NSK5 TEST REPORT

5HYN589267-TA

CLIENT

____________________________________

ABB ORDER NO.

____________________________________

STATION

____________________________________

DIRECTION

____________________________________

CABINET NO.

____________________________________

NSK 5 SERIAL NO.

____________________________________

ETL SERIAL NO.

____________________________________

TESTED BY : ________________

Edition: 03
June 2012

DATE : ______________

1 of 5

NSK5 TEST REPORT

5HYN589267-TA

SAFETY INSTRUCTIONS
Electrical Safety
WARNING

Energy hazard

The 48 V d.c. supply or any voltage converter can deliver high currents.
The DC supply can deliver high currents. Remove all rings, watches and other
metal jewellery before removing cover. Do not bridge connectors with tools, etc.

CAUTION

Static sensitive devices

The cards contain static sensitive devices. These devices are sensitive to static
electricity and must be protected by special handling and packaging.

2 of 5

NSK5 TEST REPORT

5HYN589267-TA

Designations and abbreviations used


Designation

Meaning

#
(.....)
[.....]
[X]
{ }
CTS
DCD
DTR
ETL
fc
fs
LED
LHS
mark
N?
PLC
RHS
RTS
RX
RXD
S3:10
S4
space
SS
TVN
TVP
TX
TXD
USA
USB
X2
X6
XT?
XT1
XT2
XT3
XT4

programming only for G4AF modem


measured value
programmed value
checked
designation of measuring point
clear to send - modem output signal (X6 pin 5)
data carrier detect - modem output signal (X6 pin 8)
DTE ready - modem input signal (X6 pin 20)
power line carrier transmission system
center frequency
frequency shift (from center frequency)
light emitting diode found on the front panel
left hand side
low voltage level; lower frequency shift; logic 1
position in tier
power line carrier
right hand side
request to send - modem input signal (X6 pin 4)
receiver
receiver data (X6 pin 3)
DIL switch on modems printed circuit board
toggle switch on front panel of modem
high voltage level; higher frequency shift; logic 0
select standby - modem input signal (X6 pin 11)
test voltage negative - a modem output signal (X6 pin 10)
test voltage positive - a modem output signal (X6 pin 9)
transmitter
transmitted data (X6 pin 2)
main modem and alarm supply
optional separate alarm supply
connector on back of modem
RS-232-D data connector on front panel of modem
measuring point on front panel of modem
main transmitter
standby transmitter
main receiver
standby receiver

Note that the designation main line on the G4AF modem is equivalent to line on the G4AE modem.
Test points
The test points and the line connections are in parallel so the tests can be performed
using the test points XT1 to XT4 or the line connections X8 and, for the G4AF modem, X9.
X8:

1a
1b
3a
3b

LHS XT1
RHS XT1
LHS XT3
RHS XT3

X9:

2a
2b
4a
4b

LHS XT2
RHS XT2
LHS XT4
RHS XT4

3 of 5

NSK5 TEST REPORT

Modem position: N............

Tier:

5HYN589267-TA

ETL [ ]

NSK5 [ ]

Baud rate _________________


1.

Preparation
Type of modem
(Strike out whichever not applicable)
-

Terminate the main transmitter output (1a, 1b)


with the correct impedance depending on the bridge setting:

Terminate the standby transmitter output (2a, 2b)


with the correct impedance depending on the bridge setting:

Visual check

2.1

LEDs on modem

2.1.1
2.1.2
2.1.3

TXD LED
RXD LED
Alarm LED

3.

Functional tests

3.1

Local loopback test

3.1.1
3.1.2

600 ohm
300 ohm
none

BF
BG

600 ohm
300 ohm

on
on
on (only if solder bridge DC is in)

[ ]
[ ]
[ ]

Press S4 in direction TTX and then TRX.


Wait 3 seconds.

DCD LED
TI LED
-

AF
AG
AH

Power on.

2.

G4AE / G4AF

continuously on
on

[ ]
[ ]

Press S4 in direction TTX to stop test.

# programming only for G4AF modem


3.2

Transmitter

3.2.1

Frequency XT1 {Tx}; #{Tx MAIN}

[TX fc - TX fs

3] Hz

______________

[ ]

3.2.2

Level XT1 {Tx}; #{Tx MAIN}

[TX level +0/-3] dBm

______________

[ ]

[TX level +0/-3] dBm

______________

[ ]

______________

[ ]

3.2.3 # Level XT2 {Tx STD BY}


3.2.4

Transmit a space frequency. (logical 0)

Frequency XT1 {Tx}; #{Tx MAIN}

[TX fc + TX fs

3] Hz

4 of 5

NSK5 TEST REPORT

Modem position: N............

3.3

off
on
on

[ ]
[ ]
[ ]

Increase the frequency slowly until RXD LED lights.

Center frequency
-

3.3.5

NSK5 [ ]

Inject a signal into TX3 {Rx}; #{Rx MAIN}. When the modem is inserted into an ETL tier then
the signal must be injected into XT1 {Tx}; #{Tx MAIN} on the remote modem.
Set the generators frequency to RX fc - RX fs = ____________
Set the generators output signal level to the carrier off level + 15dB = ____________

Alarm LED
RXD LED
DCD LED
-

3.3.4

ETL [ ]

Main receiver
-

3.3.1
3.3.2
3.3.3

Tier:

5HYN589267-TA

[RX fc

20] Hz = ________________

[ ]

Set the generators frequency to RX fc - RX fs = ________________


Reduce the level until DCD LED extinguishes.

RX sensitivity main XT3 {Rx}; #{Rx MAIN}

[actual carrier off level

3] dB = _______ [ ]

3.4 # Standby receiver


-

Force the receiver to switch to the standby line. (DTR must be on).
If S3:10 is on:
Disconnect the main line and wait 90 seconds.
and re-connect when modem has switched over.
OR

3.4.1

SS LED
-

3.4.2

If S3:10 is off:
Switch SS input high by connecting SS to TVP on X6.
on

[ ]

Set the generators frequency to RX fc - RX fs.


Inject the signal into XT4 {Rx STD BY}.
Increase the level until DCD LED lights.
Reduce the level until DCD LED extinguishes.

RX sensitivity standby XT4 {Rx STD BY} [actual carrier off level

3] dB

[ ]

5 of 5