High-Temperature Monobloc Air-to-Water Heat Pumps


with Integrated Hydronic Module

61AF 022-105
Nominal heating capacity 22-105 kW
The new generation of Aquasnap high-temperature heat
pumps was designed for commercial applications such as
the heating of offices, apartments and hotels as well as
domestic hot water production in new and refurbished
buildings.

Features

The main features of this product range are:

Energy savings

The 61AF range is certified to the Eurovent energy


efficiency class A with a coefficient of performance (COP)
of over 4. This complies with the COP required by the
Ecolabel certification.
Ease-of-installation
The high-temperature Aquasnap heat pumps incorporate
a hydronic module with a multi-speed pump, as standard.
An optional hydronic module with a variable-speed pump
that automatically adapts to the system requirements is
also available.
Easy integration
The low noise levels of the 61AF heat pump and its very
compact chassis reduce the noise disturbance from the unit.
Application flexibility
The operating range allows outside temperatures down to
-20C and leaving water temperatures up to 65C for
domestic hot water applications.

Availability
-- Intelligent unit control permits unit operation in extreme

conditions, minimising unit shut-down times.

-- Hot water production at 65C is available continuously.

Carrier quality is your guarantee for the safety and


durability of the installation.
The new generation of high-temperature heat pumps
incorporates the latest technological features:
-- scroll compressors with vapour injection
-- low-noise fans made of a composite material
-- auto-adaptative microprocessor control
-- electronic expansion valve
-- multi-speed pump.
The high-temperature Aquasnap heat pumps can be
equipped with a hydronic module that is integrated into
the heat pump chassis, limiting the installation to straightforward operations like the wiring and the connection of
the hot water supply and return piping.

Quiet operation

Compressors
-- Low-noise scroll compressors with low vibration level.
-- The compressor assembly is installed on an independent

chassis and supported by anti-vibration mountings.


-- Dynamic suction and discharge piping supports,
minimising vibration transmission (Carrier patent).
Evaporator section
-- Vertical evaporator coils
-- Protection grilles on anti-vibration mountings to protect
the heat exchanger against possible shocks.
-- Latest-generation low-noise Flying Bird fans, made of a
composite material (Carrier patent), are now even
quieter and do not generate intrusive low-frequency
noise.
-- Rigid fan installation for reduced start-up noise (Carrier
patent).

Environmental care

Ozone-friendly R-407C refrigerant


-- Chlorine-free refrigerant of the HFC group with zero

ozone depletion potential.

-- Very efficient - ensures an increased energy efficiency

ratio (COP).

Leak-tight refrigerant circuit


-- Brazed refrigerant connections for increased leak-

tightness.

-- Reduction of leaks due to elimination of capillary tubes

(TXVs).

-- Verification of pressure transducers and temperature

sensors without transferring refrigerant charge.

Easy and fast installation

Integrated hydronic module (option)


-- Multi-speed centrifugal water pump, based on the pressure

loss of the hydronic installation.

-- Water filter protects the water pump against circulating

debris.

-- Pump protected against cavitation by a pressure

transducer that measures the entering water pressure.

-- Overpressure valve, set to 4 bar.


-- Thermal insulation and frost protection down to -20C,

using an electric resistance heater (see table of options).

Physical features
-- The unit has a small footprint and a low height (1329 mm)

allowing it to blend in with any architectural styles.

-- The unit is enclosed by easily removable panels, covering

all components (except condensers and fans).

Simplified electrical connections


-- Single power supply point without neutral.
-- Main disconnect switch with high trip capacity.
-- Transformer for safe 24 V control circuit supply included.
Fast commissioning
-- Systematic factory operation test before shipment.
-- Quick-test function for step-by-step verification of the

instruments, electrical components and motors.

Economical operation

Increased energy efficiency


-- The exceptional energy efficiency level (COP) of the

high-temperature Aquasnap heat pumps in the heating


mode is the result of a long qualification and optimisation
process.
-- The electronic expansion device (EXV) allows operation
at a lower condensing pressure (COP optimisation).
-- Dynamic superheat management for better utilisation of
the condenser surface.
Reduced maintenance costs
-- Maintenance-free scroll compressors with vapour
injection.
-- Pro-Dialog+ control offers fast diagnosis of possible
incidents and their history.

Superior reliability

State-of-the-art concept
-- Cooperation with specialist laboratories and use of limit

simulation tools (finite element calculations) for the


design of the critical components, e.g. motor supports,
suction/discharge piping etc.
Auto-adaptive control
-- Control algorithm prevents excessive compressor
cycling and permits reduction of the water quantity in
the hydronic circuit (Carrier patent).
Exceptional endurance tests
-- Corrosion resistance tests in salt mist in the laboratory.
-- Accelerated ageing test on components that are
submitted to continuous operation: compressor piping,
fan supports.
-- Transport simulation test in the laboratory on a
vibrating table.

Pro-Dialog+ control

Pro-Dialog+ combines intelligence with operating simplicity.


The control constantly monitors all machine parameters
and precisely manages the operation of compressors,
expansion devices, fans and of the condenser water pump
for optimum energy efficiency.
Energy management
-- Seven-day internal time schedule clock: permits unit on/
off control and operation at a second set point.
-- Set point reset based on the outside air temperature or
the return water temperature or on the water heat
exchanger delta T.
-- Master/slave control of two heat pumps operating in
parallel with operating time equalisation and automatic
change-over in case of a unit fault (option).
-- Start/stop based on the outside air temperature.
Ease-of-use
-- The new backlighted LCD interface includes a manual
control potentiometer to ensure legibility under any
lighting conditions.
-- The information is displayed clearly in English, French,
German, Italian and Spanish (for other languages please
consult Carrier).
-- The Pro-Dialog+ navigation uses intuitive tree-structure
menus, similar to the Internet browers. They are userfriendly and permit quick access to the principal operating parameters: number of compressors operating, suction/
discharge pressure, compressor operating hours, set point,
air temperature, entering/leaving water temperature.
-- As standard the unit includes a board for the control of
a boiler and four electric resistance heater stages.

Pro-Dialog+ operator interface

Remote operating mode with volt-free contacts


(standard)

A simple two-wire communication bus between the RS485


port of the Aquasnap high-temperature heat pumps and
the Carrier Comfort Network offers multiple remote
control, monitoring and diagnostic possibilities.

Carrier offers a vast choice of control products, specially


designed to control, manage and supervise the operation of
a heating system. Please consult your Carrier representative
for more information on these products.
-- Start/stop: opening of this contact will shut down the
heat pump.
-- Dual set point: closing of this contact activates a second
heating set point (example: unoccupied mode).
-- Demand limit: closing of this contact limits the maximum
heat pump capacity to a predefined value.
-- User safety: this contact is connected in series with the
water flow switch and can be used for any customer
safety loop.
-- Water pump control.
-- Alert indication: this volt-free contact indicates the
presence of a minor fault.
-- Alarm indication: this volt-free contact indicates the
presence of a major fault that has led to the shut-down
of the refrigerant circuit.

Remote interface (accessory)

This accessory includes a box that can be mounted inside


the building. The power supply is provided via a 220 V/24 V
transformer supplied. This interface allows access to the
same menus as the unit interface and can be installed up
to 300 m from the 61AF unit.

Flying Bird IV fan

Circuit B Total Capacity

PRO-DIALOG+

Options and accessories


Options
Anti-corrosion protection,
traditional coils
Unit with discharge air ducts

No.
3A

Low noise level


Very low noise level

15
15LS

Soft starter
Frost protection down to -20C

25
42

Low-pressure single-pump
hydronic module
JBus gateway

116F

BacNet gateway

148C

LonTalk gateway

148D

Heating system control*

157

Water screw connection


between the customers
condenser and the unit
Welded water connection
between the customers
condenser and the unit
Accessories
Remote user interface

265

JBus gateway communication


BacNet gateway communication
LonTalk gateway communication
Twinning (lead-lag kit)

11

148B

267

Description
Fins made of pre-treated aluminium
(polyurethane or epoxy)
Fans with available pressure - max. 100 Pa

Advantages
Improved corrosion resistance, recommended for marine
environments
Enhances unit adjustment during installation (e.g. under
a roof)
Noise emission reduction
Noise emission reduction

Use
61AF 022-105

Reduced compressor start-up current


Hydronic module frost protection at low outside
temperature
Easy and fast installation

61AF 022-105
61AF 022-105
with option 116F
61AF 022-105

Two-directional communications board,


complies with JBus protocol
Two-directional communications board,
complies with BacNet protocol
Two-directional communications board,
complies with LonTalk protocol
Additional remotely installed control box,
allows control of the various heating system
components
Victaulic screw connection at the condenser
(standard on sizes 022-030)

Easy connection by communication bus to a building


management system
Easy connection by communication bus to a building
management system
Easy connection by communication bus to a building
management system
Allows control of pre-configured heating systems

61AF 022-105

Permits customer connections to be screwed to the unit

61AF 035-055

Welded Victaulic connection

Permits customer connections to be welded to the unit

61AF 035-055

Description
Remotely installed user interface (via
communication bus).
Two-directional communications board,
complies with JBus protocol
Two-directional communications board,
complies with BacNet protocol
Two-directional communications board,
complies with LonTalk protocol
Unit equipped with an additional field-installed
leaving water temperature sensor, allowing
master/slave operation of two units connected
in parallel

Advantages
Remote heat pump control up to 300 m

Use
61AF 022-105

Connection by communication bus to a building


management system
Connection by communication bus to a building
management system
Connection by communication bus to a building
management system
Operation of two units connected in parallel with operating
time equalisation

61AF 022-105

Acoustic compressor enclosure


Acoustic compressor enclosure and
fan speed reduction, when ambient air
temperature is above 20C.
Electronic compressor starter
Electric heater on the hydronic module (option
116)
See hydronic module chapter

61AF 022-105
61AF 022-105

61AF 022-105
61AF 022-105
61AF 022-105

61AF 022-105
61AF 022-105
61AF 022-105

* Option available in 2011.

Electrical data and operating conditions notes:


61AF 022-105 units have a single power connection point located immediately
upstream of the main disconnect switch.
The control box includes the following standard features:

-a main disconnect switch,

-starter and motor protection devices for the compressor, the fan and the
pump,

-the control devices.
Field connections:

All connections to the system and the electrical installations must be in full
accordance with all applicable local codes.
The Carrier 61AF units are designed and built to ensure conformance with
these codes. The recommendations of European standard EN 602041
(machine safety electrical machine components part 1: general regulations
- corresponds to IEC 60204-1) are specifically taken into account, when
designing the electrical equipment.
Notes:
Generally the recommendations of IEC 60364 are accepted as compliance
with the requirements of the installation directives. Conformance with EN
60204-1 is the best means of ensuring compliance with the Machinery
Directive 1.5.1.
Annex B of EN 602041 describes the electrical characteristics used for the
operation of the machines.

61AF 022-105


1.

The operating environment for the 61AF units is specified below:


Environment* Environment as classified in EN 60721 (corresponds to
IEC 60721):
outdoor installation*
ambient temperature range: 20C to +40C, class 4K4H
altitude: 2000 m
presence of hard solids, class 4S2 (no significant dust present)
presence of corrosive and polluting substances, class 4C2 (negligible)
2. Power supply frequency variation: 2 Hz.
3. The neutral (N) conductor must not be connected directly to the unit (if
necessary use a transformer).
4. Overcurrent protection of the power supply conductors is not provided with
the unit.
5. The factory-installed disconnect switch is of a type suitable for power
interruption in accordance with EN 60947-3 (corresponds to IEC 60947-3)
6. The units are designed for connection to TN networks (IEC 60364). For IT
networks the earth connection must not be at the network earth. Provide a
local earth, consult competent local organisations to complete the electrical
installation.

Caution: If particular aspects of an actual installation do not conform to


the conditions described above, or if there are other conditions which
should be considered, always contact your local Carrier representative.

The required protection level for this class is IP43BW (according to reference
document IEC 60529). All 61AF units are protected to IP44CW and fulfil this
protection condition.

Physical data
61AF
Nominal heating capacity*
Power input
Coefficient of performance (COP)
Eurovent class, heating
Nominal heating capacity**
Power input
Coefficient of performance (COP)
Eurovent class, heating
Operating weight***
Standard unit (without hydronic kit)
Standard unit (plus hydronic module option)
Sound levels
Sound power level 10-12 W****
Sound pressure level at 10 m
Compressor
Quantity
Number of capacity stages
Refrigerant
Charge
Capacity control
Minimum capacity
Condenser
Water volume
Max. water-side operating pressure without hydronic module
Max. water-side operating pressure with hydronic module
Fan
Quantity
Total air flow (high speed)
Speed, standard unit
Speed, unit with option 11
Evaporator
Hydronic module (option 116)
Three-speed single pump
Water connections with/without hydronic module
Connections
Outside diameter
Chassis paint colour

022
kW
20.8
kW
5.8
kW/kW 3.6
A
kW
21.2
kW
4.9
kW/kW 4.3
A

030
25.7
7.3
3.5
A
26.1
6.1
4.3
A

035
32.2
9.2
3.5
A
32.8
7.8
4.2
A

045
43.6
11.8
3.7
A
43.8
9.9
4.4
A

055
52.2
14
3.7
A
52.8
11.9
4.4
A

075
66.7
19.4
3.4
A
64.7
16.1
4.0
B

105
102
28.1
3.6
A
102
23.6
4.3
A

kg
kg

343
349

396
403

421
436

509
524

533
549

900
926

1020
1046

dB(A)
dB(A)

81
82
83
83
50
51
51
51
Hermetic scroll 48.3 r/s
1
1
1
1
1
1
1
1
R-407C
8.0
8.8
9.7
10.0
Pro-Dialog+
100
100
100
100
Direct-expansion plate heat exchanger
4.9
6.4
8.2
9.6
1000
1000
1000
1000
400
400
400
400
Axial with rotating shroud, Flying Bird IV
1
1
1
1
3800
3800
3800
3800
12
12
12
12
16
16
16
16
Grooved copper tubes and aluminium fins

84
53

84
52

85
53

1
1

2
2

2
2

13.2

22.0

26.5

100

50

50

12.1
1000
400

16.4
1000
400

22.7
1000
400

1
3800
12
16

2
7600
12
16

2
7600
12
16

kg
%
l
kPa
kPa
l/s
r/s
r/s

inch
mm

Pump, Victaulic screen filter, safety valve, purge valves (water and air), cavitation presssure sensor
Victaulic
1-1/4
1-1/4
1-1/2
1-1/2
1-1/2
2
2
42.4
42.4
48.3
48.3
48.3
60.3
60.3
Colour code: RAL 7035

* Standardised Eurovent conditions: entering leaving condenser water temperature = 40C/45C, outside air temperature db/wb = 7C/6C
** Standardised Eurovent conditions: entering leaving condenser water temperature = 30C/35C, outside air temperature db/wb = 7C/6C
*** Weight shown is a guideline only. To find out the unit refrigerant charge, please refer to the unit nameplate..
**** In accordance with ISO 9614-1 and certified by Eurovent. The values have been rounded and are for information only and not contractually binding
For information, calculated from the sound power level Lw(A)
Units 61AF 022 and 61AF 030 include two sleeves for a 1-1/4 Victaulic to 1-1/4 screw connection as standard.

Electrical data
61AF - standard unit (without hydronic module)
Power circuit
Nominal power supply
Voltage range
Control circuit supply
Maximum start-up current (Un)*
Standard unit
Unit with electronic starter option
Unit power factor at maximum capacity**
Maximum unit power input**
Nominal unit current draw***
Maximum unit current draw (Un)****
Maximum unit current draw (Un-10%)
Customer-side unit power reserve
Short-circuit stability and protection

022

030

035

045

V-ph-Hz
V

400-3-50
360-440
24 V, via internal transformer

A
A

104.6
102.6
131.0
171.0
56.1
55.1
70.0
90.8
0.82
0.82
0.82
0.82
8.7
11.6
12.9
14.6
14.3
16.9
20.2
23.2
16.1
21.3
24.1
27.1
21.1
28.4
32.2
36.4
Customer reserve at the 24 V control power circuit
See table on the next page

kW
A
A
A

055

075

105

191.0
101.2
0.82
16.8
27.9
31.1
42.0

154.5
101.5
0.82
25.8
39.7
47.5
63.7

221.5
142.5
0.82
33.7
55.1
61.5
83.3

* Maximum instantaneous start-up current (maximum operating current of the compressor + fan current + locked rotor current of the compressor).
** Power input, compressor and fan, at the unit operating limits (saturated suction temperature 10C, saturated condensing temperature 65C) and nominal voltage of 400 V (data given on the unit
nameplate).
*** Standardised Eurovent conditions: condenser entering/leaving water temperature = 40C/45C, outside air temperature db/wb = 7C/6C.
**** Maximum unit operating current at maximum unit power input and 400 V (values given on the unit nameplate).
Maximum unit operating current at maximum unit power input and 360 V.

Short-circuit stability current, main disconnect without fuse


(TN system*)

61AF - standard unit (main disconnect switch)


022
Value with unspecified upstream protection
Short-term current at 1 s (Icw)
kA rms
0.6
Admissible peak current (Ipk)
kA pk
4.5
Maximum value with upstream protection by Siemens circuit breaker
Conditional short-circuit current (Icc)
kA rms
5.4
Siemens circuit breaker - Compact range
32
Reference number**
5SY6332-7
Maximum value with upstream protection by fuses (gL/gG)

Conditional short-circuit current (Icc)


Siemens fuse (gL/gG)

kA rms

17
40

030

035

045

055

075

105

0.6
4.5

0.6
4.5

1.26
6

1.26
6

1.26
6

2
10

7
7
7.7
7.7
6.1
10
40
40
50
63
80
100
5SY6340-7 5SY6340-7 5SY4350-7 5SY4363-8 5SP4380-7 5SP4391-7
50
40

50
40

50
63

50
63

14.5
80

22
125

* Earthing system type


** If another current limitation protection system is used, its time-current and thermal constraint (It) trip characteristics must be at least equivalent to those of the recommended Siemens circuit
breaker. Contact your nearest Carrier office.
The short-circuit stability current values above are in accordance with the TN system.

Operating limits
Plate heat exchanger water flow rate

Operating range

61AF
Condenser
Entering water temperature at start-up
Leaving water temperature during operation
Entering/leaving water temperature difference
Evaporator
Entering air temperature, standard unit*
Entering air temperature, unit with option 11

C 8
C 30
K 3

57
65
**

C -20
C -15

40
40

* Outside temperature: For transport and storage of the 61AF units the minimum and maximum
allowable temperatures are -20C and +50C. It is recommended that these temperatures
are used for transport by container.
** Refer to the minmum unit flow rate.
Note: Do not exceed the maximum operating temperature.

65
Leaving water temperature, C

60
55
50
45
40
35
30
25
-25 -20 -15 -10

-5

10

15 20

25

Entering air temperature, C


Full load

022
030
035
045
055
075
105

30

35 40

45

Flow rate, l/s


Minimum Maximum*
with hydronic module
0.4
1.6
0.5
1.7
0.7
3.3
0.8
3.3
0.9
3.2
1.2
5.9
1.6
6.1

Maximum**
without hydronic module
1.8
2.4
3.1
3.8
4.6
6.4
8.5

* Maximum flow rate at an available pressure of 15 kPa.


** Maximum flow rate at a water temperature difference of 3 K in the plate heat exchanger.

70

20

61AF

Minimum Maximum

Note: For a domestic hot water application (leaving water temperature = 65C), the water
temperature difference must be at least 8 K.

Dimensions/clearances

61AF 022-035 units with and without hydronic module

1110

300

1330

1327

1000

1000

1000

Legend

1000

All dimensions are in mm



Required clearances for air flow


Recommended space for maintenance
Water inlet
Water outlet

61AF 045-055 units with and without hydronic module

Control box

Power cable connection

NOTES:
Non-certified drawings.
Refer to the certified dimensional drawings
supplied with the unit or available on request,
when designing an installation. For the location of
fixing points, weight distribution and coordinates
of the centre of gravity refer to the certified
dimensional drawings.
B In multiple-unit installations (maximum four units),
the side clearance between the units should be
increased from 1000 to 2000 mm.
C The height of the solid surface must not exceed
2 m.
A

2100

300

1330

1114

Air outlet, do not obstruct

1000

1000

1000

1000

Dimensions/clearances (continued)

61AF 075-105 units with and without hydronic module

Legend

2273

2100

1330

All dimensions are in mm

300

Water outlet

2261

1000

1000

Control box

Power cable connection

NOTES:
Non-certified drawings.
Refer to the certified dimensional drawings
supplied with the unit or available on request,
when designing an installation. For the location of
fixing points, weight distribution and coordinates
of the centre of gravity refer to the certified
dimensional drawings.
B In multiple-unit installations (maximum four units),
the side clearance between the units should be
increased from 1000 to 2000 mm.
C The height of the solid surface must not exceed
2 m.
A

Air outlet, do not obstruct

Recommended space for maintenance


Water inlet

2053

1000

Required clearances for air flow

1000

Heating capacities
Outside air temperature, C
-20
-15
-10
-5
0
2
5
61AF EWT Cap Unit Flow Dp Cap Unit Flow Dp Cap Unit Flow Dp Cap Unit Flow Dp Cap Unit Flow Dp Cap Unit Flow Dp Cap Unit Flow Dp
022
030
035
045
055
075
105
022
030
035
045
055
075
105
022
030
035
045
055
075
105
022
030
035
045
055
075
105
022
030
035
045
055
075
105
022
030
035
045
055
075
105
022
030
035
045
055
075
105

C
25

30

35

40

45

50

55

kW
10.2
10.1
15.6
20.0
25.6
32.0
47.6
9.8
10.2
15.7
18.7
25.6
31.8
47.8
10.0
10.4
15.9
18.7
25.7
31.7
48.1
10.1
9.5
16.1
19.1
25.9
31.7
48.5
10.4
9.3
15.9
17.0
25.8
31.8
49.0
10.7
10.5
16.3
18.9
26.6
32.0
49.7
-

kW
4.80
5.70
6.60
8.50
9.40
14.0
19.3
5.20
5.90
7.10
9.10
10.0
14.9
20.6
5.50
6.20
7.70
9.60
10.6
15.9
22.0
5.90
6.60
8.30
10.3
11.5
17.0
23.5
6.30
7.10
9.00
11.1
12.7
18.1
25.0
6.80
7.60
9.70
12.1
14.1
19.4
26.7
-

l/s
0.49
0.58
0.75
0.96
1.23
1.54
2.29
0.47
0.49
0.76
0.89
1.23
1.53
2.30
0.48
0.50
0.77
0.89
1.24
1.53
2.32
0.48
0.45
0.78
0.91
1.25
1.53
2.34
0.50
0.44
0.76
0.81
1.23
1.54
2.37
0.51
0.50
0.78
0.90
1.27
1.55
2.41
-

kPa
1
1
1
1
2
2
4
1
1
1
1
2
2
3
1
1
1
1
2
2
3
1
1
1
1
2
2
3
1
1
1
1
2
2
3
1
1
1
1
2
2
3
-

Legend
EWT
Cap kW
Unit kW
Flow l/s
Dp kPa

kW
12.1
13.1
18.1
24.4
29.9
37.6
54.9
11.8
13.1
18.2
23.4
29.8
37.3
55.1
11.9
13.2
18.3
23.3
29.8
37.1
55.4
12.0
12.5
18.5
23.5
30.0
37.1
55.9
12.2
12.3
18.7
21.8
30.4
37.1
56.6
12.5
13.2
18.9
23.3
31.0
37.3
57.5
-

kW
4.80
5.70
6.80
8.70
10.0
14.4
19.9
5.20
6.00
7.30
9.30
10.6
15.4
21.4
5.50
6.30
7.90
9.90
11.3
16.4
23.0
5.90
6.70
8.60
10.6
12.2
17.6
24.7
6.40
7.30
9.30
11.5
13.3
18.9
26.6
6.90
7.90
10.0
12.5
14.6
20.4
28.7
-

l/s
0.58
0.58
0.87
1.17
1.43
1.80
2.64
0.57
0.62
0.87
1.12
1.43
1.79
2.65
0.57
0.63
0.88
1.11
1.44
1.79
2.67
0.58
0.60
0.89
1.12
1.45
1.79
2.70
0.58
0.59
0.90
1.04
1.47
1.79
2.73
0.60
0.63
0.92
1.11
1.50
1.81
2.78
-

kPa
2
1
2
3
3
3
5
2
1
2
3
3
3
5
2
1
2
3
3
3
5
2
1
2
3
3
3
5
2
1
2
3
3
3
5
2
1
2
3
3
3
5
-

kW
13.9
16.0
21.0
28.5
34.5
43.8
64.0
13.9
15.9
20.9
28.2
34.4
43.4
63.9
13.9
15.9
21.0
28.0
34.3
43.2
64.0
14.0
15.4
21.1
27.9
34.4
43.0
64.4
14.1
15.3
21.2
28.0
34.7
43.1
64.9
14.3
16.0
21.4
27.7
35.1
43.2
65.7
14.9
16.6
20.9
28.7
36.6
43.9
67.7

kW
4.80
5.70
6.90
9.00
10.4
14.7
20.4
5.20
6.00
7.50
9.60
11.1
15.8
22.0
5.50
6.40
8.10
10.2
11.9
16.9
23.8
6.00
6.90
8.80
11.0
12.8
18.2
25.8
6.50
7.40
9.50
11.9
13.9
19.7
27.9
7.00
8.10
10.3
12.8
15.2
21.2
30.3
8.30
9.60
12.1
15.3
18.4
24.3
34.6

l/s
0.67
0.77
1.01
1.37
1.66
2.10
3.08
0.67
0.76
1.01
1.36
1.65
2.09
3.07
0.67
0.76
1.01
1.35
1.65
2.08
3.08
0.67
0.74
1.02
1.35
1.66
2.08
3.11
0.68
0.73
1.03
1.35
1.67
2.08
3.14
0.69
0.76
1.04
1.32
1.70
2.09
3.18
0.36
0.40
0.50
0.68
0.89
1.07
1.64

kPa
2
2
3
3
4
4
6
2
2
2
3
4
4
6
2
2
2
3
3
4
6
2
2
2
3
3
4
6
2
2
2
3
3
4
6
2
2
2
3
3
4
6
1
1
1
1
1
1
2

kW
15.9
19.0
24.3
33.1
39.8
50.7
74.1
15.8
18.8
24.1
32.7
39.5
50.3
73.9
15.7
18.7
24.0
32.3
39.3
49.9
73.8
15.8
18.4
24.0
32.1
39.2
49.7
74.0
15.9
18.3
24.1
32.0
39.3
49.6
74.5
16.1
18.8
24.2
32.1
39.6
49.7
75.3
16.7
19.2
24.1
32.7
40.2
50.3
77.2

kW
4.80
5.80
7.00
9.20
10.7
14.9
20.9
5.20
6.10
7.60
9.80
11.5
16.1
22.6
5.60
6.60
8.30
10.5
12.3
17.4
24.5
6.00
7.20
9.00
11.3
13.3
18.8
26.7
6.50
7.80
9.70
12.3
14.3
20.3
29.0
7.10
8.50
10.5
13.3
15.6
22.0
31.7
8.50
10.2
12.4
15.9
18.7
25.2
36.4

l/s
0.76
0.91
1.16
1.59
1.91
2.44
3.56
0.76
0.91
1.16
1.57
1.90
2.42
3.55
0.76
0.90
1.16
1.56
1.89
2.41
3.56
0.76
0.88
1.16
1.55
1.89
2.40
3.57
0.77
0.88
1.16
1.55
1.90
2.40
3.60
0.78
0.90
1.17
1.55
1.92
2.41
3.65
0.41
0.46
0.58
0.79
0.96
1.22
1.87

kPa
3
3
3
5
5
5
8
3
3
3
4
5
5
8
3
2
3
4
4
5
8
3
2
3
4
4
5
8
3
2
3
4
4
5
8
3
2
3
4
4
5
8
1
1
1
1
1
1
2

kW
18.0
21.9
27.7
38.1
45.3
58.3
85.4
17.9
21.7
27.5
37.6
45.0
57.8
84.9
17.8
21.5
27.4
37.2
44.7
57.3
84.7
17.7
21.4
27.3
36.7
44.6
57.0
84.8
17.8
21.4
27.2
36.5
44.5
56.8
85.0
18.0
21.5
27.2
36.4
44.6
56.8
85.7
18.5
21.9
27.3
36.6
45.2
57.2
87.5

kW
4.60
5.60
6.90
9.10
10.8
14.7
21.2
4.90
6.00
7.60
9.80
11.7
16.0
22.9
5.30
6.50
8.20
10.6
12.6
17.3
24.9
5.80
7.10
9.00
11.5
13.6
18.8
27.1
6.40
7.70
9.70
12.4
14.7
20.5
29.7
7.00
8.50
10.6
13.6
16.0
22.3
32.6
8.40
10.2
12.4
16.1
19.1
25.7
37.5

l/s
0.87
1.05
1.33
1.83
2.17
2.80
4.10
0.86
1.04
1.32
1.81
2.16
2.78
4.09
0.86
1.03
1.32
1.79
2.16
2.76
4.08
0.86
1.03
1.32
1.77
2.15
2.75
4.09
0.86
1.03
1.32
1.76
2.15
2.75
4.11
0.87
1.04
1.32
1.76
2.16
2.75
4.15
0.45
0.52
0.65
0.89
1.08
1.39
2.12

kPa
4
3
4
6
6
7
11
3
3
4
6
6
6
10
3
3
4
5
6
6
10
3
3
4
5
5
6
10
3
3
4
5
5
6
10
3
3
4
5
5
6
10
1
1
1
1
1
2
3

kW
19.0
23.2
29.2
40.1
47.5
61.6
90.2
18.8
22.9
29.0
39.6
47.2
61.0
89.7
18.6
22.7
28.8
39.1
46.9
60.5
89.4
18.6
22.5
28.6
38.7
46.7
60.1
89.4
18.6
22.5
28.6
38.4
46.7
59.9
89.6
18.7
22.6
28.6
38.2
46.7
59.8
90.1
19.2
23.0
28.6
38.4
47.2
60.2
91.9

kW
4.60
5.60
7.00
9.10
10.8
14.8
21.2
4.90
6.10
7.60
9.80
11.7
16.0
23.0
5.30
6.50
8.30
10.6
12.6
17.5
25.0
5.80
7.10
9.00
11.5
13.6
19.0
27.3
6.40
7.80
9.80
12.6
14.8
20.7
29.9
7.00
8.60
10.7
13.7
16.1
22.6
32.9
8.50
10.3
12.5
16.3
19.2
26.0
37.9

l/s
0.91
1.11
1.40
1.93
2.28
2.96
4.33
0.90
1.10
1.39
1.90
2.27
2.93
4.31
0.90
1.09
1.39
1.88
2.26
2.91
4.31
0.90
1.09
1.38
1.87
2.25
2.90
4.31
0.90
1.09
1.38
1.86
2.26
2.89
4.33
0.91
1.09
1.38
1.85
2.26
2.90
4.36
0.47
0.56
0.70
0.93
1.15
1.46
2.23

kPa
4
4
5
6
6
7
12
4
4
4
6
6
7
12
4
4
4
6
6
7
11
4
3
4
6
6
7
11
4
3
4
5
6
7
11
4
3
4
5
6
6
11
1
1
1
1
2
2
3

kW
20.4
25.2
31.6
41.3
50.3
63.1
97.6
20.2
24.8
31.2
41.8
50.4
63.8
97.2
20.0
24.6
30.9
42.1
50.2
64.7
96.8
19.9
24.4
30.7
41.7
50.0
65.0
96.6
19.9
24.3
30.6
41.3
49.8
64.7
96.8
19.9
24.3
30.5
41.1
49.8
64.6
97.2
20.4
24.6
30.6
41.1
50.3
64.8
98.6

kW
4.60
5.70
7.00
9.00
10.9
14.8
21.7
4.90
6.10
7.70
9.80
11.8
16.1
23.4
5.30
6.60
8.40
10.7
12.8
17.6
25.4
5.80
7.20
9.10
11.7
13.9
19.3
27.8
6.40
7.90
10.0
12.7
15.0
21.1
30.4
7.00
8.70
10.9
13.9
16.4
23.0
33.5
8.50
10.5
12.7
16.6
19.5
26.5
38.6

l/s
0.98
1.21
1.52
1.98
2.42
3.03
4.69
0.97
1.19
1.50
2.01
2.43
3.07
4.67
0.96
1.18
1.49
2.03
2.42
3.12
4.66
0.96
1.18
1.48
2.01
2.41
3.13
4.66
0.96
1.17
1.48
2.00
2.41
3.13
4.67
0.97
1.18
1.48
1.99
2.41
3.13
4.71
0.49
0.60
0.74
1.00
1.22
1.57
2.39

kPa
5
4
5
7
7
8
14
4
4
5
7
7
8
13
4
4
5
7
7
8
13
4
4
5
6
7
8
13
4
4
5
6
6
8
13
4
4
4
6
6
7
12
1
1
1
2
2
2
3

Application data
Entering water temperature
Heating capacity
Unit power input
Condenser water flow rate
Condenser pressure drop

Standard units, refrigerant R407C


Condenser entering/leaving water temperature difference: 5 K for EWT < 55C
Condenser entering/leaving water temperature difference: 10 K for EWT 55C
Condenser fluid: water
Relative humidity: 87%
Fouling factor: 0 (m2 K)/W - 0.18 x10-4 (m2 K)/W
Performances in accordance with EN 14511

Heating capacities
Outside air temperature, C
7
10
15
20
25
30
35
61AF EWT Cap Unit Flow Dp Cap Unit Flow Dp Cap Unit Flow Dp Cap Unit Flow Dp Cap Unit Flow Dp Cap Unit Flow Dp Cap Unit Flow Dp
022
030
035
045
055
075
105
022
030
035
045
055
075
105
022
030
035
045
055
075
105
022
030
035
045
055
075
105
022
030
035
045
055
075
105
022
030
035
045
055
075
105
022
030
035
045
055
075
105

C
25

30

35

40

45

50

55

kW
21.5
26.5
33.3
42.8
51.4
64.1
102
21.2
26.1
32.8
43.6
51.9
64.7
102
20.9
25.9
32.5
44.1
52.0
65.6
102
20.8
25.7
32.2
43.6
52.2
66.7
102
20.8
25.5
32.0
43.3
52.0
67.8
102
20.8
25.5
31.9
43.1
51.9
67.9
102
21.1
25.7
31.8
42.8
52.3
68.0
103

kW
4.60
5.70
7.10
9.10
10.9
14.8
21.9
4.90
6.10
7.70
9.90
11.9
16.1
23.6
5.30
6.70
8.50
10.8
12.9
17.7
25.7
5.80
7.30
9.20
11.8
14.0
19.4
28.1
6.40
8.00
10.1
12.8
15.2
21.3
30.8
7.10
8.80
11.0
14.1
16.5
23.3
33.9
8.60
10.6
12.9
16.8
19.6
26.8
39.1

l/s
1.03
1.27
1.60
2.04
2.47
3.08
4.90
1.02
1.26
1.58
2.08
2.49
3.11
4.89
1.01
1.25
1.56
2.11
2.51
3.16
4.90
1.00
1.24
1.55
2.08
2.52
3.22
4.90
1.00
1.23
1.55
2.07
2.51
3.28
4.92
1.01
1.23
1.55
2.06
2.52
3.29
4.94
0.51
0.62
0.77
1.02
1.27
1.65
2.51

kPa
5
5
6
7
7
8
15
5
5
6
7
7
8
15
5
4
5
7
7
8
14
4
4
5
7
7
8
14
4
4
5
7
7
8
14
4
4
5
6
7
8
14
1
1
1
2
2
2
4

Legend
EWT
Cap kW
Unit kW
Flow l/s
Dp kPa

kW
23.0
28.6
36.0
44.6
52.4
66.2
109
22.8
28.1
35.4
46.1
53.2
66.7
108
22.5
27.8
35.0
47.0
53.5
67.3
108
22.3
27.6
34.6
46.6
53.8
68.1
108
22.1
27.4
34.3
46.2
53.6
69.3
109
22.1
27.4
34.1
45.9
53.4
70.8
110
22.4
27.4
33.9
45.5
53.6
73.1
111

kW
4.60
5.70
7.20
9.10
10.9
14.8
22.3
4.90
6.10
7.80
9.90
12.0
16.2
24.0
5.40
6.70
8.60
10.8
13.1
17.7
26.1
5.80
7.30
9.30
11.9
14.2
19.4
28.5
6.40
8.10
10.2
13.0
15.4
21.3
31.3
7.10
8.90
11.1
14.3
16.8
23.5
34.5
8.60
10.8
13.0
17.0
19.9
27.2
39.6

l/s
1.11
1.37
1.73
2.13
2.50
3.18
5.23
1.09
1.35
1.70
2.20
2.54
3.21
5.20
1.08
1.34
1.68
2.25
2.56
3.24
5.20
1.07
1.33
1.67
2.22
2.57
3.28
5.22
1.07
1.33
1.66
2.21
2.56
3.35
5.25
1.07
1.33
1.65
2.19
2.55
3.43
5.31
0.54
0.67
0.82
1.09
1.28
1.77
2.69

kPa
6
6
7
8
8
9
17
5
5
6
8
8
8
16
5
5
6
8
8
8
16
5
5
6
8
8
8
16
5
5
6
8
7
9
16
5
5
5
7
7
9
16
1
1
2
2
2
2
4

kW
23.2
32.1
40.4
47.8
55.1
69.7
121
23.5
31.7
39.8
50.2
56.7
70.1
120
23.9
31.3
39.3
52.0
57.3
70.8
119
24.4
30.9
38.9
51.5
58.0
71.6
119
24.7
30.7
38.5
51.1
57.5
72.5
120
24.5
30.6
38.1
50.7
57.2
73.7
120
24.5
30.6
37.4
49.9
57.3
75.8
122

kW
4.60
5.70
7.30
9.20
11.0
14.8
23.2
4.90
6.20
8.00
10.1
12.2
16.2
24.8
5.40
6.80
8.70
11.0
13.3
17.8
26.8
5.80
7.40
9.50
12.1
14.5
19.5
29.2
6.40
8.20
10.4
13.3
15.8
21.5
32.1
7.10
9.10
11.4
14.6
17.2
23.7
35.4
8.70
11.1
13.3
17.5
20.3
27.4
40.4

l/s
1.11
1.54
1.94
2.28
2.63
3.35
5.81
1.13
1.53
1.92
2.40
2.71
3.37
5.76
1.15
1.51
1.90
2.48
2.74
3.41
5.73
1.18
1.49
1.88
2.46
2.77
3.45
5.74
1.19
1.49
1.86
2.44
2.75
3.50
5.77
1.19
1.48
1.84
2.42
2.74
3.57
5.82
0.60
0.74
0.91
1.19
1.37
1.84
2.96

kPa
6
7
8
9
8
9
21
6
7
8
10
9
9
20
6
6
7
10
9
9
19
6
6
7
10
9
9
19
6
6
7
9
8
9
19
6
6
7
9
8
9
19
2
2
2
2
2
3
5

kW
23.2
35.3
38.2
50.9
58.9
73.3
123
23.5
34.9
42.9
54.4
61.2
73.7
124
23.9
34.6
42.3
56.9
62.2
74.3
126
24.4
34.4
41.8
56.4
63.2
75.1
128
24.9
34.3
41.2
55.9
62.6
76.1
130
25.6
34.1
40.6
55.5
62.2
77.3
132
26.9
33.8
39.7
54.3
62.1
79.4
133

kW
4.60
5.60
7.40
9.30
11.1
14.9
23.3
4.90
6.20
8.10
10.2
12.3
16.3
25.1
5.30
6.80
8.90
11.1
13.6
17.9
27.3
5.80
7.50
9.70
12.3
14.9
19.7
29.8
6.40
8.40
10.6
13.6
16.2
21.7
32.8
7.10
9.30
11.6
15.0
17.6
23.9
36.3
8.70
11.3
13.6
17.9
20.7
27.6
41.2

l/s
1.11
1.70
1.83
2.43
2.81
3.52
5.92
1.13
1.68
2.05
2.60
2.92
3.55
5.99
1.15
1.67
2.02
2.72
2.97
3.58
6.07
1.18
1.66
2.00
2.69
3.02
3.62
6.17
1.21
1.66
1.97
2.67
2.99
3.68
6.29
1.24
1.65
1.94
2.65
2.97
3.74
6.37
0.65
0.82
0.95
1.30
1.48
1.93
3.23

kW
23.2
38.7
39.6
54.0
62.7
76.9
126
23.5
38.4
46.2
58.6
65.7
77.3
127
23.9
38.1
45.5
61.9
67.1
77.8
128
24.4
37.8
45.0
61.3
68.4
78.6
130
24.9
37.6
44.2
60.8
67.7
79.6
132
25.6
37.3
43.5
60.3
67.1
80.9
135
27.1
37.0
42.2
58.7
66.9
83.0
139

kW
4.50
5.90
7.50
9.40
11.2
14.9
23.4
4.90
6.40
8.30
10.3
12.5
16.3
25.2
5.30
7.10
9.10
11.2
13.8
18.0
27.4
5.80
7.80
9.90
12.5
15.2
19.8
30.0
6.40
8.70
10.9
13.9
16.6
21.8
33.0
7.10
9.60
11.8
15.3
18.0
24.2
36.5
8.70
11.7
14.0
18.4
21.1
27.9
41.6

l/s
1.11
1.85
1.89
2.58
2.99
3.70
6.03
1.13
1.84
2.21
2.80
3.14
3.72
6.10
1.15
1.82
2.17
2.96
3.21
3.75
6.18
1.18
1.81
2.15
2.93
3.27
3.79
6.27
1.21
1.80
2.11
2.90
3.23
3.85
6.40
1.24
1.78
2.08
2.88
3.21
3.91
6.55
0.66
0.88
1.01
1.40
1.60
2.01
3.38

kPa
6
10
8
11
11
11
22
6
10
10
13
12
11
22
6
9
10
14
12
11
22
6
9
9
14
12
11
22
6
9
9
13
12
11
23
6
8
8
13
11
11
23
2
2
2
3
3
3
6

Application data
Entering water temperature
Heating capacity
Unit power input
Condenser water flow rate
Condenser pressure drop

Standard units, refrigerant R407C


Condenser entering/leaving water temperature difference: 5 K for EWT < 55C
Condenser entering/leaving water temperature difference: 10 K for EWT 55C
Condenser fluid: water
Relative humidity: 87%
Fouling factor: 0 (m2 K)/W - 0.18 x10-4 (m2 K)/W
Performances in accordance with EN 14511

10

kPa
6
8
7
10
10
10
22
6
8
9
11
10
10
21
6
8
8
12
10
10
21
6
7
8
12
10
10
22
6
7
8
11
10
10
22
6
7
7
11
10
10
22
2
2
2
3
3
3
6

kW
23.2
42.1
41.8
57.1
66.5
80.6
128
23.5
41.8
50.4
62.8
70.2
81.0
129
23.9
41.5
49.6
66.9
72.0
81.5
130
24.4
41.2
49.0
66.2
73.7
82.2
132
24.9
41.1
48.1
65.6
72.8
83.2
135
25.6
40.7
47.1
65.0
72.1
84.5
138
27.1
40.2
45.5
63.1
71.6
86.6
142

kW
4.50
5.70
7.60
9.50
11.3
14.9
23.6
4.90
6.50
8.40
10.4
12.7
16.4
25.3
5.30
7.20
9.20
11.3
14.1
18.0
27.5
5.80
8.00
10.1
12.7
15.6
19.9
30.1
6.40
8.90
11.1
14.1
16.9
22.0
33.1
7.10
9.90
12.1
15.7
18.4
24.4
36.7
8.70
12.0
14.3
18.8
21.5
28.1
41.7

l/s
1.11
2.01
2.00
2.73
3.18
3.87
6.14
1.13
2.00
2.41
3.00
3.35
3.90
6.21
1.15
1.98
2.37
3.19
3.44
3.93
6.29
1.18
1.97
2.34
3.16
3.52
3.97
6.38
1.21
1.96
2.30
3.14
3.48
4.02
6.51
1.24
1.94
2.25
3.11
3.44
4.09
6.66
0.66
0.96
1.09
1.51
1.71
2.10
3.44

kPa
6
12
9
13
12
12
23
6
11
12
15
13
12
23
6
11
12
17
14
12
23
6
11
11
16
14
12
23
6
10
11
15
13
12
23
6
10
10
15
13
12
24
2
3
3
4
3
3
7

kW
23.2
42.1
41.8
57.1
66.5
84.3
130
23.5
41.8
50.4
62.8
70.2
84.7
131
23.9
41.5
49.6
66.9
72.0
85.2
133
24.4
41.2
49.0
66.2
73.7
85.9
135
24.9
41.1
48.1
65.6
72.8
86.9
137
25.6
40.7
47.1
65.0
72.1
88.1
140
27.1
40.2
45.5
63.1
71.6
90.2
144

kW
4.50
5.70
7.60
9.50
11.3
14.9
23.7
4.90
6.50
8.40
10.4
12.7
16.4
25.5
5.30
7.20
9.20
11.3
14.1
18.1
27.6
5.80
8.00
10.1
12.7
15.6
20.0
30.2
6.40
8.90
11.1
14.1
16.9
22.1
33.3
7.00
9.90
12.1
15.7
18.4
24.6
36.9
8.70
12.0
14.3
18.8
21.5
28.3
41.8

l/s
1.11
2.01
2.00
2.73
3.18
4.05
6.25
1.13
2.00
2.41
3.00
3.35
4.07
6.32
1.15
1.98
2.37
3.19
3.44
4.10
6.40
1.18
1.97
2.34
3.16
3.52
4.14
6.49
1.21
1.96
2.30
3.14
3.48
4.20
6.62
1.24
1.94
2.25
3.11
3.44
4.27
6.77
0.66
0.96
1.09
1.51
1.71
2.19
3.49

kPa
6
12
9
13
12
13
24
6
11
12
15
13
13
24
6
11
12
17
14
13
24
6
11
11
16
14
13
24
6
10
11
15
13
13
24
6
10
10
15
13
13
25
2
3
3
4
3
4
7

Hydronic module (option 116)


Typical hydronic circuit diagram

The hydronic module option reduces the installation time.


The heat pump is factory-equipped with the main hydronic
components required for the installation: screen filter,
water pump, safety valve, water pressure transducer, flow
switch.

15
18 19

17

The Pro-Dialog+ control allows integration of system and


water pump protection devices (insufficient water flow
rate, water pressure, water flow rate etc.).

14

16

22
14

The pump supplied with the hydronic module is a multispeed pump.


An automatic pump start-up algorithm protects the heat
exchanger and the hydronic module piping against frost
down to -10C outside air temperature, as standard. If
necessary, increased frost protection down to -20 C is
possible by adding heaters to the hydronic module piping
(see option 42).

12

16
17 20

13

19

11

10

21

Legend
Components of the unit and hydronic module
1 Victaulic screen filter
2 Pressure sensor
Note: Gives pump suction pressure information (see installation manual)
3 Safety valve
4 Water drain valve
5 Shut-off valve
6 Water pump
7 Temperature sensors, BPHE inlet
Note: Gives heat exchanger entering temperature information (see installation manual)
8 Pressure gauge
Note: Allows measuring of the pump suction pressure, the pump leaving pressure and the
heat exchanger leaving pressure
9 Temperature sensor, BPHE outlet
Note: Gives heat exchanger leaving temperature information (see installation manual)
10 Automatic air vent
11 Flow switch
12 Plate heat exchanger frost protection heater
13 Plate heat exchanger

The hydronic module option is integrated into the heat


pump without increasing its dimensions and saves the
space normally used for the water pump.

Hydronic module

Installation components
14 Temperature probe well
15 Air vent
16 Flexible connection
17 Shut-off valve
18 Screen filter (obligatory for a unit without hydronic module)
19 Pressure gauge
20 Water flow control valve
21 Charge valve
22 Frost protection bypass valve (when shut-off valves [17] are closed during winter)
--- Hydronic module (unit with hydronic module)

Physical and electrical data, units with hydronic module


61AF
Operating weight*
Unit with hydronic module
Hydronic module
Maximum operating pressure
Water filter
Pumps
Water pump
Shaft power input
Power input**
Nominal operating current draw
Maximum current draw at 400 V***
Water connections (with hydronic module)
Connections
Outside diameter

Notes:
Units without hydronic module (standard units) are equipped with a flow switch and two
temperature sensors (7 and 9).
For units equipped with hydronic module, the pressure sensor located upstream of the pump
to prevent cavitation is installed on a connection without Schraeder valves. Depressurise
and drain the system before any intervention.

022

030

035

045

055

075

105

kg

349

403

436

524

549

926

1044

kPa

400
400
Victaulic screen filter

400

400

400

400

400

kW
kW
A
A

TOP-S 25
0.18
0.42
0.4
0.8

TOP-S 25
0.18
0.42
0.4
0.8

TOP-S40
0.35
0.63
0.6
1.3

TOP-S40
0.35
0.63
0.6
1.3

TOP-S40
0.35
0.63
0.7
1.3

TOP-S50
0.45
0.95
1.3
1.7

TOP-S50
0.45
0.95
1.5
1.7

inch
mm

1-1/4
42.4

1-1/4
42.4

1-1/2
48.3

1-1/2
48.3

1-1/2
48.3

2
60.3

2
60.3

* Weight shown is a guideline only. To find out the unit refrigerant charge, please refer to the unit nameplate.
** To obtain the maximum power input for a unit with hydronic module, add the maximum unit power input to the pump power input.
*** To obtain the maximum operating current draw for a unit with hydronic module, add the maximum unit current draw to the pump current draw.

11

Units with fans with available pressure for indoor installation


(option 11)
Fan discharge connection

This option applies to 61AF units installed inside the


building in a plant room. For this type of installation the
cold air leaving the air-cooled evaporators is discharged by
the fans to the outside of the building, using a duct system.

A square flange is supplied mounted on the unit. An


available standard round flange can easily be installed at
the fan discharge, if the installer prefers the use of a round
connection duct.

The installation of a duct system at the air evaporator


discharge line causes a pressure drop due to the resistance
caused by the air flow.

The unit is supplied with a grille on the discharge side.


This grille has to be removed before connection to the
duct system.

Therefore more powerful fan motors than those used for


the standard units are installed in the units with this
option. For each installation of a unit installed inside a
plant room the duct pressure drops differ, depending on
the duct length, duct section and direction changes.

It is advisable to make the connection to the duct system


with a flexible sleeve. If this recommendation is not observed,
a lot of vibration and noise may be transmitted to the
building structure.

Applicable rules for units incorporated into an air


duct system

61AF units equipped with fans with available pressure are


designed to operate with air discharge ducts with maximum
pressure drops of 100 Pa.

Ensure that the suction or discharge inlets are not accidentally obstructed by the panel positioning (e.g. low return or
open doors etc.).

Electrical data for 61AF units with option 11


61AF - units with option 11 (without hydronic
kit)
Power circuit
Nominal power supply
Voltage range
Control circuit supply
Maximum start-up current (Un)*
Standard unit
Unit with electronic starter option
Unit power factor at maximum capacity**
Maximum unit power input**
Nominal unit current draw***
Maximum unit current draw (Un)****
Maximum unit current draw (Un-10%)
Customer-side unit power reserve
Short-circuit stability and protection

022

030

035

045

V-ph-Hz
V

400-3-50
360-440
24 V, via internal transformer

A
A

107,1
105,1
133,5
173,5
58,6
57,6
72,5
93,3
0,82
0,82
0,82
0,82
9,8
12,7
14
15,7
16,4
19
22,3
25,3
18,5
23,7
26,5
29,5
23,2
30,5
34,3
38,5
Customer reserve at the 24 V control power circuit
See table on page 6

kW
A
A
A

055

075

105

193,5
103,7
0,82
17,9
30
33,5
44,1

159,5
106,5
0,82
28
43,9
52,3
67,9

226,5
147,5
0,82
35,9
59,3
66,3
87,5

* Maximum instantaneous start-up current (maximum operating current of the compressor + fan current + locked rotor current of the compressor).
** Power input, compressor and fan, at the unit operating limits (saturated suction temperature 10C, saturated condensing temperature 65C) and nominal voltage of 400 V (data given on the unit
nameplate).
*** Standardised Eurovent conditions: condenser entering/leaving water temperature = 40C/45C, outside air temperature db/wb = 7C/6C.
**** Maximum unit operating current at maximum unit power input and 400 V (values given on the unit nameplate).
Maximum unit operating current at maximum unit power input and 360 V.

12

Dimensions/clearances, units with option 11

61AF 022-035 units with and without hydronic module

1327

300

1371

1110

1280

1000

1000
1

1000

1000

Legend
All dimensions are in mm

Required clearances for air flow

Recommended space for maintenance

Water inlet

NOTES:
Non-certified drawings.
Refer to the certified dimensional drawings supplied with the unit or available on request,
when designing an installation. For the location of fixing points, weight distribution and
coordinates of the centre of gravity refer to the certified dimensional drawings.
In multiple-unit installations (maximum four units), the side clearance between the units
should be increased from 1000 to 2000 mm.
The height of the solid surface must not exceed 2 m.

Water outlet

Air outlet, do not obstruct

Control box

Power cable connection

13

Dimensions/clearances, units with option 11 (continued)

61AF 045-055 units with and without hydronic module

1114

300

1371

2079

1000

1000

1000

2
1000

Legend
All dimensions are in mm

Required clearances for air flow

Recommended space for maintenance

Water inlet
Water outlet

Air outlet, do not obstruct

Control box

14

Power cable connection

NOTES:
Non-certified drawings.
Refer to the certified dimensional drawings supplied with the unit or available on request,
when designing an installation. For the location of fixing points, weight distribution and
coordinates of the centre of gravity refer to the certified dimensional drawings.
In multiple-unit installations (maximum four units), the side clearance between the units
should be increased from 1000 to 2000 mm.
The height of the solid surface must not exceed 2 m.

Dimensions/clearances, units with option 11 (continued)

61AF 075-105 units with and without hydronic module

2273

300

1371

2100

1000

1000
1

1000

Legend
All dimensions are in mm

1000

Required clearances for air flow

Recommended space for maintenance

Water inlet

NOTES:
Non-certified drawings.
Refer to the certified dimensional drawings supplied with the unit or available on request,
when designing an installation. For the location of fixing points, weight distribution and
coordinates of the centre of gravity refer to the certified dimensional drawings.
In multiple-unit installations (maximum four units), the side clearance between the units
should be increased from 1000 to 2000 mm.
The height of the solid surface must not exceed 2 m.

Water outlet

Air outlet, do not obstruct

Control box

Power cable connection

15

Available static system pressure

Plate heat exchanger pressure drop - for pure water at 20C


61AF 022-045

61AF 055-105

30

50
3

Pressure drop, kPa

20

10

16

20

10

30

15

40

Pressure drop, kPa

25

0
1
2
3
4

1
61AF 022
61AF 030
61AF 035
61AF 045

Water flow rate, l/s

2
1
2
3

61AF 055
61AF 075
61AF 105

4
6
Water flow rate, l/s

10

Pump pressure/flow rate curves for units with hydronic module - for pure water at 20C
The 61AF units are equipped with a fixed-speed pump
with three different speeds.

61AF

61AF 035-055

100

100

Presssure head, kPa

80

Presssure head, kPa

120

60
40

20

0
1
2
3

0,2

Maximum*
1.8
2.4
3.1
3.8
4.6
6.4
8.5

* Maximum flow rate at a water temperature difference of 3 K in the plate heat exchanger (unit
without hydronic module)

120

Minimum
0.4
0.5
0.7
0.8
0.9
1.1
1.5

022
030
035
045
055
075
105

These speeds can be manually adjusted by changing the


speed terminal board inside the terminal box (this operation
can only be carried out by approved personnel). The speed
initially selected corresponds to standard use for heating
water loops. If this speed needs to be changed, the pressure/
flow curves for the three speeds are shown below.

61AF 022-030

Condenser water flow rate, l/s

0,4

0,6

0,8

1,0

1,2

Water flow rate,


1 l/s

1,4

1,6

3
2

80

1
60
40
20

1,8

2,0

61AF 022-030 (speed 1)


61AF 022-030 (speed 2): selected
61AF 022-030 (speed 3)

0
1
2
3

0,4

0,8

1,2

1,6
2,0
Water flow rate, l/s

2,4

2,8

3,2

61AF 035-055 (speed 1)


61AF 035-055 (speed 2): selected
61AF 035-055 (speed 3)

61AF 075-105

Presssure head, kPa

100

80

60

40
20
0

0
1
2
3

0,5

1,0

1,5

2,0

2,5

3,0

3,5

4,0

4,5

5,0

5,5

6,0

6,5

Water flow rate, l/s

61AF 075-105 (speed 1)


61AF 075-105 (speed 2): selected
61AF 075-105 (speed 3)

17

Available static system pressure (cont.)

Available system pressure for units with hydronic module - for pure water at 20C
The available pressure curves for the 61AF units are given
for the speed initially selected. If the speed is changed by
the user, the curves below do not apply.

61AF

61AF 022-030

Condenser water flow rate, l/s


Minimum
Maximum*
0.4
1.6
0.5
1.7
0.7
3.3
0.8
3.3
0.9
3.2
1.1
5.9
1.5
8.5

022
030
035
045
055
075
105

* Maximum flow rate at an available pressure of 15 kPa (unit with hydronic module).

61AF 035-055

100

100

90
80

70

Available pressure, kPa

Available pressure, kPa

80

60
50
40
30
20

10
0

0,4

0,6

0,8

1,0

1,2

1,4

60

40
3
20

1,6

1,8

0,5

1,0

1
2

61AF 022
61AF 030

61AF 075-105
100

Available pressure, kPa

80

60

40

18

20

1
1
2

2
61AF 075
61AF 105

4
Water flow rate, l/s

2,0
Water flow rate, l/s

Water flow rate, l/s



1,5

1
2
3

61AF 035
61AF 045
61AF 055

2,5

3,0

3,5

Carrier is participating in the Eurovent Certification Programme for liquid


chilling packages. Products are as listed in the Eurovent Directory of Certified
Products or on the Internet site www.eurovent-certification.com.

Order No.: 16110-20, 03.2011. Supersedes order No.: 16110-20, 10.2010.


Manufacturer reserves the right to change any product specifications without notice.
The cover photo is solely for illustration purposes and is not contractually binding.

Manufactured by: Carrier SCS, Montluel, France.