Você está na página 1de 14

Introduction to Machine

Protection

Power System Protection


ECCE 5302
Ass. Prof. Abdelsalam M. Elhaffar
D. Sc. Tech., Senior Member IEEE
Electrical Engineering Dept.
College of Engineering, SQU
Block C, Office 211, a.elhaffar@squ.edu.om

What are Machines and what is Machine


Protection?

What are Machines and what is Machine


Protection?
The protection devices must fulfil the
following 3S criteria:

Generators (asynchronous and synchronous)


Motors (asynchronous and synchronous)

 Selectivity (switch off of the faulty

Machine protection includes all numerical


devices which are able to

system)

detect faults and abnormal operating

 Speed (fast as necessary)


 Security (high security and reliability)

conditions on machines and

react according the situation. It protects the


objects against

inadmissible stress and is indirectly also a


human protection.

Page 1

Faults in Synchronous Generators (1)

Machine
Fault Categories

1. Winding and terminal faults

Internal Faults:

2. Sustained or uncleared external faults

Stator:
Earth Faults
Short Circuits
(two and three phase)
Interturn Faults
(at separate stator
windings)
Overload

3. Abnormal operating conditions such as overload,


overvoltage and overfluxing
4. Core fault
5. Rotor Faults

Faults in Synchronous Generators (2)

Rotor, Excitation Circuit:


Earth Faults
(single, double)
Failure in the Excitation
(partly or loss of
excitation)
Voltage Rise
Overexcitation (U/f)

Main Components of Machine Protection (Part 1)


 Generator - Differential Protection

External Faults:
Grid/Transformer:
In Turbine, Regulation:
Earth Faults
Loss of Prime Mover
Short Circuits
(Reverse power)
Overload
Over- and
Unbalanced Load
Undervoltage
Asynchronous Condition
Over- and
(cap.Load, long short circuit
Underfrequency
duration)
Overexcitation (U/f)
Torsion Stress
Underfrequency (PG < PL)

87G

Transformer - Differential Protection

87T

Overcurrent Time Protection

50, 51V

Impedance Protection

21

 Stator Earth Fault Protection for:


 Generators directly connected

67N

 Generators connected via unit transformer


 Protection Range 90 %
 Protection Range 100 %

Page 2

64
64 100%

Rotor Earth Fault Protection

64R

Unbalanced Load Protection

46

Reverse Power Protection

32R

Proposal for Selection of Protection Functions

Main Components of Machine Protection (Part 2)


 Overvoltage Protection (Undervoltage) 59, (27)
 Over and Underfrequency Protection 81
 Underexcitation (Loss of field) Protection 40
 Stator Overload Protection 49
 Overexcitation (U/f) Protection 24
 Out of Step Protection 78
 Breaker Failure Protection 50BF
 Rotor Overload Protection 49R
 (Overcurrent at excitation transformer)
 Interturn Fault Protection 87G / 87T
 (separate Stator windings - hydro generators)
 Tripping matrix (Software matrix) 94

Y: Pump storage stations (motor /phase shift operation) O: option

Tripping Concept

Redundancy (Large Units) 2 devices per


Object

In unit schemes, protection is required to trip more than one


breaker.
It depends on the fault type, the plant design and plant
operation, generator operation and general operation
philosophy
Generator Breaker
 Excitation Breaker
 Turbine Rapid Shut Down
 HV Network Breaker
 Auxiliary Supply Breaker
 Aux. Supply Changeover
Unit-transformer , Aux.-transformer


Page 3

Requirements for Communication Eaxmple 1

Requirements for Communication Example 2

Introducing IEC61850 Ethernet based


Communication

IEC61850 Configuration Principles

Page 4

Protection functions

Protection functions
Rotor Faults:

Rotor Faults:
Resistance measurement with a square wave voltage
of 1 to 3 Hz

The square wave voltage injected through the controlling unit leads to
permanent recharging of the rotor earth capacitance.
By way of a shunt in the controlling unit, the flowing earth current is
measured and is injected into the protection unit (measurement input).

A higher sensitivity is required for larger generators.


On the one hand, the disturbing influence of the
rotor earth capacitance must be eliminated more
effectively

In the absence of a fault (RE=


), the rotor earth current after charging
of the earth capacitance is close to zero. In the event of an earth fault,
the fault resistance including a coupling resistance, and also the
injecting voltage, defines the stationary current.

On the other hand, the noise ratio with respect to


the harmonics (e.g. 6th harmonic) of the excitation
equipment must be increased.
Injecting a low-frequency square wave voltage into
the rotor circuit has proven itself excellent.

Protection functions

Protection functions
100% stator earth-fault protection with 20 Hz injection

Rotor Faults:

Injecting a 20 Hz voltage to detect earth faults even at the


neutral point of generators has proven to be a safe and
reliable method.

The current square wave voltage and the frequency are


measured via the second input (control input).

Contrary to the third harmonic criterion, it is independent


of the generators characteristics and the mode of
operation.

Fault resistance values up to 80 k


can be measured by
this measurement principle.

it is independent of the generators characteristics and the


mode of operation. Measurement is also possible during
system standstill
This protection function is designed so as to detect both
earth faults in the entire generator (100 %) and all
electrically connected system components.

The rotor earth circuit is monitored for discontinuities by


evaluation of the current during the polarity reversals.

Page 5

Protection functions

Protection functions

100% stator earth-fault protection with 20 Hz injection

Out-of-step protection
This protection function serves to detect power
swings in the system.

The protection unit measures the injected 20 Hz


voltage and the flowing 20 Hz current.

If generators feed too long onto a system short-circuit, a


compensation process (active power swings) may take
place between the system and the generator after fault
disconnection.

The disturbing variables, for example stator earth


capacitance, are eliminated by way of a mathematical
model, and the ohmic fault resistance is determined.

If the center of power swings is in the area of the unit, the


active power surges lead to impermissible mechanical
stressing of the generator and the whole generator
mounting including the turbine.

Protection functions

Protection functions

Out-of-step protection

Out-of-step protection
The extending of the characteristic in R direction
determines the detectable power swing angle. 120 are
practicable.

Since these are symmetrical processes, the positivesequence impedance is calculated from the voltage and
current positive-sequence components and the
impedance curve is evaluated.

The characteristic can be tilted at an adjustable angle to


adapt to the conditions when the system is feeding off
several parallel generators.
The impedances of the protected zone seen from
the protection relay are decisive for determining
the setting values.

The symmetry is monitored by evaluating the negativephase sequence system current. Two characteristics in
the R/X diagram describe the range of effect (generator,
unit transformer or system) of the out-of-step protection.

23

> Transformer Protection

Page 6

Out-of-step protection

Protection functions

Out-of-step protection

Protection functions

Parameter overview for out-of-step protection

In the direction of the


generator, the power swing
reactance of the
generator must be taken into
account;
It can be set approximately
equal to the transient
reactance xd'.
This means the transient
reactance related to the
secondary side is calculated
and set for Zb= xd'

LOSS OF FIELD PROTECTION

Protection functions

LOSS OF FIELD PROTECTION

DISTANCE SCHEME 1: UNQUALIFIED TRIP


SCHEME

DISTANCE SCHEME 1: UNQUALIFIED TRIP


SCHEME

This scheme employs a single mho element connected at


the generator terminals oriented to measure impedance
looking into the generator and trip with a time delay.

The reactance measured by the LOF relay as the generator


slips poles each slip cycle will then vary between X'd and
X'q if the generator was initially at full load and between Xd
and Xq if initial operation was at light load. Given that Xd is
greater than Xq and that X'd is less than X'q , LOF protection
must be set to encompass all reactance values between X'd
and Xd if it is to operate for all initial values of generator
loading.
It has become standard practice to set the impedance
element for this type of scheme with a diameter of Xd and an
offset of 1/2 X'd

An impedance element cannot detect a failure in the


excitation system directly. Instead, it is set to detect the
generators post failure operation as an induction
generator.
The impedance of a generator operating asynchronously at
final slip with no field excitation is unique and can be used
to differentiate a LOF event from other power system
transients.

27

Protection functions

> Transformer Protection

28

Page 7

> Transformer Protection

LOSS OF FIELD PROTECTION

Protection functions

LOSS OF FIELD PROTECTION

DISTANCE SCHEME 1: UNQUALIFIED TRIP


SCHEME

Protection functions

DISTANCE SCHEME 1: UNQUALIFIED TRIP


SCHEME
The conventional settings for Scheme 1 are:
Outer element
Diameter = Xd =1.48 pu
Offset
Time delay = 1.0 sec
Inner element
Diameter =10 pu
Offset
Time delay = 0.4 sec

Impedances on generator base 104 MVA 13.8


kV
Xd = 1.48 pu Xd ' = 0.196 pu
Xtr = 0.07 pu,
Zsyst = 0.078 pu @ 85min (normal)
= 0.225 pu @ 75max (line out)

29

> Transformer Protection

30

> Transformer Protection

Traditional Generator Protection Package

Overcurrent Protection

Page 8

Transformer Overcurrent Protection

Transient Overreach
Concerns relay response to offset waveforms (DC
transient)
Definition

Requirements

I1 - I2
x 100
I2

 Fast operation for primary short circuits


 Discrimination with downstream protections
 Operation within generator withstand

I2

 Non-operation for short or long term overloads

I1

D.C
.

I1 = Steady state
rms
pick up
current
I2 = Fully offset
rms
pickup
current

EARTH FAULT PROTECTION FOR


THE COMPLETE STATOR WINDING
The earth fault protection schemes
(percentage bias differential protection

Earth Fault Protection

or neutral overcurrent relay or voltage


relay) protect a certain portion of the
winding leaving a part of winding at the
neutral end unprotected.

36

Page 9

> Transformer Protection

STATOR PROTECTION

STATOR PROTECTION
Sub-harmonic injection method

2.Injection transformer and


reactor
grounded
generators
distribution
transformer
asaa
1.4.
3.Neutral
Voltage
Injection
injection
transformer
through
and
the
grounding distribution
resistor
transformer

Two different schemes are available for


complete protection of the stator
winding:

1. Low frequency injection scheme.

2. Third harmonic voltage scheme


37

> Transformer Protection

38

> Transformer Protection

STATOR PROTECTION
Third
voltage method
1. Thirdharmonic
harmonic under-voltage
Differential Protection

2. Third
3.
scheme
harmonic ratio
overvoltage
voltagescheme
scheme

39

> Transformer Protection

Page 10

BACK UP FAULT PROTECTION

Basic principles: measuring circuit for a 3-phase system

Motoring protection

Basic circuit for a 3- phase system:


Generator / Motor / Reactor

Mechanical protection: steam turbines

L1

Reverse-power relay (Device 32)

L2
L3

Diff.

Steam turbine

3.0%

Water wheel turbine

0.2%

Gas turbine

50.0%

Diesel engine

25.0%

Rest. current

Conventional
Differential Protection

42

EXCITATION PROTECTION

EXCITATION PROTECTION
Loss of field protection

 Over excitation protection


 Protection

Protection

1. FIELD MONITORING RELAYS

3. Frequency-sensitive excitation
Device 40
2..
Modified
Two
1.systems
DISTANCEScheme:
SCHEME
1: Impedance
UNQUALIFIED TRIP SCHEME
Elements

2. V/HZ LIMITER

43

> Transformer Protection

> Transformer Protection

44

Page 11

> Transformer Protection

Overfluxing
INTER-TURN PROTECTION BY ZERO SEQUENCE
VOLTAGE MEASUREMENT

 Generator transformers
Usually only a problem during run-up or shut down, but can be
caused by loss of load / load shedding etc.

Interturn faults in a generator with a


single winding can be detected by
observing the zero-sequence voltage
across the machine terminals.

Flux V
f
 Effects of overfluxing :






Increase in magnetising current


Increase in winding temperature
Increase in noise and vibration
Overheating of laminations and metal parts (caused by
stray flux)

 Protective relay responds to V/f ratio

 Stage 1 - lower A.V.R.


 Stage 2 - Trip field

45

> Transformer Protection

Overfluxing Basic Theory

V = kf

V/Hz Overfluxing Protection

2m

V K
f

m
 CAUSES

 Low frequency
 High voltage
 Geomagnetic disturbances

Trip and alarm outputs for clearing prolonged overfluxing


Alarm : Definite time characteristic to initiate corrective action

Ie

Trip : IDMT or DT characteristic to clear overfluxing condition


Settings

 EFFECTS

Pick-up 1.5 to 3.0 i.e.

 Tripping of differential element (Transient overfluxing)


 Damage to transformers (Prolonged overfluxing)

110V x 1.05 = 2.31


50Hz

DT setting range 0.1 to 60 seconds

Page 12

V/Hz Characteristics

Overfluxing Relay

 Enables co-ordination with plant withstand characteristics

t = 0.8 + 0.18 x K
(M - 1)2

Ex

1000
K = 63
K = 40
K = 20
K=5
K=1

100
Operating
time (s)

10

VT

AVR

1
1

1.1

1.2

1.3

1.4

1.5

R
L

1.6

M = V Hz
Setting

Effect of Overload on Transformer


Insulation Life
100

Thermal Overload Protection

Relative
rate
of using
life

10

With ambient of 20 C.
Hot spot rise of 78 C is
design normal.
A further rise of 6 C
doubles rate of
using life.

1.0
98
0.1
80

90 100 110 120 130 140


Hot spot temp C

Page 13

Thermal Overload
Oil Filled Transformers
Trip time (s)
10000

Single
characteristic:
= 120 mins

1000

Dual
characteristic

100

10
1

2
3
4
5
6
Current (multiple of thermal setting)

Single
characteristic:
= 5 mins

Page 14

Você também pode gostar