Escolar Documentos
Profissional Documentos
Cultura Documentos
9. Tolerances
9.1 Ratio. With rated voltage impressed on one winding of a transformer, all
other rated voltages at no load shall be correct within 0,5% of the name
plate markings. Rated tap voltages shall correspond to the voltage of the
nearest turn if the voltage per turn exceeds 0,5% of the desired voltage.
9.2 Impedance. The tolerances for impedance shall be as follows:
(1) The impedance of a two-winding transformer shall have a tolerance of
+/- 7,5% of the specified value. Differences of impedance between two
duplicate two-winding transformers, when two or more units of a given
rating are produced by one manufacturer at the same time, shall not exceed
7,5% of the specified value.
(2) The impedance of transformers having three or more windings or having
three or more windings or having zigzag windings shall have a tolerance of
+/-10% of the specified value. Differences of impedance between duplicate
three-winding or zigzag transformers, when two or more units of a given
rating are produced by one manufacturer at the same time, shall not exceed
10% of the specified value.
(3) The impedance of an autotransformer shall have a tolerance of +/-10%
of the specified value. Differences of impedance between duplicate
autotransformer, when two or more units of a given rating are produced by
one manufacturer at the same time, shall not exceed 10% of the specified
value.
(4) Transformers shall be considered suitable for operation in parallel if their
resistance and reactances come within the limitations of 9.2 (1) through 9.2
(3), provided turn ratios and other controlling characteristics are suitable for
such operation.
9.3 Losses. the losses represented by testing a transformer, or transformers,
on a given order shall not exceed the specified losses by more than the
percentages given in Table 8.
IEEE C57.12.91-1995
...
10.9 Insulation-resistance tests
Insulation-resistance tests are made to determine the insulation resistance
from individual windings to ground, or between individual windings. The
insulation resistance in such tests is commonly measured in megohms but
may be calculated from measurements of applied voltage and leakage
current.
Insulation-resistance tests shall be made when specified. The insulation
resistance of electrical apparatus is of doubtful significance as compared
with the dielectric strength. It is subject to wide variation with design,
temperature, dryness, and cleanliness of the parts. When the insulation
resistance falls below prescribed values, it can, in most cases, if it is of good
design and has no defect, be brought up to the prescribed value by cleaning
and drying the apparatus. The insulation resistance, therefore, may afford a
useful indication as to whether the apparatus is in suitable condition for
application of the dielectric test.
NOTES:
1 The significance of values of insulation-resistance tests generally
requires some interpretation, depending on the design, dryness, and
cleanliness of the insulation involved. If a user decides to make insulationresistance tests, it is recommended that insulation-resistance values be
measured periodically (during maintenance shutdown) and that these
periodic values be plotted. Substantial variation in the plotted values of
insulation resistance should be investigated for cause.
2 Insulation resistances may vary with applied voltage, and any
comparison must be made with measurements at the same voltage.