Example 2:
An Alternator is supplying a load of 650 kW at a P.F (Power factor) of 0.65. What size
of Capacitor in kVAR is required to raise the P.F (Power Factor) to unity (1)? And
how many more kW can the alternator supply for the same kVA loading when P.F
improved.
Solution #1 (By Simple Table Method)
Supplying kW = 650 kW
From Table 1, Multiplier to improve PF from 0.65 to unity (1) is 1.169
Required Capacitor kVAR to improve P.F from 0.65 to unity (1)
Required Capacitor kVAR = kW x Table 1 Multiplier of 65 and 100
= 650kW x 1.169
= 759.85 kVAR
We know that P.F = Cos = kW/kVA . . .or
kVA = kW / Cos
= 650/0.65 = 1000 kVA
When Power Factor is raised to unity (1)
No of kW = kVA x Cos
= 1000 x 1 = 1000kW
Hence increased Power supplied by Alternator
1000kW 650kW = 350kW
Solution # 2 (Classical Calculation Method)
Supplying kW = 650 kW
Original P.F = Cos1 = 0.65
Final P.F = Cos2 = 1
1 = Cos-1 = (0.65) = 49.45; Tan 1 = Tan (41.24) = 1.169
2 = Cos-1 = (1) = 0; Tan 2 = Tan (0) = 0
Required Capacitor kVAR to improve P.F from 0.75 to 0.90
Required Capacitor kVAR = P (Tan 1 - Tan 2)
= 650kW (1.169 0)
= 759.85 kVAR
How to Calculate the Required Capacitor bank value in both kVAR and Farads?
(How to Convert Farads into kVAR and Vice Versa)
Example: 3
A Single phase 400V, 50Hz, motor takes a supply current of 50A at a P.F (Power
factor) of 0.6. The motor power factor has to be improved to 0.9 by connecting a
capacitor in parallel with it. Calculate the required capacity of Capacitor in both
kVAR and Farads.
Solution.:
(1) To find the required capacity of Capacitance in kVAR to improve P.F from 0.6 to
0.9 (Two Methods)
Solution #1 (By Simple Table Method)
Motor Input = P = V x I x Cos
= 400V x 50A x 0.6
= 12kW
From Table, Multiplier to improve PF from 0.60 to 0.90 is 0.849
Required Capacitor kVAR to improve P.F from 0.60 to 0.90
Required Capacitor kVAR = kW x Table Multiplier of 0.60 and 0.90
= 12kW x 0.849
= 10.188 kVAR
Solution # 2 (Classical Calculation Method)
Motor Input = P = V x I x Cos
= 400V x 50A x 0.6
= 12kW
Actual P.F = Cos1 = 0..6
Required P.F = Cos2 = 0.90
1 = Cos-1 = (0.60) = 53.13; Tan 1 = Tan (53.13) = 1.3333
2 = Cos-1 = (0.90) = 25.84; Tan 2 = Tan (25.50) = 0.4843