053-149 Issue 1

TYPICAL WIRING DIAGRAM

DEEP SEA ELECTRONICS PLC


DSEP100 Installation Instructions

DSEP100 is used to detect mains failure when in


parallel and disconnect the mains supply from the the
local supply in line with common international
requirements.
Typical applications able to benefit from DSEP100
are:

Peak Lopping
Fixed Export
Short Term Operating Reserve (STOR)
No Break, Seamless Or Closed Transition
Commerical And Domestic Local Power
Generation.

The DSEP100 is intended to be placed into the


application wiring in such a way as to decouple the
mains and the generator supplies in case of a mains
failure when in parallel.
Depending upon the requirements of the system, the
relay is used to open the mains breaker, generator
breaker or both.
Additionally, any other control logic placed between
the DSEP100 and the breakers being controlled must
also be designed with fast operation in mind. The
combined time between the DSEP100 detecting the
fault, and the time of the breaker opening must be
within the specification of the legislation in place at the
site. This legislation differs between countries.
DIMENSIONS AND MOUNTING
DIN rail mounting EN50022 35mm type only
DIMENSIONS OVERALL SIZE
157 mm x 95 mm x 67 mm (6.18 x 3.74 x 2.64)

Deep Sea Electronics Plc.

Deep Sea Electronics inc.

Tel:+44 (0)1723 890099


Fax: +44 (0)1723 893303
Email: support@deepseaplc.com
Web: www.deepseaplc.com

Phone: +1 (815) 316-8706


Fax: +1 (815) 316- 8708
TOLL FREE (USA) : Tel: 1 866 636 9703
Email: dsesales@deepseausa.com
Web: www.deepseausa.com

ACCESSING THE MAIN CONFIGURATION EDITOR

ADJUSTABLE PARAMETERS

Main Editor Configuration Table (continued)

Main Editor Configuration Table


NOTE: A means of attaching a small padlock or utility company
seal is provided. When attached, this prevents the settings
being changed either from the Main Configuration Editor or via
Configuration Suite PC Software.

Press the
(Reset) and
(Tick) buttons
simultaneously. This is not possible when the setting lock is
activated.

If a module security PIN has been


set, the PIN number request is
then shown.

Press the
(Tick) button the first digit will flash to enable
the pin to be entered.

Press

Press
(Right) when the first digit is correctly entered.
The digit just entered will now show # for security.

Repeat this process for the other digits of the PIN. Press

(Up) or

(Down) to adjust it to the correct value.

(Left) to move back to adjust one of the previous digits.

When
(Tick) is pressed after editing the final PIN digit,
the PIN is checked for validity. If the number is not correct,
the PIN must be re-entered.
If the PIN has been
successfully entered (or the
module PIN has not been
enabled), the editor is
displayed :
For details how to edit parameters, see the section entitled
Editing A Parameter In The Main And Display Editor
elsewhere in this document.

ACCESSING THE DISPLAY EDITOR CONFIGURATION

Press and hold the

(Tick) button.

For details how to edit parameters, see the section entitled


Editing A Parameter In The Main And Display Editor
elsewhere in this document.

Section Parameter As Shown On Display


Display Contrast
Language
Current Date And Time
Timers LCD Page Timer
Scroll Delay
Under Voltage Stage 1
Under Voltage Stage 2
Over Voltage Stage 1
Over Voltage Stage 2
Under Frequency Stage 1
Under Frequency Stage 2
Over Frequency Stage 1
Over Frequency Stage 2
Mains ROCOF Delay
Over Zero Seq Volts Delay
Under Positive Seq Volts Delay
Over Negative Seq Volts Delay
Asymmetry High Delay
Auto-Reset Delay
Fast Reset Window
Fast Reset Delay
Supervision Delay
Mains
Nominal Voltage
Under Voltage Stage 1
Under Voltage Stage 1
Under Voltage Stage 2
Under Voltage Stage 2
Over Voltage Stage 1
Over Voltage Stage 1
Over Voltage Stage 2
Over Voltage Stage 2
High Average Voltage
High Average Voltage
Nominal Frequency
Under Frequency Stage 1
Under Frequency Stage 1
Under Frequency Stage 2
Under Frequency Stage 2
Over Frequency Stage 1
Over Frequency Stage 1 Trip
Over Frequency Stage 1 Return
Over Frequency Stage 2
Over Frequency Stage 2
Mains ROCOF
Mains ROCOF Hz/S
Mains ROCOF Cycles
Mains Vector Shift
Main Vector Shift
Over Zero Seq Volts
Over Zero Seq Volts
Under Positive Seq Volts
Under Positive Seq Volts
Over Negative Seq Volts
Over Negative Seq Volts

Values
0%
English, others.
dd mmm yyyy, hh:mm:ss
0h 0m 0s
0h 0m 0s
0.0s
0.0s
0.0s
0.0s
0.0s
0.0s
0m 0.0s
0.0s
0.0s
0m 0.0s
0m 0.0s
0m 0.0s
0m 0.0s
0h 0m 00.0s
0.0s
0.0s
0h 0m 0.0s
000.0V
Active / Inactive
000.0V
Active / Inactive
000.0V
Active / Inactive
000.0V
Active / Inactive
000.0V
Active / Inactive
000.0V
00.0Hz
Active / Inactive
00.0Hz
Active / Inactive
00.0Hz
Active / Inactive
00.0Hz
00.0Hz
Active / Inactive
00.0Hz
Active / Inactive
0.00Hz
0
Active / Inactive
0.0
Active / Inactive
00.0V
Active / Inactive
00.0V
Active / Inactive
00.0V

Section
Parameter As Shown On Display
Mains
Asymmetry High
Continued
Asymmetry High
Phase Rotation Wrong
Auto-Reset
Reset If Unhealthy
Fast Reset
Alt. Config Config To Edit

Values
Active / Inactive
00.0V
Active / Inactive
Active / Inactive
Active / Inactive
Active / Inactive
Default Config /
Alternative Config

Display Editor Configuration Table


Section
Display

Parameter As Shown On Display


Contrast
Language

Values
0%
English, Others.

EDITING A PARAMETER IN THE MAIN AND DISPLAY


EDITOR

Enter the editor as described above.

Press the
(Left) or
to view/change.

Press
(Up) or
(Down) to cycle to the parameter
within the section that has been chosen.

To edit the parameter, press


(Tick) to enter edit mode.
The parameter begins to flash to indicate the value is being
edited.

Press the
(Up) or
(Down) buttons to change the
parameter to the required value.

Press
(Tick) to save the value. The parameter ceases
flashing to indicate that it has been saved.

(Right) to cycle to the section

EXITING THE MAINS AND DISPLAY EDITOR

To exit the editor saving changes. Press and hold the


(Tick) button.
To exit the editor without saving changes, press and hold
the

(Reset) button.

NOTE: When the editor is visible, it is automatically exited after


5 minutes of inactivity to ensure security.
NOTE: The PIN is automatically reset when the editor is exited
(manually or automatically) to ensure security.