Você está na página 1de 17

ENERGY EFFICIENCY STANDARDIZATION &

LABELING PROGRAM
UAE.S 5010-1:2014
Household Air-conditioners
UAE.S 5010-5:2014
Commercial and Central Air-conditioners

Conformity Affairs Department


Emirates Authority for Standardization and Metrology
1

UAE.S 5010-1:2014
Household Air-conditioners

EESL 50101:2014&50105:2014

HOUSEHOLD AIR-CONDITIONERS
UAE.S 5010-1:2014

Program Scope:
Residentialsinglepackageandsplitsystem
nonductedairconditioners.
ImplementationDate:01November2015

EESL 50101:2014&50105:2014

HOUSEHOLD AIR-CONDITIONERS
UAE.S 5010-1:2014

Energy Efficiency Ratio (EER) Requirements:

STAR RATING

EER @ T3 (Btu-h/W)
Window-Type

Split-Type

EER 8.51

EER 9.01

8.50 EER 8.01

9.00 EER 8.31

8.00 EER 7.51

8.30 EER 7.71

7.50 EER 6.81

7.70 EER 7.11

6.80 EER 6.30

7.10 EER 6.80

EESL 50101:2014&50105:2014

HOUSEHOLD AIR-CONDITIONERS
UAE.S 5010-1:2014

Labeling Requirements:
LabelPlacement:
ACUnit/IndoorandOutdoorunit
Immediatepackagingorcartonbox
Note:
OldversionsofEELabelforAirconditionersshallbe
replacedwiththenewapprovedlabelbeginning
November1,2015.

EESL 50101:2014&50105:2014

HOUSEHOLD AIR-CONDITIONERS
UAE.S 5010-1:2014

Test Requirements:
ClimateClass:
T3Condition(IN:DB29C,IN:WB19C,OUT:DB46C,OUT:WB24C)asperISO5151
TestVoltage&Frequency:
230Vand50Hz
MaximumCoolingPerformance(fullloadoperation):
90%and110%ofratedvoltagewithasinglenameplaterating.
90%ofthelowerratedvoltageand110%ofthehigherratedvoltageforunitswitha
dualorextendednameplatevoltage.
Requiredsamplesfortesting:
2samples
Tolerance:
Inputpower:
Coolingcapacity:
EER:

EESL 50101:2014&50105:2014

+5%;10%
5%
+5%

HOUSEHOLD AIR-CONDITIONERS
UAE.S 5010-1:2014

Certification Transition:
ECASApplications(NewandRenewal)forregistrationofmodelssupportedby
performancetestreportsbasedontheoldrequirements(UAE.S50101:2011)shall
beaccepteduntil31May2015.Certificatesissuedunderthisconditionwillbevalid
onlyuptoOctober31,2015.
ECASApplications(NewandRenewal)appliedbeginningJune1,2015shallbe
requiredtoprovidedocumentstocomplywiththenewrequirements(UAE.S5010
1:2014).
Implementationofnew
requirementsincludingnew
designofEElabelfornon
ductedroomairconditioners.
Allapplications(Newor
Renewal)shallbeevaluated
basedonthenew
requirements.

Unitsapprovedbasedonold
requirementsshallberemoved
fromthemarketonthisdate.

Timeline

June1,2015
EESL 50101:2014&50105:2014

November1,2015
7

UAE.S 5010-5:2014
Commercial and Central Air-conditioners

EESL 50101:2014&50105:2014

COMMERCIAL & CENTRAL ACs


UAE.S 5010-5:2014

Program Scope:

SinglepackageandSplitsystem(NonductedRACs)
DuctedAirconditioners
Watersourceheatpumps
Waterchillingpackager
Multiplesplitsystemairconditionersandheatpumps

ImplementationDate:01November2015

EESL 50101:2014&50105:2014

COMMERCIAL & CENTRAL ACs


UAE.S 5010-5:2014

Split-ducted Unit:
TestProcedure:
UAE.SISO13253:2011
RatedCapacity
(BTU)
CC135000
135000CC240000
240000CC760000
760000CC

MinimumEnergyEfficiency
(EER)(Buth/watt)@T3
8.10
7.90
7.50
7.20

Forevaluationthefollowingconditionwillfollowed:
Thetestingcoolingcapacity95%theratedcoolingcapacity
Thetestingpowerconsumption110%theratedpowerconsumption

EESL 50101:2014&50105:2014

10

COMMERCIAL & CENTRAL ACs


UAE.S 5010-5:2014

Water Source Heat Pumps:


TestProcedure:
UAE.SISO132561:1998
UAE.SISO132562:1998
Type

Enteringwater
orfluid

RatedCapacity

MinimumEnergyEfficiency
(EER)(BtuH/Watt)T3

WaterSource

300C

ALL

7.90

GroundWaterSource

250C

ALL

8.70

EESL 50101:2014&50105:2014

11

COMMERCIAL & CENTRAL ACs


UAE.S 5010-5:2014

Water Chiller:
TestProcedure:
UAE.SAHRI550/590
Coolingtype

RatedCapacity(KW)

Aircooledpackage
chillers

CC630

MinimumEnergyEfficiency
(FullLoad)(T1)(BtuH/Watt)
8.50

630CC

9.50

CC528

13.50

528CC1055

15.00

1055CC

17.00

Watercooled
chilers

Forevaluationthefollowingconditionwillfollowed:
Thetestingcoolingcapacity95% theratedcoolingcapacity.
Thetestingpowerallowableconsumption105% theratedpowerconsumption.
EESL 50101:2014&50105:2014

12

COMMERCIAL & CENTRAL ACs


UAE.S 5010-5:2014

Multiple Split System:


TestProcedure:
UAE.SISO15042:2011

RatedCapacityBtu/h

MinimumEnergyEfficiency
(EER)(BtuH/Watt)atT3

CC90000

8.30

90000CC135000

7.80

135000CC

7.50

Forevaluationthefollowingconditionwillfollowed:
Thetestingcoolingcapacity92% theratedcoolingcapacity.
Thetestingpowerconsumption110% theratedpowerconsumption.

EESL 50101:2014&50105:2014

13

MARKET SURVEILLANCE

EESL 50101:2014&50105:2014

14

SAMPLES AIR-CONDITIONERS
ABU DHABI MARKET

EESL 50101:2014&50105:2014

15

SURVEILLANCE PROCEDURES
ESMA

SAMPLING AND VERIFICATION OF RESULTS:


1. Clientwillbenotified,oncenoncomplianceisestablishedduringmarket
surveillance.
2. ForEESLproducts,2unitsofthesamemodelwillbecollecteddirectlyfromthe
marketwiththesupervisionofESMAandthelocalauthority.
3. Unitswillbesenttoapredetermined3rd partylaboratoryforperformancetesting.
4. ReportswillbesubmittedtoESMAforevaluation.
5. Ifunitswerestillfoundnoncompliant,theclientwillberequiredtoperformthe
following:
1. Publicnotificationvialocalnewspaper(2Arabicand2English)foraproduct
recall.
2. Productrecallforthemodelunderquestion.
Note:Cost/expensesincurredduringsamplecollectionfromthemarket,
transportation/shipping,testingcostsaswellasproductrecall(ifrequired)willbethe
soleresponsibilityoftheclient.

EESL 50101:2014&50105:2014

16

For more information, please contact:


Conformity Affairs Department
Emirates Authority for Standardization &
Metrology
Email us at:
conformity@esma.gov.ae

EESL 50101:2014&50105:2014

17

Você também pode gostar