LIGHTING CALCULATION
Document no:
SLS 40 ELE CAL 001
18-Mar-2013
ARF
JPD
SUT
11-Mar-2013
ARF
JPD
SUT
PREPARED
CHECKED
APPROVAL
REV
DATE
DESCRIPTION
APPROVAL
PT. DEPRIWANGGA
NO part of this document may be reproduced, in any form or by any means, except as permitted by
the Author
DOCUMENT NUMBER
REV
PAGE
Lighting Calculation
SLS-40-ELE-CAL-001
1 of 20
REVISION SHEET
Page
Revision
A
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
Page
Revision
Page
Revision
Page
Revision
DOCUMENT NUMBER
REV
PAGE
Lighting Calculation
SLS-40-ELE-CAL-001
2 of 20
COMMENT SHEET
No
.
COMPANY
BY
POSITION
DATE
PT Depriwangga
Comment
Response
DOCUMENT NUMBER
REV
PAGE
Lighting Calculation
SLS-40-ELE-CAL-001
3 of 20
TABLE OF CONTENTS
REVISION SHEET.................................................................................................................... 1
COMMENT SHEET.................................................................................................................. 2
TABLE OF CONTENTS............................................................................................................ 3
1.
2.
Introduction........................................................................................................................ 4
1.1
Background................................................................................................................ 4
1.2
Objectives................................................................................................................... 4
1.3
Scope......................................................................................................................... 4
1.4
Associated Document.................................................................................................4
Glossary of Terms.............................................................................................................. 5
2.1
Definitions................................................................................................................... 5
2.2
Abbreviations.............................................................................................................. 5
3.
4.
5.
6.
4.1
Design Basis............................................................................................................... 5
4.2
Assumptions............................................................................................................... 6
4.3
Formulae.................................................................................................................... 6
Model of Lighting........................................................................................................ 9
5.2
Calculation.................................................................................................................. 9
Model of Lighting......................................................................................................10
6.2
Result....................................................................................................................... 10
1.
TITLE
DOCUMENT NUMBER
REV
PAGE
Lighting Calculation
SLS-40-ELE-CAL-001
4 of 20
Introduction
1.1 Background
This document covers Control Valve Calculation for FEED 75 KM pipeline project from point B
Arun to SLS A Development. The Control valve to be installed on Area 19, Arun before Metering
SKID. Located in lhokseumawe, Aceh and operated by PERTAMINA GAS., hereinafter is referred
to as COMPANY.
This document is preliminary calculation only. It is VENDORS responsibility to verify this
calculation to meet COMPANY requirement to run facilities operable and safely. The VENDOR
shall be required to update this document, once specific information has been defined. Should
there be discrepancies or anomalies between documents, VENDOR shall clarify and responsible
for the revision the document and consequences thereof.
1.2 Objectives
This document provides calculations to determine illumination level calculation of Electrical Room
and Control Room to be installed on the Electrical Room and Control Room FEED 75 KM pipeline
project from point B Arun to SLS A Development.
The purpose of this calculation is to confirm the number of fixtures required and illmunation levels
meet the requirement for Electrical Room and Control Room.
This report consist of indoor and outdoor
attached to this report. Outdoor lighting calculation is performed using Chalmlite Lighting
Software version 4.05
1.3 Scope
This assessment of electrical calculation is for FEED 75 KM pipeline project from point B Arun to
SLS A Development of PERTAMINA GAS.
1.4 Associated Document
Project Document:
-
SLS-40-ELE-CAL-00X
SLS-40-ELE-SLD-00X
SLS
International Standards used in this report of Lighting Calculation but not limited as follows:
-
DOCUMENT NUMBER
REV
PAGE
Lighting Calculation
SLS-40-ELE-CAL-001
5 of 20
EN 12464
API 500
API RP14F
2.
IEC 60079-14
NFPA 70
IEC 60598
Luminaires
Glossary of Terms
2.1 Definitions
The party that carries out all or part of the design, engineering, procurement,
construction, commissioning or management of a project. The COMPANY
may undertake all or part of the duties of the CONTRACTOR
VENDOR
2.2 Abbreviations
3.
LLF
MF
Maintenance Factor
UF
Utility Factor
IEC
IEEE
4.
This parameter will be used for lighting calculation. The building for Electrical Room and Control
DOCUMENT NUMBER
REV
PAGE
Lighting Calculation
SLS-40-ELE-CAL-001
6 of 20
:3m
:8m
: 11 m
4.2 Assumptions
Light Loss Factor (LLF) or Maintenance Factor (MF) for lighting calculation as follow:
-
4.2.2
For process area, the maintenance factor is 0.8 in indoor and outdoor
For non-process area, the maintenace factor is 0.85 for indoor and 0.8 for outdoor
Lighting system is designed to provide a level of illumination 0.75 m above the floor. The
mounting height will be 2.25 m. For outdoor area the mounting height will be 9 m.
4.2.3
Ceiling
Wall
Floor
: 0.7
: 0.5
: 0.3
4.3 Formulae
4.3.1
E=
n x N x F x UF x MF
A
(1)
Where
E = average illuminance over the horizontal working plane (lux)
n = number of lamps in each luminaire
N = number of luminaire
F = lighting design lumens per lamp (lumens)
UF = utilisation factor for the horizontal working plane
MF = maintenance factor (sometimes also called light loss factor LLF), to account for the
reduction in light output from a lighting system due to ageing of the lamps and
accumulation of dirt/dust on the light fittings and room surfaces
DOCUMENT NUMBER
REV
PAGE
Lighting Calculation
SLS-40-ELE-CAL-001
7 of 20
hm
Workin
g plane
fl
o
The utilisation factor can be obtained from Utilisation Factor Table provided by the luminaire
manufacturer based on the surface reflectance along with the room index (K), which can be
derived as:
K=
LxW
( L + W ) hm
(2)
Where
L = Room Length (m)
W = Room Width (m)
hm = Mounting Height of Fitting (from working plane) (m)
The UF parameter can be look in the table of Appendix 1
Maintenance factor (MF) is a value designed to account for the reduction in light output from a
lighting system due to:
a) Ageing of the lamps
b) Accumulation of dirt and dust on the light fittings and room surfaces.
The value can be calculated as:
DOCUMENT NUMBER
REV
PAGE
Lighting Calculation
SLS-40-ELE-CAL-001
8 of 20
(3)
0.8
b) Clean Industrial
0.7
c) Dirty Industrial
0.6
E=
I x cos
x MF x AL
d2
(7)
Where
E = illuminance at the target surface (lux)
I = luminous intensity of the source in the direction of the surface (lumens)
= angle between the light ray coming from the source to the point, and a line
that is perpendicular (normal) to the plane or surface on which the illuminance is
being measured or calculated
d = distance from the source to the surface (m)
MF = maintenance factor
AL = atmospheric loss, a factor to represent atmospheric absorption losses
DOCUMENT NUMBER
REV
PAGE
Lighting Calculation
SLS-40-ELE-CAL-001
9 of 20
If the target plane is illuminated by multiple light source, the calculations can be preformed
individually per light source. The final result can be obtained by summing all calculated
illuminance levels.
5.
5.1
Lamp type
Lamp lumens
Light loss factor
Catalgoue
5.2 Calculation
First we define the room index based on the room physical dimension from equation (2)
K=
=
LxW
( L + W ) hm
11 x 8
( 11 +8 ) 2.25
= 2.06
DOCUMENT NUMBER
REV
PAGE
Lighting Calculation
SLS-40-ELE-CAL-001
10 of 20
E A
n F UF MF
N
500 88
2 3350 0.75 0.8
N = 11.73
The number of fixtures required is set to be 16 fixtures
The average intensity of illumination for each Electrical and Control Room will be
n N UF MF F
A
E= 682.18 lux
6.
6.1
6.2
Lamp type
Lamp lumens
Light loss factor
Catalgoue
Result
From the calculation report, the minimum illumination levels is 12 lux. This has suffice the
minimum requirement illumination level for outdoor area.
DOCUMENT NUMBER
REV
PAGE
Lighting Calculation
SLS-40-ELE-CAL-001
11 of 20
DOCUMENT NUMBER
REV
PAGE
Lighting Calculation
SLS-40-ELE-CAL-001
12 of 20
Appendix 3
Outdoor Lighting Calculation Report