What is the difference between MCB, MCCB, ELCB, and

RCCB
http://electrical- engineering- portal.com/what- is- the- difference- between- mcb- mccb- elcb- and- rccb

jiguparmar

MCB (Miniature Circuit Breaker)

Characteristics
Rated current not more than 100 A.
Trip charact erist ics normally not adjustable.
Thermal or thermal-magnetic operation.
Top

MCCB (Moulded Case Circuit Breaker)

February 25, 2013

Characteristics
Rated current up to 1000 A.
Trip current may be adjustable.
Thermal or thermal-magnetic operation.
Top

Air Circuit Breaker


Characteristics
Rated current up to 10,000 A.
Trip characteristics often fully adjustable including configurable trip thresholds and delays.
Usually electronically controlledsome models are microprocessor controlled.
Often used for main power distribution in large industrial plant, where the breakers are
arranged in draw-out enclosures for ease of maintenance.
Top

Vacuum Circuit Breaker


Characteristics
With rated current up to 3000 A,
These breakers interrupt the arc in a vacuum bottle.
These can also be applied at up to 35,000 V. Vacuum circuit breakers tend to have
longer life expectancies between overhaul than do air circuit breakers.
Top

RCD (Residual Current Device / RCCB(Residual Current Circuit


Breaker)

Characteristics

Phase (line) and Neut ral both wires connected through RCD.
It trips the circuit when there is earth fault current.
The amount of current flows through the phase (line) should return through neutral .
It detects by RCD. any mismatch between two currents flowing through phase and neutral
detect by -RCD and trip the circuit within 30Miliseconed.
If a house has an earth system connected to an earth rod and not the main incoming
cable, then it must have all circuits protected by an RCD (because u mite not be able to
get enough fault current to trip a MCB)
RCDs are an extremely effective form of shock protection
The most widely used are 30 mA (milliamp) and 100 mA devices. A current flow of 30 mA (or
0.03 amps) is sufficiently small that it makes it very difficult to receive a dangerous shock. Even
100 mA is a relatively small figure when compared to the current that may flow in an earth fault
without such protection (hundred of amps)
A 300/500 mA RCCB may be used where only fire protection is required. eg., on lighting circuits,
where the risk of electric shock is small.
Top

Limitation of RCCB
St andard elect romechanical RCCBs are designed t o operat e on normal supply
wavef orms and cannot be guaranteed to operate where none standard waveforms are
generated by loads. The most common is the half wave rectified waveform sometimes
called pulsating dc generated by speed control devices, semi conductors, computers and
even dimmers.
Specially modified RCCBs are available which will operate on normal ac and pulsating dc.
RCDs dont of f er prot ect ion against current overloads: RCDs detect an imbalance in
the live and neutral currents. A current overload, however large, cannot be detected. It is a
frequent cause of problems with novices to replace an MCB in a fuse box with an RCD.
This may be done in an attempt to increase shock protection. If a live-neutral fault occurs
(a short circuit, or an overload), the RCD wont trip, and may be damaged. In practice, the
main MCB for the premises will probably trip, or the service fuse, so the situation is unlikely
to lead to catastrophe; but it may be inconvenient.
It is now possible to get an MCB and and RCD in a single unit, called an RCBO (see below).
Replacing an MCB with an RCBO of the same rating is generally safe.
Nuisance t ripping of RCCB: Sudden changes in electrical load can cause a small, brief
current flow to earth, especially in old appliances. RCDs are very sensitive and operate
very quickly; they may well trip when the motor of an old freezer switches off. Some
equipment is notoriously `leaky, that is, generate a small, constant current flow to earth.
Some types of computer equipment, and large television sets, are widely reported to
cause problems.
RCD will not prot ect against a socket out let being wired wit h it s live and neut ral
t erminals the wrong way round.
RCD will not prot ect against t he overheat ing that results when conductors are not
properly screwed into their terminals.

RCD will not prot ect against live-neut ral shocks, because the current in the live and
neutral is balanced. So if you touch live and neutral conductors at the same time (e.g.,
both terminals of a light fitting), you may still get a nasty shock.
Top

ELCB (Earth Leakage Circuit Breaker)

Characteristics
Phase (line), Neutral and Earth wire connected through ELCB.
ELCB is working based on Earth leakage current.
Operating Time of ELCB:
The safest limit of Current which Human Body can withstand is 30ma sec.
Suppose Human Body Resistance is 500 and Voltage to ground is 230 Volt.
The Body current will be 500/230=460mA.
Hence ELCB must be operated in 30maSec/460mA = 0.65msec
Top

RCBO (Residual Circuit Breaker with OverLoad)


It is possible to get a combined MCB and RCCB in one device (Residual Current Breaker
with Overload RCBO), the principals are the same, but more styles of disconnection are
fitted into one package
Top

Dif f erence between ELCB and RCCB


ELCB is the old name and often refers to voltage operated devices that are no longer
available and it is advised you replace them if you find one.
RCCB or RCD is the new name that specifies current operated (hence the new name to

distinguish from voltage operated).


The new RCCB is best because it will detect any earth fault. The voltage type only
detects earth faults that flow back through the main earth wire so this is why they
stopped being used.
The easy way to tell an old voltage operated trip is to look for the main earth wire
connected through it.
RCCB will only have the line and neutral connections.
ELCB is working based on Earth leakage current. But RCCB is not having sensing or
connectivity of Earth, because fundamentally Phase current is equal to the neutral current
in single phase. Thats why RCCB can trip when the both currents are deferent and it
withstand up to both the currents are same. Both the neutral and phase currents are
different that means current is flowing through the Earth.
Finally both are working for same, but the thing is connectivity is difference.
RCD does not necessarily require an earth connection itself (it monitors only the live and
neutral).In addition it detects current flows to earth even in equipment without an earth of
its own.
This means that an RCD will continue to give shock protection in equipment that has a
faulty earth. It is these properties that have made the RCD more popular than its rivals.
For example, earth-leakage circuit breakers (ELCBs) were widely used about ten years
ago. These devices measured the voltage on the earth conductor; if this voltage was not
zero this indicated a current leakage to earth. The problem is that ELCBs need a sound
earth connection, as does the equipment it protects. As a result, the use of ELCBs is no
longer recommended.
Top

MCB Selection
The first characteristic is the overload which is intended to prevent the accidental
overloading of the cable in a no fault situation. The speed of the MCB tripping will vary
with the degree of the overload. This is usually achieved by the use of a thermal device in
the MCB.
The second characteristic is the magnetic fault protection, which is intended to operate
when the fault reaches a predetermined level and to trip the MCB within one tenth of a
second. The level of this magnetic trip gives the MCB its type characteristic as follows:

Type

Tripping Current

Operating Time

Type B

3 To 5 time full load current

0.04 To 13 Sec

Type C

5 To 10 times full load current

0.04 To 5 Sec

Type D

10 To 20 times full load current

0.04 To 3 Sec

The third characteristic is the short circuit protection, which is intended to protect against
heavy faults maybe in thousands of amps caused by short circuit faults.
The capability of the MCB to operate under these conditions gives its short circuit rating
in Kilo amps (KA). In general for consumer units a 6KA fault level is adequate whereas for

industrial boards 10KA fault capabilities or above may be required.


Top

Fuse and MCB characteristics


Fuses and MCBs are rated in amps. The amp rating given on the fuse or MCB body is the
amount of current it will pass continuously. This is normally called the rated current or
nominal current.
Many people think that if the current exceeds the nominal current, the device will trip,
instantly. So if the rating is 30 amps, a current of 30.00001 amps will trip it, right? This is
not true.
The fuse and the MCB, even though their nominal currents are similar, have very different
properties.
For example, For 32Amp MCB and 30 Amp Fuse, to be sure of tripping in 0.1 seconds, the
MCB requires a current of 128 amps, while the fuse requires 300 amps.
The fuse clearly requires more current to blow it in that time, but notice how much bigger
both these currents are than the 30 amps marked current rating.
There is a small likelihood that in the course of, say, a month, a 30-amp fuse will trip when
carrying 30 amps. If the fuse has had a couple of overloads before (which may not even
have been noticed) this is much more likely. This explains why fuses can sometimes blow
for no obvious reason
If the fuse is marked 30 amps, but it will actually stand 40 amps for over an hour, how
can we justify calling it a 30 amp fuse? The answer is that the overload characteristics of
fuses are designed to match the properties of modern cables. For example, a modern
PVC-insulated cable will stand a 50% overload for an hour, so it seems reasonable that
the fuse should as well.