Example E.4a
Fu = 65 ksi
Geometric Properties:
W1850
Ix = 800 in.4
W2455
Ix = 1350 in.4
W1482
Ag = 24.0 in.2
Manual
Table 2-1
Manual
Table 1-1
Ix = 881 in.4
Calculate the required strength for the column between the roof and floor
LRFD
ASD
ASD
Pu 250 kips
=
= 10.4 ksi < 18 ksi
Ag 24.0 in.2
Pa
167 kips
=
= 6.96 ksi <12 ksi
Ag
24.0 in.2
= 1.00
= 1.00
Manual
Table 4-21
E-19
35.0 ft
Commentary
C2.2
881 in.4
2
( I c / Lc )
14.0 ft
Gbottom =
= (1.00)
= 1.63
1,350 in.4
( I g / Lg )
2
35.0 ft
Commentary
C2.2 &
Fig. C-C2.4
From the alignment chart, K is slightly less than 1.5. Because the column available strength
tables are based on the KL about the y-y axis, the equivalent effective column length of the
upper segment for use in the table is:
KL =
( KL ) x 1.5 (14.0 ft )
=
= 8.61 ft
2.44
rx
r
y
Take the available strength of the W14x82 from Manual Table 4.1
At KL = 9 ft, the available strength in axial compression is:
LRFD
ASD
o.k.
o.k.
Manual
Table 4-1
Calculate the required strength for the column segment between the floor and the foundation
LRFD
ASD
Pu 600 kips
=
= 25.0 ksi
Ag 24.0 in.2
= 0.890
Gtop
881 in.4
I
2
14.0 ft
L c
=
= ( 0.890 )
= 1.45
I
1350 in.4
2
L g
35.0 ft
ASD
Pa 400 kips
=
= 16.7 ksi
Ag 24.0 in.2
Manual
Table 4-21
= 0.890
Gtop =
I
Lc
I
Lg
= ( 0.890)
881 in.4
2
14.0 ft
1350 in.4
2
35.0 ft
= 1.45
Commentary
Section
C2.2b
E-20
Gbottom = 1 ( fixed )
From the alignment chart, K is approximately 1.42. Because the column available strengths
are based on the KL about the y-y axis, the effective column length of the lower segment for
use in the table is:
( KL) x 1.42 (14.0 ft )
=
= 8.15 ft
2.44
rx
ry
Take the available strength of the W14x82 from Manual Table 4-1
KL =
ASD
o.k.
A more accurate strength could be determined by interpolation from Manual Table 4-1
o.k.
Manual
Table 4-1