Você está na página 1de 2

S&C Manual Vista Underground Distribution Switchgear

Manhole Style Models

Outdoor Distribution (15.5 kV through 38 kV)

The unique benefits of S&Cs Vista Underground Distribution Switchgear are now available in 15.5-kV, 29-kV, and
38-kV models for manhole installation.
Manhole Style Vista UDS Model 110 features a manually operated, three-pole load-interrupter switch suitable
for switching 600-ampere main feeders.
Manhole Style Vista UDS Model 101 features a threepole, microprocessor-controlled vacuum fault interrupter
in series with a manually operated three-pole disconnect.
Its suitable for switching and protecting 600-ampere main
feeders, 600-ampere or 200-ampere radials, or networks.
Model 101 is available in short-circuit ratings of 12.5 kA
and 25 kA RMS symmetrical.
A portable motor operator is available for operating
the load-interrupter switch or fault interrupter from a
remote location.

The load-interrupter switch or vacuum fault interrupters are completely sealed in a rugged, cylindrical stainless-steel tank insulated with SF6 gas. Cable entrance and
exit is via 600-ampere bushings or optional 200-ampere
bushing wells.
Like all Vista UDS, Manhole Style models feature
unprecedented gas-tight construction. All gas seals have
been extensively tested and field-proven, and the entire
switchgear unit is suitable for submersion in the most
hostile environments.
With its compact design, rugged construction, and
internal visible open point, Manhole Style Vista UDS is
perfect for applications where installation space is limited.

Operating mechanism is
padlockable in any position

The available portable motor operator lets you


operate the switch or fault interrupter from a remote
location. . . particularly useful for units located in
underground vaults with other energized equipment.

Supersedes Photo Sheet 681-707 dated 10-29-01

Operation selector prevents


inadvertent operation from closed
position directly to grounded
position and vice versa

304L stainless-steel tank and


proven gas-sealing technology
provide a long lifetime of reliable
service in hostile environments

2003

PHOTO SHEET
S&C ELECTRIC COMPANY

681-707
Page 1 of 2
February 3, 2003

S&C Manual Vista Underground Distribution Switchgear

Manhole Style Models

Outdoor Distribution (15.5 kV through 38 kV)


Outdoor Distribution
The extremely large viewing window allows a clear
view of the three-position (closed-open-grounded) switch
or disconnect, with its obvious open point. The integrated
grounded position allows either incoming or outgoing
cables to be internally grounded.

Manhole Style Vista UDS can be installed on a stand or


directly on the floor. With the optional mounting bracket,
it can be mounted on a wall. Virtually any orientation or
mounting style can be accommodated.

Large viewing window for


clear conrmation of open
point

Model 110

Pressure gauge (located under window) is


temperature and altitude compensated

Model 101

Ratings:
kV, Maximum . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15.5
kV, BIL . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .95
Amperes, Continuous . . . . . . . . . . . . . . . . . . . . . . . . . . . 630*

29
125
630*

38
150
630*

Amperes, Load Dropping. . . . . . . . . . . . . . . . . . . . . . . . . 630*

630*

630*

Short-Circuit Ratings (Amperes, RMS Symmetrical)


Load-Interrupter Switch
Fault-Closing, Ten-Time . . . . . . . . . . . . . . . . 12,500
Momentary. . . . . . . . . . . . . . . . . . . . . . . . . . 12,500
One-Second . . . . . . . . . . . . . . . . . . . . . . . . 12,500

12,500
12,500
12,500

12,500
12,500
12,500

12,500
12,500

12,500
12,500

12,500
12,500

25,000
25,000

25,000
25,000

25,000
25,000

Fault-Closing, Ten-Time . . . . . . . . . . . . . . . .
Interrupting . . . . . . . . . . . . . . . . . . . . . . . . .
Fault Interrupters, 25 kA
Fault-Closing, Ten-Time . . . . . . . . . . . . . . . .
Interrupting . . . . . . . . . . . . . . . . . . . . . . . . .

*Continuous and load-dropping rating is 200 amperes when optional 200-ampere bushing wells
are provided.

681-707
Page 2 of 2
February 3, 2003

PHOTO SHEET
S&C ELECTRIC COMPANY

Printed in U.S.A.

Fault Interrupter, 12.5 kA