Escolar Documentos
Profissional Documentos
Cultura Documentos
com
www.osram.de
June 2009
DALI_Cover_E.indd 2
Contents
1
1.1
1.1.1
1.1.2
1.1.3
1.1.4
Introduction ................................................................. 4
Dimmable lighting systems .............................................. 4
Economy......................................................................... 4
Lighting comfort .............................................................. 5
Reliability/Safety .............................................................. 6
The right control unit for every application ....................... 6
2
2.1
2.2
2.2.1
2.3
2.3.1
2.3.2
2.3.3
2.3.4
2.3.5
2.3.6
2.3.7
2.4
2.4.1
2.4.2
2.4.3
2.4.4
2.4.5
2.5
2.5.1
2.5.2
2.5.3
2.5.4
2.5.5
2.6
2.6.1
2.7
2.7.1
2.8
2.9
2.9.1
3.1
3.2
3.2.1
3.2.2
3.2.3
3.2.4
3.2.5
3.2.6
3.2.6.1
3.2.6.2
3.2.7
3.3
3.3.1
3.3.2
3.3.4
3.8.1
3.8.2
3.8.3
3.8.4
3.9
3.9.1
3.9.2
5
5.1
3.3.5
3.4
3.5
3.5.1
3.5.1.1
3.5.1.2
3.5.1.3
3.5.1.4
3.6
3.6.1
3.6.2
3.6.3
3.6.4
3.7
3.7.1
3.7.2
3.7.3
3.7.4
3.7.5
3.7.6
3.8
8
8.1
8.1.1
8.1.2
8.1.3
8.1.4
8.1.5
8.1.6
8.2
8.2.1
9
9.1
9.1.1
9.2
9.3
9.4
9.5
9.6
Appendix ..................................................................... 80
Starting currents and max. number of ECGs in
automatic cutouts ......................................................... 80
Minimum triggering levels for B/C characteristic ............ 80
DALI fade time and fade rate ......................................... 81
Lamp wiring .................................................................. 81
Operating parameters of the ECG lamp combinations ... 84
Energy classifications .................................................... 85
The DALI standard (IEC 62386) at a glance ................... 86
Index
..................................................................................... 87
1 Introduction
1.1
1.1.1
Economy
Intelligent energy-saving concepts in building management lower the
lighting costs many times over:
Up to 50 % less power consumption compared to operation with
magnetic, conventional electronic control gears (CCG)
More than 50 % longer lamp lifetime compared to operation with
ECG and low-loss electronic control gears (LLG) through defined
lamp operation ! Lower maintenance costs
Lowering of energy costs for air conditioning systems by reducing
the cooling load
1.1.2
Lighting comfort
Lighting situations at the touch of a button (lighting scenes), also with
integrated presence detection and daylight/time-dependent control,
increase lighting comfort. The features of a high-quality dimmable
ECG also include:
Flicker-free ignition
Comfortable, continuously dimmable (1(3)100 %) and flicker-free
lighting without stroboscopic effects
Virtually noise-free, no irritating humming of chokes (CCG/LLG)
No flashing of defective lamps
Automatic restart after lamp replacement
Easy-to-use, feedback messages to the control unit and configuration of personal lighting values create individuality
Figure 2: Energy saving and increased lighting comfort through integrated presence detection with daylight/time-dependent control
This has been made possible mostly thanks to technical developments. Modern dimmable ECGs with digital (DALI = Digital Addressable Lighting Interface) or analog (110 V) interface in combination
with corresponding control elements, control units and sensors create
the preconditions for simple and low-cost realization of more efficient
and convenient lighting systems.
1.1.3
Reliability/Safety
Reliability and safety play a crucial role in the use of electronic control
gear. Key features of high-quality ECGs include:
Preheating of both lamp filaments
Dependable lamp ignition to an ambient temperature of -20 C1
Dependable lamp operation in the temperature range of -20 C to
75 C
Dependable shutdown of the ECG in the event of a fault and at
"End of Life" (EoL)
Compliance with all current applicable ECG standards:
Safety (EN61347)
Performance (EN60929)
Harmonic current emissions (EN61000-3-2)
Radio interference suppression from 9 kHz to 300 MHz
(EN55015: 2006 + A1:2007)/CDN measurement
Immunity (EN61547)
1.1.4
2 Overview of dimmable
electronic control gears
2.1 Block diagrams of a digital/analog dimmable ECGs2
a) Digital dimmable ECG with DALI interface
2.2
2.2.1
DALI
Non-addressable
Wiring acc. to groups required
Addressing possible:
Individual (max. 64 addresses)
In groups (max. 16)
All together
! No wiring acc. to groups
Not possible
Not possible
Not possible
Not possible
Integrated mains voltage switch (switchoff of the ECG via DALI interface, no relay
necessary)
2.3
2.3.1
Simplified installation
The installation of DALI is carried out with commercially available installation material for 230 V line voltage. The two wires of the five-wire
cables (e.g. NYM 5 x 1.5 mm) that are not needed can be used for
the DALI interface - regardless of polarity. Thus, no separate bus cable is required! The ECG and control unit can be operated on different
line voltage phases.
2.3.2
2.3.3
2.3.4
2.3.5
10
2.3.6
2.3.7
2.4
2.4.1
The electrodes of a low pressure discharge lamp are coated with an emitter (barium, strontium and
calcium oxide) to reduce the work function of the electrons from the tungsten filament wire. These
oxides are strongly hygroscopic and interact with the humidity of the air (consequence: relatively low
light yield, high lamp voltage and short service life of the lamp)
Solution: Intermediate reaction due to carbonate compounds from which the oxides are formed
at temperatures above 600 C. The actual reduction of the filament work function requires atomic
barium on the emitter surface, which is only fully formed at the max. dimming setting (100 % luminous flux) and high temperatures (1900 K electrode temperature) over a time period of 100 h. If
these conditions are not fulfilled, an increased cathode voltage drop results and leads to material
deposits on the filament: Reduced service life
In accordance with DIN VDE 0100 Part 520 Section 528.11, main current circuits and associated
auxiliary circuits can be laid together, even if the auxiliary circuits carry a lower voltage than the main
current circuits.
11
12
2.4.2
Safety instructions
13
2.4.3
ECG
PE
14
Notes:
Max. lamp cable length of the "hot end" (higher potential to
ground): T5, T8: 1 m/T4: 0.5 m
Excessively long lamp cables cause the following problems:
- Poor radio interference suppression
- Uncertain lamp detection (not in T8)
- Poor synchronization of 2-lamp OSRAM DALI/DIM ECGs
Lay the lamp cables close together and close to the lamp
Lamp cables must not be laid in metal pipes and must not be
shielded cables
Guide the cables of the different lamp ends separately
In the case of multi-lamp OSRAM DALI/DIM ECGs, the cables to
the respective lamp ends must be of the same length to prevent
differences in the brightness
When dimming florescent lamps the maximum lamp voltage is
reached at the lowest dimmer setting (3 %-10 %) due to the negative current-voltage characteristic
Maximum line lengths between dimmable ECG
(QTi DALI/DIM) and lamps
Cold ends*
Hot ends*
1-lamp 21, 22
1-lamp 26, 27
2-lamp 21, 22, 23
2-lamp 24, 25, 26, 27
T5
1.5 m
1.0 m
T8
1.5 m (2 m HF DIM)
1.0 m (1.5 m HF DIM)
DULUX D/E, T/E
Every 0.5 m
Table 2: Maximum cable lengths between dimmable ECGs and
lamps
* "Hot ends" are the lamp cables that have the highest potential to the
switching ground or protective ground. The other "cold ends" of the
lamp cables have a lower potential to ground.
Note:
Maximum capacitance of a filament cable pair to ground:
T5: 75 pF
T8/DL: 150 pF
Maximum capacitance between "hot" and "cold":
T5: 15 pF
T8: 30 pF
15
2.4.4
16
2.4.5
Wrong:
17
Wrong:
Note:
T5 florescent lamps must be used so that the lamp stamps are on
the same side. The lamp stamp must be underneath (Cold Spot) in
the upright burning position. If this is not the case, the lamp parameters will fluctuate which can lead to unstable burning behavior of the
lamp.
2.5
2.5.1
2.5.2
DALI topology
The DALI ECGs are wired in parallel to each other and groups are not
taken into consideration. Star configurations are also possible. Ring
wiring is not permitted (indicated by X in the diagram). There is also no
need for terminating resistors on the communication cable.
2.5.3
19
2.5.4
The following formula is used as a basis for finding the cable cross
section (transmission and power cable):
Line length
0.75 mm2
150 to 300 m
1.5 mm2
Note:
Because of the different technical properties of the DALI interface in
control units found on the market and the differing local conditions of
the installation, it is recommended to limit the overall line lengths used
in the system to 300 m.
2.5.5
Protective earth
e.g.
20
~
~
DA
L
N PE
DA DA
DA
DALI
controller
~
~
2
3
4
Lamp
DA
DA DA PE N L1 L2 L3
21
Lamp
DA
DA
3
4
~
DA
2
3
4
Lamp
2.6
Sender unit
Receiver unit
Undefined
22.5 V max.
20.5 V max.
High Level"
sender range
16 V typ.
High Level"
receiver range
11.5 V min.
9.5 V min.
8 V typ.
Undefined
6.5 V max.
4.5 V max.
Low Level"
sender range
0 V typ.
"Low Level"
receiver range
-4.5 V min.
-6.5 V min.
Undefined
22
Biphase" databit
coded with value 1"
Biphase" databit
coded with value 0"
Voltage
Low level
Incoming data
telegram
ECG response
Current consumption
< 250 mA (active limit
by the DALI supply)
Current
Figure 12: Data transfer using the Manchester code on the DALI line
Data is transferred using the Manchester code. The signal edges in
the middle of the bit carry the information here. A trailing edge indicates a logical zero and a rising edge a logical one.
2.6.1
2.7
The Weber-Fechner law states that the subjective strength of sensory stimuli is
logarithmically related to the objective intensity of the physical stimulus.
23
The dependency of the relative luminous flux X (n) on the digital 8-bit
value n is described by the following correlation:
X (n) = 10
n 1
253
3
X (n) X (n + 1)
= 2,8 % = Const .
X ( n)
2.7.1
0,1
0,5
1,0
10
20
60
85
126
144
170
195
30
40
50
60
70
80
90
100
210
220
229
235
241
246
250
254
24
2.8
7
8
Every ECG manufacturer that has the DALI logo on its ECG is a member of the
AG DALI
40 commands/s and 16 bits ! 640 bit/s
DALI interface on the control unit:
The DALI interface of the control unit also supplies the DALI interface of the
connected DALI components. To ensure that the total current of max. 250 mA
permitted for DALI is not exceeded, no other DALI supplies or DALI controllers
can be connected to this system. In order not to exceed the max. permissible
voltage drop of 2 V on the interface lines, the line cross section must be chosen
according to the table in the technical details (2.5.4).
25
2.9
26
Note:
Due to the characteristics of the 110 V interface, the following must
be noted:
All control lines of an ECG installation must be connected with the
right polarity (+/-)
The control line is voltage-insulated from the mains line but there is
no safety extra-low voltage (SELV). Therefore, cables and terminals
that are approved for supply voltage 230V must be used for the
installation
The control voltage is simple to limit upwards or downwards with
resistors; several control units can be combined with one another
The correct function of the ECG can be tested as follows:
Switch-on of the ECG with open control line. The lamp must
ignite and burn with max. luminous flux
Switch-on of the ECG with shorted control line (wire jumper).
The lamp must burn with min. luminous flux
Each OSRAM DIM ECG can be used as a normally non-dimmable
ECG if there is no control unit connected to the control line
The dimmable ECGs are only dimmed via the 110 V interface
and switched via the mains line
The maximum load capacity of the control unit (switched output
and 110 V output) must be heeded
The connected control unit must always be able to handle the current supplied in the control line by the ECG (current sink) and to
reduce the control voltage. This precept is fulfilled by accordingly dimensioned potentiometers as well as by all OSRAM control
components. Normal power supplies, converter boards etc. do not
necessarily have this characteristic! To check, connect the control
unit, set to the lowest brightness and measure the voltage on the
control line. The set value is 1V or less
OSRAM DIM ECGs cannot be dimmed via the mains line (e.g. with
phase control mode, round control pulses etc.)
27
luminous flux
in %
Control voltage in V
Control current
2.9.1
28
3 Additional characteristics of
dimmable electronic control
gears from OSRAM9
3.1 OSRAM DALI/110 V ECG: Added-value through intelligent features
Automatic lamp detection through intelligent multi-lamp operation
(reduction of the ECG type variety)
Lamps of the same length and different powers can be operated
on an ECG. Furthermore, there are special approvals for specific
ECG lamp combinations10
Dimming range to 1 % of the rated luminous flux (3 % in CFL)
Ignition of the lamp at an ambient temperature of -25 C
Optimized lamp warm start within 0.6 s [including HF DIM]
Temperature-dependent cut-off at dimmer settings > 80 %
Shutdown of the filament heating at dimmer settings > 80 % prevents a permanent heating current through the lamp electrodes
during operation. This reduces the filament loading and the power
loss by approx. 2W
Power reduction by the ECG at excessively high ambient temperatures in order to protect the electronics ! Can be used in very
close, hot luminaires (operating life, increased light yield, simplified
safety approval)
High Tc point values (Tc < 80 C) enable operation at high ambient
temperatures (Ta values)
Stable dimming operation also in amalgam lamps (CFL (IN) and
OSRAM T5 CONSTANT lamps) ! particularly suitable for use in
areas with low ambient temperatures (e.g. cool rooms, outdoors):
relative luminous flux > 90 % from 0 C to 70 C
Intelligent power control upon detecting instabilities in the lamp circuit (amalgam lamp start) protects lamp/ECG
Permanent Heat Mode (PHM) for lighting effects (permanent filament heating, switch-on of the continuous lamp pre-heating by
digital command, not DALI standard): The PHM ensures that, at
a light value = 0 (switched off lamp(s)), the lamp electrodes are already heated. A delay-free lamp start is therefore possible
> 1 s on/off switching cycle in the PHM ! No restrictions
0.5 s < t < 1 s on/off switching cycle in the PHM ! 30 k
switching actions with T5, 100k switching actions with T8
< 0.5 s on/off switching cycle in the PHM ! 15 k switching
actions with T5, 50k switching actions with T8
Optimized filament heating and lamp operation at mains undervoltage (no damage to the lamps)
10
29
3.2
11
30
3.2.1
~
~
DA
DA
~
~
DA
Control button
DA
DALI ECG
~
DA
T PE N
3
4
La mp
DALI ECG
~
DA
2
3
4
La mp
DALI ECG
2
3
4
La mp
L1 L2 L3
31
Note:
Only use switches without control lamp and with 230 V normallyclosed contact as the permanent current through the glow lamp
can lead to malfunctions
TouchDIM is not part of the DALI standard (IEC 62386), but rather
an additional OSRAM function
3.2.2
3.2.3
Compensation of interferences
A control transformer which complies to the following figures and values must be used with a total line length from the switch to the ECG of
25 m to 100 m in order to prevent interference (e.g. through capacitive
induction):
Primary 230 V/Secondary 12 V, transformer rating required: 25 mW
per connected ECG (i.e. 150 mW with 6 ECGs 2 mA control current
per ECG)
L
N
~
~
Installation line
PE
DALI ECG
DA
DA
Button
12 V Transformer
Min. power: 25 mW x no. of ECGs
Installation line
PE
~
~
DALI ECG
DA
DA
Button
12 V Transformer
Min. power: 25 mW x no. of ECGs
Figure 18: Control transformer close to the switch (e.g. in the subdistributor or in a flush-mounted socket)
32
L
N
R: 150kOhm, 1W
3.2.4
TouchDIM operation
Switching the lamp on/off: Short button press (< 0.5 s)
Dimming: Long button press (> 0.5 s), (dimming direction changes
each time the button is pressed)
Save the reference value in the switched-on condition: "Doubleclick (press briefly 2 x within 0.4 s)
Delete reference value: Double-click with the lamp switched off
(ECG starts with 100 % luminous flux when switched on again)
Note:
Long button press with the lamp switched off: Lamp is switched on at
the minimum dimmer setting and, hence, remains highly dimmed until
the switch is released.
3.2.5
12
33
Mode 2:
The electronic control gear switches on with the dimming value (preset value) last stored by double-clicking. The following applies:
Short press: Switching
Long press: Dimming/Switching on at minimum dimmer setting
The following figure shows the options of both operating modes to the
user:
Mode 2
Mode 1
LP
LP
DC
On
LP DC
On
DC
SP SP
Off
LP SP
Off
DC
SP
SP = Short Push
LP = Long Push
DC = Double Click
34
The following table once again explains the behavior of the ECG for
different switching actions:
Action
TouchDIM
Short press
(status: switched off)
Short press
(status: switched on)
Long press
(status: switched off)
Long press
(status: switched on)
Double-click
(status: switched off)
Double-click
(status: switched on & dimming in the last 3 s)
Swap to TDI Mode II (switch-on value = doubleclick value), confirmation: flashing and dimming
to double-click value
Double-click
(status: switched on & no
dimming in the last 3 s)
Power failure
(status switched off)
Power failure
(status switched on)
Switches on to
TDI Mode I : last value before power outage
TDI Mode II : last value before power outage
35
3.2.6
3.2.6.2 Synchronization
For physical reasons a TouchDIM can work asynchronously, i.e. the
switching status and dimming direction of the separate luminaires are
different. The following steps help in the synchronization of a TouchDIM system:
1st. step: Longpress (> 0.5 s)
! All luminaires switch on
2nd. step: Shortpress (< 0.5 s)
! All luminaires switch off
3rd. step: Longpress (> 0.5 s)
! All luminaires switch on and dim
4th. step: Double-click
! Save dimmer setting (if required)
After these four steps longshortlongdouble-click the ECGs
again behave synchronously.
Note:
TouchDIM was developed for manual control and is not suitable for
automation, e.g. for connecting to a PLC.
36
3.2.7
3.3
37
For emergency lighting/voltage loss13 in the DALI controllers two values can be configured/programmed separately for each unit (e.g. using the OSRAM DALI Luminaire Tool DLT).
System failure level: Emergency operation (1100 % light), detected by switching off the control line
Power on level: Light value after the mains voltage is restored
(1100 % light)
The system failure level always has priority over the power on level,
especially when switching over (in the event of a brief power outage, emergency operation is therefore ensured). The factory setting
for both values is 100 % light.
Typical data for the QUICKTRONIC INTELLIGENT DALI family important for emergency lighting systems are*:
Starting time of the lamp (max.)
0.6 s
154276 V
198 V
198264 V
Mains frequency
0, 5060 Hz
*Further technical data of the respective ECG type can be found in the
corresponding datasheet or on our homepage at www.osram.com/qti.
The DALI or dimming function of the QTi DALI DIM is identical in AC
and DC operation.
13
During power outages < 200 ms, the light stays on (no light failure) because
the ECGs are not preheated again.
During power outages > 200 ms, the ECGs go through the entire preheating cycle. The following applies to the QTi DALI/DIM and HF DIM family: The
starting time in HO lamps is 0.5 s and in HE lamps it is 0.7 s. DALI ECGs
require an additional 0.5 s for initialization
38
General UV lighting
L
N
General luminaire lighting
Phase
control
L
N
IN
IN
DALI
controller
~
~
D
D
DA
DA
OSRAM
DALI
ECG 4
1
2
3
4
X
.
Dimming
button
U
U
D1
D2
~
~
Monitoring module
0
0
ZB-S
D1 max. 1m
D2
DA
DA
OSRAM
DALI
ECG
1
2
3
4
X
.
From HV
3.3.1
39
3.3.2
3.3.4
3.3.5
3.4
40
Figure 22: Reading and printing of the unique OSRAM control unit
address on barcode
The following section of the software interface shows the DALI parameters that can be configured by the DLT. Special attention is drawn
here to the "System Failure Level" and "Power On Level" which come
into play for use in emergency lighting systems:
41
3.5
N
L
DIMM-ECG
+
N
L
On/Off
switch
DIMM-ECG
+
N
L
Potentiometer
R = 100 k log.
n
L N
1
2
3
4
1
2
3
4
Lamp
Lamp
DIMM-ECG
2
3
Lamp
3.5.1
3.5.1.1 Applications
a) Stairwell lighting timer switch
Here a special stairwell lighting timer switch (e.g. Siemens: Type 5TT1
303, see Siemens Catalog) provides the readiness switching of the
OSRAM DIM ECG. Functionality: The stairlight timer switch switches
on the OSRAM DIM ECG at the push of a button (100 % light). After
max. 10 min (time can be adjusted) the light is lowered to a preselected level without intermediate stages. After a total of 30 min it is
switched off entirely. This 30-min cycle can be restarted at any time
by pressing a switch. Thus, the lamp-protecting mode is employed
in the evening hours when the staircase is used more frequently. The
light only switches between the dimmer settings, real switchings are
infrequent. At night, when the stairwell lighting is not required for prolonged periods, the remaining 13 % energy consumption are also still
stored at the lowest dimmer setting.
43
44
+
Analog output,
e.g. PC
+
R
DIM SA
In
signal Out
amplifier
if necessary
45
+
Dimm-ECG
3.6
3.6.1
Temperature-dependent control
The recognized temperature problems in dimmed fluorescent lamps
can be resolved by a temperature-dependent lower limit of the dimmer setting.
The latest generation of the QTi DIM (as of the end of 2008) does this
automatically. For older versions, the following implementation applies:
The stability threshold (stable dimming operation at low temperatures
(< 10 C)) depends greatly on the lamp tolerances. In control types
where the lamp starts at 100 % (e.g. stairwell switching), the temperature limit can be lower. Therefore, in an automatic control both the
response temperature and the control voltage should be adjustable.
The following circuit is recommended:
+
Temperature
controller
46
3.6.2
+
DIMM-ECG
Zener diode
+
DIMM-ECG
+
Other ECGs
47
b) Lower limit
An effective lower limit can be realized by a series connection of 2
control units. The sum of the two units is effective. With one unit,
the default control voltage of the other unit cannot be undercut. Attention: In a series connection, two control units (e.g. DIM MCU) is
the smallest achievable control voltage approx. 2 V (~= 4 % luminous
flux) connections must be realized according to the diagram.
3.6.3
3.6.4
3.7
49
3.7.1
1. Insert extraction tool into the line guide above the line
2. Pull out line
50
3.7.2
Multi-wire conductor
max. 0.75 mm
max. 0.5 mm
Plug contact
0.51.0 mm
0.51.0 mm
(with wire-end sleeve)
Push terminal
0.51.5 mm
0.51.5 mm
(with wire-end sleeve)
Table 6: Typical cable cross sections of plug and insulation displacement contacts
3.7.3
Basic insulation
IEC 61347 demands basic insulation between the control circuit and
mains supply for control inputs. The DALI standard (IEC 62386) is
related to this. Consequently, the DALI line is only basically insulated
and must be treated like the mains voltage for this reason as is the
110 V interface.
3.7.4
Lamp holders
The lamps must be mechanically secure and make contact in the
lamp sockets. The holders must be selected according to the type of
ECG/lamp used.
3.7.5
Master/slave circuit
(2-lamp ECG for the operation of 2 single luminaires) Master/slave operation with multilamp dimmers is not permitted. This is because of
the capacitive leakage currents that can lead to imbalances, different
luminances and unstable operation in the dimmed state (flickering).
3.7.6
51
3.8
Min. temperature
at 1 % (3 % CFL)
dimmer setting
T8/26 mm lamp***
-20 C*
1 %*
+10 C
+10 C
60 %****
50 %
30 %
30 %
+10 C**
50 %
T5/16 mm lamp*
HE 1435
HO 49
HO 2480
DULUX L*
DULUX D/E, T/E, FC
Table 7
* Only with QTiDIM ** 3100 % *** L18 W, L36 W, L58 W, not
L70 W ****; The critical point from which the maintaining voltage
increases excessively for cold HO lamps lies just below the 30 % dimmer setting. For HE lamps, this point is reached at the same power density. Because of the 100 % power being approx. only half as
high, the dimmer setting is 60 % here. The HO49 lies between HE
1435 W and HO 2480 W/Dimming of the amalgam lamps T5 HO
CONSTANT (24 W, 39 W, 54 W, 80 W), CFL (DL CONSTANT 40 W,
55 W, 80 W and T/E IN PLUS 26 W, 32 W, 42 W, 57 W) is possible.
The temperature range of the luminaires can be expanded downwards by raising the lowest dimmer setting until the light has reached
a higher inner temperature, otherwise flickering or/and starting problems of the lamp can be expected. From the end of 2008 units do this
automatically.
3.8.1
52
Note:
Limits the tc temperature to < 80 C (depending on installation condition), but never switches the ECG due to excessive temperature
Thermally problematic luminaires do not necessarily become standard conformant devices, even with these ECGs
Power reduction is carried out up to 50 % of full load operation
Functionality
The ECG measures the ECG temperature once per minute. At the
selected limiting temperature it begins to reduce the power in order to
lower the temperature of the luminaire and to prevent the temperature
of the ECG from increasing further. The Tc temperature lies between
75 C and 80 C depending on installation conditions (e.g. heat coupling into the ECG from top or bottom).
A reduction of the system power by 10 %-20 % at an ambient temperature of 25 C is sufficient in most cases even in hot luminaires,
however, only approx. 1 %-2 % light is lost because the level of efficiency of the system increases.
Dimming is always possible the temperature regulation may affect
the upper dimming level only significantly.
The regulation of the lamp power compensates the loss of light
output in hot luminaires.
Tc temperature [C]
120
110
100
90
80
70
60
50
40
30
20
10
0
10
15
20
25
30
35
40
45
50
55
Figure 35: Dimmable QTi ECG from OSRAM keep their temperature at the Tc measuring point constant within wide limits and
thereby also the temperature in the luminaire. As a result, both the
ECG and all other luminaire components are relieved.
53
Ta [C]
0
5
7,5
10
15
20
25
30
35
40
45
50
55
120Tc [C]
110
100 68
90 73
8075,5
70 78
78
60 78
50 78
40 78
78
30 78
20 78
10 83
88
0
0
Telko [C]
Licht [%]
Pn [W]
70
110
165
110
75
115
165
115
77,5
116
165
116
80
115,0
165,0
115,0
115,0
80
109,5
152,9
106,5
109,7
80
104,0
140,7
98,1
104,4
80
98,5
128,6
89,6
99,1
80
92,9
116,5
81,2
93,8
thermal
management
without
limitation
of
the
temperature
80
87,4
104,3
72,7
88,5
80
81,9
92,2
64,3
80,6
with thermal management
80
76,4
80,1
55,8
71,8
85 Luminaire71,4
66,8
Abscissa:
ambient80,1
temperature [C] 55,8
90
66,4
80,1
61,8
10
15
20
25
30
35
40
45
110
115
115
110
105
100
95
90
85
80
75
50
55
10
15
20
25
30
35
40
45
50
55
Figure 37: Even so the luminous flux of the luminaire hardly decreases because the level of efficiency of the system increases due
to the temperature limitation.
140
120
100
80
60
thermal management without limitation of the temperature
40
20
0
0
10
15
20
25
30
35
40
45
50
55
Figure 38: The clear rise in the relative light output shows that the
temperature limitation has a positive effect on the energy saving of
hot luminaires.
Measurements using an example of a narrow 2x80 W luminaire:
The precise scaling depends on the type of luminaire and the installation conditions of the ECG.
54
Why are the light losses so small due to the temperature limitation?
Assuming a luminaire whose inside temperature (= lamp ambient
temperature) is to be lowered from 65 C to 55 C. A reduction of
the system power by 20 % is required for this. The diagram shows the
(T) curves of T5 lamps for 100 % and 80 % system power.
During the transition from the 100 % curve to the 80 % curve and the
lowering of the lamp ambient temperature by 10 C, the luminous
flux remains roughly the same.
120
100
80
60
temperature
regulation
40
20
0
0
10
20
30
40
50
60
70
80
55
3.8.2
Color temperature
Between the maximum and minimum luminous flux of the lamp the
color temperature of the lamp changes in a DULUX L this is approx.
150 Kelvin. Due to the great difference in luminance density, the color
difference appears to be visually considerably greater. As a result, the
subjective perception of the human eye does not reflect the objective
color temperature change. Directly after changeover from maximum
to minimum luminous flux, a temporary color displacement of up to
400 Kelvin occurs (displacement to the red end that decreases after
approx. 30-40 minutes to the color difference mentioned above (stabilization phase)).
Outdoor applications
For applications out of doors a special OSRAM housing, the
OUTKIT, is available for protecting the ECG against humidity. It is
available for ECGs with a headroom of 30 mm or even 21 mm, in the
lengths of 360 mm and 423 mm. Details of this can be found in the
current light program. For outdoor applications the temperature range
of the system lamp-ECG should be examined in detail. In all outdoor
applications attention must be paid to sufficient mains quality (above
all, lightning protection) so that the ECGs are not damaged.
56
3.8.4
3.9
HO CONSTANT:
57
24 W, 39 W, 54 W, 80 W
Dimming range 1100 %
40 W, 55 W, 80 W
Dimming range 1100 %
26 W, 32 W, 42 W, 57 W
Dimming range 3100 %
D T/E 32 W IN PLUS
D T/E 42 W IN PLUS
D T/E 57 W IN PLUS
DL 80 W CONSTANT
DL 55 W CONSTANT
DL 40 W CONSTANT
HO 80 W CONSTANT
HO 54 W CONSTANT
D T/E 26 W IN PLUS
HO 39 W CONSTANT
ECG
Lamp
x
x
x
x
x
x
x
x
x
x
x
x
*)
x
x
x
x
x
x
*)
x
x
*) Not for flashing operation, dimming operation only possible within the scope of a
special release
Also in normal mercury lamps the power boost takes effect and
simplifies dimming during the ignition phase of the lamps as well as for
very low temperatures:
When there are instabilities in the lower dimming level, the Power
Boost regulation helps to stabilize the burning conditions.
58
8
7
6
5
4
3
2
1
0
-20
20
40
60
80
100
120
140
160
180
200
Time [s]
New !
Neu!
59
90
80
70
60
50
40
30
20
10
0
-10
10
20
30
40
50
60
70
80
90%
T5 Standard
T5 C ONSTAN T of dimmable standard ECG
T5 C ONSTAN T of QTI DALI/DIM
Figure 43: QTi DALI/DIM: More luminous flux over an expanded temperature range
Lamp type
Min.
temperature at
1 % (3 % CFL)
dimmer setting
Min.
dimmer setting of -20 C to
+10 C
T5, CFL*
+10 C
30 %
3.9.1
60
3.9.2
Figure 45: More light from new luminaires thanks to amalgam technology
61
Note:
Amalgam and mercury lamps must never be mixed in multilamp
ECGs because the power increase available in amalgam lamps
would lead to a vigorous overshooting of the light in a mercury
lamp. In addition, the synchronization in the lower dimming range
would be poor.
No release: Dimming of a T5 amalgam lamp with predecessor
units up to the end of 2008 (DALI and 110 V):
For dimmer settings below 30 %, the following applies:
- Voltage peaks arise through unwanted controller oscillations14
- Unfavorable operating condition leads to lamp flickering and a
reduction of the lamp service life
Recommendation: Dimming of amalgam lamps is possible,
but this is not released by OSRAM. Burning-in of the lamps
at 100 % luminous flux after each restart for approx.
2-3 minutes, then dimming. In principle, however, dimming of
T5 amalgam lamps with predecessor units is not recommended
for the reasons mentioned above.
14
Oscillations typically in the lower third of the dimming range can develop
when fluorescent bulbs with electronic control gear are dimmed, which are
caused by the interaction of lamp characteristic, lamp time constants, resonant
circuit and control.
62
PN (d ) PN 1%
PN 100%
PN 1%
v ( d
1%)
99%
100 %
Additional savings
80 %
Savings
50 %
Consumption
4-10 %
1%
Luminous flux
Figure 46: Linear relationship, dimmer setting and energy consumption system
63
FC 22W
FC 40 W
DALI MCU
Remote switch
without battery
Radio receiver
15
Operation with a 110 V interface is also possible (QTi-T/E 1x18-57 DIM and
QTi-T/E 2x18-42 DIM)
64
5.1
Figure 49: Principle Optional cable clamps for snapping into the
housing
65
66
67
7 Tender documents
QUICKTRONIC INTELLIGENT DALI DIM for compact fluorescent lamps
Ordering designation according to lamp type: QTi DALI-T/E
DIM
Intelligent ECG with DALI interface according to IEC 60929
Compact fluorescent lamps, OSRAM DULUX T/E 18, 26, 32,
42 W and OSRAM DULUX
T/E IN 26, 32, 42 (57) W (amalgam lamps) from 3 % to 100 % can
be dimmed without any restriction
Warm start of the lamp inside 0.6 seconds without switch-on flash
Manual dimming operation (TouchDIM ) without any control gear
with standard installation switches, incl. memory function (doubleclick) and soft start
Service life: 50,000 h at maximum thermal load (tc = 75 C, max.
10 % failure)
Effective excess temperature protection of the dimming ECG
through intelligent power reduction at high tc temperatures
5-year system+ guarantee:
For every ECG that failed due to a material or production fault, a
replacement is available
CELMA energy classification EEI = A1
Maximum energy efficiency thanks to cut-off technology
EoL shutdown acc. to EN/IEC 61347-2-3 Section 17
For use in emergency lighting systems acc. to EN 50172 / DIN VDE
0108-100
Configurable emergency current features, adjustable light value
without control signal between 100 % and 3 % luminous flux
Test mark: ENEC, VDE, EMC
EN 60929, EN 61347-2-3, EN 55015, EN 61000-3-2, EN 61547,
EN 61000-3-3
QUICKTRONIC INTELLIGENT DALI DIM for T5/ 16 mm fluorescent lamps
Ordering designation for each type of lamp: QTi DALI DIM
Intelligent ECG with DALI interface according to IEC 60929
Operation of T5/ 16 mm fluorescent lamps of same length in a
luminaire for the flexible adaptation of the lighting level
Unrestrictedly dimmable from 1 % to 100 %
Max. dimming speed for dynamic RGB color light applications of
5 ms, from 1 % to 100 % through optimized regulation of the filament preheating
Warm start of the lamp inside 0.5 seconds without switch-on flash
Manual dimming operation (TouchDIM) without any control gear
with standard installation buttons, incl. memory function (doubleclick) and soft start
Service life: 50,000 h at maximum thermal load (tc = 75 C, max. 10
% failure)
Effective excess temperature protection of the dimming ECG
68
69
71
8
8.1
DALI part
8.1.1
TouchDIM
72
8.1.2
DALI in general
Do the ECGs have to be addressed in DALI?
No, it can also function without addressing (broadcast mode).
What is the difference between DSI and DALI?
DSI is a corporate solution, not a general standard like DALI. DSI
does not allow digital addressing so it is not possible to form
groups freely or check individual lamps for faults! Groups have to
be formed by wiring as well as in the case of 110 V systems.
Does attention have to be paid to the group arrangement in
DALI when wiring the system?
No, the groups are generally assigned (addressed) when the system is started up.
Does attention have to be paid to the polarity of the DALI
control line?
When OSRAM DALI control gear is used there is no need to worry
about polarity.
How can DALI ECGs be addressed?
They can be addressed individually, in groups or all together.
Can I get feedback messages from DALI ECGs?
Yes, all device settings as well as the device status, such as lamp
faults, can be checked.
73
Can a DALI ECG belong to more than one group at the same
time?
Yes. Each DALI controller can belong to up to 16 groups.
Where are the data for the group assignments and light
scene values stored?
They are stored directly in the internal EEPROM of the ECG.
Are the data in the ECG lost if there is a power failure?
No, the data are permanently stored in the ECG. They are retained
even if the power failure is prolonged.
What happens if an ECG fails?
The ECG simply has to be replaced and adjusted to the appropriate settings (the procedure depends on the control unit).
What happens if a control unit is faulty?
If the DALI interface voltage is lost, all ECGs take on the so-called
"system failure level" (ECG factory setting: 100 % light).
Can DALI be integrated in superordinate building management systems (e.g. EIB or LON)?
Yes, by using gateways or control units with the appropriate interface.
Is DALI a competitor to EIB or LON?
No, DALI is only a subsystem of the building management system
for controling the lighting.
Can 110 V components also be incorporated in a DALI
lighting control system?
Yes, by using DALI to 110 V converters.
Can existing 110 V lighting systems be upgraded with a
DALI controller?
Yes, a DALI to 110 V converter is needed for each 110 V luminaire group (e.g. DALI CON 110 SO).
Can the wiring of the DALI ECG be checked on a building
site?
This depends on the control unit used. DALI ECGs that are still in
their factory setting always produce 100 % light when the mains
voltage (with protection) is applied.
74
75
8.1.3
8.1.4
76
8.1.5
8.1.6
8.2
77
78
8.2.1
Troubleshooting 110 V
Lamp does not burn with 100 % luminous flux
The control line is not connected or not correctly connected to the
control unit, or the control unit is not a sufficiently good current sink
and, hence, cannot reduce the control voltage.
Check the wiring. Check that the control voltage is reduced while
dimming and, if necessary, install a parallel resistor in the control
line.
Also one or more control inputs may be pole reversed:
Disconnect control unit
Subdivide control circuit
Further subdivide control circuit
Lamp always burn at minimum brightness
+ and - connectors of the control line are reversed, or short circuit
in the control line.
Connect lines with correct polarity, check wiring
The lamp does not show the required luminous flux when
controlled with potentiometers or fixed resistors.
Potentiometers or resistors are wrongly dimensioned. Check the
values
Insufficient brightness along the lamp
Spacing of the reflector to the lamp is too small, capacitive discharge currents occur.
Increase gap between the reflector and the lamp
Synchronous lamp flickering
Fault is outside the dimming system, e.g. N conductor disconnection, control voltage not OK
Check N conductor connection and control unit
79
9
9.1
Appendix
80
9.2
<0.7
Not possible
0.7
357.8
1.0
253.0
1.4
178.9
2.0
126.5
2.8
89.5
4.0
63.3
5.7
44.7
8.0
31.6
11.3
22.4
10
16.0
15.8
11
22.6
11.2
12
32.0
7.9
13
45.3
5.6
14
64.0
3.9
15
90.5
2.8
Table 9: Fade time and fade rate of dimmable OSRAM DALI controllers
9.3
Lamp wiring
81
Figure 53: QTi DALI/DIM 2x: lines 24, 25 and 26, 27 max. length of
1m
82
Figure 57: HF DIM 2x: lines 24, 25 and 26, 27 max. length of 1.5 m
83
9.4
Umin-max 1)
Ubatt min-max
KHz ECG 2)
Unit
QTi DALI 1x14/24 DIM
QTi 1x14/24 DIM
QTi DALI 1x21/39 DIM
QTi 1x21/39 DIM
QTi DALI 1x28/54 DIM
QTi 1x28/54 DIM
QTi DALI 1x35/49/80 DIM
QTi 1x35/49/80 DIM
QTi DALI 2x14/24 DIM
QTi 2x14/24 DIM
QTi DALI 2x21/39 DIM
QTi 2x21/39 DIM
QTi DALI 2x28/54 DIM
QTi 2x28/54 DIM
QTi DALI 2x35/49 DIM
QTi 2x35/49 DIM
QTi DALI 2x35/49/80 DIM
QTi 2x35/49/80 DIM
QTi DALI 3x14/24 DIM
QTi 3x14/24 DIM
QTi DALI 4x14/24 DIM
QTi 4x14/24 DIM
QTi DALI 1x18 DIM
QTi 1x18 DIM
QTi DALI 1x36 DIM
QTi 1x36 DIM
QTi DALI 1x58 DIM
QTi 1x58 DIM
QTi DALI 2x18 DIM
QTi 2x18 DIM
QTi DALI 2x36 DIM
QTi 2x36 DIM
QTi DALI 2x58 DIM
QTi 2x58 DIM
HF 1x18/230-240 DIM
HF 1x36/230-240 DIM
HF 1x58/230-240 DIM
HF 2x18/230-240 DIM
HF 2x36/230-240 DIM
HF 2x58/230-240 DIM
QTi DALI-T/E 1x18-57 DIM
QTi-T/E 1x18-57 DIM
1xHE14
1xHO24
1xDL24
1xHE21
1xHO39
1xDL40
1xHE28
1xHO54
1xDL55
1xHE35
1xHO49
1xHO80
2xHE14
2xHO24
2xDL24
2xHE21
2xHO39
2xDL40
2xHE28
2xHO54
2xDL55
2xHE35
2xHO49
2xHO80
2xHO49
2xHE35
3xHE14
3xHO24
3xDL24
3xHE14
3xHO24
3xDL24
1xL18
1xDL18
1xL36
1xDL36
1xL58
2xL18
2xDL18
2xL36
2xDL36
2xL58
1xL18
1xL36
1xL58
2xL18
2xL36
2xL58
1xT/E18
1xT/E26
1xT/E32
1xT/E42
1xT/E57
1xT/E18
1xT/E26
1xT/E32
1xT/E42
198264
154276
53120
198264
154276
44120
198264
154276
44120
198264
154276
44120
198264
154276
53120
198264
154276
44120
198264
154276
44120
198264
154276
44120
198264
154276
44120
198264
154276
53120
198264
154276
53120
198264
154276
51120
198264
154276
48120
198264
198264
154276
154276
46120
51120
198264
154276
48120
198264
154276
46120
198264
198264
198264
198264
198264
198264
154276
154276
154276
154276
154276
154276
40100
40100
40100
40100
40100
40100
198264
154276
42130
198264
154276
42140
1) AC mains voltage
2) Lamp-dependent values
3) At 100 % luminous flux
84
Nominal
current
[A] 3)
0.08
0.12
0.12
0.11
0.20
0.20
0.14
0.27
0.27
0.18
0.24
0.38
0.15
0.24
0.24
0.22
0.39
0.39
0.28
0.54
0.54
0.36
0.48
0.78
0.48
0.36
0.20
0.32
0.32
0.27
0.43
0.43
0.09
0.09
0.16
0.16
0.24
Lambda
W system 3)
ln 3)
0.96
0.98
0.98
0.96
0.98
0.98
0.97
0.99
0.99
0.96
0.98
0.99
0.96
0.96
0.96
0.96
0.96
0.97
0.97
0.98
0.98
0.95
0.97
0.98
0.97
0.95
0.97
0.99
0.99
0.97
0.99
0.99
0.97
0.97
0.99
0.99
0.99
17
27
27
24
44
44
31
60
60
39
54
87
34
54
54
48
88
88
62
121
121
78
108
175
108
78
45
73
73
60
98
98
19
19
35
35
55
1x1200
1x1750
1x1800
1x1900
1x3100
1x3500
1x2600
1x4450
1x4800
1x3300
1x4300
1x6150
2x1200
2x1750
2x1800
2x1900
2x3100
2x3500
2x2600
2x4450
2x4800
2x3300
2x4300
2x6150
2x4300
2x 3300
3x1200
3x1750
3x1800
4x1200
4x1750
4x1800
1x1350
1x1350
1x3350
1x2900
1x5200
0.17
0.17
0.31
0.31
0.49
0.96
0.96
0.98
0.98
0.98
38
38
70
70
110
2x1350
2x1350
2x3350
2x2900
2x5200
0.09
0.17
0.25
0.17
0.31
0.48
0.09
0.13
0.16
0.21
0.27
0.17
0.25
0.30
0.39
0.95
0.97
0.98
0.97
0.99
0.99
0.95
0.97
0.98
0.99
0.99
0.95
0.98
0.99
0.99
19
36
56
36
71
111
20
27
39
47
62
35
56
68
90
1x1300
1x3200
1x5000
2x1300
2x3200
2x5000
1x1200
1x1800
1x2400
1x3200
1x4300
2x1200
2x1800
2x2400
2x3200
9.5
Energy classifications
In accordance with the CELMA classification scheme, the following
classes to which the typical controllers belong are available:
Class A1:
Class A2:
Class A3:
Class B1:
Class B2:
Class C:
Class D:
85
9.6
86
Index
A
Activity Group DALI ...................................................................... 67
Added-value through intelligent features ....................................... 29
Additional OSRAM function .......................................................... 32
Asynchronism............................................................................... 36
Automatic cutouts ........................................................................ 80
Automatic lamp detection............................................................. 29
B
Basic insulation ............................................................................ 11
Block diagram ................................................................................ 7
Burning-in instructions/Cable insulation ........................................ 11
C
CFL MULTI lamp ECGs .................................................................64
Characteristics of the 110 V interface........................................ 26
Chip identification number ............................................................ 30
Cold spot ..................................................................................... 18
Color-phase diagram acc. to DIN 5033 ........................................ 56
Comparison between 1...10 V and DALI......................................... 9
Compensation methods ............................................................... 31
Compensation of interferences ..................................................... 32
Control line length ........................................................................ 48
Control via PC .............................................................................. 45
Cross section of the power cable ................................................. 20
D
DALI dimming curve ..................................................................... 24
DALI installation & features ........................................................... 10
DALI topology .............................................................................. 19
Damping of the line ...................................................................... 33
Data coding.................................................................................. 25
Digital smoothing ....................................................................... 24
Dimmer setting and energy consumption system ......................... 63
Dimming of amalgam lamps ......................................................... 57
DIN VDE 0100/11.85, T 520......................................................... 12
Disconnection of the data line....................................................... 26
E
ECG and control unit manufacturers ............................................. 67
Economy ........................................................................................ 4
EEPROM ...................................................................................... 30
EIB/LON ......................................................................................... 8
Emergency lighting control systems and applications ................... 37
EoL shutdown after Test 2 ............................................................ 30
External control with an analog output .......................................... 45
87
F
Fade time and fade rate ............................................................... 81
Feedback control and relative luminous flux .................................. 55
Filament preheating ...................................................................... 11
Forming and basic stabilization ..................................................... 11
G
Ground fault interrupter ................................................................ 14
Grounded metal plate or reflector ................................................. 14
Group assignment ........................................................................ 19
H
Hot ends ...................................................................................... 15
I
IEC 60929 .................................................................................... 28
IEC 61347 .................................................................................... 51
IEC 62386 .................................................................................... 86
Ignition of the lamp ....................................................................... 29
Increase in the light yield (lm/W) of hot luminaires ......................... 52
Increased luminous flux of cold amalgam lamps ........................... 59
Individual address......................................................................... 19
Inductions between the lamp current circuits of several ECGs ...... 16
Insulation displacement contact ................................................... 49
Insulation test ............................................................................... 12
integrated safety mechanism ........................................................ 30
Integrated scene memory ............................................................. 10
Intelligent power control ............................................................... 29
Interface circuit ............................................................................. 45
Interference effects ....................................................................... 16
L
Lamp wiring ................................................................................. 81
Leakage current ........................................................................... 14
Lighting comfort ............................................................................. 5
Limited system size ...................................................................... 25
Linear relation of dimmer setting and energy consumption ........... 63
Logarithmically-dimensioned potentiometer.................................. 42
Low or high logic states .......................................................... 22
Luminaire function test ................................................................. 41
Luminous flux against control voltage ........................................... 28
88
M
Mains cable and control line ......................................................... 16
Mains voltage failure ..................................................................... 37
Maximum capacitance between hot and cold ......................... 15
Maximum capacitance of a filament cable pair to ground ............. 15
Maximum system current ............................................................. 25
Monitoring module and OSRAM DALI ECG in emergency lighting
management ............................................................................. 39
More light from new luminaires ..................................................... 61
N
NYM cable for connecting DALI ECGs.......................................... 20
O
Operating modes and operating combinations by button ............. 34
Operating parameters ............................................................ 32, 84
Operation at high ambient temperatures....................................... 29
Operation in a wide ambient temperature range through power
reduction ................................................................................... 52
Optimized filament heating and lamp operation ............................ 29
Optimized lamp warm start .......................................................... 29
Optimized radio interference suppression ..................................... 30
Optional cable clamps .................................................................. 65
OSRAM DALI ECG and TouchDIM interface ................................. 30
OSRAM CFL ECGs ...................................................................... 65
OUTKIT ..................................................................................... 56
P
Permanent Heat Mode (PHM) for lighting effects .......................... 29
Phase control mode ..................................................................... 27
Physical useful data rate ............................................................... 25
Plug contact ................................................................................. 49
Potential-free control input............................................................ 25
Power boost and amalgam lamps ................................................ 58
Power consumption of the DALI/DIM system ............................... 63
Power reduction by the ECG ........................................................ 29
Power On Level ............................................................................ 23
Protection class I luminaires ......................................................... 14
Protection of the electronics ......................................................... 29
R
Range of lamps with an ECG........................................................ 64
Reading and printing of the unique OSRAM control unit address .. 41
Reduction of capacity leakage currents ........................................ 14
Reduction of the ECG type variety ................................................ 29
Reliability/Safety ............................................................................. 6
89
S
Safe interference voltage gap ....................................................... 25
Safety instructions ........................................................................ 13
Simple integration of new components ......................................... 26
Simple system reconfiguration ...................................................... 26
Stable dimming operation also in amalgam lamps ........................ 29
Staircase operation ...................................................................... 43
Standard values for minimum ambient light temperatures ............. 52
Starting currents and max. number of ECGs in automatic cutouts ... 80
Status report from the ECG .......................................................... 10
Storage of light scenes ................................................................. 26
Switching status and dimming direction ....................................... 36
Synchronization of a TouchDIM system ........................................ 36
System Failure Level ..................................................................... 23
T
Temperature-dependent cut-off ................................................. 29
Tender documents ....................................................................... 68
Testing and programming tool ...................................................... 40
TouchDIM operation ..................................................................... 33
Transmission cable ....................................................................... 20
Two-wire control line ..................................................................... 25
Typical cable cross sections of plug and insulation displacement
contacts .................................................................................... 51
U
Unrestricted DALI communication to the ECG .............................. 40
V
Values of digital dimming value against percentage luminous flux ...24
Vibrations and noise emission ...................................................... 51
Voltage level on the DALI interface ................................................ 22
W
Weber-Fechner law ...................................................................... 23
Wiring diagram for DALI controllers .............................................. 21
Wiring examples of dimmable ECGs............................................. 17
90
Global presence.
OSRAM supplies customers in around 150 countries.
73 companies and sales offices for 111 countries
38 countries served by local agents or OSRAM GmbH, Munich
Head Ofce
Hellabrunner Strasse 1
81543 MUNICH
GERMANY
Fon +49 (0)89-6213-0
Fax +49 (0)89-6213-20 20
www.osram.com
com
DALI_Cover_E.indd 1
OSRAM GmbH
Korea
Latvia
Lithuania
Macedonia
Malaysia
Mexico
Moldova
Norway
OSRAM Region Andina
Pakistan
Philippines
Poland
Portugal
Rumania
Russia
Serbia-Montenegro
Singapore
Slovakia
South Africa
Spain
Sweden
Switzerland
Taiwan
Thailand
Tunisia
Turkey
Ukraine
United Arab Emirates
USA
Vietnam
Albania
Argentina
Asia Pacic Hongkong
Australia
Austria
Azerbaijan
Belarus
Benelux
Bosnia-Herzegovina
Brazil
Bulgaria
Canada
Chile
China
Croatia
Czechia
Denmark
Egypt
Estonia
Finland
France
Great Britain
Greece
Hungary
India
Indonesia
Iran
Italy
Japan
Kazakhstan
Kenya