ASCO Power Transfer Load Centers

ASCO, the world leader in


power switching & controls

Streamline with an Integrated System


ASCO Power Transfer Load Centers: Power Continuity
And Surge Protection In a Single Enclosure
Product Features

Product Benefits

ASCO Series 300 and 7000 Power


Transfer Load Centers integrate the
most commonly specified components required to help protect
system loads from power outages,
sags, surges and over-current protection of load conductors.

Integrating components and


factory wiring them into one
enclosure significantly reduces
installation time, overall cost and
minimizes on site problems and
installation errors.

A world-class ASCO
Automatic or Manual Power
Transfer Switch with digital microprocessor controller.
ASCO 7000 Series Power Transfer Load Center
with quick-connect Cam-Lok assembly
and Telco section

Load Distribution or Load Center


that distributes 240/120 volt
single phase or 208/120V three
phase power to site equipment.
Main and alternate source circuit
breakers that provide over-current protection and disconnect
for convenient and safe serviceability.
Transient voltage surge suppression for normal and emergency
power sources.
Optional ASCO Thin Web Server
for 24/7 remote connectivity
with a single site or a network of
sites spanning the country.

ASCO Series 300 Power Transfer Load Center


with quick-connect Cam-Lok assembly
and Telco section

Optional Telco cabinet for customer mounting of telephone


equipment.

The shallow, space saving design


provides easy access and serviceability. The load center is service
entrance rated, listed to UL 67
and is available in a UL Type 1
(indoor) or UL Type 3R (outdoor)
enclosure.
When power fails, the automatic
transfer switch follows user-set
time delays to start the generator, transfer the load to the generator, reconnect to utility power
when it returns and shut down
the generator after generator
cool down. An automatic engine
exerciser tests the generator with
or without loads.
The load center also has a controls and status indicators panel.
Controls include a test, time delay bypass and engine exerciser
switches. LEDs indicate transfer
switch position and source availability status.

Project management you can depend


on for your mission-critical loads

Why Manage Multiple Components?


Multiple power-related cabinets and components consume valuable floor and wall space inside equipment
shelters at communications sites.

Integrating components into a single, space-saving


cabinet is the answer. The components operate as a
power transfer load center.

The area they demand, including mandated clearances, can total as much as 23 sq. feet for 200 or 400
Amp Services.

Benefits include reducing installation costs, time,


potential errors and improved reliability.

And when multiple components are located outside of


shelters, the potential for leaks and weather-induced
damage is that much greater.

ASCO Power Technologies offers a comprehensive


family of power transfer load centers that can be
tailored to virtually any site.

With space at a premium and more advanced communications technologies being installed at sites, it
makes sense to streamline and simplify site power
protection and distribution strategies.
ASCO Power
Transfer Switches

Square D 42-circuit
panel board

Telco cabinet

ASCO
Transient
Voltage Surge
Suppressor

Service
Breakers

ASCO
5500 Series
Thin Web
Server

ASCO 7000L
Power Transfer Switch
Load Center Product
Features
Conventional double throw
transfer switch configuration
Automatic Transfer Switch is
listed to UL1008, the standard for
Transfer Switch Equipment, and
meets NFPA 110 for Emergency
and Standby Power Systems and
the National Electrical Code
(NEC) articles 700,701, and 702.
Also certified to CSA 22.2
No. 178
Rated up to 240VAC, 200, or
400 amps
Available in Type 1 indoor, or
Type 3R secure aluminum
outdoor enclosure
Reliable and field proven single
solenoid operating mechanism
Programmable microprocessor
controller with keypad and LCD
display
16mm, industrial grade control
switches and indicating lights
Switch position LED indicators and
source acceptability lights
Four auxiliary contacts, two
contacts closed when switch is
in normal position and two
contacts closed when switch is
in emergency position

ASCO 7000L Automatic Power Transfer Load Center shown with


optional quick connect Cam - Loc assembly and bottom Telco cabinet
section (in type 3R secure aluminum enclosure)

Short Circuit Ratings


200A Mains: 22kA at 240vac (Main circuit breaker (Normal &
Emergency) Square D circuit breakers rated 2/3 pole, 200A)
Note: If a generator input receptacle is supplied for a portable
generator then the ratings are as follows:

Suitable as service entrance


equipment, includes main circuit
breaker overcurrent protection on
the normal source, and circuit
breaker disconnect on emergency

Normal Source 22kA at 240 vac


(Utility Main Disconnect circuit breaker)

Includes a UL 67 Listed 42 position


Square D panelboard load center

Emergency Source -#1 (Portable Generator


Input circuit breaker) 5kA at 240vac

Local/remote communications
capability for interfacing with
ASCO PowerQuest communication products

Emergency Source #2 (Permanent Generator


Input circuit breaker) 10kA at 240vac

400A Mains: 42kA at 240vac (Main circuit breaker (Normal &


Emergency) Square D circuit breakers rated 2/3 pole, 400A)
Panelboard: Square D series rated panelboard single/three phase
with 100% rated neutral 42 circuits, accepts bolt on or plug in
branch devices.

7000 Series Microprocessor Controller

Features
Digital microprocessor.
Touch pad programming of features and settings
without the need for meters, or variable power supplies.
Sixteen (16) selectable operating voltages available in a
single Controller.
On-board diagnostics provide control panel and ATS status information to analyze system performance.
Displays and counts down active timing functions.

Password protection to prevent unauthorized tampering


of settings.
Remote monitoring and control with ASCO communications products. Specify optional accessory 72A or 72E.
Load shed option for bus optimization applications.
Specify optional accessory 30B.
Historical event log
Statistical ATS systems monitoring information

Selectable multi-language display


(English, German, Portuguese, Spanish, or French. For
others contact ASCO).

Voltage and Frequency Sensing

Time Delays

3-Phase under and over voltage settings on normal


and emergency sources.

Engine start time delay - delays engine starting signal to


override momentary normal source outages - adjustable
0 to 6 seconds.

Under and over frequency settings on normal and


emergency.
True RMS Voltage Sensing with +/- 1% accuracy;
Frequency Sensing Accuracy is +/- 0.2%.

Transfer to emergency time delay - adjustable 0 to 60


minutes.

Selectable settings: single or three phase voltage


sensing on normal and emergency; 50 or 60Hz.

Emergency source stabilization time delay to ignore


momentary transients during initial generator set
loading - adjustable 0 to 6 seconds.

Phase sequence sensing for phase sensitive loads.

Retransfer to normal time delay with two settings:

Voltage unbalance detection between phases.

Power failure mode - 0 to 60 minutes.

Test mode - 0 to 10 hours.

Status and Control Features


Output contact (N/O or N/C) for engine-start signals.
Selection between commit/no-commit on transfer
to emergency after engine start and normal restores
before transfer.
Advanced inphase algorithm which automatically
measures the frequency difference between the two sources
and initiates transfer at appropriate phase angles to minimize disturbances when transferring motor loads.

Unloaded running time delay for engine cooldown adjustable 0 to 60 minutes.


Pre and post transfer signal time delay for selective
load disconnect with a programmable bypass on source
failures - adjustable 0 to 5 minutes. This signal can be
used to drive a customer furnished relay, or for (2) sets
of double throw contacts rated 3 amps at 480 volts AC,
specify ASCO optional accessory 31Z.

Event log displays 99 logged events with the time and


date of the event, event type and event reason.

Fully programmable engine exerciser with seven


independent routines to exercise the engine generator,
with or without loads, on a daily, weekly, bi-weekly or
monthly basis.

Output signals for remote indication of normal and emergency source acceptability

Contains all alarm signals, logic and time delays for


use with closed transition switches.

Statistical ATS/System monitoring data screens which provide:

Insynch time delay - 0 to 3 seconds.

Total number of ATS transfers.

Failure to synchronize - 1 to 5 minutes.

Number of ATS transfers caused by power source failure.

Extended parallel - 0.1 to 1.0 seconds.

Total number of days ATS has been in operation.

Total number of hours that the normal and emergency


sources have been available.

Delayed transition load disconnect time delay -


adjustable 0 to 5 minutes.

7000 Series Microprocessor Controller

The 7000 SERIES Microprocessor Based Controller is used with all sizes of Power
Transfer Switches from 30 through 4000 Amperes. It represents the most advanced
digital controller in the industry and includes, as standard, all of the voltage,
frequency, control, timing and diagnostic functions required for most emergency
and standby power applications.
Because of severe voltage transients frequently encountered with industrial
distribution systems, the microprocessor logic board is separated and isolated from
the power board as shown below. This improves electrical noise immunity performance
and helps assure compliance with the rigorous transient suppression standards highlighted below.

7000 Series
Microprocessor Controller.

Microprocessor Power and Logic PC Boards.

7000 Series Microprocessor Based Controller


Emission Standard - Group 1, Class A
Generic Immunity Standard, from which:

Electrostatic Discharge (ESD) Immunity

Radiated Electromagnetic Field Immunity

Electrical Fast Transient (EFT) Immunity

Surge Transient Immunity

Conducted Radio-Frequency Field Immunity

Voltage Dips, Interruptions and Variations Immunity

EN 55011:1991
EN 50082-2:1995
EN 61000-4-2:1995
ENV 50140:1993
EN 61000-4-4:1995
EN 61000-4-5:1995
EN 61000-4-6:1996
EN 61000-4-11:1994

ASCO 7000L Power Transfer Switch Ordering Information


7000 + L4 +
Product
7000

200

Load
Center

Poles

4 = 42
Space

2 poles,
1

Amperes

Voltage
Code

Continuous
Rating

200
400

3 poles,
3

208

240

Controller

Options

Insert X
if optional
accessories
are required

+ 240V 60Hz

Optional
Accessories2

Enclosure

73TL1

Type 1
(Standard)

11BG - Programmable
Engine Exerciser

Type 3R
Secure
(Outdoor)

14AA/14BA - Auxiliary
Contacts (2 Sets)1
37P - Generator
Receptacle 3

Specific
Voltage & Freq
This Information
is necessary
to allow correct
settings prior to
shipment

44A - Strip Heater


w/Thermostat
72A -Serial Module
72E - Connectivity
Module
73 - Surge Suppression
(TVSS)
85L - Power Manager
117IB - Interlock Breaker
for Portable Generator
128TB - Telco Cabinet
130MG - Cam Loc3

1. Available on 300L, Power Transfer Load Center only. (two sets are standard) for 7000L Series.
2. See page 12-15 for optional accessories.
3. Available for Type 3R enclosure only, rated 200 Amps. Not available for 400 Amp.

Sizes UL-Listed Solderless Screw-Type Terminals


Switch Rating
(Amps)

Max # of Conductors Ranges of AL-CU Wire Sizes


per Terminal
(Unless Specified Copper Only)

# 4 AWG to 250 MCM


# 1 AWG to 600 MCM
# 1 AWG to 250 MCM

One
One
Two

200
400

Dimensions for UL Type 1 and 3R Secured Enclosure


Dimensions, In. (mm)
Height

Phase
Poles

Width

200

2,3

30(762)

78(1981)

6(152)

250(115)

400

2,3

38(965)

80(2032)

7-1/4(184)

300(138)

2,3

36(914)

53(1346)

11(279)

305(141)

2,3

38(965)

84(2134)

11-1/4(286)

325(149)

Switch Rating
Amps

Depth

Approx. Shipping
Weight Lb. (kg)

Enclosed UL Type1

Enclosed UL Type3R
Aluminum Secure
2001
400

1. Add 20 inches to the height of the type 3R enclosure if accessory 128TB, Telco cabinet is required.
See page 15 for description of optional Telco compartment.

ASCO 300L Power Transfer Switch


Load Center Product Features
Conventional double throw
transfer switch configuration
Automatic Transfer Switch is listed
to UL1008, the standard for Transfer Switch Equipment, and meets
NFPA 110 for Emergency an
Standby Power Systems and
the National Electrical Code (NEC)
articles 700,701,and 702.
Also certified to CSA 22.2
No. 178
Rated up to 240VAC, 200, or 400
amps
Available in Type 1 indoor, or Type
3R secure aluminum
outdoor enclosure
Reliable and field proven single
solenoid operating mechanism
Programmable microprocessor
controller with flush mounted
control and display panel
LED indicators for switch
position and source availability
Engine exerciser for weekly automatic testing of engine generator
set with or without load
Two auxiliary contacts, one contact closed when switch is in
normal position and one contact
closed when switch is in emergency position
Suitable as service entrance
equipment, includes main circuit
breaker overcurrent protection on
the normal source, and circuit
breaker disconnect device on
emergency
Includes a UL 67 Listed 42 position
Square - D panelboard load center
Local/remote communications
capability for interfacing with
ASCO PowerQuest communication products

ASCO 300L Automatic Power Transfer Load Center shown with


optional quick connect Cam - Loc assembly and bottom Telco
cabinet section (in type 3R secure aluminum enclosure)

Short Circuit Ratings


200A Mains: 22kA at 240vac (Main circuit breaker (Normal &
Emergency) Square D circuit breakers rated 2/3 pole, 200A)
Note: If a generator input receptacle is supplied for a portable
generator then the ratings are as follows:
Normal Source 22kA at 240 vac
(Utility Main Disconnect circuit breaker)
Emergency Source #2 (Permanent Generator
Input circuit breaker) 10kA at 240vac
Emergency Source -#1 (Portable Generator
Input circuit breaker) 5kA at 240vac
400A Mains: 42kA at 240vac. (Main circuit breaker (Normal &
Emergency) Square D circuit breakers rated 2/3 pole, 400A)
Panelboard: Square D 225/400A series rated 42 circuit panelboard
single/three phase with 100% rated neutral, accepts bolt on or
plug in branch devices.

Series 300 Microprocessor Controller

Battery to
Maintain Engine
Exerciser Clock
Settings

Re-transfer to
Normal Adjustable
Time Delay

Simple and Accurate


Adjustment of
Voltage, Frequency
and Time-Delay
Settings Without
Need for Meters
and Variable
Power Supplies

Transfer to
Emergency Adjustable
Time Delay

Dip Switches for Enabling


Built-In Control Functions
Serial
Communication Port

Customer Control
Interfaces

Fig. 10: Microprocessor Controller

Performance Features
600 volt spacing per UL and CSA standards.
Interfacing relays are industrial grade, plug-in type with dust covers.
Meets or exceeds the requirements for Electromagnetic Compatibility (EMC).

ANSI C37.90A/IEEE472 Voltage


Surge Test
NEMA ICS-109.21 Impulse
Withstand Test
Digital circuitry isolated from
line voltages
IEC 801-2 Electrostatic
discharge (ESD) immunity
ENV50140 and IEC 803-1: Radiated
electromagnetic field immunity

IEC 801-4 Electrical fast transient


(EFT) immunity
ENV50142 Surge transient immunity
ENV50141: Conducted
radio-frequency field immunity
EN55011: Group 1, Class A conducted and
radiated emissions
Optically isolated RS-485 Serial Port
EN61000- 4-11 voltage dips and interruptions
immunity

Series 300 Microprocessor Controller

The ASCO Series 300 Microprocessor Controller is used with all sizes of Power Transfer Switches. It represents the most
reliable microprocessor controller in the industry and includes, as standard, all of the voltage, frequency, control, timing and
connectivity functions required for most emergency and standby power applications.

Voltage & Frequency Sensing


Adjustable three-phase, close-differential voltage sensing
on normal source.
Normal source pickup voltage is adjustable to 95% of
nominal; drop-out is adjustable from 70% to 90% of nominal.
Frequency sensing on emergency source. Pickup at 95% and
dropout at 85% of nominal.

Time Delays

Fig. 8: ASCOSeries 300


Microprocessor Controller

Adjustable time delay to override momentary normal


source outages to delay all transfer switch and enginestarting signals.
Transfer to emergency time delayAdjustable from 0 to 5
minutes for controlled timing of load transfer to emergency.
Re-transfer to normal time delayAdjustable to 30 minutes.
Five-minute unloaded running time delay for emergency
engine generator cool down.
Four-second time delay to ignore momentary voltage and
frequency transients during initial genset loading.

Standard Selectable Features

Fig. 9: Door-Mounted Control & Display Panel

Inphase monitor to transfer motor loads, without any


intentional off time, to prevent inrush currents from
exceeding normal starting levels.
Engine exerciser to automatically test backup generator
each weekIncludes control switch for testing with or
without load.
Selective load disconnect, double-throw contact to operate
at an adjustable 0 to 20 second adjustable time delay prior
to transfer and reset 0 to 20 seconds after transfer.
60 Hz or 50 Hz selectable switch.
Three-phase/single-phase selectable switch.

Remote Control Features


Control and Display Panel
Easy-to-read flush-mounted control and display panel
provides LED indicators for switch position and source availability. It also includes test and time-delay bypass switches.

10

Terminal provisions for connecting:


Remote test switch.
Remote contact for test or for peak shaving applications.
Circuit will be automatically bypassed if emergency
source fails.

Inhibit transfer to emergency.

Remote time-delay bypass switch.

ASCO 300L Power Transfer Switch Ordering Information


300 + L4 +
Product
300

200

Load
Center

Poles

4 = 42
Space

2 poles,
1

Amperes

Voltage
Code

Continuous
Rating

200
400

3 poles,
3

208

240

Controller

Options

Insert X
if optional
accessories
are required

Enclosure

C
M

73TL1
Optional
Accessories2

Type 1
(Standard)

11BG - Programmable
Engine Exerciser

Type 3R
Secure
(Outdoor)

14AA/14BA - Auxiliary
Contacts (2 Sets)1
37P - Generator
Receptacle 3

+ 240V 60Hz
Specific
Voltage & Freq
This Information
is necessary
to allow correct
settings prior to
shipment

44A - Strip Heater


w/Thermostat
72A -Serial Module
72E - Connectivity
Module
73 - Surge Suppression
(TVSS)
85L - Power Manager
117IB - Interlock Breaker
for Portable Generator
128TB - Telco Cabinet
130MG - Cam Loc3

1. Available on 300L, Power Transfer Load Center only. (two sets are standard) for 7000L Series.
2. See page 12-15 for optional accessories.
3. Available for Type 3R enclosure only, rated 200 Amps. Not available for 400 Amp.

Sizes UL-Listed Solderless Screw-Type Terminals


Switch Rating
(Amps)

Max # of Conductors Ranges of AL-CU Wire Sizes


per Terminal
(Unless Specified Copper Only)

# 4 AWG to 250 MCM


# 1 AWG to 600 MCM
# 1 AWG to 250 MCM

One
One
Two

200
400

Dimensions for UL Type 1 and 3R Secured Enclosure


Dimensions, In. (mm)
Height

Phase
Poles

Width

200

2,3

30(762)

78(1981)

6(152)

250(115)

400

2,3

38(965)

80(2032)

7-1/4(184)

300(138)

2,3

36(914)

53(1346)

11(279)

305(141)

2,3

38(965)

84(2134)

11-1/4(286)

325(149)

Switch Rating
Amps

Depth

Approx. Shipping
Weight Lb. (kg)

Enclosed UL Type1

Enclosed UL Type3R
Aluminum Secure
2001
400

Note: 1. Add 20 inches to the height of the type 3R enclosure if accessory 128TB, Telco cabinet is required.
(see pg. 15 for Telco compartment description)

11

Enhanced Monitoring, Control


and Flexibility Integrated into a
Single Power Transfer Load Center
Managing power reliably for mission critical sites demands
accurate and timely information.
Personnel, whether on site or at a control center, need
that information in a format so it can be evaluated and
acted on quickly. The components and accessories shown
on the following pages deliver that information.

ASCO 7000 Series and Series 300 Power Transfer Load Centers - Optional Accessories
Accessory 11BG
A programmable engine exerciser that provides for
weekly or bi-weekly operation, includes one form C contact for source availability of normal and one contact for
availability of emergency (contact rating 2 amps @ 30
Vdc, 0.5 amp @ 125 Vac resistive). The programmable
engine exerciser incorporates a 7 day or 14 day time base
with a digital readout display. Includes with or without
load control selection for exerciser period. Available on
Series 300L Power Transfer Switch Load Center only, not
required for 7000L Series.

Accessory 73V
Transient voltage surge suppression. ASCO 458 series with
integral LED status indication per phase (Service Available &
Status OK), One (1) Form C contact connected to terminal
block to signal overall status OK.
Single Phase
73VN1: (1) TVSS connected to Normal source only
73VB1: (2) TVSS connected to Normal and Emergency sources
73VL1: (1) TVSS connected to the Load source only
Three Phase
73VN3: (1) TVSS connected to Normal source only
73VB3: (2) TVSS connected to Normal and Emergency sources
73VL3: (1) TVSS connected to Load source only
Alternate TVSS offering: Load Surge Suppressor:
Located at line side of panelboard, ASCO 510 series
with phase monitoring alarm, and load phase voltage
availability indicators (LED)
Single phase 73TL1: (2) TVSS connected to Load source only
Three phase 73TL3: (3) TVSS connected to Load source only
All TVSS UL 1449 3rd Edition Listed

12

ASCO Power Transfer Load Centers - Optional Accessories


Accessory 37P

Accessory 130MG

Receptacle for portable


generator connection,
reverse service case
grounded, NEMA type 4
construction. Right side
mounted from front of
PTLC.

Generator input receptacle


(emergency source #1) male
cam loc (Crouse Hinds)
jacks to mate with customer
provided female plug sets.
Type 3R aluminum enclosure
for bottom cable entry. Right
side mounted on front of
PTLC.

Accessory 117IB
Generator selector circuit breaker (emergency source #1 &
emergency source #2). One each for two/three pole,
200/400A circuit breaker for two separate generator
inputs (UL Listed).
200A - Manual slide type interlock to permit connection
of only one generator to the transfer switch emergency
source input.
400A Walking Beam interlock to permit connection
of only one generator to the transfer switch emergency
source input.

Accessory 85L
Power Manager for load monitoring. The Electronic
Access Module (EAM) provides measurement of voltage,
frequency, and current, and calculation of power,
energy, and power factor.
The data monitor is connected to measure single phase 2
or 3 wire, or three phase 3 or 4 wire systems based on the
configuration of the Power Transfer Load Center.

13

ASCO Power Transfer Load Centers - Optional Accessories


ASCO 5500 Series Thin Web server
Allows monitoring and control of the PTLC and engine
generator anytime via the Internet, Intranet, or Ethernet.
Measures power parameters, engine generator performance, and up to eight digital inputs anytime anywhere
in the world. It also transmits an E-mail message that an
alarm has occurred with one or more of the Power
Transfer Switch Load Centers.

Accessory 72A Serial Module


The serial module is used to allow local or remote
communications with ASCO communication products.
The module is used to connect the 300L/7000L Series
PTLC to a serial network via an RS 485 interface.
The module has two port connectors used for ATS &
Power Manager (accessory 85L) connectivity. The serial
connection is accomplished from a 5 pin terminal
header/socket block. RS 485 serial networks allow
for up to 32 modules to be set up in a daisy chain
configuration to connect to ASCO communication
systems.

Accessory 72E Connectivity Module


The connectivity module is used to bring several different
serial devices that communicate at different baud rates
and then with different protocols to a common Ethernet
media. This module is used to connect the 300L/7000L
series PTLC, and ASCO Remote Annunciators to a
standard Ethernet TCP/IP network with standard 10BaseT
(RJ-45) connectors. The module has customized
embedded JAVA applets (program applications for an
internet browser) for each monitored device that loads
automatically to a standard Web Browser.

14

ASCO Power Transfer Load Centers - Optional Accessories


Accessory 44A

Strip heater with thermostat for extremely cold areas to


prevent condensation and freezing of this condensation.
Wired to the load terminals: 120 volt, contains wring
harness for all PTLC transfer switch sizes.

Accessory 14AA/14BA
Auxiliary contacts to indicate position of main contacts.
Two (2) for normal and two emergency position (one set is
standard). Available on 300L, Power Transfer Load Center
only, (two sets are standard) for 7000L Series (7000 ATS
shown)

Accessory 128TB

Automatic Transfer Switch Annunicator

Telco cabinet includes a 20 Amp, 120 volt duplex


receptacle, insulated terminal bar with ground and two,
two inch nonmetallic conduits for service conductors.
Additional space available to mount external components.
Available on type 3R secure enclosure only.

The ASCO 5310 Annunciator is a stand alone device


capable of providing individual status annunciation for
a power transfer load center. Individual LEDs indicate
switch status and position. Separate push buttons
individually initiate PTLC operation and testing.

15

A SCO Power Technologies


50 Hanover Road
F l o r ha m Park, NJ 07932
USA
8 0 0 8 0 0 A SCO
w w w. ascopower.com
w w w. ascoapu.com

Emerson Network Power.


The global leader in enabling Business-Critical ContinuityTM.

EmersonNetworkPower.com
Outside Plant

AC Power
Connectivity

Embedded Computing
Embedded Power

DC Power

Infrastructure Management & Monitoring

Power Switching & Controls


Precision Cooling

Racks & Integrated Cabinets


Services
Surge Protection

Emerson Network Power and the Emerson Network Power logo are trademarks and service marks of Emerson Electric Co. 2009 Emerson Electric Co.
Publication 3213

September, 2009

Printed in the U.S.A.

Você também pode gostar