ZXDU68 B201

DC Power System

Product Description
Version: V5.0R06M09

ZTE CORPORATION
NO. 55, Hi-tech Road South, ShenZhen, P.R.China
Postcode: 518057
Tel: +86-755-26771900
Fax: +86-755-26770801
URL: http://ensupport.zte.com.cn
E-mail: support@zte.com.cn

LEGAL INFORMATION
Copyright 2013 ZTE CORPORATION.
The contents of this document are protected by copyright laws and international treaties. Any reproduction or
distribution of this document or any portion of this document, in any form by any means, without the prior written
consent of ZTE CORPORATION is prohibited.

Additionally, the contents of this document are protected by

contractual confidentiality obligations.


All company, brand and product names are trade or service marks, or registered trade or service marks, of ZTE
CORPORATION or of their respective owners.
This document is provided as is, and all express, implied, or statutory warranties, representations or conditions
are disclaimed, including without limitation any implied warranty of merchantability, fitness for a particular purpose,
title or non-infringement. ZTE CORPORATION and its licensors shall not be liable for damages resulting from the
use of or reliance on the information contained herein.
ZTE CORPORATION or its licensors may have current or pending intellectual property rights or applications
covering the subject matter of this document. Except as expressly provided in any written license between ZTE
CORPORATION and its licensee, the user of this document shall not acquire any license to the subject matter
herein.
ZTE CORPORATION reserves the right to upgrade or make technical change to this product without further notice.
Users may visit ZTE technical support website http://ensupport.zte.com.cn to inquire related information.
The ultimate right to interpret this product resides in ZTE CORPORATION.

Revision History
Revision No.

Revision Date

Revision Reason

R1.2

2013-01-08

The following section and chapter are modified:

R1.1

R1.0

2012-12-06

2012-11-23

Section 3.2, Environmental Specifications

Chapter 5, Alarm List

The following section and chapter are modified:


l

Section 2.4, Signal Interface Unit

Chapter 5, Alarm List

First edition

Serial Number: SJ-20120703093141-002


Publishing Date: 2013-01-08 (R1.2)

SJ-20120703093141-002|2013-01-08 (R1.2)

ZTE Proprietary and Confidential

Contents
About This Manual ......................................................................................... I
Chapter 1 System Overview ...................................................................... 1-1
1.1 System Introduction............................................................................................ 1-1
1.2 System Features ................................................................................................ 1-1

Chapter 2 System Structure and Components........................................ 2-1


2.1 System Structure................................................................................................ 2-1
2.2 ZXD3000 Rectifier .............................................................................................. 2-4
2.3 Centralized Supervision Unit ............................................................................... 2-6
2.4 Signal Interface Unit ........................................................................................... 2-7

Chapter 3 System Specifications.............................................................. 3-1


3.1 Configuration List ............................................................................................... 3-1
3.2 Environmental Specifications .............................................................................. 3-2
3.3 Technical Specifications...................................................................................... 3-2
3.4 Compliance Standards ....................................................................................... 3-5

Chapter 4 Rectifier Specifications ............................................................ 4-1


4.1 Technical Specifications...................................................................................... 4-1
4.2 Input Features.................................................................................................... 4-3
4.3 Output Features ................................................................................................. 4-4
4.4 Power Decrease With High Temperature ............................................................. 4-5

Chapter 5 Alarm List .................................................................................. 5-1


Appendix A Electrical Connection Diagram ........................................... A-1
Glossary .......................................................................................................... I

I
SJ-20120703093141-002|2013-01-08 (R1.2)

ZTE Proprietary and Confidential

II
SJ-20120703093141-002|2013-01-08 (R1.2)

ZTE Proprietary and Confidential

About This Manual


Purpose
This manual applies to the ZXDU68 B201 (V5.0R06M09) DC Power System. The ZXDU68
B201 system is designed to be installed in a cabinet/rack and provides power for -48 V
communications equipment.
This manual describes the system structure, characteristics, and configuration.

Intended Audience
This manual is intended for:
l
l

Planning engineers
Maintenance engineers

What Is in This Manual


This manual contains the following chapters/appendices:
Chapter/Appendix

Summary

1, System Overview

Introduces the system and describes the system features.

2, System Structure and

Describes the system structure, ZXD3000 rectifiers, Centralized

Components

Supervision Unit (CSU), and Signal Interface Unit (SIU).

3, System Specifications

Describes configuration list, environmental specifications, technical


specifications, and compliance standards.

4, Rectifier Specifications

Describes the ZXD3000 (V5.0) rectifier specifications, including


technical specifications, input features, output features and the feature
of power decrease with high temperature.

5, Alarm List

Describes the alarm names, default alarm levels and output relays.

A, Electrical Connection

Provides the electrical connection diagram of the ZXDU68 B201

Diagram

system.

Conventions
This manual uses the following typographical conventions:
Typeface

Meaning

Bold

Menus, menu options, function names, input fields, option button names, check boxes,
drop-down lists, dialog box names, window names, parameters, and commands.
Note: provides additional information about a certain topic.

I
SJ-20120703093141-002|2013-01-08 (R1.2)

ZTE Proprietary and Confidential

II
SJ-20120703093141-002|2013-01-08 (R1.2)

ZTE Proprietary and Confidential

Chapter 1

System Overview
Table of Contents
System Introduction....................................................................................................1-1
System Features ........................................................................................................1-1

1.1 System Introduction


The ZXDU68 B201 system is designed to be installed in a cabinet/rack. ZXDU68 B201 is
19 inches in width and 5U in height.
l
l
l

The system can provide power for -48 V communications equipment.


Single-phase AC input, 200 V - 240 V (phase voltage).
When fully configured, the power system is equipped with four ZXD3000 (V5.0)
rectifiers and can provide a maximum power output of 12 kW.

For the appearance of the ZXDU68 B201 system, see Figure 1-1.
Figure 1-1 System Appearance

1.2 System Features


Door Open Key Code Function
Delayed trigger alarm waits for technicians authorization code before informing the
Supervision Center (SC) of access attempt.
This function provides potential reduction of the SC interventions greatly.

Efficient Rectifiers
With 30% - 50% output power, the rectifier efficiency is 94%.
1-1
SJ-20120703093141-002|2013-01-08 (R1.2)

ZTE Proprietary and Confidential

ZXDU68 B201 Product Description

With 50% - 100% output power, the rectifier efficiency is 96%.

Automatically Switching the Rectifiers to the Sleep Mode


The system switches one or more rectifiers to the sleep mode according to the load power.
The power of a rectifier in sleep mode is not larger than 4 W.

A Wide Range of Input Voltage


A wide range of input phase voltage (90 V to 295 V) makes the system suitable for areas
with unstable power sources.

Capacity Expansion
When fully configured, the system is equipped with four ZXD3000 (V5.0) rectifiers and can
provide a rated output power of 12 kW when the output voltage ranges from -48 V to -57.6
V.

Accessible via Web Browser


The system can be remotely managed through a computer installed with a web browser
anywhere if Ethernet is available.

Managing Data in Batches


Users can set the parameters in batches, copy records and upgrade programs via a USB
flash drive.

Professional Monitoring and Management


l
l

The transmission speed is high via CAN bus.


Multiple protection functions, such as Load Low Voltage Disconnect (LLVD1), Load
Low Temperature Disconnect (LLTD), Battery Low Voltage Disconnect (BLVD), and
Battery High Temperature Disconnect (BHTD).
Users can press the QUY button of a rectifier to query the data of the rectifier or control
it.

Flexible Monitoring Networking


The system provides input and output relays, RJ45 Ethernet interface, RS232 interface,
RS485 interface, and USB interface. The system supports multiple monitoring networking
modes via Telnet, Hypertext Transfer Protocol (HTTP), File Transfer Protocol (FTP), and
Simple Network Management Protocol (SNMP).

1-2
SJ-20120703093141-002|2013-01-08 (R1.2)

ZTE Proprietary and Confidential

Chapter 2

System Structure and


Components
Table of Contents
System Structure........................................................................................................2-1
ZXD3000 Rectifier ......................................................................................................2-4
Centralized Supervision Unit ......................................................................................2-6
Signal Interface Unit ...................................................................................................2-7

2.1 System Structure


For the structure of the ZXDU68 B201 chassis, see Figure 2-1 and Figure 2-2.

Front View
Figure 2-1 Chassis Structure (Front View)

1. ZXD3000 (V5.0) rectifiers


2. Signal Interface Unit (SIU)
3. Centralized Supervision
Unit (CSU)
4. 48VDC generator input
connector (48VDC
GENERATOR)

5. Auxiliary DC output
connector (AUX. OUTPUT,
50A)
6. Main DC output circuit
breaker (MAIN OUTPUT)
7. Battery circuit breakers
(BATT1, BATT2, BATT3)

8. BLVD reset button (BLVD


RST)
9. PE bolts

For a description of the components, refer to Table 2-1.


2-1
SJ-20120703093141-002|2013-01-08 (R1.2)

ZTE Proprietary and Confidential

ZXDU68 B201 Product Description

Table 2-1 Chassis Components (Front View)


S.N.

Component

Description

ZXD3000 (V5.0) rectifiers

Convert AC power to DC power.


For further details, refer to 2.2 ZXD3000 Rectifier.

Signal Interface Unit (SIU)

Provides signal interfaces for supervision.


For further details, refer to 2.4 Signal Interface Unit.

Centralized Supervision

Collects the system operation data and manages the system.

Unit (CSU)

For further details, refer to 2.3 Centralized Supervision Unit.

48VDC generator input

Connects to a 48 VDC generator.

connector (48VDC
GENERATOR)
5

Auxiliary DC output

Connects to a DC load.

connector (AUX. OUTPUT,


50A)
6

Main DC output circuit

Activates/deactivates DC output for the main DC load.

breaker (MAIN OUTPUT)


7

Battery circuit breakers

Activates/deactivates battery input.

(BATT1, BATT2, BATT3)


8

BLVD reset button (BLVD

If the system has disconnected the battery branch(es) because

RST)

of low voltage, but the CSU is faulty, press the BLVD RST
button to manually reconnect the disconnected branch(es).

PE bolts

Connect to the on-site grounding busbar.

Rear View

2-2
SJ-20120703093141-002|2013-01-08 (R1.2)

ZTE Proprietary and Confidential

Chapter 2 System Structure and Components

Figure 2-2 Chassis Structure (Rear View)

1. Rear panel
2. AC input cabling hole
3. Battery input connection
terminals (BATT1, BATT2,
BATT3) (-48V)

4. Main DC output connection


terminals (MAIN OUTPUT)
(-48V)
5. -48V busbar (-48V)

6. Working ground busbar


(+/RTN)
7. AC input connection
terminals (L, N, L, N, PE)

For a description of the components, refer to Table 2-2.


Table 2-2 Chassis Components (Rear View)
S.N.

Component

Description

Rear panel

Remove the rear panel before connecting the cables.

AC input cabling hole

Cabling hole for the AC input cables (L, N, L, N, PE)

Battery input connection

Connect battery packs to the system.

terminals (BATT1, BATT2,


BATT3) (-48V)
4

Main DC output connection

Connect -48 V terminals of the main DC load.

terminals (MAIN OUTPUT)


(-48V)

2-3
SJ-20120703093141-002|2013-01-08 (R1.2)

ZTE Proprietary and Confidential

ZXDU68 B201 Product Description

S.N.

Component

Description

-48V busbar (-48V)

Working ground busbar

Connects +/RTN cables of battery packs and DC loads.

(+/RTN)
7

AC input connection

Connect AC input cables (L, N, L, N, PE).

terminals (L, N, L, N,

Caution: It is recommended to configure a 50 A circuit breaker

PE)

for each AC input branch to provide AC input power for the


ZXDU68 B201 system.

2.2 ZXD3000 Rectifier


The ZXD3000 (V5.0) rectifiers convert AC to DC, power DC loads and charge the batteries.

Appearance
For the appearance of the ZXD3000 rectifier, see Figure 2-3.
Figure 2-3 Rectifier Appearance

1. Fan

2. Indicators

3. QUY (query) button

Buttons and Indicators


l
l

Press and hold the QUY button of a rectifier for 5 seconds and then the CSU displays
the rectifiers main information screen.
The indicators display the operational status of the rectifier. For a description of the
indicators, refer to Table 2-3.

Table 2-3 Rectifier Operational Status


Indicator
Operational Status
Power
Lit

Run
Lit

Alarm
-

Fault
Not lit

Operating with Stable


Voltage

Flashing

Not lit

Not lit

Sleep

Lit

Flashing

Not lit

Output Current Limit

2-4
SJ-20120703093141-002|2013-01-08 (R1.2)

ZTE Proprietary and Confidential

Chapter 2 System Structure and Components

Indicator
Operational Status
Power

Run

Alarm

Fault

Lit

Flashing

Communication Failure

Lit

Lit

Alarm

Lit

Not lit

Lit

Fault

- means that the status of the indicator is not relevant to the condition.

Interfaces
Input and output interfaces are laid at the back of the rectifier. For the interface layout of
the rectifier, see Figure 2-4. For a description of the pin definitions, refer to Table 2-4.
The interfaces complete the electrical and signal connections between the rectifier and the
ZXDU68 B201 power system.
Figure 2-4 Rectifier Interfaces

Table 2-4 Pin Definitions of Rectifier Interfaces


Interface Name

Pin No.

Signal

Function

Definition
AC input

1-6

Connects the AC input phase cable.

7 - 12

Connects the AC input neutral cable.

18 - 20

PE

Connects the protection ground.

13

Reserved

Phase detection

14

AA

Locates the phase where an operating rectifier is.

15

AB

16

CAN-

interfaces

interfaces
CAN
communication

17

A rectifier communicates with other devices


through the interfaces. For example, a rectifier

CAN+

detection

transmits data to the CSU, and the CSU issues

interfaces

commands to a rectifier.

DC output
interfaces
Hot-plug pins

21 - 28

OUTPUT+

29 - 36

OUTPUT-

37, 38

Hot-plug pin (+)

39, 40

Hot-plug pin (-)

Provide DC output power.

Prevent sparks when a rectifier is installed into


the ZXDU68 B201 system.

2-5
SJ-20120703093141-002|2013-01-08 (R1.2)

ZTE Proprietary and Confidential

ZXDU68 B201 Product Description

2.3 Centralized Supervision Unit


The Centralized Supervision Unit (CSU) is the foreground monitoring unit of the ZXDU68
B201 system. It monitors the AC distribution, DC distribution, rectifiers and batteries of the
ZXDU68 B201 system.

Functions
l

Delayed trigger alarm waits for technicians authorization code before informing the
Supervision Center (SC) of access attempt. This function provides potential reduction
of the SC interventions greatly.
When the door with a door sensor is open, all alarms will be on hold and not sent to
output relays in this case, and the correct 4-digit key code (password) must be input
within a certain time (Login Max.Time, one minute, by default). All alarms are sent
to output relays immediately if the correct key code is not input within the time.

l
l
l
l
l
l

Gives an audible and visual alarm and provides the protection function when the
ZXDU68 B201 system is faulty.
Collects the operational data and monitors the operations of the ZXDU68 B201
system.
Performs advanced battery management with protection functions.
Manages the rectifiers and automatically switches one or more rectifiers to the sleep
mode to save energy.
Transmits data to the background Supervision Center (SC) and receives commands
from the SC. In this way, the ZXDU68 B201 system can be monitored remotely.
The CSU can be remotely managed through a computer installed with web browser
anywhere if Ethernet is available.

Appearance
For the appearance of the CSU, see Figure 2-5.
Figure 2-5 CSU Appearance (CSU500A)

1. LCD
2. USB interface

3. RJ45 Ethernet interface


4. Indicators

5. Buttons

Interfaces
l

USB interface
2-6

SJ-20120703093141-002|2013-01-08 (R1.2)

ZTE Proprietary and Confidential

Chapter 2 System Structure and Components

Supports USB flash drives but does not support portable hard disks, MP3 or MP4.

Use a 2 GB (or below) USB flash drive with available capacity of greater than 32
MB.

RJ45 Ethernet interface

The Ethernet interface rate is 10M/100M (adaptive).

The Ethernet interface supports multiple monitoring networking modes through


Telnet, HTTP, FTP and SNMP.

Indicators
The indicators display the operational status of the CSU and the ZXDU68 B201 system.
For a description of indicators, refer to Table 2-5.
Table 2-5 CSU Operational Status
Indicator
Operational Status
Power

Alarm

Run

Lit

Flashing

Not lit

Operating normally

Lit

Flashing

Alarm

Lit

Lit or not lit

Down

- means that the status of the indicator is not relevant to the condition.

Buttons and LCD


The buttons and the LCD of the CSU enable the users to query operational data of the
ZXDU68 B201 system, set parameters, and control the operation of the ZXDU68 B201
system.
The button names are as follows:
l
l
l

///: up/down/left/right
Ent: enter
Esc: escape

2.4 Signal Interface Unit


The Signal Interface Unit (SIU) contains the Signal Interface Board (SIB). For the structure
of SIU, see Figure 2-6.

2-7
SJ-20120703093141-002|2013-01-08 (R1.2)

ZTE Proprietary and Confidential

ZXDU68 B201 Product Description

Figure 2-6 Signal Interface Unit (SIU)

1. SIB

2. Interface designation

The SIB provides various supervision interfaces including input and output relay
interfaces, background communication interfaces, and environment detection interfaces.
For the layout of the interfaces on the SIB, see Figure 2-7.
Figure 2-7 Supervision Interfaces on the SIB

For a description of the interfaces on the SIB, refer to Table 2-6.

2-8
SJ-20120703093141-002|2013-01-08 (R1.2)

ZTE Proprietary and Confidential

Chapter 2 System Structure and Components

Table 2-6 Supervision Interfaces on the SIB


Interface

Description

Input and Output Relay Interfaces


X3

In-relay 1, 2

X4

In-relay 3, 4

Four input relays.


The users can set the alarms for the input relays in the
Centralized Supervision Unit (CSU).

X14

X15

X16

Out-relay 1

Alarm code A1: critical or major alarm

Out-relay 2

Alarm code A2: door alarm

Out-relay 3

Alarm code A3: AC power abnormal

Out-relay 4

Alarm code A4: ambient temperature high

Out-relay 5

Alarm code A5: minor alarm or warning

Out-relay 6

Alarm code A6: __________________________


Reserved for user definition.

X17

Out-relay 7

Alarm code A7: __________________________


Reserved for user definition.

Out-relay 8

Alarm code A8: __________________________


Reserved for user definition.

X18

CSU fault out-relay

Provides the CSU fault signal

Background Communication Interfaces


X11

RS232 communication

X11 and X13 cannot be used at the same time

X12

RS485 communication

(independent)
X13

RS485 communication

X11 and X13 cannot be used at the same time

(multiplex)
X22

RS232 communication

Multiplex with X11

Environment Detection Interfaces


X2

Flood alarm

To connect a flood sensor

X5

Door magnet alarm

To connect a door sensor

X6

Battery 1 temperature

To connect the temperature sensor for battery pack 1

X7

Battery 2 temperature

To connect the temperature sensor for battery pack 2

X8

Battery 3 temperature

To connect the temperature sensor for battery pack 3

X9

Battery 4 temperature

To connect the temperature sensor for battery pack 4

X10

Environment temperature

To connect an ambient temperature sensor

2-9
SJ-20120703093141-002|2013-01-08 (R1.2)

ZTE Proprietary and Confidential

ZXDU68 B201 Product Description

This page intentionally left blank.

2-10
SJ-20120703093141-002|2013-01-08 (R1.2)

ZTE Proprietary and Confidential

Chapter 3

System Specifications
Table of Contents
Configuration List .......................................................................................................3-1
Environmental Specifications......................................................................................3-2
Technical Specifications .............................................................................................3-2
Compliance Standards ...............................................................................................3-5

3.1 Configuration List


For the configuration list of the ZXDU68 B201 system , refer to Table 3-1.
Table 3-1 Configuration List
Component

Configuration

Chassis

One

Rectifier

ZXD3000 (V5.0)

Four (when fully configured)

Centralized

CSU500A

One (software version: V1.01F)

AC input

No AC input circuit breaker

Supervision Unit
(CSU)
AC distribution

Four AC input connection terminals (L, N, L, N, PE)


Caution: It is recommended to configure a 50 A
circuit breaker for each AC input branch to provide
AC input power for the ZXDU68 B201 system.
Standby AC output

None

Rectifier circuit

None

breaker
AC SPD

None

3-1
SJ-20120703093141-002|2013-01-08 (R1.2)

ZTE Proprietary and Confidential

ZXDU68 B201 Product Description

Component
DC distribution

Configuration
DC input

One 120 A generator input connector (48VDC


GENERATOR)

Battery input circuit

1200 A/2P, 2100 A/1P MCBs

breaker
l

DC output

Main DC output:
Two connection terminals controlled by one 200
A/2P circuit breaker

Auxiliary DC output:
One 50 A DC output connector

DC SPD

None

3.2 Environmental Specifications


For a description of the environmental specifications of the ZXDU68 B201 system, refer
to Table 3-2.
Table 3-2 Environmental Specifications
Item
Operating temperature

Specifications
-4 F to +131 F/-20 C to +55 C (+59 F to +77 F/+15 C to
+25 C, recommended)

Storage temperature

-40 F to +158 F/-40 C to +70 C

Relative humidity

10% to 90% (non-condensing); 40% to 60% recommended

Altitude

0 - 2187 yd (0 - 2000 m): 100% output power

2187 yd 3281 yd (2000 m - 3000 m): The power derating


percentage is 1% for each 100 m increase in altitude.

Other requirements

The cabinet should be stable and erect.

No explosion hazard, no shake or jolt.

Never install the equipment where there is a risk of liquid


or objects falling into the top of the equipment.

No conductive dust or corrosive gas.

No strong Electromagnetic Interference (EMI).

3.3 Technical Specifications


The ZXDU68 B201 system satisfy the following technical specifications.
l
l
l

For the system specifications, refer to Table 3-3.


For AC electrical specifications, refer to Table 3-4.
For DC electrical specifications, refer to Table 3-5.
3-2

SJ-20120703093141-002|2013-01-08 (R1.2)

ZTE Proprietary and Confidential

Chapter 3 System Specifications

l
l

For interface specifications, refer to Table 3-6.


For structure specifications, refer to Table 3-7.

Table 3-3 System Specifications


Item

Description

Rated output power of the system

12 kW (-48 V to -57.6 V)

(when fully configured)


System efficiency

93.5% (30% rated power)

95.5% (50% rated power)

95.5% (100% rated power)

Equipment noise

55 dB(A)

Monitoring networking mode

RS232/RS485 serial port, Ethernet, and transparent


transmission with the communication equipment

Design service time

10 years to 15 years

Electro Magnetic Compatibility

DIN/EN 55022

(EMC)

IEC61000

ESD immunity

Contact: 8 kV. Air: 15 kV

Radiated Susceptibility

10V/M 1 kHz 80% amplitude

(RS)

modulation

Electronic Fast Transients

AC port: 4 kV. DC port and signal

(EFT) Pulse/Burst

port: 2 kV

immunity
Surge immunity

AC port: 6 kV

Conducted susceptibility

3V 1 kHz 80% amplitude


modulation

Voltage dips, interruptions

Class 2

& variations immunity


Conducted emissions

Class A

Radiated emissions

Class A

Table 3-4 AC Electrical Specifications


Item
AC input
features

Specification
AC input mode

Single-phase three-wire (L/N/PE)

AC input voltage

Rated AC input phase voltage: 200 V - 240 V

Phase voltage range: 90 V to 295 V

Rated frequency: 50 Hz/60 Hz

Frequency range: 45 Hz - 66 Hz

AC input frequency

3-3
SJ-20120703093141-002|2013-01-08 (R1.2)

ZTE Proprietary and Confidential

ZXDU68 B201 Product Description

Item

Specification
AC input power

0.998 (with rated load)

factor
Input Total

THD 5% (30% - 100% rated power)

Harmonic Distortion
(THD)
Protection

AC over-voltage

When the input phase voltage is higher than the over-voltage

functions

protection

threshold, the system takes a protection action against


over-voltage.

AC under-voltage

When the input phase voltage is lower than the under-voltage

protection

threshold, the system takes a protection action against


under-voltage.

Table 3-5 DC Electrical Specifications


Item
DC output
features

Specification
DC output voltage

Rated output voltage: -53.5 V

Output voltage

-42 V to -58 V (adjustable in the CSU)

range
DC voltage drop

0.5 V

inside the cabinet


Regulated voltage

0.5%

precision
Weighted

noise

2 mV

noise

150 mV (20 MHz bandwidth)

voltage
Peak-peak
voltage
Protection

DC over-voltage

When the DC output voltage is higher than the over-voltage

functions

protection

threshold, the system takes a protection action against


over-voltage.

DC under-voltage

When the DC output voltage is lower than the under-voltage

protection

threshold, the system takes a protection action against


under-voltage.

Battery under-

Battery Low Voltage Disconnect (BLVD): If the battery voltage

voltage protection

is lower than the BLVD threshold, the system disconnect the


batteries.

3-4
SJ-20120703093141-002|2013-01-08 (R1.2)

ZTE Proprietary and Confidential

Chapter 3 System Specifications

Table 3-6 Interface Specifications


Location

Interface

Description

On the front

USB interface

Supports USB flash drives but does not support portable

panel of the

hard disks, MP3 or MP4.


l

CSU

Use a 2 GB (or below) USB flash drive with available


capacity greater than 32 MB.

Communication

One adaptive 10 M/100 M RJ45 Ethernet interface

interfaces
On the SIB (in

Communication

One RS232 interface, one RS485 interface

the SIU)

interfaces

Baud rate: 1200 bps, 2400 bps, 9600 bps, 19200 bps, 38400
bps, 57600 bps, 115200 bps

Input relay

Four input relays, the user can set the alarms for the input

interfaces

relays in the CSU.

Output relay

Nine output relays

interfaces

Eight for the users to set in the CSU

One for the CSU fault

Environment

Four battery temperature interfaces

detection interfaces

One environment temperature interface

One door alarm interface

One flood alarm interface

Table 3-7 Structure Specifications


Item

Specifications

Chassis dimensions (H W D)

8.6 in. 19.0 in. 14.2 in./219.4 mm 482.6 mm 360 mm

Chassis weight

Approximately 44.1 lb/20 kg (excluding rectifiers and CSU)

ZXD3000 (V5.0) rectifier weight

4.4 lb/2 kg/set, four sets (maximum)

CSU weight

2.9 lb/1.3 kg

Installation mode

Installation in a cabinet/rack

3.4 Compliance Standards


EMC Standards
The ZXDU68 B201 system is in compliance with the following Electromagnetic
Compatibility (EMC) standards:
l
l

EN55022
IEC61000-3-3; IEC61000-3-2; IEC61000-4-2; IEC61000-4-3;
IEC61000-4-6; IEC61000-4-8; and IEC61000-4-11

IEC61000-4-4;

3-5
SJ-20120703093141-002|2013-01-08 (R1.2)

ZTE Proprietary and Confidential

ZXDU68 B201 Product Description

Safety Standards
The ZXDU68 B201 system is in compliance with the UL/IEC/EN 60950 safety standards.

Other Standards
The ZXDU68 B201 system is also in compliance with the following standards:
l
l

The Restriction of Hazardous Substances (RoHS) directive (2002/95/EC) of the


European Union.
This device complies with Part 15 of the FCC Rules. Operation is subject to the following two conditions: (1) this device may not cause harmful interference, and (2) this
device must accept any interference received, including interference that may cause
undesired operations.

3-6
SJ-20120703093141-002|2013-01-08 (R1.2)

ZTE Proprietary and Confidential

Chapter 4

Rectifier Specifications
Table of Contents
Technical Specifications .............................................................................................4-1
Input Features ............................................................................................................4-3
Output Features .........................................................................................................4-4
Power Decrease With High Temperature ....................................................................4-5

4.1 Technical Specifications


For the technical specifications of the ZXD3000 (V5.0) rectifiers, refer to Table 4-1.
Table 4-1 Technical Specifications
Item

Description

AC input

Input mode

Single-phase three-wire (L/N/PE)

Input voltage

Input voltage: 85 V to 295 V

Rated input voltage: 100 V to 240 V

Maximum input current

18 A

Frequency

Frequency: 45 Hz to 66 Hz

Rated frequency: 50 Hz/60 Hz

Input power factor

0.998 (when the input and output values are


rated)

DC output

Maximum output power

3,000 W (when the input voltage is 176 V to 295 V


and the environment temperature is -40 to 55 )

Rated output voltage

53.5 V

Range of output voltage

42 V to 59.5 V
Adjusted through the monitoring unit of the power
system

Output current limit

5 A to 63.5 A
Set through the monitoring unit

Efficiency

Peak efficiency: 96%

Efficiency with the rated load: 95%

Voltage stabilizing accuracy

0.6%

Output weighted noise

2 mV

4-1
SJ-20120703093141-002|2013-01-08 (R1.2)

ZTE Proprietary and Confidential

ZXDU68 B201 Product Description

Item

Description
Broad frequency noise

50 mV (3.4 kHz to 150 kHz)

voltage

20 mV (0.15 MHz to 30 MHz)

Discrete frequency noise

5 mV (3.4 kHz to 150 kHz)

voltage

3 mV (150 kHz to 200 kHz)

2 mV (200 kHz to 500 kHz)

1 mV (0.5 MHz to 30 MHz)

Peak-to-peak noise voltage

200 mV (bandwidth of 0 Hz to 20 MHz)

Inter-rectifier load sharing

The number of the rectifiers that can be connected


in parallel is not less than 30; when the output
current of a single rectifier is 10% to 100% of the
rated value, the output current imbalance of the
rectifiers is not greater than 1.5 A.

Safety

Dielectric strength

protection

2840 VDC voltage of the AC input terminals


to the chassis for one minute: no breakdown
or arc; the stable leakage current is less than
1 mA.

4242 VDC voltage of the AC input terminals


to the DC output terminals for one minute: no
breakdown or arc; the stable leakage current
is less than 1 mA.

707 VDC voltage of the DC output terminals


to the chassis for one minute: no breakdown
or arc; the stable leakage current is less than
1 mA.

707 VDC voltage of other interfaces to the


chassis for one minute: no breakdown or arc;
the stable leakage current is less than 1 mA.

Safety standard

Compliant with IEC60950

Electromagnetic

Compliant with EN55022 Class B and IEC61000

compatibility
Mean time between failures

MTBF 2 105 h

Cooling mode

l
l

Forced cooling;
The fan speed can be adjusted according to
the environment temperature and the working
status of the rectifier.

Environment requirement

Dimensions

Operating temperature: -40 to 75

Storage temperature: -40 to 85

Relative humidity: 95% (non-condensing)

Air pressure: 80 kPa to 106 kPa

41.5 mm 132 mm 300 mm (HWD)


4-2

SJ-20120703093141-002|2013-01-08 (R1.2)

ZTE Proprietary and Confidential

Chapter 4 Rectifier Specifications

Item

Description

Weight

2 kg

4.2 Input Features


Overview
The ZXD3000 (V5.0) rectifier automatically adjusts its operational status according to the
AC input voltage.
The input features include the under-voltage protection, over-voltage protection, and power
limit.

Under-Voltage Protection
When the AC input voltage is lower than the under-voltage threshold, the rectifier
automatically shuts down and provides no output. Meanwhile, the alarm indicator is on.
After the AC input voltage reaches the under-voltage recovery threshold, the rectifier
automatically recovers.
The under-voltage recovery threshold = the AC input under-voltage threshold + the return
difference.
The AC input under-voltage threshold is (85 5) V and the return difference ranges from
8 V to 12 V.

Over-Voltage Protection
When the AC input voltage is higher than the over-voltage threshold, the rectifier
automatically shuts down and provides no output. Meanwhile, the alarm indicator is
on. After the AC input voltage falls to the over-voltage recovery threshold, the rectifier
automatically recovers.
The over-voltage recovery threshold = the AC input over-voltage threshold the return
difference.
The AC input over-voltage threshold is (295 5) V and the return difference ranges from
5 V to 10 V.

Power Limit
The rectifier limits its output power according to the input voltage.
See Figure 4-1 for the power limit feature of the rectifier when the following conditions are
met.
l
l

Environment temperature: -25 to 55


Output voltage of the rectifier: 48 V to 59.5 V
4-3

SJ-20120703093141-002|2013-01-08 (R1.2)

ZTE Proprietary and Confidential

ZXDU68 B201 Product Description

Figure 4-1 Power Limit Feature

1. Under-voltage threshold
(855 V)

2. 55% power (110 V)


3. Maximum power (176 V)

4. Over-voltage threshold
(2955 V)

For the relationship between the AC input voltage and the output power, refer to Table 4-2.
Table 4-2 Relationship Between AC Input Voltage and Output Power
AC Input Voltage

Output Power (Percentage of the Maximum Output Power)

(85 5) V

(85 5) V to 110 V

40% to 55%

110 V to 176 V

55% to 100%

176 V to (295 5) V

100%

> (295 5) V

Maximum output power: 3000 W (when the input voltage is 176 V to 295 V and the environment
temperature is -40 to +55 )

4.3 Output Features


See Figure 4-2 for the output features of the ZXD3000 (V5.0) rectifier when the following
conditions are met.
l
l

AC input voltage of the rectifier: 176 V to 295 V


Environment temperature: -25 to +55

4-4
SJ-20120703093141-002|2013-01-08 (R1.2)

ZTE Proprietary and Confidential

Chapter 4 Rectifier Specifications

Figure 4-2 Output Features

As shown in Figure 4-2, the output features of the rectifier can be concluded as follows:
l
l
l

When the output voltage ranges from 42 V to 48 V, the maximum output current is
constant.
When the output voltage ranges from 48 V to 59.5 V, the maximum output power is
constant.
When the output voltage is lower than 36 V, the rectifier restarts for protection.

When the environment temperature ranges from -25 to +55 and the input voltage
ranges from 85 V to 176 V, the rectifier still has the above output features. However,
because of the power limit feature, when the input voltage ranges from 85 V to 176 V, the
output power cannot reach the highest percentage (100%). Therefore, the input voltage
affects the maximum output power and maximum output current.

4.4 Power Decrease With High Temperature


The feature of power decrease with high temperature refers to that the output power of
the ZXD3000 (V5.0) rectifier decreases with the increase of the environment temperature
when the environment temperature reaches the over-temperature threshold.
For the feature of power decrease with high temperature, see Figure 4-3.

4-5
SJ-20120703093141-002|2013-01-08 (R1.2)

ZTE Proprietary and Confidential

ZXDU68 B201 Product Description

Figure 4-3 Power Decrease With High Temperature

For a description of the feature, refer to Table 4-3.


Table 4-3 Power Decrease With High Temperature
Environment Temperature

Output Power (Percentage of the Maximum Power)

-40 to +55

100%

+55 to 75

The output power decreases with the increase of the temperature


and is not less than 50% when the temperature is 75 .

> 75

0 (the rectifier shuts down for protection against over-temperature)

4-6
SJ-20120703093141-002|2013-01-08 (R1.2)

ZTE Proprietary and Confidential

Chapter 5

Alarm List
For a description of the alarms, refer to Table 5-1 (presently, the alarms marked with a *
do not appear in the CSU).

l
l

l
l

Note:
The software codes A1 to A8 correspond to the eight output relays on the SIB.
Multiple alarms can share one output relay. Each alarm cannot correspond to multiple
output relays but one output relay only. No means that no output relay is assigned
to an alarm.
Except for Total Alarm, the output relay for an alarm will not take effect when its alarm
level is set to Mask.
Except for Access Ctrl.Alm., the output relay for an alarm changes its state and
provides an alarm signal in 30 seconds after the alarm occurs.

Table 5-1 Alarm List


S.N.

Alarm Name

Alarm Level and

Alarm Description

Output Relay
Battery and System Alarms
1

Common Alarm

Default level: Mask

The CSU detects that an alarm occurs.

Default relay: No
2

Batt.Test Fail

Default level: Mask

A battery test is terminated when the battery

Default relay: No

voltage reaches Test Stop Volt. while the


battery capacity does not reach Test Stop Cap.

3*

LLVD1 Alarm

Default level: Critical

The system disconnects the LLVD1 loads

Default relay: A1

(secondary loads) when the system meets one


of the following conditions.
l

With Disconnect Mode set to Batt.Volt.,


the battery voltage is lower than LLVD1
Voltage.

With Disconnect Mode set to


Batt.Rem.Cap., the battery voltage
is lower than LLVD1 Voltage or the
remaining battery capacity is lower than
LLVD1 Capacity.

5-1
SJ-20120703093141-002|2013-01-08 (R1.2)

ZTE Proprietary and Confidential

ZXDU68 B201 Product Description

S.N.

Alarm Name

Alarm Level and

Alarm Description

Output Relay
l

With Disconnect Mode set to PowerOff


Time, the battery voltage is lower than
LLVD1 Voltage or the power-off time is
longer than LLVD1 Duration.

4*

LLVD2 Alarm

Default level: Critical


Default relay: A1

The system disconnects the LLVD2 loads


(primary loads) when the system meets one of
the following conditions.
l

With Disconnect Mode set to Batt.Volt.,


the battery voltage is lower than LLVD2
Voltage.

With Disconnect Mode set to


Batt.Rem.Cap., the battery voltage
is lower than LLVD2 Voltage or the
remaining battery capacity is lower than
LLVD2 Capacity.

With Disconnect Mode set to PowerOff


Time, the battery voltage is lower than
LLVD2 Voltage or the power-off time is
longer than LLVD2 Duration.

CAN Bus Abnormal

Batt.Det.Abnor.

BLVD Alarm

Default level: Mask

The CAN bus cannot send or receive data

Default relay: No

normally due to some communication error.

Default level: Critical

The battery voltage is lower than Test Stop

Default relay: A1

Volt. in the process of the battery test.

Default level: Critical

The system disconnects the batteries when the

Default relay: A1

system meets one of the following conditions.


l

With Disconnect Mode set to Batt.Volt.,


the battery voltage is lower than BLVD
Voltage.

With Disconnect Mode set to


Batt.Rem.Cap., the battery voltage
is lower than BLVD Voltage or the
remaining battery capacity is lower than
BLVD Capacity.

With Disconnect Mode set to PowerOff


Time, the battery voltage is lower than
BLVD Voltage or the power-off time is
longer than BLVD Dura.

8*

LLTD Alarm

Default level: Critical


Default relay: A1

When the environment temperature is lower


than LLTD Env.Temp., the system disconnects
the LLVD1 and LLVD2 loads.

5-2
SJ-20120703093141-002|2013-01-08 (R1.2)

ZTE Proprietary and Confidential

Chapter 5 Alarm List

S.N.

Alarm Name

Alarm Level and

Alarm Description

Output Relay
9*

BHTD Alarm

Default level: Critical

When the battery temperature is higher than

Default relay: A1

BHTD Temp., the system disconnects the


batteries.

10

All Alarm Blocked

Default level: Critical

The system does not display any other

Default relay: A1

real-time alarms. This can be set through


Alm.Ctrl.

11

12*

13

14

Batt.Equal

BMU Comm.Fail

Multi-SMR Alm

Sys. OverL Alm

Default level: Mask

The system charges the batteries in boost

Default relay: No

(equalized) charge mode.

Default level: Mask

The Battery Monitoring Unit (BMU) fails to

Default relay: 0

communicate with the CSU.

Default level: Major

Two or more Switching Mode Rectifiers (SMRs)

Default relay: A1

are faulty or fail to communicate with the CSU.

Default level: Critical

This alarm (system over-load alarm) indicates

Default relay: A1

the following:
l

All rectifier slots are occupied.

All rectifiers are operating properly.

The ratio of the total DC output current


to the sum of the rated output current of
the operating rectifiers is higher than the
system over-load threshold (Sys. OverL
Thre.)

15

Sys. LowCap. Alm

Default level: Critical

This alarm indicates the following:

Default relay: A1

Not all the rectifiers are operating properly.


For example, a DC power system is
equipped with four rectifier slots, but
only two or three rectifiers are operating
normally.

The ratio of the total DC output current


to the sum of the rated output current of
the operating rectifiers is higher than Sys.
OverL Thre.

16

Batt.Cap. NoConfig

Default level: Critical

All the battery capacities are set to values less

Default relay: A1

than 10 Ah in the CSU.

Default level: Major

The mains power fails and there is no standby

Default relay: A3

AC input.

Default level: Mask

The main AC input circuit breaker trips.

AC Alarms
17

18*

AC Power Off

AC In.Switch Off

Default relay: 0

5-3
SJ-20120703093141-002|2013-01-08 (R1.2)

ZTE Proprietary and Confidential

ZXDU68 B201 Product Description

S.N.

Alarm Name

Alarm Level and

Alarm Description

Output Relay
19

20

21

AC Volt.High

AC Volt.Low

AC Phase Lack

Default level: Major

The AC input voltage is higher than AC

Default relay: A3

Volt.H.Thre.

Default level: Major

The AC input voltage is lower than AC

Default relay: A3

Volt.L.Thre.

Default level: Major

The AC input lacks one phase or two.

Default relay: A3
22

23

24*

AC Volt.Imbala.

AC Curr.High

AC Out.Switch Off

Default level: Major

The difference between AC input voltages is

Default relay: A3

greater than AC Volt.Imbala.

Default level: Major

The AC input current is higher than AC

Default relay: A3

Curr.H.Thre.

Default level: Mask

The auxiliary AC output circuit breaker trips.

Default relay: 0
25*

AC SPD Abnor

Default level: Mask

The AC Surge Protection Device (SPD) is

Default relay: No

damaged or not installed.

Default level: Major

The rectifier fan is faulty.

Rectifier Alarms
26

SMR Fan Fault

Default relay: A1
27

SMR Ra.T.H.O

Default level: Major

The temperature of the PFC heat radiator is

Default relay: A1

higher than the maximum radiator temperature


(110 ).

28

29

30

SMR In.V.H.O.

SMR In.V.L.O.

SMR Out.V.H.O.

Default level: Major

The AC input voltage of the rectifier is higher

Default relay: A1

than the maximum input voltage (300 V).

Default level: Major

The AC input voltage of the rectifier is lower

Default relay: A1

than the minimum input voltage (80 V).

Default level: Major

The output voltage of the rectifier is higher than

Default relay: A1

the maximum output voltage (56.6 V to 62 V,


which can be set).

31

32

SMR Out.C.H.

SMR Inter.T.H.

Default level: Major

The output current of the rectifier is higher than

Default relay: A1

the maximum output current (68 A).

Default level: Major

The temperature at the air inlet of the rectifier is

Default relay: A1

higher than the maximum internal temperature


(70 ).

33

SMR Out.Fuse

Default level: Major

The output fuse of the rectifier blows.

Default relay: A1
34

SMR Curr.Share

Default level: Major

When multiple rectifiers are working in parallel,

Default relay: A1

the output current difference between these


rectifiers is greater than the threshold (8 A).

5-4
SJ-20120703093141-002|2013-01-08 (R1.2)

ZTE Proprietary and Confidential

Chapter 5 Alarm List

S.N.

Alarm Name

Alarm Level and

Alarm Description

Output Relay
35

SMR Input Off

Default level: Major

The power input of the rectifier is interrupted.

Default relay: A1
36

37

38

39

PFC Out.V.H.

PFC Out.V.L.

SMR EEPROM

SMR In.Comm F.

Default level: Major

The output voltage of PFC is higher than the

Default relay: A1

threshold (450 V).

Default level: Major

The output voltage of PFC is lower than the

Default relay: A1

threshold (345 V).

Default level: Major

Errors occur when the rectifier reads and writes

Default relay: A1

the EEPROM.

Default level: Major

The communication inside the rectifier fails.

Default relay: A1
40

41

SMR Primy.C.H.

PFC Input C.H.

Default level: Major

The primary current of the transformer is higher

Default relay: A1

than the threshold (28 A).

Default level: Major

Reserved alarm

Default relay: A1
42

43

SMR Start Abr.

SMR In.Fuse

Default level: Major

The starting time of the rectifier exceeds 5

Default relay: A1

minutes.

Default level: Major

The input fuse of the rectifier blows.

Default relay: A1
44

SMR Comm.Fail

Default level: Major

The communication between the rectifier and

Default relay: A1

the CSU is interrupted because the rectifier


is removed or there is some communication
exception.

45

SMR In.Freq.

Default level: Major

The input frequency of the rectifier is too high

Default relay: A1

(higher than 73 Hz) or too low (lower than 40


Hz).

46

SMR Out.V.L.

Default level: Major

The output voltage of the rectifier is lower than

Default relay: A1

the threshold (36 V).

Default level: Major

The DC output voltage is higher than DC

Default relay: A1

Volt.High Thre.

Default level: Major

The DC output voltage is lower than DC

Default relay: A1

Volt.Low Thre.

Default level: Mask

The DC SPD is faulty.

DC Alarms
47

48

49*

DC Volt.High

DC Volt.Low

DC SPD Abnor.

Default relay: No
50

Batt.Volt.Low

Default level: Major

The voltage of a battery pack is lower than

Default relay: A1

Batt.Volt.L.Thre.

5-5
SJ-20120703093141-002|2013-01-08 (R1.2)

ZTE Proprietary and Confidential

ZXDU68 B201 Product Description

S.N.

Alarm Name

Alarm Level and

Alarm Description

Output Relay
51

Batt.Curr.Abr.

Default level: Minor

The rate of the detected battery current to

Default relay: A5

the highest detectable current is greater than


Batt.Curr.Abn.Rate.

52

53

54

Batt.Temp.High

Batt.Temp.Low

Batt.Loop Brk.

Default level: Major

The battery temperature is higher than

Default relay: A1

Batt.Temp.H.Thre.

Default level: Major

The battery temperature is lower than

Default relay: A1

Batt.Temp.L.Thre.

Default level: Critical

The battery loop is disconnected.

Default relay: A1
55

56

Batt.Dischg.

Batt.T.Invalid

Default level: Minor

The battery discharging current is higher than

Default relay: A5

Batt.Dischg Thre.

Default level:

The system is configured with batteries, but

Warning

the battery temperature detection is ineffective.

Default relay: A5

The battery temperature sensor is not installed


or the battery temperature is out of the
detection range.

57*

58*

59*

60*

LLVD1 Extend Brk.

LLVD1 Loop B.

LLVD2 Extend Brk.

BLVD Extend Brk.

Default level: Mask

The circuit breaker or fuse of the extended

Default relay: 0

LLVD1 loop trips or blows.

Default level: Mask

The circuit breaker or fuse of the LLVD1 loop

Default relay: 0

trips or blows.

Default level: Mask

The circuit breaker or fuse of the extended

Default relay: 0

LLVD2 loop trips or blows.

Default level: Mask

The fuse of the extended BLVD loop blows.

Default relay: 0
61

BLVD Loop Brk.

Default level: Major

The fuse of the BLVD loop blows.

Default relay: A1
62

63

64

65

66

Cell Reverse

Block Reverse

Cell Poor

Block Poor

DC.Loop.Brk.

Default level: Major

One or more 2 V batteries are reversely

Default relay: A1

connected.

Default level: Major

One or more 12 V batteries are reversely

Default relay: A1

connected.

Default level: Major

The voltage of one or more 2 V batteries is

Default relay: A1

lower than Cell Volt.Diff.

Default level: Major

The voltage of one or more 12 V batteries is

Default relay: A1

lower than Block Volt.Diff.

Default level: Major

The circuit breaker (or fuse) of the DC output

Default relay: A1

loop trips (or blows).

5-6
SJ-20120703093141-002|2013-01-08 (R1.2)

ZTE Proprietary and Confidential

Chapter 5 Alarm List

S.N.

Alarm Name

Alarm Level and

Alarm Description

Output Relay
67

Load Ext.Brk.

Default level: Major

The circuit breaker (or fuse) of the extended

Default relay: A1

DC output loop trips (or blows).

Default level: Minor

The environment temperature is higher than

Default relay: A4

Env.Temp.H.Thre.

Default level: Minor

The environment temperature is lower than

Default relay: A5

Env.Temp.L.Thre.

Default level: Minor

The environment humidity is higher than

Default relay: A5

Env.Hum.H.Thre.

Default level: Minor

The environment humidity is lower than

Default relay: A5

Env.Hum.L.Thre.

Default level: Major

The sensor detects smog.

Environment Alarms
68

69

70

71

72

Env.Temp.High

Env.Temp.Low

Env.Hum.High

Env.Hum.Low

Smog Alarm

Default relay: A1
73

Flood Alarm

Default level: Major

The sensor detects flood.

Default relay: A1
74

Access Ctrl.Alm.

Default level: Minor

The sensor detects illegal intrusion.

Default relay: A5
75

Door Alarm

Default level: Major

The door with the door status switch is opened.

Default relay: A2
76

Glass Brk.Alm.

Default level: Minor

The sensor detects broken glasses.

Default relay: A5
77

78

Env.Temp.Invalid

Env.Hum.Invalid

Default level: Mask

The environment temperature sensor is

Default relay: No

damaged or not installed.

Default level: Mask

The environment humidity sensor is damaged

Default relay: No

or not installed.

Presently, the alarms marked with a * do not appear in the CSU.

5-7
SJ-20120703093141-002|2013-01-08 (R1.2)

ZTE Proprietary and Confidential

ZXDU68 B201 Product Description

This page intentionally left blank.

5-8
SJ-20120703093141-002|2013-01-08 (R1.2)

ZTE Proprietary and Confidential

Appendix A

Electrical Connection
Diagram
For the simplified block diagram of the ZXDU68 B201 (V5.0R06M09) system operating
principles, see Figure A-1.
Figure A-1 Operating Principles of the System

The system components are described as follows.


l
l
l
l
l

AC distribution unit: The AC distribution unit connects AC input to the system and
distributes AC power.
Rectifiers: The rectifiers convert AC power to DC power.
DC distribution unit: The DC distribution unit provides DC output to the loads and
connects the batteries to the system.
CSU: The Centralized Supervision Unit collects the system operation data and
manages the system.
Batteries: The batteries provides DC power to the loads with mains failure.

For the detailed electrical connection diagram of the ZXDU68 B201 (V5.0R06M09) system,
see Figure A-2.

A-1
SJ-20120703093141-002|2013-01-08 (R1.2)

ZTE Proprietary and Confidential

ZXDU68 B201 Product Description

SJ-20120703093141-002|2013-01-08 (R1.2)

Figure A-2 Electrical Connection Diagram of the ZXDU68 B201 (V5.0R06M09) System

A-2
ZTE Proprietary and Confidential

Glossary
AC
- Alternating Current
BHTD
- Battery High Temperature Disconnect
BLVD
- Battery Low Voltage Disconnect
BMU
- Battery Monitoring Unit
CAN
- Controller Area Network
CSU
- Centralized Supervision Unit
DC
- Direct Current
EMC
- Electro Magnetic Compatibility
EMC
- Electromagnetic Compatibility
EMI
- Electromagnetic Interference
ESD
- Electrostatic Discharge
FTP
- File Transfer Protocol
HTTP
- Hypertext Transfer Protocol
LCD
- Liquid Crystal Display
LLTD
- Load Low Temperature Disconnect
LLVD
- Load Low Voltage Disconnect
MCB
- Miniature Circuit Breaker
I
SJ-20120703093141-002|2013-01-08 (R1.2)

ZTE Proprietary and Confidential

ZXDU68 B201 Product Description

MTBF
- Mean Time Between Failures
PE
- Protective Earth
PFC
- Power Factor Correction
RoHS
- Restriction of Hazardous Substances
SC
- Supervision Center
SIB
- Signal Interface Board
SIU
- Signal Interface Unit
SMR
- Switching Mode Rectifier
SNMP
- Simple Network Management Protocol
SPD
- Surge Protection Device
THD
- Total Harmonic Distortion
USB
- Universal Serial Bus

II
SJ-20120703093141-002|2013-01-08 (R1.2)