61AF 022-105
Nominal heating capacity 22-105 kW
The new generation of Aquasnap high-temperature heat
pumps was designed for commercial applications such as
the heating of offices, apartments and hotels as well as
domestic hot water production in new and refurbished
buildings.
Features
Energy savings
Availability
-- Intelligent unit control permits unit operation in extreme
Quiet operation
Compressors
-- Low-noise scroll compressors with low vibration level.
-- The compressor assembly is installed on an independent
Environmental care
ratio (COP).
tightness.
(TXVs).
debris.
Physical features
-- The unit has a small footprint and a low height (1329 mm)
Economical operation
Superior reliability
State-of-the-art concept
-- Cooperation with specialist laboratories and use of limit
Pro-Dialog+ control
PRO-DIALOG+
No.
3A
15
15LS
Soft starter
Frost protection down to -20C
25
42
Low-pressure single-pump
hydronic module
JBus gateway
116F
BacNet gateway
148C
LonTalk gateway
148D
157
265
11
148B
267
Description
Fins made of pre-treated aluminium
(polyurethane or epoxy)
Fans with available pressure - max. 100 Pa
Advantages
Improved corrosion resistance, recommended for marine
environments
Enhances unit adjustment during installation (e.g. under
a roof)
Noise emission reduction
Noise emission reduction
Use
61AF 022-105
61AF 022-105
61AF 022-105
with option 116F
61AF 022-105
61AF 022-105
61AF 035-055
61AF 035-055
Description
Remotely installed user interface (via
communication bus).
Two-directional communications board,
complies with JBus protocol
Two-directional communications board,
complies with BacNet protocol
Two-directional communications board,
complies with LonTalk protocol
Unit equipped with an additional field-installed
leaving water temperature sensor, allowing
master/slave operation of two units connected
in parallel
Advantages
Remote heat pump control up to 300 m
Use
61AF 022-105
61AF 022-105
61AF 022-105
61AF 022-105
61AF 022-105
61AF 022-105
61AF 022-105
61AF 022-105
61AF 022-105
61AF 022-105
61AF 022-105
1.
The required protection level for this class is IP43BW (according to reference
document IEC 60529). All 61AF units are protected to IP44CW and fulfil this
protection condition.
Physical data
61AF
Nominal heating capacity*
Power input
Coefficient of performance (COP)
Eurovent class, heating
Nominal heating capacity**
Power input
Coefficient of performance (COP)
Eurovent class, heating
Operating weight***
Standard unit (without hydronic kit)
Standard unit (plus hydronic module option)
Sound levels
Sound power level 10-12 W****
Sound pressure level at 10 m
Compressor
Quantity
Number of capacity stages
Refrigerant
Charge
Capacity control
Minimum capacity
Condenser
Water volume
Max. water-side operating pressure without hydronic module
Max. water-side operating pressure with hydronic module
Fan
Quantity
Total air flow (high speed)
Speed, standard unit
Speed, unit with option 11
Evaporator
Hydronic module (option 116)
Three-speed single pump
Water connections with/without hydronic module
Connections
Outside diameter
Chassis paint colour
022
kW
20.8
kW
5.8
kW/kW 3.6
A
kW
21.2
kW
4.9
kW/kW 4.3
A
030
25.7
7.3
3.5
A
26.1
6.1
4.3
A
035
32.2
9.2
3.5
A
32.8
7.8
4.2
A
045
43.6
11.8
3.7
A
43.8
9.9
4.4
A
055
52.2
14
3.7
A
52.8
11.9
4.4
A
075
66.7
19.4
3.4
A
64.7
16.1
4.0
B
105
102
28.1
3.6
A
102
23.6
4.3
A
kg
kg
343
349
396
403
421
436
509
524
533
549
900
926
1020
1046
dB(A)
dB(A)
81
82
83
83
50
51
51
51
Hermetic scroll 48.3 r/s
1
1
1
1
1
1
1
1
R-407C
8.0
8.8
9.7
10.0
Pro-Dialog+
100
100
100
100
Direct-expansion plate heat exchanger
4.9
6.4
8.2
9.6
1000
1000
1000
1000
400
400
400
400
Axial with rotating shroud, Flying Bird IV
1
1
1
1
3800
3800
3800
3800
12
12
12
12
16
16
16
16
Grooved copper tubes and aluminium fins
84
53
84
52
85
53
1
1
2
2
2
2
13.2
22.0
26.5
100
50
50
12.1
1000
400
16.4
1000
400
22.7
1000
400
1
3800
12
16
2
7600
12
16
2
7600
12
16
kg
%
l
kPa
kPa
l/s
r/s
r/s
inch
mm
Pump, Victaulic screen filter, safety valve, purge valves (water and air), cavitation presssure sensor
Victaulic
1-1/4
1-1/4
1-1/2
1-1/2
1-1/2
2
2
42.4
42.4
48.3
48.3
48.3
60.3
60.3
Colour code: RAL 7035
* Standardised Eurovent conditions: entering leaving condenser water temperature = 40C/45C, outside air temperature db/wb = 7C/6C
** Standardised Eurovent conditions: entering leaving condenser water temperature = 30C/35C, outside air temperature db/wb = 7C/6C
*** Weight shown is a guideline only. To find out the unit refrigerant charge, please refer to the unit nameplate..
**** In accordance with ISO 9614-1 and certified by Eurovent. The values have been rounded and are for information only and not contractually binding
For information, calculated from the sound power level Lw(A)
Units 61AF 022 and 61AF 030 include two sleeves for a 1-1/4 Victaulic to 1-1/4 screw connection as standard.
Electrical data
61AF - standard unit (without hydronic module)
Power circuit
Nominal power supply
Voltage range
Control circuit supply
Maximum start-up current (Un)*
Standard unit
Unit with electronic starter option
Unit power factor at maximum capacity**
Maximum unit power input**
Nominal unit current draw***
Maximum unit current draw (Un)****
Maximum unit current draw (Un-10%)
Customer-side unit power reserve
Short-circuit stability and protection
022
030
035
045
V-ph-Hz
V
400-3-50
360-440
24 V, via internal transformer
A
A
104.6
102.6
131.0
171.0
56.1
55.1
70.0
90.8
0.82
0.82
0.82
0.82
8.7
11.6
12.9
14.6
14.3
16.9
20.2
23.2
16.1
21.3
24.1
27.1
21.1
28.4
32.2
36.4
Customer reserve at the 24 V control power circuit
See table on the next page
kW
A
A
A
055
075
105
191.0
101.2
0.82
16.8
27.9
31.1
42.0
154.5
101.5
0.82
25.8
39.7
47.5
63.7
221.5
142.5
0.82
33.7
55.1
61.5
83.3
* Maximum instantaneous start-up current (maximum operating current of the compressor + fan current + locked rotor current of the compressor).
** Power input, compressor and fan, at the unit operating limits (saturated suction temperature 10C, saturated condensing temperature 65C) and nominal voltage of 400 V (data given on the unit
nameplate).
*** Standardised Eurovent conditions: condenser entering/leaving water temperature = 40C/45C, outside air temperature db/wb = 7C/6C.
**** Maximum unit operating current at maximum unit power input and 400 V (values given on the unit nameplate).
Maximum unit operating current at maximum unit power input and 360 V.
kA rms
17
40
030
035
045
055
075
105
0.6
4.5
0.6
4.5
1.26
6
1.26
6
1.26
6
2
10
7
7
7.7
7.7
6.1
10
40
40
50
63
80
100
5SY6340-7 5SY6340-7 5SY4350-7 5SY4363-8 5SP4380-7 5SP4391-7
50
40
50
40
50
63
50
63
14.5
80
22
125
Operating limits
Plate heat exchanger water flow rate
Operating range
61AF
Condenser
Entering water temperature at start-up
Leaving water temperature during operation
Entering/leaving water temperature difference
Evaporator
Entering air temperature, standard unit*
Entering air temperature, unit with option 11
C 8
C 30
K 3
57
65
**
C -20
C -15
40
40
* Outside temperature: For transport and storage of the 61AF units the minimum and maximum
allowable temperatures are -20C and +50C. It is recommended that these temperatures
are used for transport by container.
** Refer to the minmum unit flow rate.
Note: Do not exceed the maximum operating temperature.
65
Leaving water temperature, C
60
55
50
45
40
35
30
25
-25 -20 -15 -10
-5
10
15 20
25
Full load
022
030
035
045
055
075
105
30
35 40
45
Maximum**
without hydronic module
1.8
2.4
3.1
3.8
4.6
6.4
8.5
70
20
61AF
Minimum Maximum
Note: For a domestic hot water application (leaving water temperature = 65C), the water
temperature difference must be at least 8 K.
Dimensions/clearances
1110
300
1330
1327
1000
1000
1000
Legend
1000
Control box
NOTES:
Non-certified drawings.
Refer to the certified dimensional drawings
supplied with the unit or available on request,
when designing an installation. For the location of
fixing points, weight distribution and coordinates
of the centre of gravity refer to the certified
dimensional drawings.
B In multiple-unit installations (maximum four units),
the side clearance between the units should be
increased from 1000 to 2000 mm.
C The height of the solid surface must not exceed
2 m.
A
2100
300
1330
1114
1000
1000
1000
1000
Dimensions/clearances (continued)
Legend
2273
2100
1330
300
Water outlet
2261
1000
1000
Control box
NOTES:
Non-certified drawings.
Refer to the certified dimensional drawings
supplied with the unit or available on request,
when designing an installation. For the location of
fixing points, weight distribution and coordinates
of the centre of gravity refer to the certified
dimensional drawings.
B In multiple-unit installations (maximum four units),
the side clearance between the units should be
increased from 1000 to 2000 mm.
C The height of the solid surface must not exceed
2 m.
A
2053
1000
1000
Heating capacities
Outside air temperature, C
-20
-15
-10
-5
0
2
5
61AF EWT Cap Unit Flow Dp Cap Unit Flow Dp Cap Unit Flow Dp Cap Unit Flow Dp Cap Unit Flow Dp Cap Unit Flow Dp Cap Unit Flow Dp
022
030
035
045
055
075
105
022
030
035
045
055
075
105
022
030
035
045
055
075
105
022
030
035
045
055
075
105
022
030
035
045
055
075
105
022
030
035
045
055
075
105
022
030
035
045
055
075
105
C
25
30
35
40
45
50
55
kW
10.2
10.1
15.6
20.0
25.6
32.0
47.6
9.8
10.2
15.7
18.7
25.6
31.8
47.8
10.0
10.4
15.9
18.7
25.7
31.7
48.1
10.1
9.5
16.1
19.1
25.9
31.7
48.5
10.4
9.3
15.9
17.0
25.8
31.8
49.0
10.7
10.5
16.3
18.9
26.6
32.0
49.7
-
kW
4.80
5.70
6.60
8.50
9.40
14.0
19.3
5.20
5.90
7.10
9.10
10.0
14.9
20.6
5.50
6.20
7.70
9.60
10.6
15.9
22.0
5.90
6.60
8.30
10.3
11.5
17.0
23.5
6.30
7.10
9.00
11.1
12.7
18.1
25.0
6.80
7.60
9.70
12.1
14.1
19.4
26.7
-
l/s
0.49
0.58
0.75
0.96
1.23
1.54
2.29
0.47
0.49
0.76
0.89
1.23
1.53
2.30
0.48
0.50
0.77
0.89
1.24
1.53
2.32
0.48
0.45
0.78
0.91
1.25
1.53
2.34
0.50
0.44
0.76
0.81
1.23
1.54
2.37
0.51
0.50
0.78
0.90
1.27
1.55
2.41
-
kPa
1
1
1
1
2
2
4
1
1
1
1
2
2
3
1
1
1
1
2
2
3
1
1
1
1
2
2
3
1
1
1
1
2
2
3
1
1
1
1
2
2
3
-
Legend
EWT
Cap kW
Unit kW
Flow l/s
Dp kPa
kW
12.1
13.1
18.1
24.4
29.9
37.6
54.9
11.8
13.1
18.2
23.4
29.8
37.3
55.1
11.9
13.2
18.3
23.3
29.8
37.1
55.4
12.0
12.5
18.5
23.5
30.0
37.1
55.9
12.2
12.3
18.7
21.8
30.4
37.1
56.6
12.5
13.2
18.9
23.3
31.0
37.3
57.5
-
kW
4.80
5.70
6.80
8.70
10.0
14.4
19.9
5.20
6.00
7.30
9.30
10.6
15.4
21.4
5.50
6.30
7.90
9.90
11.3
16.4
23.0
5.90
6.70
8.60
10.6
12.2
17.6
24.7
6.40
7.30
9.30
11.5
13.3
18.9
26.6
6.90
7.90
10.0
12.5
14.6
20.4
28.7
-
l/s
0.58
0.58
0.87
1.17
1.43
1.80
2.64
0.57
0.62
0.87
1.12
1.43
1.79
2.65
0.57
0.63
0.88
1.11
1.44
1.79
2.67
0.58
0.60
0.89
1.12
1.45
1.79
2.70
0.58
0.59
0.90
1.04
1.47
1.79
2.73
0.60
0.63
0.92
1.11
1.50
1.81
2.78
-
kPa
2
1
2
3
3
3
5
2
1
2
3
3
3
5
2
1
2
3
3
3
5
2
1
2
3
3
3
5
2
1
2
3
3
3
5
2
1
2
3
3
3
5
-
kW
13.9
16.0
21.0
28.5
34.5
43.8
64.0
13.9
15.9
20.9
28.2
34.4
43.4
63.9
13.9
15.9
21.0
28.0
34.3
43.2
64.0
14.0
15.4
21.1
27.9
34.4
43.0
64.4
14.1
15.3
21.2
28.0
34.7
43.1
64.9
14.3
16.0
21.4
27.7
35.1
43.2
65.7
14.9
16.6
20.9
28.7
36.6
43.9
67.7
kW
4.80
5.70
6.90
9.00
10.4
14.7
20.4
5.20
6.00
7.50
9.60
11.1
15.8
22.0
5.50
6.40
8.10
10.2
11.9
16.9
23.8
6.00
6.90
8.80
11.0
12.8
18.2
25.8
6.50
7.40
9.50
11.9
13.9
19.7
27.9
7.00
8.10
10.3
12.8
15.2
21.2
30.3
8.30
9.60
12.1
15.3
18.4
24.3
34.6
l/s
0.67
0.77
1.01
1.37
1.66
2.10
3.08
0.67
0.76
1.01
1.36
1.65
2.09
3.07
0.67
0.76
1.01
1.35
1.65
2.08
3.08
0.67
0.74
1.02
1.35
1.66
2.08
3.11
0.68
0.73
1.03
1.35
1.67
2.08
3.14
0.69
0.76
1.04
1.32
1.70
2.09
3.18
0.36
0.40
0.50
0.68
0.89
1.07
1.64
kPa
2
2
3
3
4
4
6
2
2
2
3
4
4
6
2
2
2
3
3
4
6
2
2
2
3
3
4
6
2
2
2
3
3
4
6
2
2
2
3
3
4
6
1
1
1
1
1
1
2
kW
15.9
19.0
24.3
33.1
39.8
50.7
74.1
15.8
18.8
24.1
32.7
39.5
50.3
73.9
15.7
18.7
24.0
32.3
39.3
49.9
73.8
15.8
18.4
24.0
32.1
39.2
49.7
74.0
15.9
18.3
24.1
32.0
39.3
49.6
74.5
16.1
18.8
24.2
32.1
39.6
49.7
75.3
16.7
19.2
24.1
32.7
40.2
50.3
77.2
kW
4.80
5.80
7.00
9.20
10.7
14.9
20.9
5.20
6.10
7.60
9.80
11.5
16.1
22.6
5.60
6.60
8.30
10.5
12.3
17.4
24.5
6.00
7.20
9.00
11.3
13.3
18.8
26.7
6.50
7.80
9.70
12.3
14.3
20.3
29.0
7.10
8.50
10.5
13.3
15.6
22.0
31.7
8.50
10.2
12.4
15.9
18.7
25.2
36.4
l/s
0.76
0.91
1.16
1.59
1.91
2.44
3.56
0.76
0.91
1.16
1.57
1.90
2.42
3.55
0.76
0.90
1.16
1.56
1.89
2.41
3.56
0.76
0.88
1.16
1.55
1.89
2.40
3.57
0.77
0.88
1.16
1.55
1.90
2.40
3.60
0.78
0.90
1.17
1.55
1.92
2.41
3.65
0.41
0.46
0.58
0.79
0.96
1.22
1.87
kPa
3
3
3
5
5
5
8
3
3
3
4
5
5
8
3
2
3
4
4
5
8
3
2
3
4
4
5
8
3
2
3
4
4
5
8
3
2
3
4
4
5
8
1
1
1
1
1
1
2
kW
18.0
21.9
27.7
38.1
45.3
58.3
85.4
17.9
21.7
27.5
37.6
45.0
57.8
84.9
17.8
21.5
27.4
37.2
44.7
57.3
84.7
17.7
21.4
27.3
36.7
44.6
57.0
84.8
17.8
21.4
27.2
36.5
44.5
56.8
85.0
18.0
21.5
27.2
36.4
44.6
56.8
85.7
18.5
21.9
27.3
36.6
45.2
57.2
87.5
kW
4.60
5.60
6.90
9.10
10.8
14.7
21.2
4.90
6.00
7.60
9.80
11.7
16.0
22.9
5.30
6.50
8.20
10.6
12.6
17.3
24.9
5.80
7.10
9.00
11.5
13.6
18.8
27.1
6.40
7.70
9.70
12.4
14.7
20.5
29.7
7.00
8.50
10.6
13.6
16.0
22.3
32.6
8.40
10.2
12.4
16.1
19.1
25.7
37.5
l/s
0.87
1.05
1.33
1.83
2.17
2.80
4.10
0.86
1.04
1.32
1.81
2.16
2.78
4.09
0.86
1.03
1.32
1.79
2.16
2.76
4.08
0.86
1.03
1.32
1.77
2.15
2.75
4.09
0.86
1.03
1.32
1.76
2.15
2.75
4.11
0.87
1.04
1.32
1.76
2.16
2.75
4.15
0.45
0.52
0.65
0.89
1.08
1.39
2.12
kPa
4
3
4
6
6
7
11
3
3
4
6
6
6
10
3
3
4
5
6
6
10
3
3
4
5
5
6
10
3
3
4
5
5
6
10
3
3
4
5
5
6
10
1
1
1
1
1
2
3
kW
19.0
23.2
29.2
40.1
47.5
61.6
90.2
18.8
22.9
29.0
39.6
47.2
61.0
89.7
18.6
22.7
28.8
39.1
46.9
60.5
89.4
18.6
22.5
28.6
38.7
46.7
60.1
89.4
18.6
22.5
28.6
38.4
46.7
59.9
89.6
18.7
22.6
28.6
38.2
46.7
59.8
90.1
19.2
23.0
28.6
38.4
47.2
60.2
91.9
kW
4.60
5.60
7.00
9.10
10.8
14.8
21.2
4.90
6.10
7.60
9.80
11.7
16.0
23.0
5.30
6.50
8.30
10.6
12.6
17.5
25.0
5.80
7.10
9.00
11.5
13.6
19.0
27.3
6.40
7.80
9.80
12.6
14.8
20.7
29.9
7.00
8.60
10.7
13.7
16.1
22.6
32.9
8.50
10.3
12.5
16.3
19.2
26.0
37.9
l/s
0.91
1.11
1.40
1.93
2.28
2.96
4.33
0.90
1.10
1.39
1.90
2.27
2.93
4.31
0.90
1.09
1.39
1.88
2.26
2.91
4.31
0.90
1.09
1.38
1.87
2.25
2.90
4.31
0.90
1.09
1.38
1.86
2.26
2.89
4.33
0.91
1.09
1.38
1.85
2.26
2.90
4.36
0.47
0.56
0.70
0.93
1.15
1.46
2.23
kPa
4
4
5
6
6
7
12
4
4
4
6
6
7
12
4
4
4
6
6
7
11
4
3
4
6
6
7
11
4
3
4
5
6
7
11
4
3
4
5
6
6
11
1
1
1
1
2
2
3
kW
20.4
25.2
31.6
41.3
50.3
63.1
97.6
20.2
24.8
31.2
41.8
50.4
63.8
97.2
20.0
24.6
30.9
42.1
50.2
64.7
96.8
19.9
24.4
30.7
41.7
50.0
65.0
96.6
19.9
24.3
30.6
41.3
49.8
64.7
96.8
19.9
24.3
30.5
41.1
49.8
64.6
97.2
20.4
24.6
30.6
41.1
50.3
64.8
98.6
kW
4.60
5.70
7.00
9.00
10.9
14.8
21.7
4.90
6.10
7.70
9.80
11.8
16.1
23.4
5.30
6.60
8.40
10.7
12.8
17.6
25.4
5.80
7.20
9.10
11.7
13.9
19.3
27.8
6.40
7.90
10.0
12.7
15.0
21.1
30.4
7.00
8.70
10.9
13.9
16.4
23.0
33.5
8.50
10.5
12.7
16.6
19.5
26.5
38.6
l/s
0.98
1.21
1.52
1.98
2.42
3.03
4.69
0.97
1.19
1.50
2.01
2.43
3.07
4.67
0.96
1.18
1.49
2.03
2.42
3.12
4.66
0.96
1.18
1.48
2.01
2.41
3.13
4.66
0.96
1.17
1.48
2.00
2.41
3.13
4.67
0.97
1.18
1.48
1.99
2.41
3.13
4.71
0.49
0.60
0.74
1.00
1.22
1.57
2.39
kPa
5
4
5
7
7
8
14
4
4
5
7
7
8
13
4
4
5
7
7
8
13
4
4
5
6
7
8
13
4
4
5
6
6
8
13
4
4
4
6
6
7
12
1
1
1
2
2
2
3
Application data
Entering water temperature
Heating capacity
Unit power input
Condenser water flow rate
Condenser pressure drop
Heating capacities
Outside air temperature, C
7
10
15
20
25
30
35
61AF EWT Cap Unit Flow Dp Cap Unit Flow Dp Cap Unit Flow Dp Cap Unit Flow Dp Cap Unit Flow Dp Cap Unit Flow Dp Cap Unit Flow Dp
022
030
035
045
055
075
105
022
030
035
045
055
075
105
022
030
035
045
055
075
105
022
030
035
045
055
075
105
022
030
035
045
055
075
105
022
030
035
045
055
075
105
022
030
035
045
055
075
105
C
25
30
35
40
45
50
55
kW
21.5
26.5
33.3
42.8
51.4
64.1
102
21.2
26.1
32.8
43.6
51.9
64.7
102
20.9
25.9
32.5
44.1
52.0
65.6
102
20.8
25.7
32.2
43.6
52.2
66.7
102
20.8
25.5
32.0
43.3
52.0
67.8
102
20.8
25.5
31.9
43.1
51.9
67.9
102
21.1
25.7
31.8
42.8
52.3
68.0
103
kW
4.60
5.70
7.10
9.10
10.9
14.8
21.9
4.90
6.10
7.70
9.90
11.9
16.1
23.6
5.30
6.70
8.50
10.8
12.9
17.7
25.7
5.80
7.30
9.20
11.8
14.0
19.4
28.1
6.40
8.00
10.1
12.8
15.2
21.3
30.8
7.10
8.80
11.0
14.1
16.5
23.3
33.9
8.60
10.6
12.9
16.8
19.6
26.8
39.1
l/s
1.03
1.27
1.60
2.04
2.47
3.08
4.90
1.02
1.26
1.58
2.08
2.49
3.11
4.89
1.01
1.25
1.56
2.11
2.51
3.16
4.90
1.00
1.24
1.55
2.08
2.52
3.22
4.90
1.00
1.23
1.55
2.07
2.51
3.28
4.92
1.01
1.23
1.55
2.06
2.52
3.29
4.94
0.51
0.62
0.77
1.02
1.27
1.65
2.51
kPa
5
5
6
7
7
8
15
5
5
6
7
7
8
15
5
4
5
7
7
8
14
4
4
5
7
7
8
14
4
4
5
7
7
8
14
4
4
5
6
7
8
14
1
1
1
2
2
2
4
Legend
EWT
Cap kW
Unit kW
Flow l/s
Dp kPa
kW
23.0
28.6
36.0
44.6
52.4
66.2
109
22.8
28.1
35.4
46.1
53.2
66.7
108
22.5
27.8
35.0
47.0
53.5
67.3
108
22.3
27.6
34.6
46.6
53.8
68.1
108
22.1
27.4
34.3
46.2
53.6
69.3
109
22.1
27.4
34.1
45.9
53.4
70.8
110
22.4
27.4
33.9
45.5
53.6
73.1
111
kW
4.60
5.70
7.20
9.10
10.9
14.8
22.3
4.90
6.10
7.80
9.90
12.0
16.2
24.0
5.40
6.70
8.60
10.8
13.1
17.7
26.1
5.80
7.30
9.30
11.9
14.2
19.4
28.5
6.40
8.10
10.2
13.0
15.4
21.3
31.3
7.10
8.90
11.1
14.3
16.8
23.5
34.5
8.60
10.8
13.0
17.0
19.9
27.2
39.6
l/s
1.11
1.37
1.73
2.13
2.50
3.18
5.23
1.09
1.35
1.70
2.20
2.54
3.21
5.20
1.08
1.34
1.68
2.25
2.56
3.24
5.20
1.07
1.33
1.67
2.22
2.57
3.28
5.22
1.07
1.33
1.66
2.21
2.56
3.35
5.25
1.07
1.33
1.65
2.19
2.55
3.43
5.31
0.54
0.67
0.82
1.09
1.28
1.77
2.69
kPa
6
6
7
8
8
9
17
5
5
6
8
8
8
16
5
5
6
8
8
8
16
5
5
6
8
8
8
16
5
5
6
8
7
9
16
5
5
5
7
7
9
16
1
1
2
2
2
2
4
kW
23.2
32.1
40.4
47.8
55.1
69.7
121
23.5
31.7
39.8
50.2
56.7
70.1
120
23.9
31.3
39.3
52.0
57.3
70.8
119
24.4
30.9
38.9
51.5
58.0
71.6
119
24.7
30.7
38.5
51.1
57.5
72.5
120
24.5
30.6
38.1
50.7
57.2
73.7
120
24.5
30.6
37.4
49.9
57.3
75.8
122
kW
4.60
5.70
7.30
9.20
11.0
14.8
23.2
4.90
6.20
8.00
10.1
12.2
16.2
24.8
5.40
6.80
8.70
11.0
13.3
17.8
26.8
5.80
7.40
9.50
12.1
14.5
19.5
29.2
6.40
8.20
10.4
13.3
15.8
21.5
32.1
7.10
9.10
11.4
14.6
17.2
23.7
35.4
8.70
11.1
13.3
17.5
20.3
27.4
40.4
l/s
1.11
1.54
1.94
2.28
2.63
3.35
5.81
1.13
1.53
1.92
2.40
2.71
3.37
5.76
1.15
1.51
1.90
2.48
2.74
3.41
5.73
1.18
1.49
1.88
2.46
2.77
3.45
5.74
1.19
1.49
1.86
2.44
2.75
3.50
5.77
1.19
1.48
1.84
2.42
2.74
3.57
5.82
0.60
0.74
0.91
1.19
1.37
1.84
2.96
kPa
6
7
8
9
8
9
21
6
7
8
10
9
9
20
6
6
7
10
9
9
19
6
6
7
10
9
9
19
6
6
7
9
8
9
19
6
6
7
9
8
9
19
2
2
2
2
2
3
5
kW
23.2
35.3
38.2
50.9
58.9
73.3
123
23.5
34.9
42.9
54.4
61.2
73.7
124
23.9
34.6
42.3
56.9
62.2
74.3
126
24.4
34.4
41.8
56.4
63.2
75.1
128
24.9
34.3
41.2
55.9
62.6
76.1
130
25.6
34.1
40.6
55.5
62.2
77.3
132
26.9
33.8
39.7
54.3
62.1
79.4
133
kW
4.60
5.60
7.40
9.30
11.1
14.9
23.3
4.90
6.20
8.10
10.2
12.3
16.3
25.1
5.30
6.80
8.90
11.1
13.6
17.9
27.3
5.80
7.50
9.70
12.3
14.9
19.7
29.8
6.40
8.40
10.6
13.6
16.2
21.7
32.8
7.10
9.30
11.6
15.0
17.6
23.9
36.3
8.70
11.3
13.6
17.9
20.7
27.6
41.2
l/s
1.11
1.70
1.83
2.43
2.81
3.52
5.92
1.13
1.68
2.05
2.60
2.92
3.55
5.99
1.15
1.67
2.02
2.72
2.97
3.58
6.07
1.18
1.66
2.00
2.69
3.02
3.62
6.17
1.21
1.66
1.97
2.67
2.99
3.68
6.29
1.24
1.65
1.94
2.65
2.97
3.74
6.37
0.65
0.82
0.95
1.30
1.48
1.93
3.23
kW
23.2
38.7
39.6
54.0
62.7
76.9
126
23.5
38.4
46.2
58.6
65.7
77.3
127
23.9
38.1
45.5
61.9
67.1
77.8
128
24.4
37.8
45.0
61.3
68.4
78.6
130
24.9
37.6
44.2
60.8
67.7
79.6
132
25.6
37.3
43.5
60.3
67.1
80.9
135
27.1
37.0
42.2
58.7
66.9
83.0
139
kW
4.50
5.90
7.50
9.40
11.2
14.9
23.4
4.90
6.40
8.30
10.3
12.5
16.3
25.2
5.30
7.10
9.10
11.2
13.8
18.0
27.4
5.80
7.80
9.90
12.5
15.2
19.8
30.0
6.40
8.70
10.9
13.9
16.6
21.8
33.0
7.10
9.60
11.8
15.3
18.0
24.2
36.5
8.70
11.7
14.0
18.4
21.1
27.9
41.6
l/s
1.11
1.85
1.89
2.58
2.99
3.70
6.03
1.13
1.84
2.21
2.80
3.14
3.72
6.10
1.15
1.82
2.17
2.96
3.21
3.75
6.18
1.18
1.81
2.15
2.93
3.27
3.79
6.27
1.21
1.80
2.11
2.90
3.23
3.85
6.40
1.24
1.78
2.08
2.88
3.21
3.91
6.55
0.66
0.88
1.01
1.40
1.60
2.01
3.38
kPa
6
10
8
11
11
11
22
6
10
10
13
12
11
22
6
9
10
14
12
11
22
6
9
9
14
12
11
22
6
9
9
13
12
11
23
6
8
8
13
11
11
23
2
2
2
3
3
3
6
Application data
Entering water temperature
Heating capacity
Unit power input
Condenser water flow rate
Condenser pressure drop
10
kPa
6
8
7
10
10
10
22
6
8
9
11
10
10
21
6
8
8
12
10
10
21
6
7
8
12
10
10
22
6
7
8
11
10
10
22
6
7
7
11
10
10
22
2
2
2
3
3
3
6
kW
23.2
42.1
41.8
57.1
66.5
80.6
128
23.5
41.8
50.4
62.8
70.2
81.0
129
23.9
41.5
49.6
66.9
72.0
81.5
130
24.4
41.2
49.0
66.2
73.7
82.2
132
24.9
41.1
48.1
65.6
72.8
83.2
135
25.6
40.7
47.1
65.0
72.1
84.5
138
27.1
40.2
45.5
63.1
71.6
86.6
142
kW
4.50
5.70
7.60
9.50
11.3
14.9
23.6
4.90
6.50
8.40
10.4
12.7
16.4
25.3
5.30
7.20
9.20
11.3
14.1
18.0
27.5
5.80
8.00
10.1
12.7
15.6
19.9
30.1
6.40
8.90
11.1
14.1
16.9
22.0
33.1
7.10
9.90
12.1
15.7
18.4
24.4
36.7
8.70
12.0
14.3
18.8
21.5
28.1
41.7
l/s
1.11
2.01
2.00
2.73
3.18
3.87
6.14
1.13
2.00
2.41
3.00
3.35
3.90
6.21
1.15
1.98
2.37
3.19
3.44
3.93
6.29
1.18
1.97
2.34
3.16
3.52
3.97
6.38
1.21
1.96
2.30
3.14
3.48
4.02
6.51
1.24
1.94
2.25
3.11
3.44
4.09
6.66
0.66
0.96
1.09
1.51
1.71
2.10
3.44
kPa
6
12
9
13
12
12
23
6
11
12
15
13
12
23
6
11
12
17
14
12
23
6
11
11
16
14
12
23
6
10
11
15
13
12
23
6
10
10
15
13
12
24
2
3
3
4
3
3
7
kW
23.2
42.1
41.8
57.1
66.5
84.3
130
23.5
41.8
50.4
62.8
70.2
84.7
131
23.9
41.5
49.6
66.9
72.0
85.2
133
24.4
41.2
49.0
66.2
73.7
85.9
135
24.9
41.1
48.1
65.6
72.8
86.9
137
25.6
40.7
47.1
65.0
72.1
88.1
140
27.1
40.2
45.5
63.1
71.6
90.2
144
kW
4.50
5.70
7.60
9.50
11.3
14.9
23.7
4.90
6.50
8.40
10.4
12.7
16.4
25.5
5.30
7.20
9.20
11.3
14.1
18.1
27.6
5.80
8.00
10.1
12.7
15.6
20.0
30.2
6.40
8.90
11.1
14.1
16.9
22.1
33.3
7.00
9.90
12.1
15.7
18.4
24.6
36.9
8.70
12.0
14.3
18.8
21.5
28.3
41.8
l/s
1.11
2.01
2.00
2.73
3.18
4.05
6.25
1.13
2.00
2.41
3.00
3.35
4.07
6.32
1.15
1.98
2.37
3.19
3.44
4.10
6.40
1.18
1.97
2.34
3.16
3.52
4.14
6.49
1.21
1.96
2.30
3.14
3.48
4.20
6.62
1.24
1.94
2.25
3.11
3.44
4.27
6.77
0.66
0.96
1.09
1.51
1.71
2.19
3.49
kPa
6
12
9
13
12
13
24
6
11
12
15
13
13
24
6
11
12
17
14
13
24
6
11
11
16
14
13
24
6
10
11
15
13
13
24
6
10
10
15
13
13
25
2
3
3
4
3
4
7
15
18 19
17
14
16
22
14
12
16
17 20
13
19
11
10
21
Legend
Components of the unit and hydronic module
1 Victaulic screen filter
2 Pressure sensor
Note: Gives pump suction pressure information (see installation manual)
3 Safety valve
4 Water drain valve
5 Shut-off valve
6 Water pump
7 Temperature sensors, BPHE inlet
Note: Gives heat exchanger entering temperature information (see installation manual)
8 Pressure gauge
Note: Allows measuring of the pump suction pressure, the pump leaving pressure and the
heat exchanger leaving pressure
9 Temperature sensor, BPHE outlet
Note: Gives heat exchanger leaving temperature information (see installation manual)
10 Automatic air vent
11 Flow switch
12 Plate heat exchanger frost protection heater
13 Plate heat exchanger
Hydronic module
Installation components
14 Temperature probe well
15 Air vent
16 Flexible connection
17 Shut-off valve
18 Screen filter (obligatory for a unit without hydronic module)
19 Pressure gauge
20 Water flow control valve
21 Charge valve
22 Frost protection bypass valve (when shut-off valves [17] are closed during winter)
--- Hydronic module (unit with hydronic module)
Notes:
Units without hydronic module (standard units) are equipped with a flow switch and two
temperature sensors (7 and 9).
For units equipped with hydronic module, the pressure sensor located upstream of the pump
to prevent cavitation is installed on a connection without Schraeder valves. Depressurise
and drain the system before any intervention.
022
030
035
045
055
075
105
kg
349
403
436
524
549
926
1044
kPa
400
400
Victaulic screen filter
400
400
400
400
400
kW
kW
A
A
TOP-S 25
0.18
0.42
0.4
0.8
TOP-S 25
0.18
0.42
0.4
0.8
TOP-S40
0.35
0.63
0.6
1.3
TOP-S40
0.35
0.63
0.6
1.3
TOP-S40
0.35
0.63
0.7
1.3
TOP-S50
0.45
0.95
1.3
1.7
TOP-S50
0.45
0.95
1.5
1.7
inch
mm
1-1/4
42.4
1-1/4
42.4
1-1/2
48.3
1-1/2
48.3
1-1/2
48.3
2
60.3
2
60.3
* Weight shown is a guideline only. To find out the unit refrigerant charge, please refer to the unit nameplate.
** To obtain the maximum power input for a unit with hydronic module, add the maximum unit power input to the pump power input.
*** To obtain the maximum operating current draw for a unit with hydronic module, add the maximum unit current draw to the pump current draw.
11
Ensure that the suction or discharge inlets are not accidentally obstructed by the panel positioning (e.g. low return or
open doors etc.).
022
030
035
045
V-ph-Hz
V
400-3-50
360-440
24 V, via internal transformer
A
A
107,1
105,1
133,5
173,5
58,6
57,6
72,5
93,3
0,82
0,82
0,82
0,82
9,8
12,7
14
15,7
16,4
19
22,3
25,3
18,5
23,7
26,5
29,5
23,2
30,5
34,3
38,5
Customer reserve at the 24 V control power circuit
See table on page 6
kW
A
A
A
055
075
105
193,5
103,7
0,82
17,9
30
33,5
44,1
159,5
106,5
0,82
28
43,9
52,3
67,9
226,5
147,5
0,82
35,9
59,3
66,3
87,5
* Maximum instantaneous start-up current (maximum operating current of the compressor + fan current + locked rotor current of the compressor).
** Power input, compressor and fan, at the unit operating limits (saturated suction temperature 10C, saturated condensing temperature 65C) and nominal voltage of 400 V (data given on the unit
nameplate).
*** Standardised Eurovent conditions: condenser entering/leaving water temperature = 40C/45C, outside air temperature db/wb = 7C/6C.
**** Maximum unit operating current at maximum unit power input and 400 V (values given on the unit nameplate).
Maximum unit operating current at maximum unit power input and 360 V.
12
1327
300
1371
1110
1280
1000
1000
1
1000
1000
Legend
All dimensions are in mm
Water inlet
NOTES:
Non-certified drawings.
Refer to the certified dimensional drawings supplied with the unit or available on request,
when designing an installation. For the location of fixing points, weight distribution and
coordinates of the centre of gravity refer to the certified dimensional drawings.
In multiple-unit installations (maximum four units), the side clearance between the units
should be increased from 1000 to 2000 mm.
The height of the solid surface must not exceed 2 m.
Water outlet
Control box
13
1114
300
1371
2079
1000
1000
1000
2
1000
Legend
All dimensions are in mm
Water inlet
Water outlet
Control box
14
NOTES:
Non-certified drawings.
Refer to the certified dimensional drawings supplied with the unit or available on request,
when designing an installation. For the location of fixing points, weight distribution and
coordinates of the centre of gravity refer to the certified dimensional drawings.
In multiple-unit installations (maximum four units), the side clearance between the units
should be increased from 1000 to 2000 mm.
The height of the solid surface must not exceed 2 m.
2273
300
1371
2100
1000
1000
1
1000
Legend
All dimensions are in mm
1000
Water inlet
NOTES:
Non-certified drawings.
Refer to the certified dimensional drawings supplied with the unit or available on request,
when designing an installation. For the location of fixing points, weight distribution and
coordinates of the centre of gravity refer to the certified dimensional drawings.
In multiple-unit installations (maximum four units), the side clearance between the units
should be increased from 1000 to 2000 mm.
The height of the solid surface must not exceed 2 m.
Water outlet
Control box
15
61AF 055-105
30
50
3
20
10
16
20
10
30
15
40
25
0
1
2
3
4
1
61AF 022
61AF 030
61AF 035
61AF 045
2
1
2
3
61AF 055
61AF 075
61AF 105
4
6
Water flow rate, l/s
10
Pump pressure/flow rate curves for units with hydronic module - for pure water at 20C
The 61AF units are equipped with a fixed-speed pump
with three different speeds.
61AF
61AF 035-055
100
100
80
120
60
40
20
0
1
2
3
0,2
Maximum*
1.8
2.4
3.1
3.8
4.6
6.4
8.5
* Maximum flow rate at a water temperature difference of 3 K in the plate heat exchanger (unit
without hydronic module)
120
Minimum
0.4
0.5
0.7
0.8
0.9
1.1
1.5
022
030
035
045
055
075
105
61AF 022-030
0,4
0,6
0,8
1,0
1,2
1,4
1,6
3
2
80
1
60
40
20
1,8
2,0
0
1
2
3
0,4
0,8
1,2
1,6
2,0
Water flow rate, l/s
2,4
2,8
3,2
61AF 075-105
100
80
60
40
20
0
0
1
2
3
0,5
1,0
1,5
2,0
2,5
3,0
3,5
4,0
4,5
5,0
5,5
6,0
6,5
17
Available system pressure for units with hydronic module - for pure water at 20C
The available pressure curves for the 61AF units are given
for the speed initially selected. If the speed is changed by
the user, the curves below do not apply.
61AF
61AF 022-030
022
030
035
045
055
075
105
* Maximum flow rate at an available pressure of 15 kPa (unit with hydronic module).
61AF 035-055
100
100
90
80
70
80
60
50
40
30
20
10
0
0,4
0,6
0,8
1,0
1,2
1,4
60
40
3
20
1,6
1,8
0,5
1,0
1
2
61AF 022
61AF 030
61AF 075-105
100
80
60
40
18
20
1
1
2
2
61AF 075
61AF 105
4
Water flow rate, l/s
2,0
Water flow rate, l/s
1,5
1
2
3
61AF 035
61AF 045
61AF 055
2,5
3,0
3,5