TCE CONSULTING ENGINEERS LIMITED

30421007-3CL-00007P0A

SIZING REPORT FOR NEUTRAL GROUNDING


RESISTOR OF 33/4.16kV STATION TRANSFORMER

SHEET i OF i

SAUDI ELECTRICITY COMPANY


EASTERN OPERATING AREA
Dammam, Saudi Arabia
GENERATION EXPANSION OF ARAR POWER PLANT
(CONTRACT NO :30421007/00)
DESIGN BASIS
FOR
NEUTRAL GROUNDING RESISTOR
OF 33/4.16kV STATION TRANSFORMER
DOCUMENT NO. : 30421007-3CL-00007-P0A
JULY 2004

ENGINEERING CONSULTANT
TCE CONSULTING ENGINEERS LIMITED
73/1, ST. MARKS ROAD
BANGALORE 560 001
INDIA

CONTRACTOR:
AL-TOUKHI COMPANY FOR INDUSTRY & TRADING
P.O. BOX 497, RIYADH 11411, KINGDOM OF SAUDI ARABIA
TEL. 00966-1-4633660 : FAX. 009661-4631150

P0A
29-07-2004

DG

SR

REV NO . DATE

PREPARED BY

CHECKED BY

CLEARED BY

APPROVED BY

FILENAME : NGR sizing for Arar.doc

TCE FORM 032 R1

TCE CONSULTING ENGINEERS LIMITED


30421007-3CL-00007P0A

CONTENTS

SIZING REPORT FOR NEUTRAL GROUNDING


RESISTOR OF 33/4.16kV STATION TRANSFORMER

SHEET i OF i

CONTENTS

CLAUSE No.

DESCRIPTION

PAGE No.

1.0

INTRODUCTION

2.0

OBJECT

3.0

REFERENCES

4.0

SIZING CALCULATION

5.0

CONCLUSIONS

ISSUE
A
FILE NAME: F120R1

FORM NO. 120 R1

TCE CONSULTING ENGINEERS LIMITED


30421007-3CL-00007P0A

SIZING REPORT FOR NEUTRAL GROUNDING


RESISTOR OF 33/4.16kV STATION TRANSFORMER

WRITEUP
SHEET 1 OF 4

1.0

INTRODUCTION:

1.1

Al-Toukhi company for Industry & Trading has been awarded turnkey
contract for Open Cycle Gas Turbine based CPS expansion project at
Arar of Saudi Electric Company-Eastern Operation Area (SEC-EOA),
Saudi Arabia.

1.2

The project consists of design, engineering, procurement, installation,


testing and commissioning of two (2) Nos. 60.16MW @ 50?C, PG7121
(EA) model Gas Turbine Generator unit of GE make along with
associated Generator Transformer and other balance of plant electromechanical equipment.

ISSUE
A
FILE NAME: F120R1

FORM NO. 120 R1

TCE CONSULTING ENGINEERS LIMITED


30421007-3CL-00007P0A

SIZING REPORT FOR NEUTRAL GROUNDING


RESISTOR OF 33/4.16kV STATION TRANSFORMER

WRITEUP
SHEET 2 OF 4

2.0

OBJECT:

2.1

The object of this report is to determine the following :

2.1.1

The rating of Neutral grounding Resistor for 33/4.16kV Station


Transformers.

ISSUE
A
FILE NAME: F120R1

FORM NO. 120 R1

TCE CONSULTING ENGINEERS LIMITED


30421007-3CL-00007P0A

SIZING REPORT FOR NEUTRAL GROUNDING


RESISTOR OF 33/4.16kV STATION TRANSFORMER

WRITEUP
SHEET 3 OF 4

3.0

REFERENCES:

3.1

Key One Line Diagram: Drawing No.30421007-E3-00001-P0A.

3.2

SEC-EOAs Drawing No. KT-808215 Rev A.

ISSUE
A
FILE NAME: F120R1

FORM NO. 120 R1

TCE CONSULTING ENGINEERS LIMITED


30421007-3CL-00007P0A

4.0

WRITEUP

SIZING REPORT FOR NEUTRAL GROUNDING


RESISTOR OF 33/4.16kV STATION TRANSFORMER

SHEET 4 OF 4

SIZING CALCULATION :
Neutral Grounding Resistor Sizing for Station Transformer

4.1

Neutral Grounding Resistor of 33/4.16kV Station Transformer shall


be sized to limit the earth fault current to 400A for 1 minute as
indicated in SEC-EOAs drawing No.KT-808215 Rev A attached
with Specification PTS-1022.

4.2

The Resistance value of the Resistor is calculated as per the


following equation:
Resistance ( R ) in ohms =

EL
3

x I

where E L = Line to Line voltage in volts

4.16kV

I = 400A for 1 minute as per Cl.No.5.6.1 above.


Resistance ( R ) in ohms

= 4.16 x 1000/ 1.732 x 400


= 6 ohms

4.3

Hence, 6 Ohms, Neutral grounding resistor rated to carry 400A for


one minute has been selected.

5.0

CONCLUSION:

5.1

The final selected ratings of NGR for Station transformer is


tabulated below
Sl.No.

Parameter

Unit

NGR

Resistance

ohms

Current Rating

400 for 60
seconds

Reference
As per Cl No.4.3
above
As per Cl No.4.3
above

ISSUE
A
FILE NAME: F120R1

FORM NO. 120 R1