Escolar Documentos
Profissional Documentos
Cultura Documentos
Protection
system)
Page 1
Machine
Fault Categories
Internal Faults:
Stator:
Earth Faults
Short Circuits
(two and three phase)
Interturn Faults
(at separate stator
windings)
Overload
External Faults:
Grid/Transformer:
In Turbine, Regulation:
Earth Faults
Loss of Prime Mover
Short Circuits
(Reverse power)
Overload
Over- and
Unbalanced Load
Undervoltage
Asynchronous Condition
Over- and
(cap.Load, long short circuit
Underfrequency
duration)
Overexcitation (U/f)
Torsion Stress
Underfrequency (PG < PL)
87G
87T
50, 51V
Impedance Protection
21
67N
Page 2
64
64 100%
64R
46
32R
Tripping Concept
Page 3
Page 4
Protection functions
Protection functions
Rotor Faults:
Rotor Faults:
Resistance measurement with a square wave voltage
of 1 to 3 Hz
The square wave voltage injected through the controlling unit leads to
permanent recharging of the rotor earth capacitance.
By way of a shunt in the controlling unit, the flowing earth current is
measured and is injected into the protection unit (measurement input).
Protection functions
Protection functions
100% stator earth-fault protection with 20 Hz injection
Rotor Faults:
Page 5
Protection functions
Protection functions
Out-of-step protection
This protection function serves to detect power
swings in the system.
Protection functions
Protection functions
Out-of-step protection
Out-of-step protection
The extending of the characteristic in R direction
determines the detectable power swing angle. 120 are
practicable.
Since these are symmetrical processes, the positivesequence impedance is calculated from the voltage and
current positive-sequence components and the
impedance curve is evaluated.
The symmetry is monitored by evaluating the negativephase sequence system current. Two characteristics in
the R/X diagram describe the range of effect (generator,
unit transformer or system) of the out-of-step protection.
23
Page 6
Out-of-step protection
Protection functions
Out-of-step protection
Protection functions
Protection functions
27
Protection functions
28
Page 7
Protection functions
Protection functions
29
30
Overcurrent Protection
Page 8
Transient Overreach
Concerns relay response to offset waveforms (DC
transient)
Definition
Requirements
I1 - I2
x 100
I2
I2
I1
D.C
.
I1 = Steady state
rms
pick up
current
I2 = Fully offset
rms
pickup
current
36
Page 9
STATOR PROTECTION
STATOR PROTECTION
Sub-harmonic injection method
38
STATOR PROTECTION
Third
voltage method
1. Thirdharmonic
harmonic under-voltage
Differential Protection
2. Third
3.
scheme
harmonic ratio
overvoltage
voltagescheme
scheme
39
Page 10
Motoring protection
L1
L2
L3
Diff.
Steam turbine
3.0%
0.2%
Gas turbine
50.0%
Diesel engine
25.0%
Rest. current
Conventional
Differential Protection
42
EXCITATION PROTECTION
EXCITATION PROTECTION
Loss of field protection
Protection
3. Frequency-sensitive excitation
Device 40
2..
Modified
Two
1.systems
DISTANCEScheme:
SCHEME
1: Impedance
UNQUALIFIED TRIP SCHEME
Elements
2. V/HZ LIMITER
43
44
Page 11
Overfluxing
INTER-TURN PROTECTION BY ZERO SEQUENCE
VOLTAGE MEASUREMENT
Generator transformers
Usually only a problem during run-up or shut down, but can be
caused by loss of load / load shedding etc.
Flux V
f
Effects of overfluxing :
45
V = kf
2m
V K
f
m
CAUSES
Low frequency
High voltage
Geomagnetic disturbances
Ie
EFFECTS
Page 12
V/Hz Characteristics
Overfluxing Relay
t = 0.8 + 0.18 x K
(M - 1)2
Ex
1000
K = 63
K = 40
K = 20
K=5
K=1
100
Operating
time (s)
10
VT
AVR
1
1
1.1
1.2
1.3
1.4
1.5
R
L
1.6
M = V Hz
Setting
Relative
rate
of using
life
10
With ambient of 20 C.
Hot spot rise of 78 C is
design normal.
A further rise of 6 C
doubles rate of
using life.
1.0
98
0.1
80
Page 13
Thermal Overload
Oil Filled Transformers
Trip time (s)
10000
Single
characteristic:
= 120 mins
1000
Dual
characteristic
100
10
1
2
3
4
5
6
Current (multiple of thermal setting)
Single
characteristic:
= 5 mins
Page 14