RCCB
http://electrical- engineering- portal.com/what- is- the- difference- between- mcb- mccb- elcb- and- rccb
jiguparmar
Characteristics
Rated current not more than 100 A.
Trip charact erist ics normally not adjustable.
Thermal or thermal-magnetic operation.
Top
Characteristics
Rated current up to 1000 A.
Trip current may be adjustable.
Thermal or thermal-magnetic operation.
Top
Characteristics
Phase (line) and Neut ral both wires connected through RCD.
It trips the circuit when there is earth fault current.
The amount of current flows through the phase (line) should return through neutral .
It detects by RCD. any mismatch between two currents flowing through phase and neutral
detect by -RCD and trip the circuit within 30Miliseconed.
If a house has an earth system connected to an earth rod and not the main incoming
cable, then it must have all circuits protected by an RCD (because u mite not be able to
get enough fault current to trip a MCB)
RCDs are an extremely effective form of shock protection
The most widely used are 30 mA (milliamp) and 100 mA devices. A current flow of 30 mA (or
0.03 amps) is sufficiently small that it makes it very difficult to receive a dangerous shock. Even
100 mA is a relatively small figure when compared to the current that may flow in an earth fault
without such protection (hundred of amps)
A 300/500 mA RCCB may be used where only fire protection is required. eg., on lighting circuits,
where the risk of electric shock is small.
Top
Limitation of RCCB
St andard elect romechanical RCCBs are designed t o operat e on normal supply
wavef orms and cannot be guaranteed to operate where none standard waveforms are
generated by loads. The most common is the half wave rectified waveform sometimes
called pulsating dc generated by speed control devices, semi conductors, computers and
even dimmers.
Specially modified RCCBs are available which will operate on normal ac and pulsating dc.
RCDs dont of f er prot ect ion against current overloads: RCDs detect an imbalance in
the live and neutral currents. A current overload, however large, cannot be detected. It is a
frequent cause of problems with novices to replace an MCB in a fuse box with an RCD.
This may be done in an attempt to increase shock protection. If a live-neutral fault occurs
(a short circuit, or an overload), the RCD wont trip, and may be damaged. In practice, the
main MCB for the premises will probably trip, or the service fuse, so the situation is unlikely
to lead to catastrophe; but it may be inconvenient.
It is now possible to get an MCB and and RCD in a single unit, called an RCBO (see below).
Replacing an MCB with an RCBO of the same rating is generally safe.
Nuisance t ripping of RCCB: Sudden changes in electrical load can cause a small, brief
current flow to earth, especially in old appliances. RCDs are very sensitive and operate
very quickly; they may well trip when the motor of an old freezer switches off. Some
equipment is notoriously `leaky, that is, generate a small, constant current flow to earth.
Some types of computer equipment, and large television sets, are widely reported to
cause problems.
RCD will not prot ect against a socket out let being wired wit h it s live and neut ral
t erminals the wrong way round.
RCD will not prot ect against t he overheat ing that results when conductors are not
properly screwed into their terminals.
RCD will not prot ect against live-neut ral shocks, because the current in the live and
neutral is balanced. So if you touch live and neutral conductors at the same time (e.g.,
both terminals of a light fitting), you may still get a nasty shock.
Top
Characteristics
Phase (line), Neutral and Earth wire connected through ELCB.
ELCB is working based on Earth leakage current.
Operating Time of ELCB:
The safest limit of Current which Human Body can withstand is 30ma sec.
Suppose Human Body Resistance is 500 and Voltage to ground is 230 Volt.
The Body current will be 500/230=460mA.
Hence ELCB must be operated in 30maSec/460mA = 0.65msec
Top
MCB Selection
The first characteristic is the overload which is intended to prevent the accidental
overloading of the cable in a no fault situation. The speed of the MCB tripping will vary
with the degree of the overload. This is usually achieved by the use of a thermal device in
the MCB.
The second characteristic is the magnetic fault protection, which is intended to operate
when the fault reaches a predetermined level and to trip the MCB within one tenth of a
second. The level of this magnetic trip gives the MCB its type characteristic as follows:
Type
Tripping Current
Operating Time
Type B
0.04 To 13 Sec
Type C
0.04 To 5 Sec
Type D
0.04 To 3 Sec
The third characteristic is the short circuit protection, which is intended to protect against
heavy faults maybe in thousands of amps caused by short circuit faults.
The capability of the MCB to operate under these conditions gives its short circuit rating
in Kilo amps (KA). In general for consumer units a 6KA fault level is adequate whereas for