1AB

1-5

---

0.55

1.5

140M-C2N-B16

20

100-C09...

193-EECB

1.0 - 5.0

193-EC1AB

1-5

---

0.75

1.9

140M-C2N-B25

32

100-C09...

193-EECB

1.0 - 5.0

193-EC1AB

1-5

---

1.1

2.7

140M-D8N-B40

52

100-C09...

193-EECB

1.0 - 5.0

193-EC1AB

1-5

1.5

3.6

140M-D8N-B40

52

100-C09...

193-EECB

1.0 - 5.0

193-EC1AB

1-5

2.2

4.9

140M-D8N-B63

82

100-C09...

193-EEDB

3.2 - 16

193-EC1BB

3 - 15

---

6.5

140M-D8N-C10

130

100-C09...

193-EEDB

3.2 - 16

193-EC1BB

3 - 15

---

8.5

140M-D8N-C10

130

100-C09...

193-EEDB

3.2 - 16

193-EC1BB

3 - 15

---

5.5

11.5

140M-D8N-C16

208

100-C12...

193-EEDB

3.2 - 16

193-EC1BB

3 - 15

---

7.5

15.5

140M-D8N-C16

208

100-C16...

193-EEDB

3.2 - 16

193-EC1CB

5 - 25

---

11

22

140M-D8N-C25

325

100-C23...

193-EEEB

5.4 - 27

193-EC1CB

5 - 25

---

15

29

140M-D8N-C32

448

100-C30...

193-EEFD

9 - 45

193-EC1DD

9 - 45

---

18.5

35

140M-F8N-C45

585

100-C37...

193-EEFD

9 - 45

193-EC1DD

9 - 45

---

22

41

140M-F8N-C45

585

100-C43...

193-EEFD

9 - 45

193-EC1DD

9 - 45

---

30

55

140MG-G8P-D12

375 - 1,375

100-C60...

193-EEGE

18 - 90

193-EC1EE

18 - 90

---

37

66

140MG-G8P-D12

375 - 1,375

100-C72...

193-EEGE

18 - 90

193-EC1EE

18 - 90

45

80

140MG-G8P-D12

375 - 1,375

100-C85...

193-EEGE

18 - 90

193-EC1EE

18 - 90

55

97

140MG-G8P-D12

375 - 1,375

100-C97...

193-EEVE

60 - 120

63

113

140MG-J8P-D25

1,250 - 2,500

100-D115...

193-EEHF

30 - 150

193-EC1FF

28 - 140

75

132

140MG-J8P-D25

1,250 - 2,500

100-D140...

193-EEJF

40 - 200

193-EC1GF

42 - 210

90

160

140MG-J8P-D25

1,250 - 2,500

100-D180...

193-EEJF

40 - 200

193-EC1GF

42 - 210

---

110

195

140MG-K8P-D40

400 - 4,000

100-D210...

193-EEJG

40 - 200

193-EC1GG

42 - 210

---

132

230

140MG-K8P-D40

400 - 4,000

100-D250...

193-EEKG

60 - 300

193-EC1HG

60 - 302

160

280

140MG-K8P-D40

400 - 4,000

100-D300...

193-EEKG

60 - 300

193-EC1HG

60 - 302

200

350

140MG-K8P-D40

400 - 4,000

100-D420...

193-EELG

100 - 500

193-EC1JG

84 - 420

---

250

430

140MG-M8P-D80

800 - 8,000

100-D630

193-EEMH

120 - 600

193-EC1KH

125 - 630

---

315

540

140MG-M8P-D80

800 - 8,000

100-D630

193-EEMH

120 - 600

193-EC1KH

125 - 630

355

610

140MG-M8P-D80

800 - 8,000

100-D630

193-EENH

160 - 800

193-EC1KH

125 - 630

400

690

140MG-M8P-D80

800 - 8,000

100-D860

193-EENH

160 - 800

193-EC1LH

172 - 860

450

770

140MG-M8P-D80

800 - 8,000

100-D860

193-EENH

160 - 800

193-EC1LH

172 - 860

---

500

850

140MG-M8P-D80

800 - 8,000

100-D860

193-EC1LH

172 - 860

---

--Type "2"

Type "2"

Typical motor currents according IEC 60947-4-1 Table G.1

2)

140MG "Max" circuit breaker size, lower current rating devices can be used. 140MG-G Frame can be replaced with the 140MG-H Frame

3)

Incomplete catalog number, add coil and auxiliary contact codes

4)

Overload relay 193-ED with the same current setting range may also be used (up to 45A)

5)

Overload relays 193-EC2 (up to 90 A), EC3, EC5 or E300 with the same current range may also be used

400V_3C_MCP_E_65kA

-------

Type "2"

Type "2"

TS-1037-1M

TS-1037-1M

---

-----

--Type "2"

Note: This data is subject to change by Rockwell Automation without notice. Go to www.rockwellautomation.com/go/globalsccr for latest information.

SCCR-1000A 040314 PH

TS-1037-1M

---

---

Heavy Duty Starting and High Inrush motors may require oversizing of circuit breaker and/or contactor
1)

TS-1000-1A

TS-1037-1M

-----

Você também pode gostar