SUPERTAPP
APPLICATIONS GUIDE
SuperTAPP System
APPLICATIONS GUIDE
SuperTAPP System
Contents
1.
INTRODUCTION
2.
2.1.
2.2.
2.3.
2.3.1.
2.3.2.
NETWORK REQUIREMENTS
Voltage Standards
Increasing the Network Capability
A Flexible Distribution System
Dissimilar Transformers
Abnormal Feeding Arrangements
1
1
2
3
3
3
3.
3.1.
3.2.
SELECTION OF RELAYS
Existing Installations
New Installations
4
4
4
4.
WIRING DIAGRAMS
5.
5.1.
5.2.
5.3.
5.3.1.
5.3.2.
5.4.
TRANSFORMER GROUPS
Independent Single Transformers
Parallel Transformers
Parallel Transformer Groups
Single Bus-Wire Group Method
Multi Bus-Wire Group Method
Parallel networks
4
4
4
4
5
6
6
6.
6.1.
6.1.1.
6.1.2.
6.2.
6.3.
EMBEDDED GENERATION
Generator Types
Synchronous
Asynchronous (Induction Generators)
Relative Fault Levels
Application of SuperTAPP
6
6
6
6
7
7
7.
8.
8.1.
VOLTAGE TRANSFORMERS
Operational Considerations
7
7
APPLICATIONS GUIDE
SuperTAPP System
1. INTRODUCTION
The comprehensive design of the RVM series of relays and the
TAPP circuitry simplifies the design of a tap change control
system. In order to provide a complete understanding of the
benefits and application this guide includes the use of the RTMU
monitor relay and RTPI tap position indicator when describing
the various applications.
2. NETWORK REQUIREMENTS
For this example the network voltage levels are: 33kV, 11kV
and LV.
Table 1 lists voltage drops starting at the in-feed point, this
example being only one of many, but used here for the purpose
of explanation. The tables use figures for fixed tap distribution
transformers based on a nominal output equivalent to the
statutory voltage and off load adjustment in 2.5% and 5%
steps. In practice the nominal voltage of fixed tap transformers
is higher than the statutory voltage, giving a fixed boost over the
levels used in this example.
At Source
Remote End
No Load
Full Load
No Load
-7
-7
+7
+7
11kV System
-8
11kV / LV Transformer
-1.5
-1.5
LV System
-7.0
Total
-1.5
-16.5
1.5
Full Load
16.5
APPLICATIONS GUIDE
SuperTAPP System
2.2. Increasing the Network Capability
At Source
Remote End
No Load
Full Load
No Load
-7
-7
-2.5
+4.5
-2.5
+4.5
+5
11kV System
-8
11kV / LV Transformer
-1.5
-1.5
LV System
-7
-2.5
-2.5
-14
Total
3.5
Full Load
11.5
APPLICATIONS GUIDE
SuperTAPP System
Voltage
Boost
Voltage
Monitor
Blocking
Full Load
Source Voltage A
32.6kV
Source Voltage B
33.4kV
10MVA
8%
Figure 2
Table 3
Source A
Source B
1 circ
C
Figure 1
3
APPLICATIONS GUIDE
SuperTAPP System
3. SELECTION OF RELAYS
The method has two other advantages. The CT's for each
transformer do not have to be in the same phase and other
manufacturers relays can be incorporated into the overall
scheme provided they can be configured for Reverse Reactance
mode.
RVM
RVM
4. WIRING DIAGRAMS
5. TRANSFORMER GROUPS
Summation
Buswires
RVM
RVM
The simplest method of voltage control is to not use any buswires at all, Figure 3. Each transformer at a site is allowed to
operate independently of others. Any circulating current
between transformers connected in parallel on the same busbar will bias the SuperTAPP relays to operate in a direction
which will reduce the circulating current to a minimum.
APPLICATIONS GUIDE
SuperTAPP System
5.3.1. Single Bus-Wire Group Method
This method has the advantage that the effective LDC value is
maintained when any of the transformers is switched out of
service. Furthermore if different basic settings and/or different
LDC settings have been applied to the different groups then the
correct compromise values will automatically be produced
(based on the average) when the bus-bars are paralleled or the
transformers are re-grouped.
This is probably the best all round scheme allowing both the
proper use of LDC and 100% flexibility in the system running
arrangement with very little compromise. SuperTAPP is unique
in providing this level of flexibility and simplicity with such a
small compromise in performance.
Summation
Buswires
RVM
RVM
RVM
RVM
X
X
X
Normally
Closed
APPLICATIONS GUIDE
SuperTAPP System
3
5.3.3
6. EMBEDDED GENERATION
Optional
Summation
Buswires
Summation
Buswires
RVM
Summation
Buswires
RVM
RVM
RVM
X
X
X
Normally
Open
APPLICATIONS GUIDE
SuperTAPP System
around 0.96/0.97 (15) lagging, therefore, the error starts to be
significant.
APPLICATIONS GUIDE
SuperTAPP System
This ensures that the transformer to be restored (the follower)
will be kept on a similar tap to the master. This method does
not, however, always ensure the best result. At medium to high
substation loading there will be a significant step increase in
voltage at the instant the idle transformer is restored to service
due to the voltage drop being suddenly halved.
3 Phase
Power
Supply
Isolator
Master Lockout
Relay Trip Coil
(Runaway Prevention)
Overload
Raise
Contactor
Lower
Contactor
Raise
Lower
Limit Switches
Maintaining Switch
Driven by Mechanism
Operating
Handle
Interlock
Motor
APPLICATIONS GUIDE
SuperTAPP System
Note:
CT & VT Earthing
not shown
TRANSFORMER
4, 5 or 6
S1
CT
S2
10
RVM Relay
21
22
a b c
VT
21B
21C
RTMU Relay
21A
Phase Rotation
A-B-C
3
APPLICATIONS GUIDE
SuperTAPP System
Local
Remote
11
RTMU/1m
Lower
Raise
26
24/25
23
20
19
VC Relay
12
15
16
17
Voltage Inhibit
V High
V Low
Lower
18
14
DSS Closed
during tap
change
Raise
11
Manual
24
20
10
Auto
Pulse
Detection
23
19
RTMU/1m
Step by Step
Lower
Raise
Motor
Contactors
Limit
Switches
Operating
handle
Interlock
DSS Open
during tap
change
APPLICATIONS GUIDE
SuperTAPP System
Moving Contact
Top Tap
Tap 1
12
RTMU - BCD TPI
33 -20
32 -10
31 -8
30 -4
29 -2
28 -1
27
26
25
27
26
25
3%
1.5%
-6%
-3%
34
33
32
31
30 common
3
APPLICATIONS GUIDE
SuperTAPP System