Escolar Documentos
Profissional Documentos
Cultura Documentos
VOCATIONAL EDUCATION
REVITALISATION PROJECT-PHASE II
NATIONAL DIPLOMA IN
MECHANICAL ENGINEERING TECHNOLOGY
COURSE INDEX.
WEEK 1.
WEEK 2.
REFRIGERATION
1.1
Introduction......1
1.2
DEFINITION OF REFRIGERATION.2
1.3
Methods of Refrigeration3
2.0
REFRIGERATION PRACTICE
WEEK 3.
2.1
2.2
2.3
3.0
UNDERSTAND
THE
VARIOUS
TYPES
OF
REFRIGERATION CYCLES
3.1
3.2
PRACTICAL
WEEK 4.
3.3
3.4
System Representation
3.5
REFRIGERATION CYCLE
4.0
REFRIGERATION
WEEK 5.
4.1
4.2
4.3
4.4
UNIT OF REFRIGERATION
4.5
4.6
4.7
4.8
4.9
4.10
REFRIGERANTS
5.2
REFRIGERANTS:
QUALITIES
OF
DESIRED
REFRIGERANTS
5.3
CLASSIFICATIONS
5.4
5.5
PROPERTIES OF REFRIGERANTS
5.6
5.7
5.8
5.9
5.10
REFRIGERANT CHARGING
5.11
WEEK 6.
6.0
6.1
REFRIGERANTS
6.2
6.3
CLASSIFICATIONS
6.4
6.5
PROPERTIES OF REFRIGERANTS
6.6
6.7
6.8
6.9
WEEK 7.
7.0
REFRIGERATION CIRCUIT
7.1
REFRIGERANT CHARGING
WEEK 8.
7.2
8.0
8.1
8.2
CLASSIFICATION
OF
APPLICATION
OF
REFRIGERATION SYSTEM
WEEK 9.
9.0
BUILDING
9.1
9.2
9.3
PLANT
WEEK 10.
WEEK 11.
WEEK 12.
12.1
WEEK 13.
WEEK 14.
WEEK 15.
WATER PUMPS
WEEK 1
1.0
1.1
Fig 1.0
Fig 1.1
Making cold depends on a few simple principles. Of these, the most important is that
heat always flow from a warm to a cool body and never reverse.
Heat
Warm
Fig 1.2
Heat flow
Cool
To cool a warm object therefore, we need to place it near a cold one like a block of
ice, or in a cold well, pond or lake as is obtained in countries in cold regions. Using
natural ice and cold water to remove heat provided mans first cooling systems.
Fig 1.3
Typical heat flow principles are thus so illustrated. If we put some ice cubes in a jar
with a thermometer was in fig4, heat flowing from the room and surrounding air
melts the cubes, if the room temperature is above 00c. To melt 1 kg of ice, 339.94 kg
of energy in the form of heat must be absorbed.
Fig 1.4
Heat flow
Fig. 1.5
Ice melts
Conceivably, we could cool an entire room with ice cube, but the process would not be
efficient and ultimately cumbersome.
If a concentrated heat source is applied to a jar, fig 2, water formed from the ice cubes boils
when it reaches a temperature of 1000c. Once again, heat is flowing from a warm body to a
cooler one. To make the water change to steam, a gas like vapor, we need to ad a certain
quantity of heat energy to the 1kg of water. This heat quantity is the enthalpy of
vaporization of water the steam, there is no temperature change heat absorbed by ice in
melting is enthalpy of fusion.
Fig.1.6 Superheating
When all the water changes to steam, further heat addition causes super heating,
indicating that the temperature of the steam is higher that corresponding to its
pressure fig1.6.
Water boils at 1000C when subjected to atmospheric pressure on surface of a liquids
pressure. Increasing the pressure on surface of a liquid raises the reverse of
vaporization also at constant temperature. For a given pressure of the liquid,
condensation occurs at the same temperature as vaporization.
Refrigerants are fluids that, with few exceptions, boil at low temperatures at
atmospheric pressure. For example, ammonia at 1 atm (1.013 bar) boils at 33.30,
while F-12 (Freon 12) boils at -300c- at the same pressure. Boiling and condensation
process of refrigerants are the same as for water.
The phenomena discussed above are mainly heat transfer processes. The aspect of
refrigeration can come in when the principle of heat transfer is so applied to bring
about an artificial change in a well regulated cold state production that is
reproducible irrespective of the location or environment.
Applying the concepts of heat transfer using refrigerants as a medium or system fluid
the fig. 5 represents an insulated box. With normal atmospheric pressure the liquid
boils at -150C absorbing about 1315KJ of heat energy during vaporization. Since little
heat can pass through the insulated box, heat needed for vaporization will come
from the air or other contents of the box. Thus, we have a crude system for
producing refrigeration.
Fig 1.8
Recovering Ammonia
This cycle can be repeated by replacing the condensed ammonia in insulated box.
This process can also be carried out the same result in different locations provided
the parameters are the same. The process so far explained is a typical refrigeration
process.
If Q is heat removal rate from the coolant (we call it the cooling load),
then Qout = MCP (Tf Ti) - - - - - (i)
Qin
Tf
Ti
Then
Cp
Tf
Ti
Ti > Tf i.e
Qin
iii.
(1.2)
Heat of vapourisation =
Heat of sublimation
Examples
(a).
dW=0
Chilled space (space whose
dQ
dm2
U2 =(Uf)2
Ice
Mi
= Me
= Ue
V2
Hence,
DQ + Mi Ui = dm2 h2 +Me Ue
DQ = dm2 (h2) (MiUi MeUe)__________ (1.3)
U refers to the internal energy of all the content in the chilled space, ice, chilled
air, food etc.
and
dm2 = Mi Me
Fig 1.9
(b).
Fig 1.10
(c).
(vi).
Expansion of a liquid.
If the expansion occurs entirely in the liquid state, fall in temperature will be quite
small as in a- a1. Expansion that leads in liquid vapour phase will lead to higher
temperature drop in (b bi) the fluid. This expansion process of a liquid is employed
in vapour compression cycle.
T
b
a
b1
a1
Fig 1.11
(v).
The throttling process for real fluid comes into this category. Throttling may lead to
cooling depending on the condition at (1). Suppose the flow passage were
converging (velocity) V2 >V1 so then h2< hi. Ideal fluids will reach a stage where h2
in less than h1 i.e T2<T1.
So, if flow passage converges, we can produce cooling effect.
H1 + V21 = h2 + V22
i.e h1 h2 = (V22 V21)
So if V2 > V1, h2<h1
(vi).
By Expansion Turbines
The expansion of gas in a turbine while producing work will produce some cooling
effect. This is used in aircraft air conditioning.
For a turbo jet, a kg of air is bled out and passed through heat exchanger. The air
leaving the compressor has high temperature and pressure and in the turbine, its
temperature and pressure are lowered and discharged into the aircraft cabin.
Humidity is low at high attitude even if temperature is comfortable. For a plane that
is in motion, we get the cooling air from the atmosphere we dont need fan.
(v).
Electrical Process
By electrical process, cooling can be produced by either of these two process.
(a).
(c).
Purposes of Refrigeration
The followings are major and encompassing purpose of refrigeration.
(i)
(ii).
(iii).
(iv).
(v).
WEEK 2
2.0
KNOW
THE
BASIC
TOOLS
AND
THE
EQUIPMENT
USED
IN
REFRIGERATION PRACTICE
2.1
2.2
(i)
Portable electric drills:- These are used extensively by refrigeration and air conditioning
technicians. They are available in cord type (115v) or cordless (battery operated)
(ii)
Flaring tools: - The flaring tools has s flaring bar to hold the tubing, a slid- on yoke and a feed
screw with flaring core and handle. Several sizes of tubing can be flared with this tool.
(iii)
Swaging tools: - Swaging tools are available in punch type and lever type
Fig 2.1
(iv)
Working tools
Tube benders: - Three types of tube benders may be used: spring type, lever type and to a
lesser extend, gear type. These tools are used for bending soft copper and aluminum.
(v)
Plastic tubing shear: - A plastic tubing shear cuts plastics tubing and non-wire-reinforced or
synthetic hose.
(vi)
Tubing pinch-off tool: - A tubing pinch off tool is used to pinch shut the short stub of tubing
often provided for service, such as the service stub on a compressor. This tool is used to
pinch shut this stub before sealing it by soldering.
(vii)
Metal workers hammer: - A metal workers hammers straightens and form sheet metal for
duct work.
2.3
Gage manifold: - This is one of the most important of all pieces of refrigeration and
air conditioning service equipment. It normally includes the compound gage, the
manifold, valves, and hoses. The four valve design has separate valves for the
vacuum, how pressure, high pressure and refrigerant cylinder connections
(ii)
(iii)
(iv)
Halide leak detector: A hide leak detector detects refrigerant leaks. It is used with a
acetylene or propane gas. When the detector is ignited, the flame heats a copper disc. Air
for the combustion is drain through the attached hose. The end of the hose is passed over or
near fitting or other area where a leak the refrigerant will be drain into the hose and contact
the copper disc. This breaks down the halogen refrigerant into other compounds and
changes the colour of the flame. The colour change from green to purple, depending on the
size of the leak.
(iv)
Vacuum pump: Vacuum pumps designed specifically for servicing air conditioning
and refrigeration systems remove the air and non-condensable gases from the
system. This is called evacuating the system and is necessary because the air and
(v)
Refrigerant recovery recycling station: It is illegal to vent refrigerant to the air. The
refrigerant from refrigeration and air-conditioning system is pumped into a cylinder
or container at this station where it is stored until it can be changed back into the
system if it meets the requirements or transferred to another approved container
for transportation to a refrigerant reclaiming facility.
(vii)
Compressor Oil Charging Pump: This is use specifically for charging refrigeration
compressors with oil without pumping the compressor down.
WEEK 3
3.0
3.1
Isobaric Process:
During the process, Pressure remain constant The can also be referred to an
isopiestic process
Adiabatic Process:
No heat transfer, Q = O
Psychrometry deals with the state of atmosphere with respect to moisture content. It
deals with the thermal properties of air and the control and measurement of the
moisture content of air in addition to the stud of effects of atmospheric moisture on
commodities and human comforts.
Dew point Tdp: It is the temperature at which the liquid droplets just appear when the
moist air is cooled continuously.
Absolute humidity: It is the amount of water vapour per unit volume of the gas
Relative humidity ; It is the ratio of the actual partial pressure of water vapour in the
moist air to the saturation pressure of water vapour corresponding to the dry-bulb
temperature
= Existing partial pressure of water vapour, Pv
The saturation pressure of pure water vapour
at the same temerpature Bs
Pv/Ps
(1)
Humidity ratio, w: This is called specific humidity it is defined as the amount of water
vapour in the moist air per unit mass of the dry air in a given volume.
Using the perfect gas relation for air and water vapour for a given volume V of the
Moist air,
Mv
Pv V/(Rv T) -
--
(3)
(2)
From definition
0.622
- -
(4)
Saturated air: A mixture of dry air and enough water vapour all at the same dry-bulb
temperature
(6)
(5)
/
/
and
= / [1 (1-) Ps/P]
(8)
!
(i)
Solution
From steam table,
Ps
Pv
(7)
Pv
0.0174 bar
Ps
0.04242 bar
1bar
'.'(')
"#$%# &
* &
'.'(')
'.'(' '.')+)+
*
'.')+)+
0.39
Specific Quantities: In case of moist air, the specific enthalpy, specific volume, specific
entropy specific humidity etc are expressed per unit mass of the dry air (moisture free air). If
the air is moist having specific humidity.
Specific enthalpy:
h = ha + w hv
Specific volume:
v = V a + w Vv
Specific entropy: S = Sa + W Sv
Where a and v stand for dry air and water vapour respectively
V = Ra Tdb /P Pv)
Enthalpy, h = Cp Tdb + w hv
Pv = Pwb P
/01 /61
3''
Pv = Pw -
(1)
Pv = Pwb -
To determine
Ambient pressure =
()'
(8'
1.013 0.9863;<=
Pv = Pw -
0.02337
0.96293 x 10
1518.2
0.02337 0.0063426
0.017027 bar
Relative humidity, R. H =
Ps = 0.04242 bar
0.017027
0.042242
*
& * &
'.'('+(
&'.7482 '.'('+(*
0.3909
'.7)244
&'.')+)+*
0.4014
'.8++
'.''37'4
'.787+(2
'.'('+(
'.7482 '.'('+(
'.''7+83>?
@A
>?
B=C <D=
Specific volume,
E
FG H
287.2 303
I
0.9863 0.017027
4('+.8
'.787+(2
10 3
3.2
principles of conservation of energy. It forms the basis of many of the scientific laws
including the first law of thermodynamics.
Energy is defined as the capacity of a system for interacting with and influencing its
environment or surroundings. It is the central figure or factor in all interactions between
systems. All interactions involve the flow, one way or the other of energy between the
systems involved. The flow of energy occurs either by way of heat or in the form of work, the
variety of work being extensive.
Heat and work are energy in transits (i.e. is flow) from one system to another. They may not
be said to be contained in any system. They are only recognized as such during interaction.
Systems do contain energy, but not work nor heat. Energy contained in a system is internal
energy, the sum total of the kinetic energy (or translation rotation and vibration) and
potential energy of all, along with the energy of chemical bonding and unclear bonding
among all the particles of matter making up the system. The reference to potential energy
suggests immediately that some datum or reference level must be identified from which
such energy is reckoned. The datum is usually arbitrary. In thermodynamics, the concern is
ultimately with changes in internal energy and other system properties notwithstanding the
arbitraries of the datum. When energy content of a system is reckoned relative to a different
but equally arbitrary datum, the resulting energy property of the system is known as
enthalpy.
Therefore, energy may flow from one system to another by means of either heat or work
but it may not be said to be contained in these form. This is part of the substance of the first
law of thermodynamics which states that Energy may be transferred to and from a system
by means of either heat or work. In any event, energy is conserved; it can neither be created
nor destroyed. Put differently; when any closed system is taken through a cycle, the net
work delivered to the surrounding is proportional to the net heat taken from the
surrounding
This can be expressed mathematically
As
@ OP B
Or
QP Q
This means that some work can be converted to heat in a system and some heat converted
conversely into work
Thus,
W =Q
Where W
Work
and
Heat
For a non-flow energy equation, Heat absorbed by the system = Increase in internal energy +
work done by the system
Hence Q = u +W
(1)
3.3
3.3.1
Where W
work
And
Heat
This means that some work can be converted into heat is system and conversely some heat
can be change into work
For a non flow energy equation, the can be represented thus
Q
= u+w
T1
HOE
Source
Q1
W
Q2
Sink
T2
HOE
Carnot =
RS RT
RS
1
RT
RS
For a Carnot refrigerator or reversible engine, R1 work W is done o the engine to take away
heat Q1 from a source at T1 (cold space). This work, W, is converted into heat Q2 which is
rejected into the sink at T2
The efficiency of this system is given by
RS
RT RS
System Representation
This diagram is a flow diagram of a simple vapour compression system.
The parts include:
1.
Evaporator
2.
Suction line
3.
Vapour compressor
4.
Discharge line
5.
Condenser
6.
Receiver tank
7.
Liquid line
8.
Evaporator
(Inside)
Valve
(Refrigerant flow
control)
Liquid
Line
Section
Line
Discharge
Line
Receiver
Tank
Assignment
Briefly describe the function and features of each of the various parts of a vapour compression
system as outlined above. Use also diagrams for your illustration
3.5
REFRIGERATION CYCLE
As the refrigerant circulates through the system, it passes through a number of changes in
state or condition. Each of this stage of change is called process. The refrigerant starts at
some initial state, passes through a series of processes in a definite sequence and returns to
the initial condition. This series of processes is called a cycle.
The charts below are the various cycle representations based on the given relationships.
Liquid
a
Vapour
Out
Liquid
Vapour
e
T2
Qout
T2
S=c
S=c
T1
T1
c
b
Qin
Qin
S
Mother Chart
P.V Chart
Qout
Qout
b
T2
T2
e
d
S=c
T1
b
T1
c
b
Qin
Qin
V
T.S Chart
c
H
Isentropic Chart
The cycle description for the processes using these charts include:
1.
ab
2.
b-c
3.
c-d
4.
d-e
5.
e-a
Qin = h c - h b
Qout = h d - h a
but h a = h b since a - b is isentropic
Qin = h c - h a
= hc - h b
= Refrigerating effect
Also
C.O.P. =
Qin
Q out - Qin
hc - h b
h d - h a - (h c - h b )
hc - ha
hd - hc
3.4.1
qc = h c - h a
P
= h1 - h 4
= h1 - h 3
= s T1
= (S1 - S4 )T
21
H
21
T1
4
1
S
This is sometimes called valuable commodity. Theoretically, this equal to the latent heat of
vapourisation. In actual practice, the refrigerant is at the condensing temperature before it
enters the expansion valve (point a in the diagram) and must be first reduced to the
evaporator temperature. That is, only part of the refrigerant vapours in the evaporator.
Latent heat
= hc - hf
Saturation Line
P
R. E. = q c = h c - h b
Loss (part of to cool
T2
from T1 T2) = h b - h f
T1
f
b
WEEK 4
4.0
4.1
(a)
Q = W
T1 (S1 - S4 ) = Q 4 -1 = W4 -1
= Area 5416
Qout
2
T2-T3
T1-T4
4
Qin
S3-S4
5
Cycle on T-S Diagram
6
S1-S2
S
(b)
1-2,
Q1- 2 = 0
Condenser
and W1- 2 = u1 - u 2
Expander
Compressor
1
Evaporator
System Diagram
fig 4.1
(c)
T2 = T3
Also T2 (S 2 S3 ) = - T2 (S1 - S4 )
= - Q 2- 3 = - W2 -3 = Area 5623
The ve sign is because of the negative heat transfer. This means that the heat transfer is a
loss here. Heat is rejected into the atmosphere.
(d)
3-4,
Q 3- 4 = 0
and
W3 4 = - U 3- 4
Qout
2
Compressor
We
Expander
We
4
Qin
Fig 4.2
System representation
= T1 (S1 - S4 )
For a cycle, i.e. 12341
= Q
= T1 (S1 - S4 ) - T2 (S1 - S4 )
= s T1 - sT2
= s (T2 T1 ) = (T2 - T1 )(S1 - S4 )
The ve sign shows that work must be supplied to perform the cycle. Thus, the external
energy supplied to perform the cycle = (T2 - T1 )(S1 - S4 )
= (T2 - T1 ) s
For Carnot cycle, heat engine,
Work done
Heat absorbed
W
Q out
(T2 - T1 )
T2
(T2 - T1 )
T2
Q4 - Q2
Q -Q
= 2 1
Q2
Q2
=1-
Q1
Q2
=1-
T1
T2
For a refrigeration cycle (reversed Carnot cycle), the valuable commodity here is Qin and heat
extracted = sT1
C. O. P. =
Valuable commodity
Net work
Refrigerating Effect
External energy supplied
C. O. P. =
sT1
s (T2 T1 )
T1
T2 - T1
T1 (S1 - S4 )
(T2 - T1 )(S1 S 4 )
1
T2
-1
T1
Q1
Q 2 - Q1
Evidently, the COP of a Carnot refrigeration cycle is a sole function of upper and lower
temperatures.
COP can be raised by raising the top temperature and or by making (T2 T1 ) small.
T
3
Tb
(Condenser)
Tb
Ta
Ta
(Room)
4
T1
1
S
For effective exchange of heat to occur, then, the temperature of space, T0 from T1
and the space where you are depositing heat, its temperature Tb must be less than
T1, i.e. for heat to be extracted from inside the room, Ta , Ta > T1 and for heat to be
sent into the environment, Tb , T2 > Tb .
The Carnot cycle is practically not feasible since isothermal energy rejection requires
extremely slow motion followed by isentropic process during which the piston
should move at extremely faster rate. Such motion is mechanically not obtainable.
On the other hand if phase change is allowed for isothermal energy transfers, the
compression will be so wet that the same will lead to severe mechanical difficulties
since the liquid present inside the compressor may get squeezed causing bursting of
the cylinder or other components due to practically incompressible temperature of
liquid.
As such, the Carnot cycle serves as the basic ideal cycle meant for comparison of
other cycles. The deviation of various values in other cycles will be for measure of
presence of irreversibility in various processes.
4.1.1 Summary
For heat engine, Carnot efficiency
T2 - T1
T2
. (1)
Qout
T3
T1
s
S
Qin
Qout = s T2 .. (0)
C.O.P =
4.2
Refrigerating effect
Net work
T1
s T1
(3)
=
s (T2 - T1 )
T2 - T1
latent heat to the circulating water of the water. The vapour compression refrigeration
system is therefore a latent heat pump, as it pumps its latent heat from the brine and
delivers it to the cooler.
The vapour compression refrigeration system is universally employed for all purpose
refrigeration. Its is generally used for all industrial purposes form small domestic
refrigerators to big air conditioning plant.
(ii)
(iii)
(iv)
4.2.2 Disadvantages
(i)
(ii)
4.3
Insulated
Chamber
Evaporator
Low pressure
liquid
Expansion valve or
refrigerant control valve
Pressure
Gauge
Pressure gauge
High pressure
vapour
Receiver
Condenser
Compressor
Fig4. 3
The figure show schematic diagram of a simple vapour compression refrigeration system. It
consists of the following five essential parts
1.
Compressor: The low pressure and temperature vapour refrigerant from evaporate
is drawn into the compressor through the inlet or suction value A, where it is
compressed to high pressure and temperature. This high pressure and temperature
vapour refrigerant is discharged into the condenser through the delivery or
discharge value B.
2.
Condenser: the condenser or cooler consists of coils of pipe in which the high
pressure and temperature vapour refrigerant is cooled and condensed. The
refrigerant, while passing through the condenser, gives up its latent heat to the
surrounding condensing medium which is normally air or water.
3.
Receiver: The condenser Liquid refrigerant from the condenser is stored in a vessel
known as receiver from where it is supplied to the evaporator through the
expansion valve or the refrigerant control value.
4.
Expansion value: It is also called throttle value or refrigerant control value. The
function of the expansion valve is to allow the liquid refrigerant under high pressure
and temperature to pass at a controlled rate after reducing its pressure and
temperature. Some of the liquid refrigerant evaporates as it passes through the
expansion value the greater portion is vaporized in the evaporator at the low
pressure and temperature.
5.
In any compression refrigeration system, there are two different pressure conditions. One is
called the high pressure side and the other is known as low pressure side. The high pressure
side includes the discharge line (i.e. piping from delivery value B to the condenser),
condenser, receiver and expansion value. The low pressure side includes the evaporator,
piping from the expansion value to the evaporator and the suction line (i.e. piping from the
evaporator to the suction value A).
4.4
UNIT OF REFRIGERATION
The unit used in refrigeration industry is tone of refrigeration (TR). A tone of refrigeration is
defined as the amount of refrigeration effect produced by the uniform melting of one tone
(1000Kg) of ice from and at 0oC in 24 hours. It is equivalent to the rate of heat transfer
needed to produce 1 tonne (20001b) of ice at 0oC from water at 0oC (32oF) in one day.
Since latent heat of ice which is enthalpy of solidification of water is given in S. I unit as
334.94Kd/kg and British unit 144Btu/1b,
ITR
=
=
1000 x 335
24 x 60
=
232.6 KJ/min
3.88KW /ton
In actual practice, one tone of refrigeration is as equivalent to 210 KJ/min or 3.5 Kw (or 3.5
KJ/S)
In British unit therefore, 1 ton of refrigeration =
2000 1b x 144
24 x 60
2000BTU /min
12,000BTU/hrs
4.5
= 144 BTU
= 334.944KJ/Kg
1 ton of refrigeration (of ice per 24hr day) will absorb heat at the rate of =
/hr
=
210KJ/min
3.54KW
(a)
(b)
Where qe
12,000BTU
In
Wt
3.5
>V
WXYZ
.[
Note that the refrigerating capacity is actually an energy transfer rate and as such is an expression of
power.
4.6
4.7
V = MV
Where
V
m3/kg
4.8
Hence
P
COP
Useful refrigeration
Net Work
hc ha
hd - hc
e
b
refrigeration effect
Work input
Refrigerated effect
Heat of compression
The two terms which make up the COP must be in the same unit so that the COP is therefore
dimensionless.
4.9
3
T
Net work
T
3
2
21oC
-18oC
4
1
DT
S
The above analysis gives a false impression that we have complete control over T1, and T2.
This highlights the limitations imposed by temperature on COP. The temperature
recruitments is governed by vaporizing temp of refrigerant and the condenser heat load. For
example, if the refrigeration system must maintain a cold room at 18oC and can reject heat
to atmosphere at 21oC, these two terms are limitations with which the cycle must abide.
The two temperature are shown in dotted liens I the T.S diagram. During the heat rejection
process, the refrigerant temperature must be higher than 21oC. During the refrigeration
process, the refrigerant temperature has to be lower than 18oC in order is transfer heat
from the cold space to the refrigerant. The cycle that result us 1-2 3-4-1
4.10
Source T1
Q
R
Q-W
Sink T2
Let this engine receive Q units of heat at a given period of time from a source whole
temperature is T1. Let this engine convert W units of this heat into work and
WEEK 5
UNDERSTAND THE VARIOUS TYPES OF PARCTICAL
REFRIGERATION CYCLES & KNOW THE FUNCTIONS AND
PROPERTIES OF REFRIGERANTS
REFRIGERANTS
A refrigerant is a medium of heat transfer through phase change
such as evaporation at low temperature and pressure, with some
exception where the sensible energy transfer occurs. There are
many substances which are used in refrigeration system for
energy transfer purposes. These refrigerants are classified under
the following headings.
A.
B.
Based on safety
Safety consideration as categorized into three:
(i).
(ii).
R - 11
R 12
Dichlorodifluoromethane
R - 13
Monochloro-trifuoro-methane
R 14
Carbon Tetrafluriode
R - 21
Dchlorofluoromethane
R 22
Chlorodifluoromethane
R - 113
Trichdifluoromethane
R 114
Dichlorodifluoromethane
Methyl chloride
Carbon dioxide
Water
These
include,
dichloroethylene,
methyl
formate,
C.
(ii).
CLASSIFICATIONS
-
Gzeotropes.
A.
The Helogens
The Ferons contains one or more of the halogenne made up of
chlorine, fluorine and Bromixe. F11, F12, or R12, etc sold under
several trade names e.g. freous, genetrons, isotrons, avetrous
(see table).
Chemical Designation
Chemical Name
Chemical Formula
Bond
CL
F11
11
Trichloromonflur
CCL3F
CL
oromethane
CL
CL
R11
12
CL
Dichlorofluoro
methane
CCL2F2
CL
C
F
22
Monochlorodi-
CCLHF2
C
CL
fluoromethane
or CHCLF2
F
40
Methychloride
CH3CL
CL
113
CL
Trichlorofluoroethene
114
CL
CCL2F-CF2CL
CL
Dichlorotetraflu
CL
oroethene
CCLF2 CCLF2
CL
(ii)
Refrigerant-ii (CFC)
(iv)
Refrigerant-22
(CHCLF2):-
the
chemical
name
of
R-22
is
boiling
temperature
is-33.3oc
and
latent
heat
of
PROPERTIES OF REFRIGERANTS
Chemical properties of refrigerant
(i)
e.t.c are
(iii)
(iv)
refrigerant vapour. The refrigerant should not in any form mix with
the oil within the crank case
(v)
(i)
(ii)
(iii)
(iv)
(v)
(vi)
the
refrigerating
cycle
of
evaporation,
recovery
i.
PIPE JOINTS
Depending on the type and size of the piping, joints for refrigerant
piping may be severed, flanged flared, welded, brazed or soldered
when refrigerant pressures are below 250sil (17bar), screwed
joints may be used on pipe sized up to 80mm. for higher
pressures, screwed joint are limited to pipe sized B5mm and
smaller. Above these sizes, flanged joints of the tongue and
groove type should be used. Welting is probably the most
commonly used method of joining iron and steel piping.
ii.
LOCATION
In general, refrigerant piping should be located so that it does not
present a safety hazard, obstruct the normal operation and
maintenance of the equipment, or restrict the used of adjoining
spaces.
iii.
If you have to open a circuit, or purge it, make sure that the liquid
cannot spray on you.
2.
litmus Paper: Moist red limits paper will turn blue if exposed
to ammonia vapour, but cannot be used with any of the
halogen family refrigerants.
3.
4.
5.
WEEK 6
6.0
6.1
REFRIGERANTS
A refrigerant is a medium of heat transfer through phase change such as evaporation at low
temperature and pressure, with some exception where the sensible energy transfer occurs.
There are many substances which are used in refrigeration system for energy transfer
purposes. These refrigerants are classified under the following headings.
6.1.1 A
These refrigerants are categorized under common and secondary refrigerants. The common
refrigerants pass through compression, cooling or condensation, expansion and evaporation
or warming up doing cyclic. In case of phase change media such NH3, R-12, R 22, CO2 sulphur
dioxide etc, the heat transfer is associated with phase change while sensible energy transfer
takes place with air.
A medium which does not undergo the cyclic process in refrigeration system but is used only
as a medium of heat transfer is often referred to as a secondary refrigerant. E.g water, brine
solutions of sodium chloride calcium chloride.
6.1.2 B.
Based on safety
Safety refrigerants: These are non-toxic, non-inflammable and include the following.
R - 11 -
R 12 -
Dichlorodifluoromethane
R - 13 -
Monochloro-trifuoro-methane
R 14 -
Carbon Tetrafluriode
R - 21 -
Dchlorofluoromethane
R 22 -
Chlorodifluoromethane
R - 113 -
Trichdifluoromethane
R 114 -
Dichlorodifluoromethane
-
Methyl chloride
(ii).
Carbon dioxide
Water
(iii).
Very flammable refrigerants: They are such compounds like Butane, Isobutane,
propane, ethane, methane, and ethylene.
6.1.3 C.
Halocarbon compounds: The are obtained after replacing one or more hydrogen
atoms in a hydrocarbon ethane or methane with halogens (chloride, bromine or
fluorine).
(ii).
(iii).
Azeotropes are those mixtures of two or more refrigerants which behave as if they
are compounds.
(iv).
(v).
Oxygen and nitrogen compounds are grouped in one category and as given 600
series.
(vi).
Cryogenic
(b).
Non- cryogenic
Cryogenic fluids are those which are employed for achievement of temperatures in the
range of 113k to OK, Nitrogen, Oxygen, Helium, and Hydrogen are used to achieve
temperature below 113K.
Non-cryogenic refrigerants are those inorganic compounds which are employed above the
cryogenic ranges such as water, ammonia, sulphur dioxide. These are grouped into 700
series.
(vii).
Unsaturated compounds such as ethylene, propylene etc are grouped into 1000 series.
6.2
Refrigerants with high specific volume means big compressor. So the better the sp.
Should not be flammable to avoid out break of five and so eliminates possibility of
explosion.
-
In vapour compressor system, refrigerant should operate at temp above its freezing
point.
-
Should be stable to keep its properties same throughout its working cycle.
Should have high thermal conductivity so in to increase mass rate on high K gives
6.3
CLASSIFICATIONS
-
Azeotropes.
6.3.1 A.
The Helogens
The Freons contains one or more of the halogens made up of chlorine, fluorine and Bromixe.
F11, F12, or R12, etc sold under several trade names e.g. freous, genetrons, isotrons, avetrous
(see table).
Azeotrope: Is a physical mixture of two chemically pure substances which cannot be separated
by distillation. It will possess properties different from the two substances but behaves like
another separate pure substance e.g R500 = F12 (73.8% by mass) + F152 cas (26.2% by mass).
Chemical Designation Chemical Name Chemical Formula
Bond
CL
F11
11
Trichloromonflur
CCL3F
CL
CL
oromethane
CL
R11
CL
12
Dichlorofluoro
CL
CCL2F2
methane
22
Monochlorodi-
CCLHF2
CL
fluoromethane
or CHCLF2
F
40
Methychloride
CH3CL
CL
114
CL
Trichlorofluoroethene
114
CL
CCL2F-CF2CL
CL
Dichlorotetraflu
CL
oroethene
CCLF2 CCLF2
CL
6.4
Ammonia: - Ammonia is the only refrigerant outside of the halocarbon group that is
being used to any great extent at the present time. Although ammonia is toxic and also
some what flammable and explosive under certain conditions, its excellent thermal
properties make it the predominant refrigerant in the production end of the food industry.
Ammonia has advantage of being an environmentally safe refrigerant.
(ii)
Refrigerant-ii (CFC)
It is probably the most widely used of all of the refrigerants. It is a safe refrigerant in that it is
non toxic, non flammable and non explosive. Further more, it is a highly stable compound
that is difficult to break down even under extreme operating conditions. However if brought
into contact with an open flame or an electrical heating element R-12 will decomposes into
highly toxic products. It is suitable refrigerant for use in high, medium and lo-temperature
applications and with all three types of compressor.
(iv)
6.5
PROPERTIES OF REFRIGERANTS
Ammonia is also somewhat flammable and becomes explosive when mixed with air
Toxicity: - some non-toxic refrigerant (i.e. all fluorocarbon refrigerants) when mixed
with certain percentage of air become toxic. Toxic refrigerant are not used in domestic
refrigerant and comfort air conditioning the use of toxic refrigerant is only limited to cold
storages..
(iii)
Solubility of Water: - water is only slightly soluble in R-12 the solution formed is very
slightly corrosive to any of the common metals. Solubility of water with refrigerant should
be reducing to minimal.
(iv)
Miscibility: - the ability of refrigerant to mix with oil is called miscibility. The degree
of miscibility. The degree miscibility depends upon the temperature of the oil and pressure
of the refrigerant vapour. The refrigerant should not in any form mix with the oil within the
crank case
(v)
Plant and in domestic refrigerators should be such that incase of leakage, it should have no
effect on the perishable materials.
6.6
temperature normally encountered in the refrigerating system. It should function for long
period of time with out dissociating into other compound.
(ii)
consideration while selecting the refrigerant. The Freon group of refrigerant is non-corrosive
with all metals ammonia is used only with iron or steel. Sulphur dioxide is non-corrosive to
all in the absence of water good refrigerants should not have corrosive tendency.
(iii)
Viscosity: - The refrigerant in the liquid and vapour states should have low viscosity.
The heat transfer through the condenser and evaporator is improved at low viscosities.
(iv)
Thermal conductivity: - The refrigerant in the liquid and vapour states should have
high thermal conductivity. It requires the heat transfer coefficients in evaporator and
condensers.
(v)
Dielectric strength: - this is a measure of the resistance that the refrigerant offers to
the flow of electric current it is important in hermetically sealed units in which the electric
motor is expose to the refrigerant.
(vi)
leakage of refrigerant, it should be easily detectable the leakage occurs due to opening in
the joints or flaws in material used for construction.
(vii)
Cost: - this is important in high capacity refrigerating system like industrial and
commercial the ammonia, being the cheapest is widely used in large industrial plants such as
cold storage and ice plants.
6.7
Primary Refrigerant: - These are that working fluid which passes through the
(ii)
Secondary refrigerants: - these are those working fluids which act as cooling, medium but do
not undergo the refrigerating cycle. Air, brine and any other freezing solution are its example
6.8
6.8.2 LOCATION
In general, refrigerant piping should be located so that it does not present a safety hazard,
obstruct the normal operation and maintenance of the equipment, or restrict the used of
adjoining spaces.
6.9
At all times bear in mind that refrigerants have been specially developed to remove a lot of
heat quickly through any surface on which they boil. If liquid refrigerant sprays onto your
skin, you will apply the necessary first aid for the treatment of cold burn.
If you have to open a circuit, or purge it, make sure that the liquid cannot spray on you.
Sulphur candles: When lit and exposed to air containing ammonia vapour, these
give off a white cloud of ammonium chloride or ammonium sulphide. This method
cannot be used to pin point leak position.
7.
Litmus Paper: Moist red limits paper will turn blue if exposed to ammonia vapour,
but cannot be used with any of the halogen family refrigerants.
8.
Bubbles tests: Soapy water, a washing up liquid, or better, still a purpose developed
leak detector will indicate the locations of leaks by the formation of bubbles by
escaping refrigerant. However, this type of test can only be made on piping or
fittings known to be at higher pressure than that of the atmosphere. Test solutions
applied low temperature; low pressure suction lines could cause considerable
damage because the liquid could be drawn into the pipes.
9.
Halide test lamps: Detectors fuelled with propane, butane, or mentholated spirit
can be used to locate fluorocarbon refrigerants leaks. The detector includes a fuel
tank which is or can be pressurized to supply fuel at the at a steady and controlled
pressure and a jet to admit the fuel to a burner. When lit, the burner flame is
supported by oxygen in the air which is drawn through the tube used as a sensing
probe. The probe is passed slowly over the joint or surfaces being leak tested. If any
fluorocarbon refrigerants are drawn into the tube, the colour of the lamp flame will
change to green or blue, depending on the quantity of gas passed over the burner
element.
This type of detector can only be used with non-flammable gases and care must be
taken to avoid igniting any other gases or material.
10.
Electronic leak detectors: A wide range of electronic detectors is available. All are
extremely sensitive. Battery operated models for use on site will pick up leaks which
give a little as 14gm per year.
The refrigerant is sensed by a plug- element, exposed to air drawn through a probe
or tube. Its presence will be indicated by a flashing lamp, an audible bleep or buzz or
a meter reading each increasing in speed or intensity as more refrigerant passes
over the element.
compressor which can be over 20years. The choice of oil and nomination of acceptable
alternatives can only be made by the compressor manufacturers. It is not advisable to use
other than the recommended lubricants.
Contaminations of oil by moisture or moist air cannot be tolerated. Oil containers must
therefore be stored in dry well ventilated rooms and not opened until the moment the oil is
to be used.
It must be remembered that oil is constantly circulated around systems charged with the
refrigerants. The fluorocarbon refrigerants all dissolved in oil and oil is carried away from the
compressor crankcase in refrigerants as they are pumped around the systems. Pipelines and
heat exchangers must therefore be designed to help oil flow back to the crankcase.
6.11.1 COMPRESSOR LUBLICATING OILS
The fact that the compressor lubricating oil usually comes in to contact with, and often
mixed with the system refrigerant makes it necessary that the oil used to lubricate
refrigeration compressors be special prepared for that purpose some of the more important
properties of the oil that must be considered when selecting the compressor lubricating oil
are :(1)
Chemical stability: - The important of chemical stability is emphasized by the fact that it is
necessary for the compressor lubricating oil to perform its lubricating function continuously
and effective without undergoing change for long period of time.
(2)
Dielectric strength: - The dielectric strength of oil is a measure of the resistance that oil
offers to the flow of electric current. If is expressed in terms of the voltage required to cause
an electric current to arc across a gap between two poles immersed in the oil. Since any
moisture, dissolved metal or other impurities contained in the oil will lower its dielectric
strength, a high dielectric strength is an indication that the oil is relatively free of
contaminants.
(3)
Viscosity:- viscosity is defined as the resistance that a fluid offers to flow, with regard to the
lubricating oil, viscosity may also be defined as a measure of the body of the oil or of the
ability of the oil to perform its lubricating function by forming a protective film or coaling
between the parts separated and preventing wear. In order to provide adequate lubrication
for the compressor, the viscosity of the oil must be maintained within reasonable limits.
(3)
Pour, Cloud And Floc Points: - the pour point of oil is the lowest temperature at which the oil
will flow or pour, when tested under certain specified conditions of two oil having the
same viscosity; one may have a higher pour point than the other because of a greater wax
tent.
Since all lubricating oils contain a certain amount of paraffin, wax will precipitate from any
oil if the temperature of the oil becomes cloudy at this point, the temperature at which the
wax begins to precipitate from the oil is called the cloud point of the oil.
The flash point of the oil is the temperature at which wax will start to precipitate from a
mixture of 90% R-12 and 10% oil by volume.
(i)
Splash method: - in this, the compressor crank case acts as an oil sump and is filled
with oil to a level approximately even with the bottom of the main crank bearings
with each revolution of the crank shaft, the connecting rod and crank shaft dip into
the oil causing the oil to be splashed up on the cylinder walls bearings and other
rubbing surfaces.
(2)
Forces Feed: - in the forces feed method of lubrication, the oil is forced under
pressure through oil tubes and/or rifle drilled passage in the crankshaft and
connecting rods to the various rubbing surfaces. After performing its lubricating
function, the oil drains by gravity back into a sump located in the crankcase of the
compressor, usually at the end of the crankshaft. Since most oil pumps are
automatically reversible, the direction of crank rotation is not usually critical with
regard to compressor lubrication.
Assignment
1.
(i).
Pouring point
(ii).
(iii).
Close point
(iv).
Dielectric strength
2.
Week 7
7.0
7.1
REFRIGERANT CHARGING
Refrigerant can be charged in liquid or gaseous form, using one of several types of
equipments. As a general rule, liquid charging methods are used on new equipment
requiring a known weight of refrigerant. The method is fast and extremely accurate when
charges do no exceed the limits 4.5kg of transparent, calibrated refrigerant vessels.
Fig 7.1
Gas charging is normally used to top-up systems. The procedure is slow, but enables gas
volumes to be accurately controlled in accordance with the readings of suction and
discharge gauges, an ammeter showing the power drawn by the compressor motor and the
absence of bubbles in liquid-line sight glasses.
Fig 7.2
7.1.1
CYLINDER POSITIONS
The logical positions of refrigerant cylinders are:
Fig 7.3
(a).
For liquid charging cylinder inverted above the system, charging value down.
(b).
For gas charging charging vertical, value uppermost, beneath the system.
7.1.2
Conventional charging hoses: These are used to connect main items of equipment.
2.
3.
Service manifolds: These are arranged for one suction and one discharge gauge; and
either three or four flared connectors for lines from the vacuum pump, refrigerant
cylinder, and the appliance to be tested. High vacuum designs have special,
diaphragm type soft seat shut off values, a vacuum port and oversize internal
passages.
fig 7.4
Compound gauge
4.
Conventional gauges: These are normally of 60mm diameter with threaded pipe
connectors. Normal calibration ranges are 0-3400kpa for pressure gauges and
760mm Hg- 800kpa for compound types.
5.
High vacuum gauges: These are electronic types. The range covered should be
20mmto zero enabling unit pressures to be watched throughout the dehydration
process which starts at approx. 210C.
6.
Vacuum Pumps: Conventional and high vacuum types are available in portable sets
suitable for site work. The high vacuum models use special high quality paraffin
based oil. Its vapour pressure is not more than 0.005mm at 37.70C; and a vacuum
pump cannot pull a total absolute pressure less than the vapour pressure of its
sealing oil.
7.
Charging stations: Many models, portable and immovable are available. They
normally incorporate a vacuum pumps; transparent, calibrated refrigerant vessels
for each important fluorinated refrigerant; gauges, valves; piped circuits, and
connections to complete.
7.2
The requirement for storage of cylinders in well ventilated rooms covers both the need to
remove any refrigerant which might escape, and the need to keep the cylinders as cool as
possible. In practical terms, storage are temperature should not reach levels at which
excessive refrigerant pressure is generated. An upper limit of not more than 2070kpa is
recommended.
At all times bear in mind that refrigerants have been specially developed to remove a lot of
heat quickly through any surface on which they boil. If liquid refrigerant sprays onto your
skin, you will apply the necessary first aid for the treatment of cold burn.
If you have to open a circuit, or purge it, make sure that the liquid cannot spray on you.
WEEK 8
8.0
8.1
In the light of the above, refrigeration industries are varied and target the following six
principals areas:
In the early days of mechanical refrigeration, the equipment available was bulky, expensive
and not too efficient. Also it was of such a nature as to require that a mechanic or operating
engineer will be on duty at all times. This limited the use of mechanical refrigeration to a few
large applications.
It is earlier stated that refrigeration is principally carried out for a number of reasons which
can be narrowed down to a desire to bring about cooling by reducing the temperature of a
space or product. It may be to change the state of a product, thereby transforming it from
liquid to solid. A typical example is water and similar liquid products being changed into ice.
Again, it may be directed at maintaining the state of a product as is obtainable in food
presentation. Manufacturing of certain product may require specific temperature condition
for a given property of product to be obtained, hence the need for refrigeration. Also certain
dimensional accuracies can only be obtained during manufacture under controlled
temperature condition. For effective performance of some control instruments and panels,
limits are set on the temperature of the control room to avoid overheat resulting from
instruments and power control equipment.
In the light of the above, refrigeration industries are varied and target the following six
principal areas:
8.2
8.2.1
DOMESTIC REFRIGERATION
Domestic refrigeration is rather limited in scope being concerned primary with household
refrigerators and home freezers. However, because the numbers of units in service is quite
large, domestic refrigeration represent a significant portion of this refrigeration industry.
Fig 8.1 a
Refrigerators
Domestic
Fig 8.1 b
8.2.2
Domestic Refrigerators
COMMERCIAL REFRIGERATION
Fig 8.2
8.2.3
Display cabinets
INDUSTRIAL REFRIGERATION
Industrial refrigeration is often confused with commercial refrigeration because the divisions
between these two are not clearly defined. As a general role, industrial applications are
larger than commercial applications and have the disguising feature of requiring on
attendant on duty, usually a licensed operating engineer. Typical industrial applications are
ice plants, large food creameries and industrial plants such as oil refineries chemical plants
and rubber plants.
Fig 8.3
8.2.4
Industrial Refrigerators
Application falling into this category could be listed partly under commercial refrigeration
and partly under industrial refrigeration. However, both these areas of specialization have
grown to sufficient size to warrant special instruction.
Fig 8.4
8.2.5
Refrigerated truck
AIR CONDITIONING
As the name implies, air conditioning is concerned with the condition of the air in some
designated areas on space. This usually involves control not only of the space. This usually
involves controls not only of the space temperature but also of spaces humidity and air
motion, along with the filtering and clearing of the air.
Air-conditioning application are of two types, either comfort or industrial according to their
purpose. Any air-conditioning that has as its primary function the conditioning of air for
human comfort air-conditioning are in homes, schools offices, house of workshop, hotels,
retail stores public buildings factorize auto mobiles, buses, trains, planer and ships.
Any air-conditioning that does not have as its primary purpose the conditioning of air for
human comfort is called industrial air-conditioning. This does not necessarily mean that
industrial air-conditioning systems cannot serve also as comfort air-conditioning
coincidentally with their primary function often this secondary function is served although
not always.
The application of industrial air-conditioning are almost without limit both in number and in
variety generally peaking, the function of industrial air-conditioning system are to
(1)
(2)
(3)
Limit the variations in the size of precision manufactured articles because of thermal
(4)
Provide clean, filtered air that is often essential to trouble free operation and to the
Fig 8.5
WEEK 9
9.0
9.1
Fig 9.1
3. Control of industrial Environment A/C:- To maintain efficiency, health and safety of workers
at safe tolerance limits.
Application of air conditioning can be found in to major grouping namely.
1. Industrial air condition:- This include such area as.
a. Laboratories
b. Printing industries
c. Pharmaceutical industries
d. Photographic industries
e. Control rooms (Electrical/Electrics)
2. Comfort air conditioning: This include areas like:
a. Eating and amusement locations
b. Store/super markets
c. Residences
d. Large buildings e.g offices, hotels, hospitals etc.
e. Transportation e.g car, buses, plane.
9.2
5. filtering
2. Heating
6. circulation
3. Humidifying
7. ventilation
4. de-humidifying
Fig 9.2
9.3
Evaporative cooler
ASSIGNMENT
Sketch a window air conditioner, label it properly and briefly explain the function of the
major component parts.
WEEK 10
10.0 KNOW HOW TO CALCULATE COOLING LOADS FOR REFRIGERATION
AND AIR CONDITIONING SYSTEMS
10.1 COOLING LOADS AND CALCULATION
Cooling load is the rate at which heat must be removed from the refrigerated space or
material in order to produce and maintain the desired temperature condition.
Some of the sources of heat in the refrigerated space include:
1. Heat leak by conduction from outside into the refrigerated space through the insulated
walls. This is called wall gain load.
2. Heat by radiation through glass windows and other transparent items into the
refrigerated space.
3. Heat by warm outside air entering through open doors, or through cracks around
windows and doors. This is called air change load. This air change load can be due to air
infiltration into the refrigerated space or ventilation airs to make up for require air in a
conditioned space for the occupants.
4. Heat given off by warm products entering into the refrigerated space. This is called
product load.
5. Heat given off by people occupying the refrigerated space.
6. Heat given off by heat producing equipment located inside the refrigerated space.
h1
ho
t1
Wall thickness
k1
Thermal conductivity
Where
Wp = weight of product
C = specific heat capacity
T1 = entering temperature
T2 = storage temperature
For storage temperature below freezing point of product (24 - hr)
Qpf = Wp x Cf x (T1 Tf) + W f + Wp x Cf x (Tf T2)
Tf
= freezing point
From the above, the quantity of heat given off by product in cooling from entering
temperature to its freezing temperature is
Qp = Wp x Cf x (T1 - Tf)
Also the quantity of heat off by the product of in solidifying or freezing is given by
Qpp
= Wf
The quantity of heat given off by the product in cooling from its freezing temperature to
final storage temperature is given by
Qps
Wp x C x (T2 T1)
Chilling time(s) x chilling rate factor
Qp =
WCDT x 24 hr
Chilling rate x MAT
W = wt of product
C = specific heat capacity
DT = change in temperature
MAT = Max allowable time.
Change load:
QA = M (ho - hi)
Where
QA
M
ho
Also the heat load due to infiltration can be calculated for a known volume of air.
If
Then
V1
Va
ho
hi
WEEK 11
11.0 KNOW THE FUNCTION OF AN AIR CONDITIONING SYSTEM FOR A
BUILDING CONTD
11.1 REFRIGERATED COOLING OR AIR CONDITIONING
Refrigerated air conditioning is similar to commercial refrigeration because of the same
components that are used to cool the air: (1) the evaporator, (2) The compressor, (3) the
condenser and (4) metering devices. These components are assembling in several ways to
accomplish the same goal, refrigerated air to cool space.
11.2 PACKAGED AIR CONDITIONING
The four components are assembled into two basic types of equipments for air conditioning
purposes: packaged equipment and split system equipment. With package equipment all of
the components are building into one cabinet. It also called self contained equipment.
Package equipment may be located beside the structure or on top of it. In some instances the
heating equipment is built into the same cabinets.
11.3.1THE EVAPORATOR
The evaporator is the component that absorbs heat into the refrigeration system; it is a
refrigeration coil made of aluminum fins on either type attached to the coil to give it more
surface area for better heat exchange.
The evaporator coil has several designs for airflow through the coil and draining the
condensate water the coil, depending on the installation. The different designs are known as
the A coil the slant coil and the H coil.
11.3.2THE A COIL
The A coil is used for upflow; downflow, and horizontal flow applications. It consists of two
coils with their circuits side by side and spread apart at the bottom in the shape of the letter
A, in the figure below. When used for upflow or downflow, the condensate pan is at the
bottom of A pattern. When used for horizontal flow, a pan is placed at the bottom of the coil
and the coil is turned on its side. The air flows through A coil is through the coil of the coil. It
can not be from side to side with the two coils in series. A coil is not the best coil application
for horizontal application. When horizontal air flow is needed slant or H coils may be more
desirable.
Fig 11.4
An A coil
11.3.4THE H COIL
The H coil is normally applied to horizontal applications although it can be adopted to
vertical applications by using special drain pan configuration. The drain is normally at the
bottom of the H pattern.
window units: These are self-contained units of small capacity of 1 TR 3TR and are
mounted in a window or through the wall. They are employed to condition the air of
one room only. If the room is bigger in size, then two or more unit are installed.
Vertical packed unit: These are self contained unit of bigger capacity of 5-20TR and
are installed adjacent to the space to be conditioned. This is very useful for
conditioning the air of a restaurant, bank or small office.
WEEK 12
12.0 KNOW HOW TO SERVICE REFRIGERATION SYSTEM
If the above checks prove satisfactory, check the valve superheat as follows.
a) Using (preferably) an electronic thermometer, or alternatively a sensitive dial thermometer with a
gas-filled bulb, clamp the thermocouple or bulb securely to the suction line at point A.
b) Using a self-sealing access valve at point B, fit a gauge to read the evaporator outlet pressure and,
using a pressure/temperature chart, convert this to the equivalent temperature. (N.B. suction
temperature can be calculated from the pressure at the compressor suction port, minus say 1 C or a
more accurate estimate of pressure drop in the suction line; but this is not as accurate as the method
first described.) Subtract temperature B from temperature A to determine the superheat of the
system.
For example:
a revolution at a time. Note the effect on the temperature at point A (remembering that it can take up
to half an hour for a valve to settle down gain). Unfortunately, TEV manufacturers have not
standardized settings - one cannot, for example, say 'turn anti-clockwise to reduce superheat'. To be
safe, look up the technical data on the valve concerned, or be prepared to spend time getting the
correct setting by trial and error. If It is necessary to strip a TEV for any reason, the system should be
pumped down and valves off so that the valve is at a slight positive refrigerant pressure - say 14 kPa (2
psi). This system pressure will resist the entry of air or other contaminants.
Either may result in any of the common symptoms 'valve will not open'; 'valve will not close'; Valve is
not seating properly' or 'the coil has burned out'. Cross-sections through various types of solenoid
valve appear in Fig. below (reversing) and (liquid-line).
In the event of trouble with a solenoid valve, pump down to a slight positive pressure and
check it for wax, carbonized oil or other contaminants. If any are present, strip and
thoroughly clean the valve and renew the refrigerant strainer ahead of the valve, as well
as the strainer in the entry port of the valve (if applicable). Distorted valve bodies can only be
replaced. If doing this, note the procedures detailed in the previous lessons point the flame
away from the valve body. If possible favour designs with longer, not shorter sweat
connection 'tails'. Valves must be installed in the same plane (horizontal or vertical) as the
original, and be of the same make and type - some will only work if plungers are vertical (i.e.
the body is horizontal) but others have strong enough coils to work in any plane.
Fig 12.2
typical installation layout. The set point pressure is adjusted by the control spring, and the
valve remains closed so long as evaporator pressure is above the preset level. If it falls below
the set point, the valve starts to open and hot gas is injected into the entrance to the
evaporator. This increases suction pressure, and the load on the compressor, and prevents
frosting back or liquid slugging. Note from Fig. below that a solenoid valve is installed in the
discharge line ahead of the bypass valve (it is wired in parallel with the liquid-line solenoid
valve) to prevent the refrigerant pump-down system from being bypassed and rendered
inoperative. To adjust such a valve, fit a suction gauge and coarse-set the desired suction line
pressure by adjusting the liquid-line valve. Finer settings can then be made by retensioning
the adjustment spring. Bypass valve problems are not common if systems are free from
contaminants. Two types of defects can be found.
a) Valve will not open - due to the seat or piston being affected by sludge or other
contaminants. Pump down to a slight positive pressure and strip and clean the valve
b) Valve will not close - due to one of:
i) presence of contaminants - see (a) above
ii) bypass tube blockage or restriction -clean or replace bypass, and strip and clean valve
iii) diaphragm failure - replace valve power element.
WEEK 13
issued
by
their
13.2
PRESSURE CONTROLS
A typical pressure control section is illustrated in Fig. below. To adjust control settings, fit suction and
discharge pressure gauges and make only small changes to settings before checking effects on system
procedures. Control operation, and the accuracy of existing settings, can be tested by 'rigging' the
equipment. For a high pressure control, progressively blank off an air-cooled condenser with a sheet
of hardboard, and note the pressure at which the control operates (or fails to operate!). For a low
pressure control, system pressures can be steadily reduced by throttling down at the liquid-line valve.
In either case, be ready to remove the 'obstruction' quickly if pressure changes are greater, and occur
more quickly, than expected.
Fig. 13.2
Pressure control
The weakest point of an open compressor is its shaft seal, which is likely to leak oil and refrigerant as
the result of mechanical damage by misaligned drive kits, as well as 'fair wear and tear1. A typical shaft
seal is illustrated in Fig. below. The seal is contained between a step (or 'shoulder') in the shaft, and a
bolt-on seal (or 'gland') cover. The shaft passes through the seal and cover, to carry the half shaft or
vee belt pulley.
The wearing surfaces of a seal are held in place by a spring, or bellows. This is slipped over the shaft,
and secured at the shaft 'shoulder' by a sleeve. At its front end, the spring presses a carbon sealing
ring against a matching metallic surface. The two wearing surfaces are lapped to optical standards of
flatness and covered by a film of recirculated refrigeration oil, which provides the ultimate seal against
differing pressures at each side of the assembly. A gasket is normally used inside the seal end cover,
which is itself machined to close tolerances around the shaft aperture. A shaft seal leak is indicated
first by loss of refrigerant - which can be detected by a lamp or electronic refrigerant detector -and
then by refrigeration oil seeping through the seal. To replace a seal, the compressor should be
pumped down to a slight positive pressure (14 kPa (2 psi)), switched off, and its service valves frontseated. N.B. This procedure is followed every time, it is necessary to open an open or accessible
hermetic sealed compressor or system component.
The seal cover is then carefully unbolted, leaving two bolts at opposite extremes of the cover until last,
so that any excess pressure can be released in a controlled fashion. When the cover has been removed,
the seal components can be removed by hand, or using a seal withdrawal tool. The wearing surfaces of
seals which are leaking but not badly damaged can be repaired by carefully relapping.
13.3.2
The valve plate and suction/discharge reed assemblies can be easily removed after an open or
accessible hermetic compressor has been pumped down. Valve plates can be relapped if slightly
worn, but there is little future in attempting to repair damaged valve reeds. Note that new
gaskets should always be fitted when a compressor Component is removed for scrutiny or repair.
13.3.3
STRIPPING COMPRESSORS
After systems are pumped down, and seal end covers removed, compressors can be separated from
their service valves and the Oil poured into suitable containers. Examine the oil to see if it contains any
swarf or contaminants, but do not use it again in the compressor. After removing the rear (or motor)
end cover and gasket, the compressor pistons, connecting rods and crankshaft can be removed in that
order. Con rods and pistons must be marked, to ensure that they are replaced in their original
positions. Any damaged items must be replaced and all components should be stored in clean
refrigeration oil until it is time for them to be cleaned (preferably using R11 or a non-toxic, nonexplosive cleansing/grease solvent; caustic soda and trichloroethylene are not recommended) and
replaced. Do not forget Shaft or other bearings, which must be examined for fit and wear and must be
replaced if their condition is less than excellent. Oil strainers and channels must also be carefully
inspected, and any contaminants removed.
When re-assembling compressors, take care not to use the original gaskets (or other sealing materials)
or oil. All components (including the crankcase and other castings) must be cleaned and examined to
ensure they are free of defects, then coated with fresh, dry refrigeration oil. Care must be taken not to
over-tighten bolts, and the use of torque-indicating wrenches is desirable. We list a logical order in
which components can be refitted.
a) Crankshaft bearings (often grooved or marked to indicate which side should contact the thrust
surfaces of the crankshaft).
b) Crankshaft (inserted from the front (seal) end) then the seal end cover.
c) Oil pump end bearing head. Adjust the end play of the crankshaft by shims between the bearing head
and housing. Double check the end play with a feeler gauge after the bearing head is positioned and
tightened.
d) Remove the seal end cover, and insert the shaft seal. Replace the end cover.
e) Install the oil pump and suction strainer.
f) Assemble and test (i) valve plates and reeds, and (ii) the cylinder unloader mechanism, if used.
g) Fit piston compression oil rings, if used.
h) Assemble pistons, con rods, and (if used) cylinder liners,
i) Properly position the crankshaft, insert pistons and con rods through cylinders, and complete the
assembly to the crankshaft.
j) Refit the valve plate and cylinder head,
k) Replace the compressor on its base, and connect the service valves.
l) Insert a new charge of dry refrigeration oil.
m) Evacuate and leak test the compressor,
n) Return the unit to operation.
Fig 13.6
WEEK 14
Fig. 14.1
Hand pump
be 100 per cent certain that it is necessary to fit a replacement before proceeding beyond the test stage.
The electrical checks to be made to establish whether motor windings or insulation have been
irrevocably damaged are detailed in the next chapter. Mechanical defects which justify replacing a
compressor are as follows.
a) Components being jammed, or 'frozen' - normally follows lubrication problems, but can occur as
the result of tight tolerances between piston and cylinder or stator and rotor. In this case, it may be
possible to get a compressor "running by increasing the starting torque of its motor (using 'starting
gear' or fitting it for C.S.R. operation) arid/or running the motor backwards for a minute or two.
b) The unit 'jumping' from its internal mounting springs as the result of mishandling (normally the
consequence of an appliance not standing upright during transit). The symptom is an abnormally high
noise level (hammering), frequently followed by loss of pumping efficiency as the result of internal
pipelines fracturing.
c) Damage to suction or discharge valves, or other components, resulting in unacceptably low
pumping efficiency. This condition can be positively checked if the compressor does not incorporate
gauge ports, by installing line-tap or Schrader valves close to suction and discharge tubing connections
to the compressor casing. The most serious damage is that which results from a compressor motor
burning out. This causes oil to carbonize, form sludge, and contain acids as well as pieces of charred
winding insulation and electrical materials. All traces of these contaminants must be removed from the
system when the compressor is replaced, since their presence inevitably leads to a repeat burnout.
Burned out compressors must be handled with caution. If the seal of the service (or 'slave') tube is
broken, the characteristic smell of burned windings is unmistakable and the compressor oil will be
dark, evil-smelling and contaminated with carbonised particles. Contaminated refrigerant should be
purged to fresh air, using a disposable length of tubing, before the compressor is removed; and
protective clothing (goggles and gloves) must be worn to prevent refrigerant, oil or acids from injuring
skin or the eyes. Compressor replacement procedures are given below.
a) With power off, remove all electric conductors and accessories. Using a pipe cutter, cut suction and
discharge lines close to (within 50 mm of) the compressor housing, unless service valves are fitted.
h) Using a fully-equipped charging station, add the correct refrigerant (and if applicable oil)
charge.
i) Remove the charging equipment, remake all electrical equipment and start up the new
compressor.
j) Check the pressure drop across the suction-line filter-drier, using a differential pressure
gauge if possible and check the amperage drawn by the compressor.
k) After one hour, recheck the pressure drop. Ideally, this should not exceed the values.
I) After three hours, again check the pressure drop. If this exceeds three times the value
quoted, fit new liquid and suction-line driers. This procedure must be repeated until the
pressure drop stabilizes at or below the levels indicated above, for permanent operation.
m) Where the replacement compressor is a second or third replacement, i.e. the system is
one in which there have been several burn-outs, an oil sample should be taken and acid-tested
when the suction line drier pressure drop is at an acceptable level. Only if the oil is confirmed
to be acid-free can the operation be regarded as satisfactorily completed.
The above procedures are fully current, many being based on Tecumseh recommendations.
The sequence of operations and end objectives is of course the same in systems using welded
or accessible hermetic compressors. The only changes are those resulting from variations in
evacuation and leak testing procedures when working on large systems.
Fig 14.3
A second type of fitting uses a steel adaptor, which fits over and is silver-soldered to stub tube
connections emerging from the compressor casing. (Don't forget to cut the end seals from stubs
before fixing the adaptors!) The other end of the adaptor is threaded to receive a screw-on Rotolock
valve (which has a capped service or charging port). Electrically or mechanically operated recording
Instruments covering a variety of applications are available - some forming in Integral part of control
systems. Figure below, Illustrates a two-pen, 24-hour DB and WB temperature recorder which is typical
of a wide range of instruments available.
Fig 14.5
REVISION QUESTIONS
1 The plant for a commercial cold room includes a 0-5 kW semi-hermetic compressor charged with R12. It is
suspected that air has entered the system, and service pressure gauges have been installed.
a) List two major observations made using the gauges which would confirm the presence of air.
b) Enumerate two other ways in which the presence of air could be confirmed.
c) Describe in detail the method used to eliminate the air.
d) What signs would confirm that air has been present, the compressor valve cover and valve plate having been
removed for inspection?
2 a) Make a labeled line sketch showing the layout of a commercial refrigeration evaporator and an externally equalized
thermostatic expansion valve.
b) With the help of your diagram, explain briefly how the TEV superheat setting can be checked and altered.
WEEK 15
completely vaporized from being carried over into ducts or conditioned space. Efficiency will vary with
changes in the temperatures of the water or room air.
Fig 15.3
Water atomizers
15.4
CONDENSERS
15.4.1
AIR -COOLED
Structural details are as described in Chapter 6, and the use of motor speed controllers or fan outlet
dampers is more common in tropical installations than would at first sight seem likely. It must be
remembered that condensers operating in extremely hot climates are 'oversized' to secure acceptable
condensing pressures by day in extreme heat. When temperatures fall overnight, or in winter, condensers
may become effectively oversized and be unable to maintain liquid refrigerant at pressures high enough to
ensure satisfactory system operation. Whilst it is not necessary to build solar screens for properly designed
condensers, it is desirable to take advantage of any shade provided by buildings when outdoor
temperatures are at their peak.
Fig 15.4
Fig 15.5
15.5
WATER PUMPS
For air-conditioning needs - whether circulating chilled or condenser water -centrifugal
pumps such as the one shown in Fig. below are invariably used. These operate on similar
principles to the centrifugal compressors described earlier in this chapter. Water enters at
the centre of a fast-turning impeller; it is thrown to the outside of the impellers, the
converging blades of which add to its speed; and it collects in a volute leading to a discharge
port at right angles to the direction of entry. In many cases, the casing can be rotated to
enable the discharge connection to be made to pipework at several optional positions
around 'the clock'.
Two pump speeds are most likely to be used on 50 Hz supplies: 1 500 or 3 000 r.p.m.
synchronous. The faster the speed, the greater the head against which the pump can deliver
water, but the more noise it generates. There is also a risk that pumps running at the same
speed as centrifugal compressors may set up sympathetic vibrations which affect both, so
the lower running speed is usually favoured.
The bodies of pumps designed to handle water are likely to be of cast-iron construction,
trimmed in bronze with a bronze or stainless-steel shaft, and bronze impeller(s) - like
compressors, pumps can have several stages to enable them to operate against higher
pressures - and bearings. Water leaks are normally avoided by the use of rotary shaft seals.
The old fashioned stuffing box is rarely seen on new equipment.
There are several means of connecting the motor and the pump. If the pump is mounted on
a baseplate a direct-drive coupling is usually employed, but some prefer to use pulleys and
vee belts. The most foolproof arrangement is that used in accessible hermetic compressors
with both pump and motor on a common shaft and secured within a single-piece or closecoupled body assembly.
Whilst installation and instrumentation needs are covered in the previous discussion, it
should be noted that pumps should always have a valve, an anti-vibration coupling and
provision for the use of a pressure gauge on both suction and discharge sides. The use of a
water strainer immediately before the pump is essential. In many cases, a second pump is
piped into the circuit ready for use if the first fails. This entails some complicated pipework,
and, in order to avoid the need for this, an increasing number of manufacturers now offer
factory-assembled dual-pump assemblies, with both the running and standby pumps
completely plumbed in at the factory. One such assembly is shown in Fig. below.
There is little basic difference between pumps designed to handle water, brine or
refrigerants. All components in contact with the liquid being handled must be chemically
compatible with it at operating temperatures, but operating principles are little changed.
Fig 15.6a
Fig 15.6b
Centrifugal
entrifugal water pump
Dual
ual pump assembling
Fig 15.7
e) Discharging all air at a pressure equaling the sum of the resistances to airflow offered by
ductwork, supply grilles and diffusers, and all airhandling unit components. Each of these
requirements can be satisfied in one of several ways. We shall note most in passing, but study in
detail only those in widespread use in our specific (geographical) areas of interest.
filtered before
being mixed with return air in either a plenum, or a mixing box fitted with opposed-blade
dampers
regulate the volume of each type. In regions with wide seasonal variations in temperature,
air
intake
temperatures,
reduce demands for refrigeration or heating at times when the ambient air temperatures
to
to
approach
15.6.2 FILTRATION
There are three types of filter for normal use:
a) Throwaway types, of foamed plastic or glass fibre construction.
b) Cleanable types, normally using metal 'wool* or fibre as the filtering medium. This can be
washed clean, and may be coated with oil or other viscous material to increase its efficiency,
c) High efficiency filters, used dry and made from pleated mats of
fibre,
wool
felt,
cellulose
or synthetic materials. The choice of material in this and other types of filter depends upon the
information by automatically winding on a new section of filter material, are very effective, but their use is
limited by first costs. Electrostatic or electronic air filters are discussed later.
coils The main difference between direct-expansion and chilled-water coils is that water designs
use only one circuit, Capacity control is provided by modulating the volume of chilled water
passing through the coil, or by using face and bypass dampers to vary the quantity of air passing
over it. The use of one continuous tube would result in excessive water pressure drops and, to
avoid this, headered construction is used to supply a number of circuits in parallel. Air vent plugs
are usually provided at the top of coils, and drainage plugs at low level. Water inlets are normally at
the top of coils. Condensate disposal Cooling coils - and control valves - must be provided with fullsize condensate trays, to collect moisture removed from conditioned air. These trays are
normally of pressed-steel construction, insulated with sprayed-on polystyrene or polyurethane
to prevent condensation forming on external surfaces. They also include provision for the
connection of drainage lines.
15.6.4
Heating coils
Electric heating coil construction, and safety provisions, has already been described. We
must also be familiar with hot-water and steam heating coils; which are sometimes needed
in even the hottest of climates, to treat air used in industrial processes. General
construction
two rows
those used for chilled water, but coil depth is only one or
with a
Low pressure hot water (LPHW) The maximum temperature of water leaving a low
pressure boiler is 121 C (250F). Typical water conditions through coils are: entry at 82 C
(180 F) and exit at 71 C (160 F). Air quantities over LPHW coils normally produce
velocities between 2-0 and 4-0 m/s (400 and 800 ft/min).
Medium pressure hot water (MPHW) This type, which is seldom used, has a
maximum temperature of water leaving the boiler only slightly higher than
that of LPHW types. In practice, water temperatures at coils are generally of the order of
127 C (260 F) at entry and 99 C (210F) at discharge.
Steam
There is a wide variety of operating ranges of steam boilers and gauge pressures at coil
entries can be between 34 kPa (5 psig) and 1 380 kPa (200 psig). These pressures are
equivalent to temperatures of 108 C (227 F) and 198 C (388 F). Face velocities of air
usually fall in the 2-54 to 6-60 m/s (500 to 1 300 ft/min) range. Coil tubes are normally
larger (25 mm (1") OD) than those used for water, and installations must include steam
traps and condensate return lines. Capacity control is by hot-water or steam flow-control
valves. Water valves are likely to be of three-way, bypass design, and steam valves
two-
15.6.5 Fans
It is unusual to find airhandling units of factory-assembled or 'modular' types, which do not use
centrifugal fans. These are normally double-width, double-inlet types with forward-inclined
blades; and consist of scroll(s), impeller(s) and cone(s), and bearing support pedestals. Sleeve-type
bearings are normally used when motor sizes do not exceed 2-25kW (3 hp), plummer blocks being
fitted for larger capacities. Fan speeds can normally be varied by altering the pitch of a motor
pulley designed for use with either one or two vee belts (although the use of direct-drive, variablespeed electric motors is likely to increase as electronic controllers become more competitive). The
main components of a centrifugal fan, and the varying names which they may be called, are
illustrated below. Other types of centrifugal fans available have backward-inclined, radial or
airfoil blades. The main advantages of centrifugal fans as a class are compact size, reasonable
efficiency and low noise levels in applications against head pressures up to approximately 250 mm
(10 in) water gauge (wg).