Você está na página 1de 101

Generator Protection Setting Calculations

Voltage Inputs,

3Y-3Y VT, secondary wired L-L Example

Example:
Generator rating VL-L = 13,800V
VT Ratio = 14,400/120V = 120/1
13,800V

= 120

13,800/120 = 115

M-3425A

VT Type: Line-to-Line
VNOM = 115 V

Generator Protection Setting Calculations

Voltage Inputs
3Y-3Y VT, secondary wired L-G Example
Example:
Generator rating VL-L = 13,800V
VT Ratio = 14,400/120V = 120
A

VT Type: Line-to-Ground
VNOM = 115/3 = 66.4 V
13,800 V

14,440
VT Ratio = 14,410
120V120

13,800
3

a
V

NOMINAL

= 115
3 =66.5 Line-to-Ground

Generator Protection Setting Calculations

Voltage Inputs
3Y-3Y VT, secondary wired L-G (L-G to L-L selection)
Use of L-L Quantities for Phase Voltage-based elements
The Line-Ground to Line-Line selection should be used
when it is desired to provide the phase voltage-based
elements (27, 59, 24 functions) with phase-to-phase voltages

They will not operate for neutral shifts that can occur during
stator ground faults on high impedance grounded generators

The oscillograph in the relays will record line-ground voltage


to provide stator ground fault phase identification

Generator Protection Setting Calculations

Neutral Shift on Ground Fault:


High Impedance Grounded Generator
C
B

System

a
Van=Vag

SLG

Fault
a

ground

n=g

vag=0

Vbn=Vbg

Van= -Vng

b
Vbn=Vbg

Vcg

Vbg
n

High
Impedance
Ground

c
Vcn

Vbn

A ground fault will cause LG connected phase elements


through a 3Y-3Y VT to have undervoltage or overvoltage
(depending on faulted phase)

Generator Protection Setting Calculations

Voltage Inputs
3Y-3Y VT, secondary wired L-G (L-G to L-L selection on
the relay). This selection is recommended for the
example generator.
Generator rating VL-L = 13,800V
VT Ratio = 14,400/120V
A

13,800 V

B
C

14,440
VT Ratio = 14,410
120
120V

13,800
3

VT Type: LG to LL
VNOM = 115 V

a
V

NOMINAL

= 115
3 =66.5 Line-to-Ground

Software converts
(66.4V) voltages to
LG (66.5V)
LL (115V) quantities

Generator Protection Setting Calculations

Current Inputs
Determine primary current at rated power
Ipri nom = MVA*106 / 3*VLL
Ipri nom = 125*106/(1.732*13800)
Ipri nom = 5,230 A
Convert to secondary value
Ct ratio is denoted as RC
RC = 8000/5 = 1600
Isec nom = I pri nom/RC
Isec nom = 5230/1600
Isec nom = 3.27 A
INOM = 3.27A

Generator Protection Setting Calculations

Delta-Y transform setting (used with 21, 51V)


This setting Determines calculation used for 21
and 51V functions (calculates the GSU high side
voltages and currents)
Disable: Used for YY and Delta/Delta
connected transformers
Delta-AB: Used for Delta-AB/Y connected
transformers
Delta-AC: Used for Delta-AC/Y
connected transformers

Generator Protection Setting Calculations


59/27 Magnitude Select:
This setting adjusts the calculation used for the overvoltage and
undervoltage functions. RMS selections keeps the magnitude
calculation accurate over a wide frequency range. RMS setting is
preferred for generator protection applications where the frequency
can vary from nominal value especially during startup and
shutdown.
Phase Rotation (32, 46, 81):
This setting adjusts nominal rotation. We do not recommend
reversing the CT and PT connections to change the rotation. Using
the software switch will result in proper phase targeting.
50DT Split phase Differential:
Used for split phase hydro machine applications. This setting
changes IA, IB, and IC metering labels and does not affect the
operation of any protective element.

Generator Protection Setting Calculations


Relay Seal In Time:
Normal output mode: Sets the minimum amount of time a
relay output contact will be closed.
Pulse output mode: Sets the output relay pulse length.
Latched: No affect
Pulse Relay:
When selected, the output contacts close for the seal in
time setting then de-energize, regardless of function
status.
Latched Outputs:
This function simulates lock out relay (LOR) operation.
When selected, the output contacts remain closed until
the function(s) have dropped out and the target reset
button is pressed.

Generator Protection Setting Calculations

Generator Protection Setting Calculations

59N Neutral Overvoltage (Gen)

IS

VLL Rating

= 13,800 V

PRIS

IS = 3.5 x 13,800 = 201.3A


240
V59N = 0.7 x 201.3 = 140.9V
Therefore, for a terminal L-G fault, there will be 140.9 V applied to
the generator relay neutral voltage input connection.

Generator Protection Setting Calculations

59N Neutral Overvoltage (Gen)


59N setpoint # 1 = 5.4 V, 2 ~ 10 sec.
This is a standard setting which will provide protection for
about 96% of the stator winding
- The neutral-end 4% of the stator winding will be protected by the
27TN or 59D elements
59N setpoint #1 time delay should be set longer than the
clearing time for a 69 KV fault
- GSU transformer-winding capacitance will cause a voltage
displacement at the neutral. 10 seconds should be long enough
to avoid this situation, or the voltage generated at the neutral
resistor can be calculated and a high enough setting with small
delay may be applied.

Generator Protection Setting Calculations

59N Neutral Overvoltage (Gen)


59N Setpoint #2 = 35 V,
5 sec. (300 cycles)
Note: Setpoints should be
coordinated
with
low
voltage secondary VT
fuses
59N #3 can be used for
alarm and trigger an
oscillograph (set to 5 V
at 1 sec)

Generator Protection Setting Calculations

27TN is set by measurement of


third harmonic voltage during
commissioning
3rd

Observe
harmonic voltage
under various loading conditions
Set the 27TN pickup to 50% of the
observed minimum
Set power and other supervisions
as determined from the data
collected above

3rd H arm o n ic V o ltag e

27TN Third Harmonic Undervoltage

1.50
1.25
1.00
0.75
0.50
Desired Minimum Setting

0.25
10%

30%
20%

50%
40%

70%
90%
60%
80% 100%

Power / VAr

Generator Protection Setting Calculations

27TN Third Harmonic Undervoltage

0.3

Generator Protection Setting Calculations

27TN Third Harmonic Neutral Undervoltage


The 27TN function overlaps with the 59N function to
provide 100% stator ground fault protection. See the
graph below.

Overlap of Third Harmonic (27TN) with 59N Relay

Generator Protection Setting Calculations

59N Neutral Overvoltage (Bus)

14,400
120 V VT

59N is connected to a
broken-delta VT input
on the line side of the
generator breaker for
ungrounded system
bus protection
The
system
is
ungrounded
when
backfed from the GSU
and the generator
disconnect switch is
open

3EO = 3 x 66.5 = 200 V

Generator Protection Setting Calculations

59N Neutral Overvoltage (Bus)


The maximum voltage for a solidly-grounded fault
is 3 x 66.5 = 200 V.
Because of the inaccuracies between the VTs, there
can be some normal unbalanced voltages.
59N Setpoint #1 Pick-up = 12 V, 12 sec (720 cycles)
59N Setpoint # 2 Pick-up = 35 V, 5.5 sec (330
cycles)

Generator Protection Setting Calculations

46 Negative Sequence
Nameplate
10% continuous capability of stator rating (125 MVA),
the same as that stipulated in ANSI/IEEE C37.102.
The K factor is 30.
Set Inverse Time Element for Trip

Pick-up for tripping the unit (Inverse Time) = 9%


K=29

Definite Maximum time = 65,500 cycles.


Set Definite Time Element for Alarm

Pickup =5%
Time delay = 30 sec (1800 cycles). Note that 30 sec
should be longer than a 69 KV system fault clearing
time.

Generator Protection Setting Calculations

46 Negative Sequence
Check the response of the 46 function for high-side (69 kV)
phase-to-phase faults.

Relay operating time is 7


seconds for 69 kV faults.
This should provide
adequate coordination
with 69 kV system.

Generator Protection Setting Calculations

Negative Sequence Overcurrent (46)


46IT Pickup=9%
Definite maximum time (65,500 cycles)

Pickup 5%
46DT Alarm
Time Delay = 30 s

46IT, K=29

Generator Protection Setting Calculations

46 Negative Sequence

29

Generator Protection Setting Calculations

87G Generator Differential

CTs are of C800 Standard quality

Generator Protection Setting Calculations

87G Generator Differential


Generator CT Short Circuit Calculation:
Check for the maximum three-phase fault on the terminals
of the generator to determine the secondary current for
the worst-case internal fault.

X "d ( saturated ) = 15.6%


Xd

V 100
=
6.4 pu
I 15.6
I pri (13.8 KV ) = 5230(6.4) = 33,472 A

I pu =

I sec

I pri

33,472
=
=
= 20.92 A
Rc
1600

Generator Protection Setting Calculations

87G Generator Differential


69KV Fault Current Calculation:
Check for the maximum three-phase fault on the terminals
of the generator to determine the secondary current for
the worst-case external fault.

X "d ( saturated ) = 15.6%


Xd

X sys = 10%(125MVA)
I pu

100
V
=
=
3.9 pu
X "d + X t 15.6 + 10

I pri (13.8 KV ) = 5230 3.9 = 20,397 A


I sec

I pri

20,397
=
=
= 12.75 A
Rc
1600

Generator Protection Setting Calculations

87G Generator Differential


CT Requirement Check
Rctr

RW

45

RR

VK
VS

VS
Rctr = CT Resistance
Rw = Wiring Resistance
RR = Relay Burden = 0.5 VA @ 5A
= 0.02

IS
VK > VS

CTs should perform well since the maximum current is only


21 A (CT secondary) for worst-case short circuit.

Generator Protection Setting Calculations

87G Generator Differential


IEEE GUIDE FOR THE APPLICATION OF CURRENT TRANSFORMERS
IEEE Std C37.110-1996

Generator Protection Setting Calculations

87G Generator Differential


Setting Summary
Pick-up = 0.3 A (480 A primary sensitivity)
Slope = 10%
Time Delay = 1 cycle (no intentional time delay)
(if ct saturation is possible time delay should be
increased to 5 cycles)

Generator Protection Setting Calculations

87G Generator Differential

Generator Protection Setting Calculations

24 Volts/Hertz (Overfluxing)
1.40
p.u.

1.35

1.30

1.25

1.20

1.15

1.10

1.05

1.00
0

200

400

600

800

1000

1200

time

Overfluxing Capability, Diagram

1400

1600

1800

2000

Generator Protection Setting Calculations

24 Volts/Hertz (Overfluxing)
10000

1000

Inverse Time Element


Pickup = 110%
Curve #2
K= 4.9

Generator V/Hz Capability


V/Hz Protection Curve (Inverse)
V/Hz Protection Curve (Definite time)

Time in sec

t = 60 e (115 +2.5 K VHz ) / 4.8858


100

Alarm Settings:
Definite Element #2
Pickup = 106%
Time Delay = 3 sec

10

Definite time element #1


Pickup = 135%
Time Delay = 4 sec

0.1
100

105

110

115

120

125

130

135

140

145

V/Hz in percent of nominal

Protection can be provided with an inverse time element (24IT) in combination


with a definite time element (24DT#1)

Another definite time element (24DT#2) can be used for alarm with a typical
pickup of 106% and a time delay of 3 sec

Generator Protection Setting Calculations

24 Volts/Hertz (Overfluxing)

Generator Protection Setting Calculations

50/27 Inadvertent Energizing


The 50/27 inadvertent energizing element senses the value of the current for
an inadvertent energizing event using the equivalent circuit below.

X2 = 16.4 %
X1SYS = 6.25%

Values shown above are from


generator test sheet

X2
All reactances on generator base (125 MVA)

Where X2 is the negative sequence reactance of the generator


The current can be calculated as follows:
I = ES/(X2 + XT1 + X1SYS)
= 100/(16.4 + 10 + 6.25)
= 3.06 pu
= 3.06 x 5230 = 16,004 A

Generator Protection Setting Calculations

50/27 Inadvertent Energizing


The current can be calculated as follows:
I = ES/(X2 + XT1 + X1SYS)
= 100/(16.4 + 10 + 6.25) = 3.06 pu
= 3.06 x 5230 = 16,004 A
The relay secondary current :
= 16004/RC = 16004/1600 = 10 A
Set the overcurrent pickup at 50% of this value = 5 A
For situations when lines out of the plant are removed from service,
X1SYS can be larger. Considering this case set 50 element pickup at 125%
of full load or 4.0 A. Many users set the 50 Relay below full load current
for more sensitivity, which is ok.

Generator Protection Setting Calculations

50/27 Inadvertent Energizing


The undervoltage element pickup should be set
to 40 to 50% of the nominal value:
The undervoltage pickup = 0.4 x 115 V = 46.1 V
The pickup time delay for the 27 element should
be set longer than system fault clearing time.
Typical value is 5 sec (300 cycles)
The dropout time delay is set to 7 sec (420
cycles).

Generator Protection Setting Calculations

50/27 Inadvertent Energizing

46

Generator Protection Setting Calculations

Voltage Control/Restraint Overcurrent (51V)

System Configuration with Multiple In-Feeds

Provide backup for system phase faults

Difficult to set: must coordinate with system backup protection

Coordinate general setting criteria


-

backup relaying time

breaker failure

Consideration should be given to system emergency conditions.

Generator Protection Setting Calculations

Voltage Control/Restraint Overcurrent (51V)


Voltage control/restraint needed because of generator fault current decay

Voltage Control Types:


Voltage Control (VC): set 51V pickup at a percent of full load (40-50%)
Voltage Restraint (VR): set 51V pickup at about 150% of full load

Generator Protection Setting Calculations

51V Voltage Restraint Overcurrent


This function provides backup protection for phase faults out in the
power system.
Set this relay for Voltage Restraint mode.
It will have the following characteristic.

Pickup = 1.5 x Generator Full Load


Rating

% Pickup

IFL = 3.27A
Pickup current = 3.27 x 1.5 = 4.9 A

Input Voltage (% of rated voltage)

Where % pickup is the adjusted pickup current based on the


voltage as a percent of pickup setting.

Generator Protection Setting Calculations

Voltage Control/Restraint Overcurrent (51V)


Calculate the fault current for a 3 phase 69 KV fault:

Egen

XT

Xd

X"d (saturated) = 15.6%


X sys = 10% (125MVA)
E gen

100
I pu =
=
3.9pu
X"d + X t 15.6 + 10
I pri (13.8KV) = 5230(3.9) = 20,397A
I sec =

I pri
Rc

20,397
= 12.75A
1600

Generator Protection Setting Calculations

Voltage Control/Restraint Overcurrent (51V)


Determine generator phase voltage for 3 phase 69KV fault:

Vgen =

Xt
10
100% =
100% = 39%
15.6 + 10
X "d + X t

Multiples of pickup (MPU) for a 3 phase fault on 69KV bus:

MPU =

I fault
I pickupVgen (%)

12.75
= 6.67
4.9(0.39)

Generator Protection Setting Calculations

Definite Time Overcurrent Curve


Select the Curve and Time
Dial to get 1.0 sec clearing
time for 69KV fault:
Definite Time curve
Time Dial = 4.5

MPU = 6.67

Generator Protection Setting Calculations

Voltage Control/Restraint Overcurrent (51V)


51V Setting Summary:
Pickup = 4.9 A
Definite Time Curve
Time Dial = 4.5
Voltage Restraint

Generator Protection Setting Calculations

Voltage Control/Restraint Overcurrent (51V)


Now calculate the lowest fault current for a 3-phase fault:
Assumptions:
Generator was not loaded prior to fault
Automatic Voltage Regulator was off-line
Transient and Subtransient times have elapsed and the machine
reactance has changed to its steady state value (Xd).
The fault current is given by the same equivalent circuit except
replace the subtransient reactance of the generator with
synchronous reactance (Xd) of 206.8%.

I MinFault =

E gen
Xd + Xt

100
= 0.46 pu
206.8 + 10

I sec = I MinFault I no min al = 0.46(3.27) = 1.5 A

Generator Protection Setting Calculations

Voltage Control/Restraint Overcurrent (51V)


It can be seen that for a bolted 3-phase fault (at the transformer
terminals), the current is less than 50% of the full load current. This is
the reason why we need to apply Voltage restraint/Voltage control
setting for overcurrent function.

The voltage at the generator terminals during this condition is


given by:
Vgen = (Egen x XT)/(Xd + XT)
= 100 x 10/(206.8+10) = 0.04612 pu
= 0.04612 x 115 = 5.3 V
Since the voltage is below 25% of the rated voltage, the
overcurrent pickup will be 25% of the setting:

Generator Protection Setting Calculations

Voltage Control/Restraint Overcurrent (51V)


Over Current pickup = 4.9 x 25% = 1.225 A.
Since the fault current is 1.5 A, the multiple of
pickup is 1.5/1.225 = 1.23 multiple.
With time dial setting of 4.5 and definite time curve,
the relay operating time is around 5.3 seconds.
Since the actual fault current during transient and
subtransient periods are much higher than 1.5 A
the operating time will be between 1 and 5.3
seconds.

Generator Protection Setting Calculations

Voltage Control/Restraint Overcurrent (51V)

=>Enable Voltage Restraint


=>Do not select blocking on VT fuse loss (only for Beckwith Relays,
other relays may require blocking). VT fuse-loss blocking is not required
for Voltage restraint and it is only required for Voltage Control. For
voltage restraint the relay will internally keep the 51V pickup at 100%
during VT fuse-loss condition.

Generator Protection Setting Calculations

System Phase Fault Backup (21)

Provides protection for failure of system primary relaying

Provides protection for breaker failure

Must balance sensitivity vs. security


-

loadability

load swings

Generator Protection Setting Calculations

System Phase Fault Backup (21)

For a fault at F the approximate apparent impedance effect is:

The fault appears farther than the actual location due to infeed.

Generator Protection Setting Calculations

System Phase Fault Backup (21)

Transformer
Direct Connected

Transformer DeltaAC Connected

Transformer DeltaAB Connected

VT Connection

VT Connection

VT Connection

L-L or
L-G to L-L

L-G

L-L or
L-G to L-L

L-G

L-L or
L-G to L-L

L-G

AB Fault

VAB
Ia-Ib

VA-VB
Ia-Ib

VBC-VAB
(3)Ib

VB-VO
Ib

VAB-VCA
(3)Ia

Va-Vo
Ia

BC Fault

VBC
Ib-Ic

VB-VC
Ib-Ic

VCA-VBC
(3)Ic

VC-VO
Ic

VBC-VAB
(3)Ib

Vb-Vo
Ib

CA Fault

VCA
Ic-Ia

VC-VA
Ic-Ia

VAB-VCA
(3)Ia

VA-VO
Ia

VCA-VBC
(3)Ic

Vc-Vo
Ic

Generator Protection Setting Calculations

System Phase Fault Backup (21)

0.85 power factor corresponds to 31.8

Generator Protection Setting Calculations

21 Phase Distance
The 21 function should be set to provide system backup protection.
To 5559
line 86

line 96
3976

To PP4

3975
line 87

125 MVA base


10%
GEN

69 KV
4,000 foot cable

21
To line 83

To sub 47

3974

3977

line 97
3978

3972

3973
line 94

To sub PP4

To PP4

All breakers have breaker failure protection.

All lines out of the substation have high-speed pilot


wire protection.
The 4,000 foot cable of 69 KV is protected by a HC8-1
pilot wire scheme. We need to provide backup if this
high-speed scheme fails. Set 21-2 unit to look into the
substation.

Generator Protection Setting Calculations

21 Phase Distance
Typical 69 kV cable impedance: (0.2 + j0.37)% per mile
= (0.2 + j0.37) x 4000 = (0.152 + j0.28)% @100 MVA
5280
Change base to 125 MVA:
= (0.152 + j0.28)x (125/100) = (0.19 + j0.35)%
The transformer impedance is 0.1 pu on generator base
The secondary (relay) impedance = 0.1 x 20.3 = 2.03 ohms.

Generator Protection Setting Calculations

21 Zone-1 Settings:
Zone-1 will be set to look into the low side of the
step-up transformer, but not into the 69kV system.

125 MVA base


10% or 0.10 p.u.
GEN

(0.19 + j0.35)%
69 KV
4,000 foot cable
21

Generator Protection Setting Calculations

21 Zone-1 Settings:
Set zone 21-1 into generator step-up transformer but short
of 69 kV bus. A margin of .8 is used to compensate for LTC
(if used).
(0.1 for margin, and 0.1 for the LTC variation)
2.03 x .8 = 1.60
Setting Summary for 21-1
Diameter =1.6
Time delay = 0.5 sec. (30 cycles)
Angle of maximum torque: 85
60FL supervised

Generator Protection Setting Calculations

21 Zone-2 Settings:
Zone-2 will be set to look up to the substation bus.
Calculate zone 21-2 setting as follows:
(0.19 + j0.35) + j10.0 = 0.19 + j10.35 10.35%
Set zone 21-2 with 1.3 margin:
10.35% x 1.3 13.45%
From our earlier calculations 1.0 pu secondary (relay) impedance
= 20.3
Then the Zone-2 reach setting is:
= 0.1345 x 20.3 = 2.73 .

Generator Protection Setting Calculations

21 Zone-2 Settings:
Setting Summary for 21-2
Diameter = 2.73
Time delay = 1.0 sec (60 cycles). This should cover
backup clearing for fault on transmission (69 KV)
system. Most lines have a dual primary.
Angle of maximum torque: 85
60FL supervised

Generator Protection Setting Calculations

Phase Distance (21)


RPFA: Rated Power
Factor Angle

jX

Generator loadability
considerations:

Z2

2.7

Z1
1.6

85o

Z2 reach at
RPFA 1.64 (31.8o)

Z2 at RPFA should
not exceed 150 to 200
% of generator rating

In our example Zone-2 reach at RPFA should not exceed 50% to 66.66% of
1.0 pu impedance (200% to 150% load).
50% impedance = 10.15 Ohms at 0.85 pf (31.8o)
With Zone-2 set at 2.7 Ohms and MTA of 85o the reach at RPFA of 31.8o
= 2.73 x (Cos (MTA-RPFA) = 1.64 Ohms.
Normal load will not encroach into the Zone-2 characteristic.

Generator Protection Setting Calculations

(21) Phase Distance

Generator Protection Setting Calculations

Breaker Failure-50BF
When the relay (or another device) send a trip signal to open the
breaker and current continues to flow OR the breaker contact
continues to indicate closed, the upstream breaker is tripped.

Generator Protection Setting Calculations

50BF Generator Breaker Failure


Steady state bolted fault current for a 3-phase fault at the
transformer terminals is 1.5 A (relay secondary).
Set the 50BF phase function current pickup at 1 A, which is below
the fault current.
Set the breaker failure time longer than the maximum clearing time
of the breaker plus the margin.
Initiate 50BF with all relays that can trip the generator breaker.
Set the 50BF Timer: 4(margin) + 1(accuracy) + 5(breaker time)
= 10 cycles.
Use programmable inputs to initiate the breaker failure for all other
relays that trip the generator breaker.

Generator Protection Setting Calculations

50BF Generator Breaker Failure


Setting Summary

50BF Pickup = 1 A
Time Delay = 10 cycles
Initiate the breaker failure with programmable inputs
from external trip commands.
Initiate the breaker failure with the outputs (from
internal trip commands) connected to trip.

Generator Protection Setting Calculations

50BF Generator Breaker Failure


1.00

Breaker Failure Trip Output

BFI

BFI

Output Initiate Output contacts within M-3425A that trip


generator breaker.
Input Initiate Input into breaker failure logic tripping of
generator breaker of other trip device i.e., turbine
trip, other relays.

Generator Protection Setting Calculations

Loss of Field Protection (40)


TYPICAL GENERATOR CAPABILITY CURVE

Generator Protection Setting Calculations

TRANSFORMATION FROM MW-MVAR TO R-X PLOT

MVA = kV2
Z

MW MVAR

R-X PLOT

( Rc )
Rv

Generator Protection Setting Calculations

LOSS OF FIELD PROTECTION


SETTING CHARACTERISTICS
+X

-R

HeavyLoad

- Xd
2

1.0pu

Heavy Load Light Load

LightLoad
+R

Zone1

Xd

-R

XTG +Xmin SG1


- Xd
2

Zone 2

ImpedanceLocus
During Loss of Field

Zone 1
1.1Xd

Zone2

-X

Scheme 1

Scheme 2

Directional
Element

+R

Impedance Locus
During Loss of Field

Generator Protection Setting Calculations

40 Loss of Field
Generator Ratings (Primary):
Rated (base) MVA = 125
Rated (base) Phase-PhaseVoltage (VB): 13.8 kV
Rated (base) Current (IB) = MVA x 103/(3 VB) = 5,230 A
Secondary (Relay) quantities:
CT Ratio (RC) = 8000/5 = 1600; VT Ratio (RV) = 14400/120 = 120
Nominal VT Secondary (VNOM): = VB/ RV
= 13.8 x 103/120 = 115 V
Nominal CT Secondary (INOM): = IB/ RC = 5230/1600 = 3.27 A
Nominal (1.0 pu) impedance = VNOM/INOM
= 115/ (3 x 3.27) = 20.3

Generator Protection Setting Calculations

40 Loss of Field (Scheme 1)


Generator Parameters (125 MVA base)
Xd = 2.068 pu
X' = 0.245 pu
d

Zone-1 Settings
Diameter: 1.0 pu = 1.0 x 20.3 = 20.3 ohms
Offset = -X ' /2 = (0.245/2)x20.3 = -2.5 ohms
d

Time Delay = 5 cycles

Zone-2 Settings
Diameter: X

= 2.068 x 20.3 = 42.0 ohms

Offset = -X' /2 = (0.245/2)x20.3 = -2.5 ohms


d

Time Delay = 30 cycles

Generator Protection Setting Calculations

40 Loss of Field
0

Xd = 2.5
2

Zone 1

1.0 p.u. = 20.3

Xd = 42.0

Zone 2

-X

Generator Protection Setting Calculations

Generator Characteristics
20

Q(Mvar)_)

Reactive Power into the Generator

Overexcited
Real Power into the System

P (MW)

0
0

20

40

60

80

100

120

140

Underexcited
-20

-40

-60

MEL

GCC

SSSL

MEL
GCC
SSSL

-80

If it is possible, it is desirable to fit the relay characteristic


between the steady state stability limit and generator capability
curve. In this example the Zone-2 diameter can be reduced to
meet this criteria.

Generator Protection Setting Calculations

Loss of Filed Settings on the R-X Plane


10

jX

MEL
GCC
SSSL

(Scheme 1)

0
-30

-20

-10

-10

Zone 2

Zone 1
-20

-30

-40

-50

10

20

30

Generator Protection Setting Calculations

Loss Field Settings on P-Q Plane


(Scheme 1)
20

Overexcited
P (MW)

Real Power into the System


0
0

Reactive Power into the Generator

-20

20

40

60

80

100

120

Underexcited
MEL

GCC
SSSL

-40

MEL
GCC
SSSL

-60

Zone 2
-80

-100

Q (Mvar)_

140

-120

-140

Zone 1

Generator Protection Setting Calculations

40 Loss of Field (Scheme 1)

Generator Protection Setting Calculations

40 Loss of Field (Scheme 2)


Zone-1 Settings
Diameter
= 1.1 Xd Xd/2 = 1.1 x 42 5/2 = 43.7 ohms
Off-set

= -Xd/2 = -5/2 = -2.5 ohms

Time Delay

= 15 cycles

Zone-2 Settings
Diameter
= 1.1 Xd + XT + Xsys
= 1.1 x 42+2.03+1.27 = 49.5 Ohms
Off-set
= XT+Xsys = 2.03 + 1.27 = 3.3 ohms
Angle of Directional Element: -13o
Time Delay
= 3,600 cycles (60 cycles if (accelerated
tripping with undervoltage supervision is not applied)
Undervoltage Supervision:
Undervoltage Pickup = 80% of nominal voltage
= 0.8 x 115 = 92 V
Time Delay with undervoltage = 60 cycles.

Generator Protection Setting Calculations

Loss of Filed Settings on the R-X Plane


(Scheme 2)
10

jX

Directional Element

0
-30

-20

-10
Zone 2

MEL
GCC
SSSL

Zone 1
-10

-20

Dir Element
X
0
10
-10

-30

-40

-50

10

20

30

Generator Protection Setting Calculations

Loss Field Settings on P-Q Plane


(Scheme 2)

Q(Mvar)_)

Reactive Power into the Generator

20

Overexcited
Real Power into the System

P (MW)

0
0

20

40

60

80

100

120

140

Underexcited
-20

MEL

GCC
Zone 2

-40

SSSL

-60

-80

MEL
GCC
SSSL

Zone1

Generator Protection Setting Calculations

40 Loss of Field (Scheme 2)

Generator Protection Setting Calculations

Reverse Power (32)


Prevents generator from motoring on loss of prime mover
Typical motoring power in percent of unit rating
Prime Mover
Gas Turbine:
Single Shaft
Double Shaft
Four cycle diesel
Two cycle diesel
Hydraulic Turbine
Steam Turbine (conventional)
Steam Turbine (cond. cooled)

% Motoring Power
100
10 to 15
15
25
2 to 100
1 to 4
0.5 to 1.0

Generator Protection Setting Calculations

Reverse Power (32)


Generator is not affected by motoring (runs like a
synchronous motor)
Turbine can get damaged
Since the example generator is driven by a gas
turbine (10 to 15%) the reverse power relay pickup is
set at 8%
Time delay is set at 30 sec.

Generator Protection Setting Calculations

Reverse Power (32)


In some applications it
is desirable to set a
low forward power
setting
instead
of
reverse power.
This can be achieved
by selecting Under
Power selection along
with a positive pickup
setting.

Generator Protection Setting Calculations

78 Out-of-Step
Generator and transformer test sheet data, and system
information:
Xd =24.5%
XT = 10% on generator base
XSYS = 6.25% on generator base

Use graphical method to determine settings.

Generator Protection Setting Calculations

78 Out-of-Step
The per unit secondary (relay) impedance = 20.3
Convert all impedances to secondary (relay):
Direct axis transient reactance (Xd) =
(24.5/100)x 20.3 = 5.0
Transformer impedance (XT) =
(10/100)x 20.3 = 2.03
System impedance (XSYS) =
(6.25/100)x 20.3 = 1.27 .

Generator Protection Setting Calculations

Out-of-Step (78)
jX

XSYS
1.5 XT = 3 ohms

XT

1.5 XT
0

T
GEN
(Xd' )

R
N
120o

S
swing locus

'
2 Xd = 10 ohms
d
2.4 ohms

Generator Protection Setting Calculations

Settings of 78 Function From Graph:


Circle diameter

= (2 Xd+ 1.5 XT) = 10 + 3 = 13

Offset

= -2 Xd = -10

Impedance angle = 90
Blinder distance (d) = ((Xd+ XT+XSYS)/2) tan (90-(120/2))
d = 2.4
Time delay = 2 to 6 cycles (3 cycles)
Trip on mho exit = Enable
Pole slip counter = 1.0
Pole slip reset = 120 cycles

Generator Protection Setting Calculations

78 Out-of-Step

Generator Protection Setting Calculations

Fuse Loss Detection (60FL)


(block 51V, 21, 40, 78, 32)

Generator Protection Setting Calculations

Phase Undervoltage (27)

Under voltage condition generally


does not cause generator
damage.
The limitation will be with the
dropping of the plant auxiliaries
Undervoltage function is typically
set to Alarm rather than Trip.

Definite time element #1


Pickup = 90% (104 V)
Time delay = 10 sec (600 cycles)

Definite time element #2


Pickup = 80% (92 V)
Time delay = 5 cycles

104
600

92
120

Ensure fuse loss and


breaker position (52b)
are set to block.

Generator Protection Setting Calculations

Phase Overvoltage (59)


Generators are designed to
operate continuously at 105%
of the rated voltage
Overvoltage condition can cause
over fluxing and also can
cause excessive electrical
stress.

127
600

173

Set the overvoltage function as


follows:
Definite time element #1
Pickup = 110% (127 V)
Time delay = 10 sec (600 cycles)
Definite time element #2
Pickup = 150% (173 V)
Time delay = 5 cycles

Generator Protection Setting Calculations

81 Frequency Protection
The generator 81U relay should be set below the pick-up of
underfrequency load shedding relay set-point and above the off
frequency operating limits of the turbine generator.
If there are any regional coordinating council requirements they
must be met also.
The multiple setpoint underfrequency protection is common on
Steam turbine generators and for gas turbines a single setpoint
underfrequency protection may be employed.
In this example the Florida Coordinating Council requirements
are used as a guideline for under frequency/over frequency
settings. Due to the lack of information from the
generator/turbine manufacturer and load shedding relay
settings.

Generator Protection Setting Calculations

81 Frequency Protection
Florida Regional Coordinating Council
guidelines:

Generator Protection Setting Calculations

81 Frequency Protection
Generator limits: IEC 60034-3: 2005
This IEC standard specifies that the generator is required to
deliver rated power at the power factor over the ranges of +/- 5%
in voltage and +/-2% in frequency.
Operation beyond these limits must be restricted both in time
and extent of abnormal frequency.

Generator/Turbine Mechanical Limits:


Depending upon the type of machine, additional mechanical limits
may be in place that should be considered when setting this
element.

Generator Protection Setting Calculations

81 Frequency Protection
Setting Summary:
81-1 : Pickup: 60.6 Hz
Time Delay: 10 sec
(may be set to alarm)
81-2: Pickup: 59.4 Hz
Time Delay: 60 sec
81-3: Pickup: 58.4 Hz
Time Delay: 10 sec
81-4: Pickup: 57.4 Hz
Time Delay: 1 sec

Generator Protection Setting Calculations

Field Ground Protection (64F)


Field Tests of the 64F

Safety Considerations

The signal applied by the


M-3425 64F is less than
20Vp-p.
Generator and Field must
be
de-energized for
this test.
All test equipment must
be removed prior to
energization.

Generator Protection Setting Calculations

Field Ground Protection (64F)


Injection Frequency adjustment

Decade
Box

Initial Conditions:
Field breaker closed
Relay energized
Generator and excitation system
must be ground free (resistance
field-ground >100Kohms)
Test Setup:
Connect a decade box (0-100K
range) between the field winding
and ground
Injection Frequency Adjustment:
Set the decade box to 50K ohms
Monitor the measured field
insulation resistance and adjust
the injection frequency setting
until a 50K ohm reading is
obtained.
Reset the decade box to 5K and
check the measured resistance.
Reset the decade box to 90K and
check the measured resistance.
Fine tune the injection frequency
for best overall performance
Disconnect the decade box

Generator Protection Setting Calculations

Field Ground Protection - Metering


Real-Time Insulation Measurements

Field Insulation
Real-Time Monitoring

Generator Protection Setting Calculations

Field Ground Protection (64F)

Setting the 64F:


General Guidelines
- Setting should not exceed
60% of ungrounded resistance
reading to prevent nuisance
tripping
Typical settings
- #1 Alarm 20 K ohms, 600 cyc
delay
- #2 Trip 5 K ohms, 300 cyc
delay
-

Time delay setting must


be greater than 2/finjection

Generator Protection Setting Calculations

Field Ground Protection (64F)


Factors affecting 64F performance
Brushes

- Excitation systems have


capacitors installed between the
+/- field and ground for shaft
voltage and surge suppression. To
minimize this effect, injection
frequency may be adjusted
downwards at the expense of
response time.

Generator Protection Setting Calculations

Brush Lift Detection (64B)

Initial Conditions:
> Field breaker closed
> Relay energized
> Generator and excitation
system
must be ground free (resistance
field-ground >100Kohms)
Brush lift-off simulation:
> Using the M-3425 secondary
metering screen or the status
display, record the brush lift
detection voltage.
> Remove the machine ground
connection and record the
brush voltage (denoted as
faulted condition).
> Restore the ground connection

Generator Protection Setting Calculations

Field Ground Fault Protection


Real-Time Measurement

Brush Voltage

Generator Protection Setting Calculations

Brush Lift Detection (64B)


Setting the 64B:
General Guidelines:
- 64B pickup = unfaulted voltage + 0.5 (faulted brush voltageunfaulted brush voltage)
- 64B delay = 600 cycles
Factors affecting 64B performance:
- The brush voltage rise (faulted brush voltage-unfaulted
brush voltage) varies directly with the capacitance between
the rotor and ground. Therefore machines with lower
capacitance will exhibit a smaller change in brush voltage
when faulted. These machines may require experimentation
to yield a pickup setting that provides the necessary security
and sensitivity.

Generator Protection Setting Calculations

64F/B - Field Ground Protection

300

600

0.5

2008 Beckwith Electric Co., Inc.

Você também pode gostar