Escolar Documentos
Profissional Documentos
Cultura Documentos
System Description
DCS 600 MultiDrive
II F i
3ADW000072R0501_DCS600_System_description_e_e
Volume II F Volume II F1 Volume II F2
How the DCS 600 MultiDrive Documentation Sys-
System Description System Description tem works
DCS(F) 600 DCA 600 Enclosed
3ADW000072 3ADW000121 This is to give you an overview how the system of
information for DCS 600 MultiDrive converters is
built up. The shaded part indicates the volume within
Volume III the total system you are just now working with. In
12-Pulse Manual addition you see all other available documents for the
Technical Data
3ADW000165 DCS 600
same system.
3ADW000115
Volume IV F Volume VI F1
Oper. Instructions Installation Man.
DCS(F) 600 DCA 600 ...
3ADW000080 3ADW000091
Volume V F
SW Description
List of contents
DCS(F) 600
3ADW000076
II F SYSTEM DESCRIPTION
1 DCS 600 MultiDrive - the power converter II F 1-1
Volume VI A
Service Manual 2 DCS 600 MultiDrive components overview II F 2-1
2.1 Environmental conditions .............................................. II F 2-3
DCS 500/600
3ADW000093
2.2 DCS 600 power converter modules .............................. II F 2-4
2.3 DCS 600 overload withstand capability ........................ II F 2-7
2.4 Field Supply .................................................................. II F 2-9
2.5 Options for power converter modules ......................... II F 2-11
In-/output signals ........................................................ II F 2-11
Serial interfaces
Operation by the panel .............................................. II F 2-13
Panel (control and display panel) .............................. II F 2-14
Operation by the PC .................................................. II F 2-15
Drive control ............................................................... II F 2-15
2.6 Options ........................................................................ II F 2-17
Line reactors for armature (DCS600) and
field (DCF600) supply ................................................ II F 2-17
Aspects of fusing for armature circuits and field
supplies of DC drives .............................................. ...II F 2-19
Semiconductor type F1 fuses and fuse holders for
AC and DC power lines ............................................. II F 2-21
Fuses F3.x fuses and fuse holders for 2-phase
field supply ................................................................. II F 2-21
Transformer T3 for field supply .................................. II F 2-22
Commutating reactor ................................................. II F 2-22
Auxiliary transformer T2 for electronic system /
fan supply ................................................................... II F 2-22
Residual current detection ......................................... II F 2-22
EMC filters ................................................................. II F 2-23
II F ii
3ADW000072R0501_DCS600_System_description_e_e
1 DCS 600 MultiDrive - the power converter
❖ state-of-the-art technology
❖ flexible design
❖ user-friendly
II F 1-1
3ADW000072R0501_DCS600_System_description_e_e
Basic functions Design and commissioning tools
All units are provided with the same digital control DriveWindow
boards and software. The DCS 600 MultiDrive flexi- PC program for commissioning and maintenance un-
bility allows the user to configure functions of the drive der Windows® for:
easily, suitable for different applications. Functions of Parameter setting
the DCS 600 MultiDrive are normally activated by Fault detection
parameters. Trending
Data logger
The basic software includes the following options: Fault logger
• Processing the speed reference with a speed ramp Local operation (Drives Panel)
generator (S-ramp capability, accel/decel ramp)
• Processing the speed feedback CDP 312 removable control and display panel with
• Speed controller plain text display for:
• Torque reference processing Drive control signal
• Current controller Parameter setting
• Field weakening Fault detection
• Automatic/manual field reversal Parameter uploading and downloading
• Autotuning of current controller Local operation
• Speed monitor
• Drive control logic
• Remote/local operation Monitoring functions
• Emergency stop Self-test
• Electronic circuits are not sensitive to line phase Fault logger
sequence Motor protection
• Electrical and mechanical brake control In the event of:
• Motor overload supervision • Speed feedback error
• Dual field • Overtemperature
• Programmable analogue outputs • Overload
• Field supply • Overspeed
• Master follower via fibre optics • Zero speed
• 12-pulse link • Armature overcurrent
• Armature ripple
Controlling and operating • Armature overvoltage
via I/O's • Minimum field current
analogue and digital inputs and outputs • Field overcurrent
• Motor stalled
via bus systems Power converter protection
e.g.: Profibus, Modbus Plus, AF100 etc. • Overtemperature
• Software errors (watchdog function)
via HMI (Human Machine Interface) Incorrect supply protection
Outputs: • Mains overvoltage and undervoltage
Alarms • Auxiliary undervoltage
Faults • Incorrect mains phase sequence (only inform.)
Status information
Parameter setting
Local control of the drive
II F 1-2
3ADW000072R0501_DCS600_System_description_e_e
≤ 1000V
2
EMC filter
Fig. 2/1:
Earth-fault monitor
≤ 690V
PC + F2 Q1 F3
MultiDrive
DriveWindow socket F1
T2 T3
NDPI
-NDPA-02 Panel Monitoring
(PCMCIA) K3
-NDPC-12 K1 Power
CDP 312 LED bar
-NISA-03 (ISA)
Rev D or later NLM D supply
X3 K5
L1
NDBU95 L3
X3
X2
12-Pulse link T90
U1 V1 U1 V1 W1
DCS 6..-....-.1-15..... (.... -.1-18.....)
AMC-DC X99
CH3 POW 1 U1 V1 W1 X1 X1
DCS 600 Armature converter
CON 2
X33 X37 X37
V260
CH0
FEX 1 FEX 2
DSP X12 X12
to other drives
PIN 1x
CH2 X10 X11
X13 X13
based on the DCS 600 power converter modules. This
control DC motors. It consists of individual components,
system of components and complete standard cabinets to
The DCS 600 MultiDrive power converter range is a
X12 M
PIN 20xB X14 X14
X2
µP X13
X16
DCF 503A
DCF 601 / 602
Three-phase field supply
X12 PIN 41
PIN 51
X16 X1 X2 X17 X16 X14 *
(24V) X13 PIN 41 C1 D1 X1 X1
/ 504A
C1 D1
A92 C1 D1
3ADW000072R0501_DCS600_System_description_e_e
Nxxx X3 X1
with the system; its main components are shown in the diagram above.
This overview has been designed to help you to familiarize yourself
X4,5 X6 X4 X3 X3 X5 X2 X1 Legend
3 5 2
CON x - short designation of components
8 8 7
DCS 600 MultiDrive Components Overview
II F 2-1
DCF 600 Field supply converter
The DCF 600 field supply converter range is a system of the modified power interface board SDCS-PIN-1x (if
components and complete standard cabinets to control used) and the reduced range of current and voltage types
the field supply of DC motors. It consists of individual (see table 2.2/2). The function for field supply will be
components, based on the DCS 600 power converter selected by software parameters.
modules. The difference to the armature converter is only Note: Armature and field converters use the same firmware.
dcf6_sys_h.dsf
analogue input / output
X4
DCF 506
X11
X12
M
DCS 600
optical fibre
X16
Legend
digital input / output
alternative
M
Earth-fault monitor
7.1
K5
EMC filter
U1 V1 W1
C1 D1
K3
L1
Q1
F1
≤ 600V
X17
IOE 1
7
X2 X1
ied
2
di f
PIN 20xB
mo
PIN 1x
POW 1
X99
IOB 3
X2
F2
X37
X12
X13
X12
X13
T2
≤ 690V
X1
5
X4 X3
DCF 6..-....-.1-15.....
3
Monitoring
CZD-0x
X37
LED bar
X14
X3
X12
X13
X3
NLMD
X1
8
X4,5 X6
IOB 2x
V260
8
X16
CON 2
µP
X3
X17
Rev D or later
MultiDrive
CDP 312
socket
Follower
NDPI
Panel
- Master/
X1 X2
X33
X11
X2
to the PLC
Field Bus
(24V)
Adapter
X16
Module
Nxxx
X10
(PCMCIA)
DriveWindow
AMC-DC
DSP
-NISA-03 (ISA)
PC +
8
4
CH3
CH2
CH0
-NDPA-02
-NDPC-12
-Advant
control
7
3
PLC
NDBU95
to other drives
Fig. 2/2: DCS 600 MultiDrive Components overview for field supply converters
II F 2-2
3ADW000072R0501_DCS600_System_description_e_e
2.1 Environmental Conditions
90
100
80
90
70
80
60
50 70
1000 2000 3000 4000 5000 m 30 35 40 45 50 55°C
Fig. 2.1/1: Effect of the site elevation above sea level Fig. 2.1/2: Effect of the ambient temperature on the
on the converter’s load capacity. converter module load capacity.
Regulatory Compliance North American Standards
The converter module and enclosed converter components are designed for use In North America the system components fulfil
in industrial environments. In EEA countries, the components fulfil the require- the requirements of the table below.
ments of the EU directives, see table below.
Harmonized Standards Rated Standards
European Union Directive Manufacturer's Assurance supply Converter module Enclosed converter
Conver ter module Enclosed conver ter
voltage
Machinery Directive
Declaration of EN 60204-1 EN 60204-1 to 600 V UL 508 C UL/CSA types: on request
98/37/EEC Power Conversion
Incor poration [IEC 60204-1] [IEC 60204-1]
93/68/EEC Equipment
EN 60146-1-1 EN 60204-1 CSA C 22.2 No. 14-95
Low Voltage Directive [IEC 60146-1-1] [IEC 60204-1] Industrial Control
73/23/EEC Declaration of Conformity EN 50178 [IEC --] EN 60439-1 Equipment,
93/68/EEC see additional [IEC 60439-1] Industrial Products
IEC 60664 Available for converter
Declaration of Conformity modules including field
EN 61800-3 ➀ EN 61800-3 ➀ exciter units.
(Provided that all [IEC 61800-3] [IEC 61800-3]
EMC Directive installation instructions Types with UL mark:
89/336/EEC concerning cable • see UL Listing
93/68/EEC ➀ in accordance
selection, cabling and ➀ in accordance with www.ul.com /
with 3ADW 000 032/ certificate no.
EMC filters or dedicated 3ADW 000 032
3ADW 000 091 E196914
transformer are followed.)
• or on request
> 600 V EN / IEC xxxxx see EN / IEC types: on request
to table on the left (for details see table on the
1000 V Available for converter left)
modules
including field exciter
units.
II F 2-3
3ADW000072R0501_DCS600_System_description_e_e
2.2 DCS 600 Power Converter Modules
The power converter modules are modular in construc- volved, e.g. a field supply for the motor, or an interface
tion. They are based on the housing, which contains the board to connect the converter to an overriding control
power section with the RC snubber circuit. There are system. A control/display panel is available for the
different sizes, depending on current and voltage. All operator. It can be mounted to the power converter
units are forced cooled. module or installed in the cabinet's door by means of a
mounting kit.
The power section is controlled by the unit’s electronic
system, which is identical for the entire product range. Accessories such as external fuses, line reactors and the
Parts of the unit’s electronic system can be installed in like are available, for putting together a complete drive
the unit, depending on the particular application in- system.
Table 2.2/1: DCS 600 max. DC voltages achievable with a specified input
voltage.
If armature voltages higher than recommended are re-
quested, please check carefully, wether your system is still
working under safe conditions.
Max. permitted armature voltage depending on
Field exciter type
Application Armature converter SDCS-FEX-1 SDCS-FEX-2A DCF 504A
DCF 503A/504A
DCF 501B DCF 502B
Power always positive (Ua and Ia pos.). 2-Q Udmax 2-Q Udmax 2-Q -
Extruder
Power often or always negative. 2-Q Udmax 4-Q Udmax 4-Q Udmax 4-Q
Unwinder, suspended load
Power sporadically negative. 2-Q - - Udmax 2-Q +
Printing machine at electrical stop change
software
parameter
Power positive or negative. 4-Q Udmax 4-Q Udmax 4-Q -
Test rig
Power positive, sporadically negative. 4-Q Udmax 4-Q Udmax 2-Q + -
change
software
parameter
II F 2-4
3ADW000072R0501_DCS600_System_description_e_e
Converter type y→ y=4 (400 V) y=5 (500 V) y=6 (600 V) y=7 (690 V)
x=1 → 2-Q IDC [A] IAC [A] P [kW] P [kW] P [kW] P [kW]
x=2 → 4-Q 4Q 2Q 4Q 2Q 4Q 2Q 4Q 2Q 4Q 2Q 4Q 2Q
DCS60x-0025-y1 25 25 20 20 10 12 13 15
DCS60x-0050-y1 50 50 41 41 21 23 26 29
DCS60x-0050-61 50 50 41 41 31 35
DCS60x-0075-y1 75 75 61 61 31 35 39 44
DCS60x-0100-y1 100 100 82 82 42 47 52 58
DCS60x-0110-61 110 100 90 82 69 70
DCS60x-0140-y1 140 125 114 102 58 58 73 73
DCS60x-0200-y1 200 180 163 147 83 84 104 104
DCS60x-0250-y1 250 225 204 184 104 105 130 131
DCS60x-0270-61 270 245 220 200 169 172
DCS60x-0350-y1 350 315 286 257 145 146 182 183
DCS60x-0450-y1 450 405 367 330 187 188 234 235 281 284
DCS60x-0520-y1 520 470 424 384 216 219 270 273
DCS60x-0680-y1 680 610 555 500 282 284 354 354
DCS60x-0820-y1 820 740 670 605 340 344 426 429
DCS60x-1000-y1 1000 900 820 738 415 418 520 522
DCS60x-0903-y1 900 900 734 734 563 630 648 720
DCS60x-1203-y1 1200 1200 979 979 498 558 624 696
DCS60x-1503-y1 1500 1500 1224 1224 623 698 780 870 938 1050 1080 1200
DCS60x-2003-y1 2000 2000 1632 1632 830 930 1040 1160 1400 1600
DCF60x-0025-y1 25 25 20 20 10 12 13 15
DCF60x-0050-y1 50 50 41 41 21 23 26 29
DCF60x-0075-y1 75 75 61 61 31 35 39 44
DCF60x-0100-y1 100 100 82 82 42 47 52 58
DCF60x-0200-y1 200 180 163 147 83 84 104 104
DCF60x-0350-y1 350 315 286 257 145 146 182 183
DCF60x-0450-y1 450 405 367 330 187 188 234 235
DCF60x-0520-y1 520 470 424 384 216 219 270 273
Table 2.2/3: Table of DCS 600 / DCF 600 units - construction types C1, C2, A5
Converter type y→ y=4 (400 V) y=5 (500 V) y=6 (600 V) y=7 (690 V) y=8 (790 V) y=9 (1000V) y=1 (1190V)
IDC [A] IAC [A] P [kW] P [kW] P [kW] P [kW] P [kW] P [kW] P [kW] ➀
2-Q converters
DCS601-1903-y1 1900 1550 1740
DCS601-2053-y1 2050 1673 1190 1430 1640
DCS601-2503-y1 2500 2040 1160 1450 1750 2000 2300
DCS601-3003-y1 3000 2448 1395 1740 2090 2400 2750
DCS601-2053-y1 2050 1673 2390
DCS601-2603-y1 2600 2121 3030 on request
DCS601-3303-y1 3300 2693 1540 1925 2310 2660 3040 3850 on request
DCS601-4003-y1 4000 3264 1870 2330 2800 3220 3690 4670 on request
DCS601-4803-y1 4800 3917 3360 3860 4420
DCS601-5203-y1 5200 4243 2430 3030
4-Q converters
DCS602-1903-y1 1900 1550 1560
DCS602-2053-y1 2050 1673 1070 1280 1470
DCS602-2503-y1 2500 2040 1040 1300 1560 1800 2060
DCS602-3003-y1 3000 2448 1250 1560 1880 2150 2470
DCS602-2053-y1 2050 1673 2390
DCS602-2603-y1 2600 2121 3030 on request
DCS602-3303-y1 3300 2693 1375 1720 2060 2370 2720 3440 on request
DCS602-4003-y1 4000 3264 1670 2080 2500 2875 3290 4170 on request
DCS602-4803-y1 4800 3917 3000 3450 3950
DCS602-5203-y1 5200 4243 2170 2710
➀ These converters are equipped with additional components. More information on request
Table 2.2/4: Table of DCS 600 units - construction type A6 / A7
Higher currents up to 15,000 A are achieved by
paralleling converters - information on request.
II F 2-5
3ADW000072R0501_DCS600_System_description_e_e
Construction type C1 Construction type C2 Construction type A5 Construction type A6 Construction type A7
left busbar connection
Converter type ➁ Dimensions Weight Clearances Construct. Power loss Fan Semiconductor
HxWxD top/bottom/side type at 500V connection Fuses
[mm] [kg] [mm] PV [kW]
DCS60x-0025-y1 420x273x195 7.1 150x100x5 C1a < 0.2 230 V/1 ph external
DCS60x-0050-y1 420x273x195 7.2 150x100x5 C1a < 0.2 230 V/1 ph external
DCS60x-0050-61 420x273x195 7.6 150x100x5 C1a - 230 V/1 ph external
DCS60x-0075-y1 420x273x195 7.6 150x100x5 C1a < 0.3 230 V/1 ph external
DCS60x-0100-y1 469x273x228 11.5 250x150x5 C1b < 0.5 230 V/1 ph external
DCS60x-0110-61 469x273x228 11.5 250x150x5 C1b - 230 V/1 ph external
DCS60x-0140-y1 469x273x228 11.5 250x150x5 C1b < 0.6 230 V/1 ph external
DCS60x-0200-y1 505x273x361 22.3 250x150x5 C2a < 0.8 230 V/1 ph external
DCS60x-0250-y1 505x273x361 22.3 250x150x5 C2a < 1.0 230 V/1 ph external
DCS60x-0270-61 505x273x361 22.8 250x150x5 C2a - 230 V/1 ph external
DCS60x-0350-y1 505x273x361 22.8 250x150x5 C2a < 1.3 230 V/1 ph external
DCS60x-0450-y1 505x273x361 28.9 250x150x10 C2a < 1.5 230 V/1 ph external
DCS60x-0520-y1 505x273x361 28.9 250x150x10 C2a < 1.8 230 V/1 ph external
DCS60x-0680-y1 652x273x384 42 250x150x10 C2b < 1.6 230 V/1 ph external
DCS60x-0820-y1 652x273x384 42 250x150x10 C2b < 2.0 230 V/1 ph external
DCS60x-1000-y1 652x273x384 42 250x150x10 C2b < 2.5 230 V/1 ph external
II F 2-6
3ADW000072R0501_DCS600_System_description_e_e
2.3 DCS 600 Overload Capability
To match a drive system’s components as efficiently as possible to the driven
machine’s load profile, the armature power converters DCS 600 can be dimensio-
ned by means of the load cycle. Load cycles for driven machines have been defi-
ned in the IEC 146 or IEEE specifications, for example.
The currents for the DC I to DC IV types of load (see diagram on the following page) for the power converter
modules are listed in the table below.
Unit type IDC I IDC II IDC III IDC IV
contin- 100 % 150 % 100 % 150 % 100 % 200 %
uous 15 min 60 s 15 min 120 s 15 min 10 s
400 V / 500 V [A] [A] [A] [A]
DCS 60x-0025-41/51 25 24 36 23 35 24 48
DCS 60x-0050-41/51 50 44 66 42 63 40 80
DCS 60x-0075-41/51 75 60 90 56 84 56 112
DCS 60x-0100-41/51 100 71 107 69 104 68 136
DCS 601-0140-41/51 125 94 141 91 137 90 180
DCS 602-0140-41/51 140 106 159 101 152 101 202
DCS 601-0200-41/51 180 133 200 132 198 110 220
DCS 602-0200-41/51 200 149 224 146 219 124 248
DCS 601-0250-41/51 225 158 237 155 233 130 260
DCS 602-0250-41/51 250 177 266 173 260 147 294
DCS 601-0350-41/51 315 240 360 233 350 210 420
DCS 602-0350-41/51 350 267 401 258 387 233 466
DCS 601-0450-41/51 405 317 476 306 459 283 566
DCS 602-0450-41/51 450 352 528 340 510 315 630
DCS 601-0520-41/51 470 359 539 347 521 321 642
DCS 602-0520-41/51 520 398 597 385 578 356 712
DCS 601-0680-41/51 610 490 735 482 732 454 908
DCS 602-0680-41/51 680 544 816 538 807 492 984
DCS 601-0820-41/51 740 596 894 578 867 538 1076
DCS 602-0820-41/51 820 664 996 648 972 598 1196
DCS 601-1000-41/51 900 700 1050 670 1005 620 1240
DCS 602-1000-41/51 1000 766 1149 736 1104 675 1350
DCS 60x-1203-41/51 1200 888 1332 872 1308 764 1528
DCS 60x-1503-41/51 1500 1200 1800 1156 1734 1104 2208
DCS 60x-2003-41/51 2000 1479 2219 1421 2132 1361 2722
DCS 60x-2053-51 2050 1550 2325 1480 2220 1450 2900
DCS 601-2503-41/51 2500 1980 2970 1880 2820 1920 3840
DCS 602-2503-41/51 2500 2000 3000 1930 2895 1790 3580
DCS 601-3003-41/51 3000 2350 3525 2220 3330 2280 4560
DCS 602-3003-41/51 3000 2330 3495 2250 3375 2080 4160
DCS 60x-3303-41/51 3300 2416 3624 2300 3450 2277 4554
DCS 60x-4003-41/51 4000 2977 4466 2855 4283 2795 5590
DCS 60x-5203-41/51 5200 3800 5700 3669 5504 3733 7466
600 V / 690 V
DCS 60x-0050-61 50 44 66 43 65 40 80
DCS 601-0110-61 100 79 119 76 114 75 150
DCS 602-0110-61 110 87 130 83 125 82 165
DCS 601-0270-61 245 193 290 187 281 169 338
DCS 602-0270-61 270 213 320 207 311 187 374
DCS 601-0450-61 405 316 474 306 459 282 564
DCS 602-0450-61 450 352 528 340 510 313 626
DCS 60x-0903-61/71 900 684 1026 670 1005 594 1188
DCS 60x-1503-61/71 1500 1200 1800 1104 1656 1104 2208
DCS 601-2003-61/71 2000 1479 2219 1421 2132 1361 2722
DCS 60x-2053-61/71 2050 1520 2280 1450 2175 1430 2860
DCS 601-2503-61/71 2500 1940 2910 1840 2760 1880 3760
DCS 602-2503-61/71 2500 1940 2910 1870 2805 1740 3480
DCS 601-3003-61/71 3000 2530 3795 2410 3615 2430 4860
DCS 602-3003-61/71 3000 2270 3405 2190 3285 2030 4060
DCS 60x-3303-61/71 3300 2416 3624 2300 3450 2277 4554
DCS 60x-4003-61/71 4000 3036 4554 2900 4350 2950 5900
DCV 60x-4803-61/71 4800 3734 5601 3608 5412 3700 7400
790 V
DCS 60x-1903-81 1900 1500 2250 1430 2145 1400 2800
DCS 601-2503-81 2500 1920 2880 1820 2730 1860 3720
DCS 602-2503-81 2500 1910 2865 1850 2775 1710 3420
DCS 601-3003-81 3000 2500 3750 2400 3600 2400 4800
DCS 602-3003-81 3000 2250 3375 2160 3240 2000 4000
DCS 60x-3303-81 3300 2655 3983 2540 3810 2485 4970
DCS 60x-4003-81 4000 3036 4554 2889 4334 2933 5866
DCS 60x-4803-81 4800 3734 5601 3608 5412 3673 7346 Table 2.3/1:
1000 V Power converter module
DCS 60x-2053-91 2050 1577 2366 1500 2250 1471 2942 currents with corresponding
DCS 60x-2603-91 2600 2000 3000 1900 2850 1922 3844 load cycles.
DCS 60x-3303-91 3300 2551 3827 2428 3642 2458 4916 The characteristics are
DCS 60x-4003-91 4000 2975 4463 2878 4317 2918 5836 based on an ambient tem-
1190 V Data on request perature of max. 40°C and
x=1 → 2-Q; x=2 → 4-Q an elevation of max. 1000 m
a.s.l.
II F 2-7
3ADW000072R0501_DCS600_System_description_e_e
Types of load
15 min
DC II IDC II for 15 min and extruders, conveyor belts
1,5 * IDC II for 60 s 150% 100%
DC III * IDC III for 15 min and extruders, conveyor belts 15 min
1,5 * IDC III for 120 s
150% 100%
* Load cycle is not identical with menu item Duty cycle in DCSize !
Table 2.3/2: Definition of the load cycles
II F 2-8
3ADW000072R0501_DCS600_System_description_e_e
2.4 Field Supply
General data
• Currents from 6 to 520 A. All field power converters (except for the SDCS-FEX-
• Minimum field current monitor. 1) are controlled by the armature converter via a serial
• Integrated or external field power converter or in a link with a speed of 62.5 kBaud. The link serves to
completely separate cabinet. parameterize, control and diagnose the field power
• 2-phase or 3-phase model. converter and thus provides an exact control. Moreo-
• Fully digital control (except SDCS-FEX-1). ver, it enables you to control an internal (SDCS-FEX-
2A) and an external (DCF 601/602/503A/504A) or
We recommend integrating an autotransformer in the
two external field supply units (2 x DCF 601/602/
field power converter's supply to adjust the AC input
503A/504A). The respective software function required
voltage to the field voltage, to reduce the voltage and
is available in every DC power converter.
current ripple of the field.
SDCS-FEX-1 SDCS-FEX-2A
• Diode bridge. • Half controlled thyristor/diode bridge (1-Q)
• 6 A rated current. • Microprocessor control, with the electronic system
• Internal non adjustable minimum field current being supplied by the armature converter.
monitor. • Construction and components have been designed
• Construction and components have been designed for an insulation voltage of 600 V AC.
for an insulation voltage of 600 V AC. • Fast-response excitation is possible with an appro-
• Output voltage UA: priate voltage reserve; de-excitation takes place by
field time constant.
100% + TOL
U A = UV * * 0.9 • Output voltage UA:
100%
100% + TOL
TOL = tolerance of line voltage in % U A = UV * * 0.9
UV = Line voltage 100%
TOL = tolerance of line voltage in %
• Recommendation:
UV = Line voltage
Field voltage ~ 0.9 * UV
• Recommendation:
Field voltage 0.6 to 0.8 * UV
SDCS-FEX-1
SDCS-FEX-2A
II F 2-9
3ADW000072R0501_DCS600_System_description_e_e
DCF 503A DCF 600
• Half controlled thyristor/diode bridge (1-Q). This field power converter is used mainly for armature
• Microprocessor control with the control electronics converters with rated currents of 2050 to 5200 A. It is
being supplied separately (115...230 V/1-ph). a modified armature circuit converter.
• Construction and components have been designed • Output voltage UA respectively Udmax 2-Q :
for an insulation voltage of 690 V AC. see table 2.2/1.
• Output voltage UA: • Recommendation:
Field voltage 0.5 to 1.1 * UV
100% + TOL
U A = UV * * 0.9 • The three-phase field supply converters DCF 600
100% needs a separate active overvoltage protection unit
TOL = tolerance of line voltage in % DCF 506 for protecting the power part against too
UV = Line voltage
high voltages.
• Recommendation: The overvoltage protection unit DCF 506 is suitable
Field voltage 0.6 to 0.8 * UV for 2-Q converters DCF 601 and for 4-Q converters
DCF 602.
DCF 504A
Assignment Field supply converter to Overvol-
• Fully controlled antiparallel thyristor bridges (4-Q).
• With this unit fast response excitation / de-excita- tage protection unit
tion and field reversal is possible. For fast response
excitation an appropriate voltage reserve is neces- Field supply converter Overvoltage Protection
sary. for motor fields
In steady-state condition, the fully controlled bridge
DCF60x-0025-51
runs in half controlled mode to keep the voltage ... DCF506-0140-51
ripple as low as possible. With a fast changing field DCF60x-0140-51
current, the bridge runs in fully controlled mode.
• Same design as DCF 503A DCF60x-0200-51
... DCF506-0520-51
DCF60x-0520-51
➀ Current reduction see also 2.1 Environmental conditions Fig.: 2.1/1 and 2.1/2
Table 2.4/1: Data field converter units
II F 2-10
3ADW000072R0501_DCS600_System_description_e_e
2.5 Options for DCS 600 MultiDrive converter modules
In-/output signals
The converter can be connected in 4 different ways to addition to this an extension of I/O´s by SDCS-IOE 1
a control unit via analogue/digital links. Only one of is possible.
the four choices can be used at the same time. In
SDCS-CON-2 SDCS-CON-2
X17: X17:
1 2 1 X3: X1:
SDCS-IOB-2
Fig. 2.5/1: I/O´s via SDCS-CON-2 Fig. 2.5/2: I/O´s via SDCS-CON-2 and SDCS-IOB-2
Analogue I/O´s: standard Analogue I/O´s: standard
Digital I/O´s: not isolated digital I/O´s: all isolated by means of
Encoder input: not isolated optocoupler/relay; the signal
status is indicated by LED
SDCS-CON-2 SDCS-CON-2
X17: X17:
X6: X7:
3 3 4
Fig. 2.5/3: I/O´s via SDCS-CON-2 and SDCS-IOB-3 Fig. 2.5/4: I/O´s via SDCS-IOB-2 and SDCS-IOB-3
Analogue I/O´s: more input capacity Analogue I/O´s: more input capacity
digital I/O´s: not isolated digital I/O´s: all isolated by means of
encoder input: isolated optocoupler/relay; the signal
current source for: PT100/PTC element status is indicated by LED
current source for: PT100/PTC element
II F 2-11
3ADW000072R0501_DCS600_System_description_e_e
Description of I/O signals SDCS-CON-2 Description of I/O signals SDCS-IOB-2x & SDCS-IOB-3
Mechanical system integrated in control board Mechanical system always external, outside the module
Terminals Terminals
Screw type terminals for finely stranded wires up to 2.5 mm2 Screw type terminals for finely stranded wires up to 2.5 mm2
Functionality Functionality of SDCS-IOB-3
1 tacho input 1 tacho input
Resolution: 12 bit + sign; differential input; common mode range ±20 V Resolution: 12 bit + sign; differential input; common mode range ±20 V
3 ranges from 8...30...90...270 VDC with nmax Range 8 V- with nmax; if higher tacho voltages are in use tacho adaptation
board PS 5311 is needed.
4 analogue inputs 4 analogue inputs
Range -10...0...+10 V, 4...20 mA, 0...20 mA All as differential inputs; time constant of smoothing capacitor ≤2 ms
All as differential inputs; RE = 200 kΩ; time constant of smoothing Input 1: Range -10 V...0...+10 V; -20 mA...0...+20 mA; 4... 20 mA
capacitor ≤2 ms unipolar; RE = 200 kΩ/ 500Ω/ 500Ω; Resolution: 12 bit + sign; common
Input 1: Resolution: 12 bit + sign; common mode range ±20 V mode range ±20 V
Inputs 2, 3, 4: Resolution: 11 bit + sign; common mode range ±40 V Inputs 2+3: Range see input 1, in addition -1 V...0...+1 V
Current source for PTC element evaluation via jumper and input 2 RE = 200 kΩ/ 500Ω/ 500Ω/ 20kΩ; Resolution: 11 bit + sign; common
mode range with -1 V...0...+1 V range ±10 V, otherwise ±40 V
Input 4: Range see input 1
RE = 200 kΩ/ 500Ω/ 500Ω; Resolution: 11 bit + sign; common mode
range ±40 V
Residual current detection in combination with analogue input 4
(sum of phase currents ≠ 0)
2 outputs 2 outputs
+10 V, -10 V, IA ≤ 5 mA; sustained short-circuit-proof +10 V, -10 V; IA ≤ 5 mA; sustained short-circuit-proof
voltage supply for reference potentiometer voltage supply for reference potentiometer
1 analogue output 1 analogue output
bipolar current actual - from power section; decoupled Bipolar current actual - from power section; decoupled
IdN = ±3 V; IA≤ 5 mA, short-circuit-proof IdN = ±3 V (at gain = 1); IA≤ 5 mA; UAmax = 10 V; gain can be adjusted by
means of a potentiometer between 0.5 and 5; short-circuit-proof
2 analogue outputs 2 analogue outputs
Range -10...0...+10 V; IA ≤ 5 mA Range -10...0...+10 V; IA ≤ 5 mA; short-circuit-proof
Output signal and scaling can be selected by means of software Output signal and scaling can be selected by means of software
Resolution: 11 bit + sign Resolution: 11 bit + sign
Current source for PT 100 or PTC element
IA = 5 mA / 1.5 mA
1 pulse generator input 1 pulse generator input
Voltage supply for 5 V/12 V/24 V pulse generators (sustained short- Voltage supply, output current, input range: see SDCS-CON-2
circuit-proof) Inputs electrically isolated from 0 V (housing) by means of optocoupler
Output current with 5 V: IA ≤ 0.25 A and voltage source.
12 V: IA ≤ 0.2 A
24 V: IA ≤ 0.2 A
Input range: 12 V/24 V: asymmetrical and differential
5 V: differential
Pulse generator as 13 mA current source: differential
Line termination (impedance 120Ω), if selected
max. input frequency ≤300 kHz
Functionality of SDCS-IOB-2x
3 different designs available:
SDCS-IOB-21 inputs for 24...48 V DC; RE = 4.7 kΩ
SDCS-IOB-22 inputs for 115 V AC; RE = 22 kΩ
SDCS-IOB-23 inputs for 230 V AC; RE = 47 kΩ
Terminals
Screw type terminals up to 4 mm2
8 digital inputs 8 digital inputs
The functions can be selected by means of software. The functions can be selected by means of software.
Input voltage: 0...8 V ⇒ "0 signal", 16...60 V ⇒ "1 signal" The signal status is indicated by LED.
Time constant of smoothing capacitor: 10 ms All isolated by means of optocouplers.
RE = 15 kΩ Input voltage: IOB-21:0...8 V ⇒ "0 signal", 18...60 V ⇒"1 sig."
The signal refers to the unit housing potential. IOB-22:0...20 V ⇒ "0 signal", 60...130 V ⇒"1 sig."
Auxiliary voltage for digital inputs: +48 V DC, ≤ 50 mA, sustained short- IOB-23:0...40 V ⇒ "0 signal", 90...250 V ⇒"1 sig."
circuit-proof Filter time constant: 10 ms (channels 1...6); 2 ms (channels 7+8)
Auxiliary voltage for digital inputs: +48 V DC; ≤ 50 mA; sustained short-
circuit-proof; referenced to the unit housing potential.
7+1 digital outputs 8 digital outputs
The function can be selected by means of software. The functions can be selected by means of software.
7 outputs: relay driver with free-wheeling diode, total current limitation The signal status is indicated by LED.
≤ 160 mA; short-circuit-proof. 6 of them potential isolated by relay (N.O. contact: AC: ≤250 V/ ≤3 A /
1 relay output - on power board SDCS-POW-1 (N.O. contact: DC: ≤24 V/ ≤3 A or ≤115/230 V/ ≤0.3 A), protected by VDR component.
AC: ≤250 V/ ≤3 A / DC: ≤24 V/ ≤3 A or ≤115/230 V/ ≤0.3 A) protected 2 of them potential isolated by optocoupler, protected by zener diode
by VDR component. (open collector) 24 V DC external, IA ≤ 50 mA.
II F 2-12
3ADW000072R0501_DCS600_System_description_e_e
Serial interfaces
There are various serial interface options available for Different SDCS-AMC 2 boards are available to adapt
operation, commissioning, diagnosis and controlling. optical cables, cable length and serial interfaces. The
For the control and display panel CDP 312 are serial different SDCS-AMC 2 boards are equipped with 10
connections X33:/X34: on the SDCS-CON-2 availa- or 5 Mbaud optical transmitter and receiver devices.
ble. Three additional serial interfaces are available on A few basic rules must be considered:
the SDCS-AMC-DC 2 board. • Never connect 5 Mbaud and 10 Mbaud devices.
These interfaces use plastic or HCS optical fibres. • 5 Mbaud can handle only plastic fibre optic.
Channel 3 is used for drive/PC interfacing. Channel 0 • 10 Mbaud can handle plastic or HCS cable.
for fieldbus module interfacing or communication to • The branching unit NDBU 95 extends the maxi-
the overriding control system. Channel 2 is used for mum distance.
Master-Follower link or for I/O extension. All three • The maximum distance and suitable configuration
serial interfaces are independent from each other. can be found in the manual Configuration Instruc-
tions NDBU 85/95; Doc no.: 3ADW000100.
CDP 312
Remark: SDCS-CON-2
SDCS-AMC-DC Classic 2
Fieldbus modules Nxxx Power supply
D400
D200
SDCS-AMC-DC 2
SDCS-AMC-DC Classic 2 PE
X2 RXD
SH SHF DG D(N) D(P)
CH 0
CH 2
CH 3
xxxxxxxx
ADAPTER
XM IT
OFF
RxD
RxD
RxD
TxD
TxD
TxD
SDCS-AMC-DC 2 board. X1 ERRO R
to the PLC
X33: electrical
X16:
FCI X34: connection
≤3m Dcs6_com1b.dsf
AC80
optical fibre
PC
AC800M
Interface
- Master-Follower link
Control Operation
Fig. 2.5/5: Options for serial communication
R R F
D U L
0 50 100 150
1 Y N T
SDCS-CON-2
X33:/
X34:
R
D
R
U
F
L
0
NLMD100
50 150
1 Y N T
NDPI
CDP 312
SDCS-CON-2
X33:/
X34:
R
D
R
U
F
L
0
NLMD100
50 150
1 Y N T
II F 2-13
3ADW000072R0501_DCS600_System_description_e_e
Panel (control and display panel) Features
The CDP 312 control and display panel communicates • 16 membrane pushbuttons in three function groups
with the power converter via a serial connection in • LCD display has four lines with 20 characters each
accordance with the RS 485 standard at a transmission • Language: English
rate of 9.6 kBaud. It is an option for the converter unit. • Options for the CDP 312:
After completion of commissioning, the panel is not – cable, separated from the power converter for
necessarily required for diagnostic. The basic unit has a utilization; 3 m long
7-segment display indicating errors. – kit for mounting the panel in the switchgear
cubicle door
Parameters Function
For selecting and adjusting Selects the “functions” operating mode; can be used
all parameters and signals. to perform special functions such as uploading and
0 L 0,0 rpm 00 downloading of parameter sets.
Group
and name 17 RAMP GENERATOR
Subgroup 08 ACCEL 1
and name Status row 0 L 0,0 rpm 00
20.0 s
Value Functions to be UPLOAD <==
selected DOWNLOAD ==>
Display contrast CONTRAST
setting
Actual
Selects the display of feedback values plus the
signal group and the error memory group. Drive
for extensions
ID number Control Speed Main contactor Run status
of the location reference status 1 = Run
drive L = local rpm 0 = open 0 = Stop
selected = remote 1 = closed
Enter
is used in the following modes:
Status row 0 L 0,0 rpm 00 Parameter setting: enter new parameter value
Actual signal SPEEED ACT 0,0 rpm Actual value
name and value CONV CUR 0 A signal display: enter the current signal selec-
Cursor shows U ARM ACT 0 V tion mode
the row selected Signal selection: accept selection and return to
the feedback value signal dis-
play mode
Twin arrow keys
are used to change the group. In the parameter and Arrow keys
reference presetting modes, you can alter the param- are used to select parameters within a group. You al-
eter value or the reference setting ten times faster by ter the parameter value or the reference setting in
means of the twin arrow keys than by means of the the parameter and reference presetting modes. In
single arrow key. the feedback signal display mode, you select the line
you want.
Local/Remote
is used to select local (control
panel) or remote control. Start
starts the drive in local mode.
Reset
Fault acknowledge key. Stop
1 = last fault 0 L 0,0 rpm 00 shuts the drive down if you are in local mode.
2 = last-but-one fault
99 = last fault 1 LAST FAULT
Name of Fault Emergency stop
or alarm
3212:59:35:56 Reference
Total time after
switch-on
is used to activate the reference presetting mode.
HHHH:MM:SS.ss
On Off
in local mode switches the main contactor on. in local mode switches the main contactor off.
II F 2-14
3ADW000072R0501_DCS600_System_description_e_e
Operation by PC Drive control
Components required: Components required:
• Plastic optical fibre for distances up to 20 m. • Plastic optical fibre for distances up to 15 m.
• Network up to 200 drives (same as for ACS 600). • Field bus module Nxxx-xx
• HCS optical fibre cable up to 200 m. • FCI (CI810)
See separate manual Configuration Instructions • AC80 (PM825)
NDBU 85/95; Doc no.: 3ADW000100. • AC800 M
Functionality:
• DriveWindow software package➀ for commission- Functionality:
ing, diagnosis, maintenance and trouble shooting; Depends on the used module, interface e.g. to:
structure of connections see Technical Data; Doc • PROFIBUS with NPBA-12
no.: 3ADW000165. • MODBUS with NMBA-01
System requirements/recommendation: • AF100 with FCI (CI810)
• PC (IBM-compatible) with 486 processor or higher • AC80 (PM825) or
(min. 50 MHz). • AC800 M
• 8 MB RAM. • further modules on request
• DOS version 5.0 or later. You will find more detailed information on data ex-
• Windows NT4.0, WIN 2000, WIN XP change in the specific PLC or fieldbus module docu-
• VGA monitor. mentation.
• CD-ROM drive.
• PCMCIA slot or PCI/PCMCIA bridge.
In addition to the options provided by the CDP 312
control and display panel, there are further functions
available, and these are described on the following page.
II F 2-15
3ADW000072R0501_DCS600_System_description_e_e
Operation by PC (continued)
Features
• Easy-to-use tool for com-
missioning and mainte-
nance.
• Several drives connected
and monitored at the same
time.
• Monitor, edit or save sig-
nals and parameters, clear
graphical presentation.
• High speed communica-
tion between PC and drive
• Versatile back-up func-
tions.
II F 2-16
3ADW000072R0501_DCS600_System_description_e_e
2.6 Options
Line reactors
for armature (DCS 60x) and field
(DCF 60x) supply
Line Configuration C
If an isolation transformer is used, it is
Connecting possible to comply with certain con-
point
necting conditions per Configuration
B without using an additional line reac-
tor. The condition described in Con-
figuration A will then likewise be satis-
fied, since the uk is >1 %.
II F 2-17
3ADW000072R0501_DCS600_System_description_e_e
Line reactors L1
DCS Type Line choke Design Line choke Design
400V-690V type for Fig. type for Fig.
50/60 Hz configur. A configur. B
DCS60x-0025-41/51 ND01 1 ND401 4
DCS60x-0050-41/51 ND02 1 ND402 4
DCS60x-0050-61 ND03 1 on request -
DCS60x-0075-41/51 ND04 1 ND403 5
DCS60x-0100-41/51 ND06 1 ND404 5
DCS60x-0110-61 ND05 1 on request -
DCS60x-0140-41/51 ND06 1 ND405 5
DCS60x-0200-41/51 ND07 2 ND406 5
DCS60x-0250-41/51 ND07 2 ND407 5
DCS60x-0270-61 ND08 2 on request -
DCS60x-0350-41/51 ND09 2 ND408 5
DCS60x-0450-41/51 ND10 2 ND409 5
DCS60x-0450-61 ND11 2 on request -
DCS60x-0520-41/51 ND10 2 ND410 5
DCS60x-0680-41/51 ND12 2 ND411 5
DCS601-0820-41/51 ND12 2 ND412 5
DCS602-0820-41/51 ND13 3 ND412 5
DCS60x-1000-41/51 ND13 3 ND413 5
DCS60x-0903-61/71 ND13 3 on request -
DCS60x-1203-41/51 ND14 3 on request -
DCS60x-1503-41/51/61/71 ND15 3 on request -
DCS60x-2003-41/51 ND16 3 on request -
DCS601-2003-61/71 ND16 * 3 on request -
* with forced cooling
Table 2.6/1: Line reactors (for more information see publication Technical Data)
Fig. 4 Fig. 5
II F 2-18
3ADW000072R0501_DCS600_System_description_e_e
Aspects of fusing for armature circuits and field supplies of DC drives
Unit configuration Due to cost saving standard fuses are used instead of the
Protection elements such as fuses or overcurrent trips more expensive semiconductor fuses at some applica-
are used whenever overcurrents cannot entirely be tions. Under normal and stable operating conditions,
ruled out. In some configurations, this will entail the this is understandable and comprehensible, as long as
following questions: firstly, at what point should which fault scenarios can be ruled out.
protective element be incorporated? And secondly, in In the event of a fault , however, the saving may cause
the event of what faults will the element in question very high consequential costs. Exploding power semi-
provide protection against damage? conductors may not only destroy the power converter,
but also cause fires.
AC supply: public mains / plant's mains
Cabinet Adequate protection against short-circuit and earth
fault, as laid down in the EN50178 standard, is possi-
3 2
M ble only with appropriate semiconductor fuses.
.
. .
. .
4-Q resp.
2-Q non-regen. 2-Q regenerative
Semiconductor
fuses
M M
II F 2-19
3ADW000072R0501_DCS600_System_description_e_e
Conclusion for the field supply
ND30 /
F3.3 built-in
F3.1
2
FF_ASP_b.dsf
II F 2-20
3ADW000072R0501_DCS600_System_description_e_e
Semiconductor type F1 fuses and fuse holders for AC and DC power lines
(DCS 601 /DCS 602 - DCF 601/DCF 602)
The converter units are subdivided into two Type of converter Type Fuse holder
groups: DCS60x-0025-41/51 170M 1564 OFAX 00 S3L
– Unit sizes C1 and C2 with rated currents DCS60x-0050-41/51 170M 1566 OFAX 00 S3L
up to 1000 A require external fuses. DCS60x-0050-61 170M 1566 OFAX 00 S3L
– In unit sizes A5, A6 and A7 with rated DCS60x-0075-41/51 170M 1568 OFAX 00 S3L
DCS60x-0100-51 170M 3815 OFAX 1 S3
currents of 900 A to 5200 A, the semicon- DCS60x-0110-61 170M 3815 OFAX 1 S3
ductor fuses are installed internally (no DCS60x-0140-41/51 170M 3815 OFAX 1 S3
additional external semiconductor fuses DCS60x-0200-41/51 170M 3816 OFAX 1 S3
are needed). DCS60x-0250-41/51 170M 3817 OFAX 1 S3
DCS60x-0270-61 170M 3819 OFAX 1 S3
The table on the right assigns the AC fuse DCS60x-0350-41/51 170M 5810 OFAX 2 S3
type to the converter type. In case the con- DCS60x-0450-41/51/61 170M 6811 OFAS B 3
verter should be equipped with DC fuses DCS60x-0520-41/51 170M 6811 OFAS B 3
according to the hints use the same type of DCS60x-0680-41/51 170M 6813 OFAS B 3
DCS60x-0820-41/51 170M 6813 OFAS B 3
fuse used on the AC side now in the plus and DCS60x-1000-41/51 170M 6166 3x 170H 3006
minus line. Blade type fuses are used for all
the converters construction type C1 and C2 Table 2.6/2: Fuses and fuse holders (details see Technical Data)
except the biggest one.
II F 2-21
3ADW000072R0501_DCS600_System_description_e_e
Commutating reactor
Converter Reactor
≤ 500 V; 50/60 Hz
SDCS-FEX-2A ND 30
II F 2-22
3ADW000072R0501_DCS600_System_description_e_e
II F 2-23
3ADW000072R0501_DCS600_System_description_e_e
EMC filters
You will find further in- The paragraphs below describe selection of the electri- • the product's actual emissions
formation in publica- cal components in conformity with the EMC Guide- The EMC Guideline expects EMC to be taken into
tion: line. account when a product is being developed; however,
Technical Guide EMC cannot be designed in, it can only be quantita-
chapter: EMC Com- The aim of the EMC Guideline is, as the name implies, tively measured.
pliant Installation and to achieve electromagnetic compatibility with other Note on EMC conformity
Configuration for a products and systems. The guideline ensures that the The conformity procedure is the responsibility of both
Power Drive System emissions from the product concerned are so low that the power converter's supplier and the manufacturer of
they do not impair another product's interference the machine or system concerned, in proportion to
immunity. their share in expanding the electrical equipment in-
In the context of the EMC Guideline, two aspects must volved.
be borne in mind:
• the product's interference immunity
First environment (residential area with light industry) with restricted distribution
satisfied
Residential area Supply transformer for a residential Light industry Supply transformer for a residential
area (rating normally ≤ 1,2 MVA) area (rating normally ≤ 1.2 MVA)
Residential area
Earthed
neutral
Earthed
neutral Earthed public 400-V Earthed public 400-V Earthed public 400-V
network with neutral network with neutral network with neutral
conductor conductor conductor
To other loads which have to be protected from the system disturbances caused by
To other loads which have to be protected from the system disturbances caused by
power converters (HF interference and commutation notches)
Line reactor +
Line reactor Y-capacitor Line reactor Line reactor
alternative
M M M M M M M M
Operation at public An isolating transformer Operation at public Operation at public An isolating transformer
low-voltage network with an earthed screen low-voltage network low-voltage network with an earthed screen
together with other and earthed iron core together with other together with other and earthed iron core
loads of all kinds. renders mains filter and loads of all kinds. loads of all kinds. renders mains filter and
line reactor superfluous. line reactor superfluous.
II F 2-24
3ADW000072R0501_DCS600_System_description_e_e
For compliance with the protection objectives of the For emitted interference, the following apply:
German EMC Act (EMVG) in systems and machines, EN 61000-6-3 Specialised basic standard for emissions in light industry can
the following EMC standards must be satisfied: be satisfied with special features (mains filters, screened power
cables) in the lower rating range *(EN 50081-1).
Product Standard EN 61800-3
EN 61000-6-4 Specialised basic standard for emissions in industry
EMC standard for drive systems (PowerDriveSys-
*(EN 50081-2)
tem), interference immunity and emissions in resi-
dential areas, enterprise zones with light industry For interference immunity, the following apply:
and in industrial facilities. EN 61000-6-1 Specialised basic standard for interference immunity in residen-
tial areas *(EN 50082-1)
This standard must be complied with in the EU for
EN 61000-6-2 Specialised basic standard for interference immunity in indus-
satisfying the EMC requirements for systems and
try. If this standard is satisfied, then the EN 61000-6-1 standard
machines! is automatically satisfied as well *(EN 50082-2).
Standards Classification
Second environment (industry) with restricted distribution EN 61800-3 The following overview
utilises the terminology
Not applicable EN 61000-6-3 and indicates the action
required in accordance
satisfied on customer's request satisfied EN 61000-6-4
with Product Standard
EN 61000-6-2 EN 61800-3
satisfied For the DCS 500B series,
EN 61000-6-1
the limit values for emit-
Medium-voltage network Medium-voltage network ted interference are complied with,
Industrial zone
Supply transformer for a
Industrial zone Converter provided the action indicated is car-
residential area (rating transformer
normally ≤ 1.2 MVA) with earthed ried out. This action is based on the
Converter
transformer
term Restricted Distribution used in
Earthed iron core the standard (meaning a sales chan-
neutral Earthed 400-V network
(and earthed I > 400 A
with neutral conductor;
screen where and/or nel in which the products concerned
appropriate)
3~ ≤ 400 A U > 500 V can be placed in the stream of com-
merce only by suppliers, customers
or users which individually or jointly
possess technical EMC expertise).
alternative
alternative
alternative
II F 2-25
3ADW000072R0501_DCS600_System_description_e_e
Filter in a grounded line (earthed TN or TT
network)
The filters are suitable for grounded lines only, for
example in public European 400 V lines. According to
EN 61800-3 filters are not needed in insulated indus-
trial lines with own supply transformers. Furthermore
they could cause safety risks in such floating lines (IT
networks).
Converter IDC [A] Const. Filter type for y=4 Filter type for y= 5 Filter type for y=6 or 7
type
DCS60x-0025-y1 25A C1a NF3-440-25 NF3-500-25 ---
DCS60x-0050-y1 50A C1a NF3-440-50 NF3-500-50 ---
DCS60x-0075-y1 75A C1a NF3-440-64 NF3-500-64 ---
DCS60x-0100-y1 100A C1b NF3-440-80 NF3-500-80 ---
DCS60x-0140-y1 140A C1b NF3-440-110 NF3-500-110 ---
DCS60x-0200-y1 200A C2a NF3-500-320 NF3-500-320 ---
DCS60x-0250-y1 250A C2a NF3-500-320 NF3-500-320 ---
DCS60x-0270-61 250A C2a NF3-500-320 NF3-500-320 NF3-690-600 ➀
DCS60x-0350-y1 350A C2a NF3-500-320 NF3-500-320 ---
DCS60x-0450-y1 450A C2a NF3-500-600 NF3-500-600 NF3-690-600 ➀
DCS60x-0520-y1 520A C2a NF3-500-600 NF3-500-600 ---
DCS60x-0680-y1 680A C2b NF3-500-600 NF3-500-600 ---
DCS601-0820-y1 740A C2b NF3-500-600 NF3-500-600 ---
DCS602-0820-y1 820A C2b NF3-690-1000 ➀ NF3-690-1000 ➀ ---
DCS60x-1000-y1 1000A C2b NF3-690-1000 ➀ NF3-690-1000 ➀ ---
DCS60x-0903-y1 900A A5 NF3-690-1000 ➀ NF3-690-1000 ➀ NF3-690-1000 ➀
DCS60x-1203-y1 1200A A5 NF3-690-1000 ➀ NF3-690-1000 ➀ NF3-690-1000 ➀
DCS60x-1503-y1 1500A A5 NF3-690-1600 ➀ NF3-690-1600 ➀ NF3-690-1600 ➀
DCS60x-2003-y1 2000A A5 NF3-690-1600 ➀ NF3-690-1600 ➀ NF3-690-1600 ➀
≤ 3000A A6 NF3-690-2500 ➀ NF3-690-2500 ➀ NF3-690-2500 ➀
➀ Filter only available on request
Single - phase filters for field supply Converter type of dc current Filter type ➊
Many field supply units are single - phase converters for field supply unit Umax = 250 V
II F 2-26
3ADW000072R0501_DCS600_System_description_e_e
3 Overview of software (Version 15.xxx)
Communication
Drive Control
Application Control
Torque Control
SDCS-CON-2
Software 15.2xx
I/O handling
II F 3-1
3ADW000072R0501_DCS600_System_description_e_e
3.3 Start, Stop and Fault Reactions
During operation, the drive is in one of the following Normal stop
states (ABB Drive profile): RUN = 0 sets the speed reference to zero and the drive
decelerates.
After emergency stop After the actual speed has reached zero the status bit
(OFF3_N) or emergency off RUNNING is reset, the armature converter sets the
ON_INHIBIT
(OFF2_N) this state is firing angle to maximum. The state RDY_RUN is
entered until ON = 0
entered, when the actual current has reached zero.
OFF
Main contactor is off, OFF3_N ON = 0 sets RDY_RUN = 0 and the field current
or OFF2_N active reference to zero. The field converter sets the firing
RDY_ON Main contactor is off angle to maximum . The contactors are opened, when
the actual current has reached zero.
Main, field and fan contactor ON = 0 internally forces RUN = 0.
are closed, field control
RDY_RUN
activated, ready for run
Emergency off
command
Field and armature current are removed as fast as
RDY_REF
Drive is running, all possible. After the current has reached IDC = 0 the
controllers are released contactors are opened. The normal start command is
TRIPPED Drive is faulted accepted when OFF2_N = EME_OFF_N = 1.
II F 3-2
3ADW000072R0501_DCS600_System_description_e_e
Voltage Switch on ABB Drive Profile
switched off inhibit Status Disable
ON INHIBIT (MSW Bit6=1)
for DC-drives
Power ON OFF 1 (MCW Bit0=0)
Control and
not ready Status
to swich on Status Not ready for startup
A B C D E F OFF (MSW Bit0=0)
B C D
RFG-output
disable
(MCW Bit4=0
RAMP_OUT_ZERO) Enable Release electronics and pulses
Operation RDY_REF (MSW Bit2=1) Status Operation released
CD
A MCW : Bit 4 = 0 and Bit 5 = 0 and Bit 6 = 0
RFG-output free Purpose: Main speed ref. is deactivated
RFG stop RAMP_OUT_ZERO
(MCW Bit5=0 (MCW Bit4=1) INCHING 1 ON (MCW Bit 8 = 1)
RAMP_HOLD)
RFG: Enable Inching 1 Active
output Drive Running Inching 1 setpoint
D to speed control
B RFG-output released
Setpoint E
RAMP_HOLD
disabled INCHING 1 OFF (MCW Bit 8 = 0)
(MCW Bit6=0 (MCW Bit5=1)
RAMP_IN_ZERO) RFG: Accelerator
enable INCHING 2 ON (MCW Bit 9 = 1)
II F 3-3
3ADW000072R0501_DCS600_System_description_e_e
3.4 Speed Control 3.5 Torque Control
The speed controller is located in the AMC board Flux and Torque Calculation
software. The torque control is in general an open loop control.
The flux is adjusted by the field current. The reference
Speed reference of the field current is generated by the superimposed
The source of the reference is depending on the oper- armature voltage control.
ating mode. The torque is adjusted by the armature current. The
conversion from torque to current reference is done by
Overriding control means of the calculated flux (based on the field current
system, fieldbus adapters ➔ remote mode, DDCS and saturation characteristic).
via AMC board
DriveWindow ➔ local mode, DDCS via Torque reference features
AMC board • Torque reference A with 1st order filter and load
Panel CDP312 ➔ local mode, connector share
on CON-2 • Torque reference B with torque ramp
Analogue inputs ➔ local I/O • Torque reference limiter
• Torque correction and torque step
Speed reference features • Torque correction by means of analogue input 1
• Speed reference limiter
• Additional speed ramp for emergency stop A good behaviour in the field weakening requires speed
• Variable slope rate measurement by tachometer or encoder.
• Speed correction
• Reference for inching before the ramp A simplified scheme of the torque reference chain is
• 2 different references for inching behind the ramp given in diagram fig. 3.8/2.
Speed measurement
The actual speed may be calculated from:
3.6 HMI (Human Machine Interface)
• Armature voltage The HMI is performed by CDP 312 control panel
• Analogue tachometer or by DriveWindow.
• Pulse encoder Both tools contain:
• Display of drive signals
Controller features • Setting of drive parameters
• PID controller • Display fault and alarm messages
• 2 first order low pass filters • Control the drive in local operation
• Window control
• Acceleration compensation
• Speed and torque adaptation
• Droop
• Additional torque references
• Torque limitation and gear backlash function (the
integral part of the controller is set to a suitable value
on limitation)
• Oscillation damping (band rejection filter for speed
error)
II F 3-4
3ADW000072R0501_DCS600_System_description_e_e
3.7 Torque Generation
II F 3-5
3ADW000072R0501_DCS600_System_description_e_e
3.8 Software diagrams
Introduction
The designation of parameters and signals consist of a On the following pages the simplified software struc-
group and a index. ture is shown. Additionally there are specific tables for:
23.05
X • Main Status Word (MSW)
• Auxiliary Status Word (ASW)
Signal • Digital Inputs (Armature converter mode)
Parameter • Digital Inputs (Field converter mode)
• Digital Outputs (Armature converter mode)
Index • Digital Outputs (Field converter mode)
Group • Analogue Inputs (Armature converter mode)
II F 3-6
3ADW000072R0501_DCS600_System_description_e_e
Fig. 3.8/2:
SPEED REFERENCE CHAIN
LOCAL
FIELDBUS AI SPEED SELECT 13.17
ADAPTER AN IN 1 VALUE ACW B12 ACCELERATION
COMM MODULE AN IN 2 VALUE
Datasets LOCAL AN IN 3 VALUE
COMPENSATION SPEED CONTROL
[70.20]+0 ... [70.20]+14 98.02 AN IN 4 VALUE
LOCAL REF1 AN IN TACHO VALUE
Selector
MCW
0 TORQ ACC COMP REF
REF1
REF2 2.07
23.01
Datasets SPEED REF 24.14 ACC COMP DER TIME
[70.20]+1 ... [70.20]+15 SPEED CORR RAMP 23.13
MSW 24.15 ACC COMPFILT TIME
ACT1 RAMPED INCH REF 23.12
ACT2 DROOP RATE
ERROR 24.11
50.02 SPEED MEAS MODE 50.06 SP ACT FILT TIME BAL REF
TACHO AI1 22.06 VARIABLE SLOPE NEG
50.03 SPEED FB SEL 23.07 WINDOW INTG ON ACW B8 BAL_NCONT
22.07 VARIABLE SLOPE
50.04 MOTOR SPEED RATE 20.07 SPC TORQMAX
ENCODER PULSE NR 23.08 WINDOW WIDTH POS
ACW B3 BAL RAMP OUT 20.08 SPC TORQMIN
23.09 WINDOW WIDTH NEG KPS
FILTER MOTOR 22.08 BAL RAMP REF 24.03 KPS
SPEED ACW B2 RAMP BYPASS 24.04 KPS MIN
CON FILT
DV/DT 2.16 24.05 KPS WEAKPOINT TORQ
REF 2
AMC 1.01 SPEED 24.06 KPS WP FILT TIME
ACTUAL MCW Bx = MAIN CONTROL WORD (7.01)
50.13 SP ACT FTC
ACW Bx = AUX CONTROL WORD (7.02) 24.09 TIS KPS, TIS
B = bit 24.10 TIS INIT VALUE KPS VAL
7.01 MAX SPEED
24.17 KPS TIS MIN SPEED KPS
3ADW000072R0501_DCS600_System_description_e_e
DIGITAL 7.02
ABB DRIVE PROFIL CONTROL 24.18 KPS TIS MAX SPEED TIS
INPUT
START / STOP 7.03 24.19 KPS VAL MIN SPEED
CONTROL MCW ACW ACW 2 MSW ASW DI STATUS WORD 24.20 TIS VAL MIN SPEED TIS VAL
8.01 MIN SPEED
7.01 MAIN CONTROL WORD 7.02 AUX CONTROL WORD 7.03 AUX CONTROL WRD 2 8.01 MAIN STATUS WORD 8.02 AUX STATUS WORD 8.05 DI STATUS WORD
24.12 DERIVATION TIME motor speed
CDP312 or 8.02 B0 ON B0 RESTART_DLOG B0 DIG_OUT_7 B0 RDYON B0 LOGG_DATA_READY DI1 CONV FAN ACK
B0 24.13 DERIV. FILT TIME KPS TIS MAX SPEED
B1 OFF2 B1 TRIGG_LOGGER B1 DIG_OUT_8 B1 RDYRUN B1 OUT_OF_WINDOW B1 DI2 MOT FAN ACK
DRIVES 8.05 B2 OFF3 B2 RAMP_BYPASS B2 B2 RDYREF B2 EMERG_STOP_COAST B2 DI3 MAIN CONT ACK KPS TIS MIN SPEED
WINDOW B3 RUN B3 BAL_RAMP_OUT B3 B3 TRIPPED B3 B3 DI4 configurable
LOCAL CTRL B4 RAMP_OUT_ZERO B4 DYN_BRAKE_ON_APC B4 B4 OFF_2_STA B4 ON_DISABLED B4 DI5 configurable
B5 RAMP_HOLD B5 B5 B5 OFF_3_STA B5 SYNC_RDY B5 DI6 configurable
PANEL B6 RAMP_IN_ZERO B6 HOLD_NCONT B6 B6 ON_INHIBIT B6 FEX1_ACK B6 DI7 configurable
DIGITAL B7 RESET B7 WINDOW_CTRL B7 B7 ALARM B7 FEX2_ACK B7 DI8 configurable
OUTPUTS B8 INCHING1 B8 BAL_NCONT B8 DRIVE_DIR B8 AT_SETPOINT B8 B8 DI9
B9 INCHING2 B9 SYNC_COMMAND B9 SPEED_EXT B9 REMOTE B9 LIMITING B9 DI10
II F 3-7
B10 VALID_COMMAND B10 SYNC_DISABLE B10 B10 ABOVE_LIMIT B10 TORQ_CONTROL B10 DI11
B11 B11 RESET_SYNC_RDY B11 B11 B11 ZERO_SPEED B11 DI12
B12 B12 JOG_REF B12 B12 B12 EMF_SPEED B12 DI13
B13 B13 DIG_OUT4 B13 B13 B13 FAULT_OR_ALARM B13 DI14
B14 B14 DIG_OUT5 B14 B14 B14 DRIVE_DIR_ASW B14 DI15
B15 B15 DIG_OUT6 B15 B15 B15 AUTO_RECLOSING B15
dcs_600\docu\fig_1a.dsf
MODE SWITCH SEL 26.04 TORQUE CONTROL CHAIN
II F 3-8
TORQUE SELECTOR 26.01 0
AUX CONTROL WRD 2
B 9 (SPEED_EXT)
DI1 1
DI2
DI3
Fig. 3.8/3:
DI4
1
Selector
DI5
DI6 TORQUE REFERENCE
FILTER SELECTOR (26.01)
DI7
TORQ REF A
2 TORQUE STEP
DI8 8 26.03 TORQUE LIMITER
TORQUE SELECTOR
25.01
gear TORQ USED REF
0 26.02 TORQ REF 5
25.02 2.12
backlash 2.13
TORQ REF A FTC
21 LOAD COMPENSATION TORQ
LIMITER 3 compen- to SUM
4 REF 4
25.03 TORQ REF 1 MIN 5 6 sation
2.08 2.11
LOAD SHARE
TORQ REF 3 20.05 MAXIMUM TORQUE
AMC
CON
Analogue outputs
3ADW000072R0501_DCS600_System_description_e_e
Analogue inputs
AIx
A [AN OUT x INDEX] + D
AN IN x VALUE AO1
+ (AO2)
D A
AN IN x HI VAL AN IN x LO VAL
AN OUT x NOM VOLT
AN OUT x NOM VAL
AN IN TACHO VALUE (signal) 5.01
AN IN TACH HI VAL (at +10V) 13.01
AN IN TACH LO VAL (at -10V) 13.02 AN OUT 1 INDEX 14.04
AN OUT 1 NOM VAL 14.03
AN IN 1 VALUE (signal) 5.02 AN IN 3 VALUE (signal) 5.04 ANOUT 1 OFFS VOLT 14.02
AN IN 1 HI VAL (at +10V) 13.03 AN IN 3 HI VAL (at +10V) 13.07 AN OUT 1 NOM VOLT 14.01
AN IN 1 LO VAL (at -10V) 13.04 AN IN 3 LO VAL (at -10V) 13.08
AN OUT 2 INDEX 14.08
AN IN 2 VALUE (signal) 5.03 AN IN 4 VALUE (signal) 5.05 AN OUT 2 NOM VAL 14.07
AN IN 2 HI VAL (at +10V) 13.05 AN IN 4 HI VAL (at +10V) 13.09 ANOUT 2 OFFS VOLT 14.06
AN IN 2 LO VAL (at -10V) 13.06 AN IN 4 LO VAL (at -10V) 13.10 AN OUT 2 NOM VOLT 14.05
dcs_600\docu\fig_2a.dsf
U_SUPPLY
42.06
ARMATURE CURRENT CONTROL
Mains 1.11 RL MAINS VOLT ACT
Voltage
Measurem. 1.12 MAINS VOLT ACT
Fig. 3.8/4:
1.15 RL CONV CUR ACT
ALPHA_MAX Current
M N = 10000 = CUR LIM MOT BRIDGE 20.14 Measurem.
Calc. 1.16 CONV CUR ACT
M max = 3.2 * M N
20.12 CURRENT CONTROLLER
FIRE UNIT
3ADW000072R0501_DCS600_System_description_e_e
3.18 FIELD EXCITER
FLD CUR @90% FLUX
FLUX REF 41.16 FIELD CUR REF M2
MOT 2 NOM FLD CUR 41.17
45.01 set to 0, if FIX field selected (15.06)
set to MAXIMUM FLUX (45.07), if FIX field selected (15.06)
3.14
FLUX
CONTROL FLUX REF FLD WEAK
MOTOR SPEED
Diagram for
1.02 dcs_600\docu\fig_3a_a.dsf
OPER MODE SELECT (15.16) < 5
II F 3-9
OR
MOTOR NOM
46.07 flux ref sel = EXT REF
SPEED 99.05
MAXIMUM
FLUX 45.07
U_SUPPLY
42.06
TORQUE USED REF INDUCTIVE LOAD CURRENT CONTROL
- CUR REF 1 := LOCAL REF 3,
2.13 if local mode and REF SEL (43.15) < 3 Mains RL MAINS VOLT ACT
- CUR REF 1 := LOCAL CUR REF (43.19), (EXCITATION: 15.16 = 5) 1.11
TORQUE CORRECTION not used Voltage
if local mode and REF SEL (43.15) >= 3 CUR REF 3 Measurem.
Fig. 3.8/5:
1.12 MAINS VOLT ACT
2.14
3.12
CUR LIM MOT
II F 3-10
CUR REF 1 FLUX REF SUM CUR REF 2 BRIDGE MAX FIRING ANGLE Converter
FLUX REF SEL 1.15 RL CONV CUR ACT
ALPHA_MAX Current
3.27 3.15 3.28 20.12 20.14 Measurem. CONV CUR ACT
46.07 Calc. 1.16
CURRENT CONTROLLER
FIRE UNIT
0 FLUX/FIELD
CURRENT REF 0 LINEARIZATION PI-IP 4.13
1 Reference di/dt HL + HL
3.11 CONV NOM CURR
2 MUX Selection 3.13
and
AI CUR REF 3 -
min/max- CONTROL TYPE SEL 43.01 FIRING ANGLE
3.30 4 CUR REF LL LL
Logic SLOPE ARM CUR PI P-GAIN 43.02
41.10 MOTOR NOM 99.02
REF SEL
FEX LINK REF ARM CUR PI I-GAIN 43.03 20.15 VOLTAGE
43.15
FLD CUR @40% FLUX 20.13 43.04
SEL MAX MIN ARM CUR IP P-GAIN MIN FIRING ANGLE MOTOR NOM 99.03
INT CUR REF 41.14 1.19
43.16 CUR LIM ARM CUR IP I-GAIN 43.05 CURRENT
43.17 FLD CUR @70% FLUX GEN BRIDGE SELECTED BRIDGE
41.15 DISCONT CUR LIMIT 43.06
FLUX COR
FLD CUR @90% FLUX LOAD CUR ACT
43.20
41.16
Armature
FLUX STEP 1.27
Current
1.28 Measurem.
43.21 4096 == Load nominal current
3ADW000072R0501_DCS600_System_description_e_e
41.19 2 MUX V LIM N 46.14 EMF CON BLOCK
LEV 46.05
3 V REF SLOPE
46.12
AI V REF
V COR 46.10 3.25 V REF 2
3.29 V STEP 46.11
REF SEL 43.15
V REF 1 := LOCAL REF 3,
if local mode; Diagram for
scaled to CUR REF 1
NOM SUPPLY VOLT (42.06) 3.27 OPER MODE SELECT (15.16) = 5 dcs_600\docu\fig_3b_a.dsf
Control and Status Words
In remote mode, the drive is controlled by the main control word and the auxiliary control words.
The drive’s status is read from the main status word and the auxiliary status word.
Main Control Word (7.01) Auxiliary Control Word (7.02)
2 OFF3_N reser ved for emergency stop 2 RAMP_BYPASS Speed ramp is bypassed
II F 3-11
3ADW000072R0501_DCS600_System_description_e_e
Main Status Word (8.01) Auxiliary Status Word (8.02)
II F 3-12
3ADW000072R0501_DCS600_System_description_e_e
Digital inputs/outputs
Depending on the drive modes there are different
possibilities for digital inputs and outputs.
Digital Inputs Armature converter mode Digital Inputs Field converter mode
Input Signal use Description Input Signal use Description
DI 1 DI 1 Acknowledge over voltage
12.13 ACK Conver ter fan DI 2 ACK_OVERVOLT fix
protection DCF 505/506
DI 2 DI 2 12.14 ACK Motor fan
12.15 ACK Main contactor DI 1 DI 1 12.13 ACK Conver ter fan
DI 3 DI 3 12.16 Emergency STOP 12.14 ACK Motor fan
DI 4 DI 4 15.13 electrical disconnect DI 3 DI 3 12.15 ACK Main contactor
configurable
15.14 ON INHIBIT 1 12.16 Emergency STOP
DI 5 DI 5 →
15.15 ON INHIBIT 2 15.13 electrical disconnect
DI 4 DI 4
DI 6 DI 6 15.18 ACK DC breaker 15.14 ON INHIBIT 1
15.20 ACK DYN brake configurable 15.15 ON INHIBIT 2
DI 5 DI 5
DI 7 DI 7 28.18 Klixon (motor 1 trip) → 15.18 ACK DC breaker
28.25 Klixon (motor 2 trip) 15.20 ACK DYN brake
DI 8 DI 8 DI 6 DI 6
28.18 Klixon (motor 1 trip)
if COMMAND SEL 15.22 = 1 (local I/O) then 28.25 Klixon (motor 2 trip)
DI 6 = Reset; DI 7 = ON; DI 8 = RUN DI 7 DI 7
Note: Do not select DI 2 for
Table 3.8/6: Digital inputs Armature converter mode (DCS 600) DI 8 DI 8 these functions!
if COMMAND SEL 15.22 = 1 (local I/O) then
DI 6 = Reset; DI 7 = ON; DI 8 = RUN
Digital Outputs Armature converter mode Digital Outputs Field converter mode
Output Signal use Description Output Signal use Description
free / program. by 12.02 free / program. by 12.02
DO 1 DIG_OUT 1 DO 1 DIG_OUT 1
default: FANS ON CMD default: FANS ON CMD
free / program. by 12.05 free / program. by 12.05
DO 2 DIG_OUT 2 DO 2 DIG_OUT 2
default: FIELD ON CMD default: FIELD ON CMD
free / program. by 12.08 free / program. by 12.08
DO 3 DIG_OUT 3 default: MAIN CONT ON DO 3 DIG_OUT 3 default: MAIN CONT ON
CMD CMD
DO 4 DIG_OUT 4 configurable free / program. by 14.10 DO 4 DIG_OUT 4 configurable free / program. by 14.10
→ →
DO 5 DIG_OUT 5 free / program. by 14.13 DO 5 DIG_OUT 5 free / program. by 14.13
DO 6 DIG_OUT 6 free / program. by 14.16 DO 6 DIG_OUT 6 free / program. by 14.16
DO 7 DIG_OUT 7 free / program. by 14.19 DO 7 DIG_OUT 7 free / program. by 14.19
free / program. by 14.22 free / program. by 14.22
e.g. MAIN_CONT_ON_CMD e.g. MAIN_CONT_ON_CMD
DO 8 DIG_OUT 8 DO 8 DIG_OUT 8
14.22 = 605 14.22 = 605
14.23 = 6 14.23 = 6
Table 3.8/8: Digital outputs Armature converter mode (DCS600) Table 3.8/9: Digital outputs Field converter mode (DCF600)
II F 3-13
3ADW000072R0501_DCS600_System_description_e_e
Analogue inputs
Depending on the drive modes there are different
possibilities for analogue inputs.
AI SPEED SELECT AI SPEED SELECT AI SPEED SELECT AI SPEED SELECT AI SPEED SELECT
SPEED REFERENCE
13.17=5 13.17=1 13.17=2 13.17=3 13.17=4
SPEED SPEED_MEAS_MODE
MEASUREMENT 50.03=4
II F 3-14
3ADW000072R0501_DCS600_System_description_e_e
U
4
M V
3~ W 2 4 6
400V 50Hz
F7
L1 L2 L3
Fig. 4.1/1:
1 3 5
2 4 6
K6
1 3 5
F1
T3
2 4 6
K16 500V 12
F6 460V 11
1 3 5 415V 10
F3
400V 9
8
365V
EMER. ELECTR. 350V 7
STOP DISCON- K10 K12 K11 K12 T2 265V 6
NECT 230V 11 690V 250V 5
* [K13] 4
1 1 12 10 660V 1 3 90V
9 600V 60V 3
X2:4 F4 F5 F2 2
F6 8 575V 4 30V
K15 2 2 2 1
X2:5 7 525V
115V 6 500V
13 5 450V
4 415V
3 400V
2 380V
1 1 3 5 1 3
14 K1 K3
K15 K16 K6 K5 K13 K3 K1
2 4 6 2 4
Connection examples
* if contactor relay 1 3
K13 is used L1 L3
K5
2 4
4.1 Armature current converter DCS 600
AMC-DC 2
Power supply depending on the unit type (C1, C2, A5, C4)
(POW-1) DCS 600
CH 3 S4
Converter Field exciter
5 6 module unit (FEX-1/2)
AITAC AI1 AI2 AI3 AI4
X33 _ + _ + _ + _ + _ + +10V -10V AO1 AO2 IACT DI1 DI2 DI3 DI4 DI5 DI6 DI7 DI8 +48V DO1 DO2 DO3 DO4 DO5 DO6 DO7
0V 0V 0V 0V 0V
3ADW000072R0501_DCS600_System_description_e_e
CDP 312 K6 K16
If SDCS-IOB-2
e.g. Pressure is in use K10,
switch at C4 K10 K12 K11 and K12
module are not
K11 necessary
K5 K1 K15
if there are intermediate terminals the polarities are shown for motoring
T M
II F 4-1
+
T
_
Note: In case the supply voltage for the excitation
is switched on the primary side of its supply
transformer additional overvoltage protec-
tion is required. Please contact ABB!
400V 50Hz
L1 L2 L3
Fig. 4.2/1:
II F 4-2
F1
K16
ELECTR.
DISCON- K10 K12 K12 T2
NECT 230V 11 690V
* [K13]
1 1 12 10 660V 1 3
9 600V F2
X2:4 F4 F5 8 575V
2 4
X2:5 2 2 7 525V
115V 6 500V
13 5 450V
4 415V
3 400V
2 380V
1 1 3 5
14 K1
K16 K5 K13 K1
2 4 6
* if contactor relay 1 3
L1
4.2 Field supply converter DCF 600
K13 is used K5
2 4
3ADW000072R0501_DCS600_System_description_e_e
M
DO8
CH 2 ~
AMC-DC 2
Power supply depending on the unit type (C1, C2)
(POW-1) DCF 600 DCF 506
CH 3 S4
5 6
AITAC AI1 AI2 AI3 AI4
X33 _ + _ + _ + _ + _ + +10V -10V AO1 AO2 IACT DI1 DI2 DI3 DI4 DI5 DI6 DI7 DI8 +48V DO1 DO2 DO3 DO4 DO5 DO6 DO7
Field supply Overvoltage
0V
converter protection
0V 0V 0V 0V
module
X3: 1 2 3 4 5 6 7 8 9 10 X4: 1 2 3 4 5 6 7 8 9 10 X6: 1 2 3 4 5 6 7 8 9 10 X7: 1 2 3 4 5 6 7 8 X5: 1...10 C1 D1 X11 X12
_ _
+ +
PANEL
CDP 312 K16
If SDCS-IOB-2
is in use K10,
K10 K12 K11 and K12
are not
K11 necessary
K5 K1 M
K11 = Alarm
Notes
II F 4-3
3ADW000072R0501_DCS600_System_description_e_e
DC Drives Product Portfolio
The drive module for standard applications
DCS 400 ● Integrated field supply (max. 20 A)
● Accurate speed and torque control
● Extremely small and compact design
● Very easy installation and commissioning
● Express delivery
● Power range: 10...500 kW (13...670 HP)
II F 4-4 *072R0501A4080000*
3ADW000072R0501_DCS600_System_description_e_e
*072R0501A4080000*