Underexcitation Protection
(Loss of Field protection)
Presenter: Dr. Hans-Joachim Herrmann
PTD PA13
Phone +49 911 433 8266
E-Mail: Hans-Joachim.Herrmann@siemens.com

Power Automation

Power Transmission and Distribution

Reasons for Underexcitation


Power Automation
Progress. Its that simple.

? Failure of the excitation device


? short circuit in the excitation circuit
ZLoad

? interruption in the excitation circuit


? Maloperation of the automatic voltage
regulator
? Incorrect handling of the voltage regulator
(generator, transformer)
? Generator running with capacitive load

Countermeasure:
GS
3~

excitation
device

Underexcitation Protection
Note: This protection is also called
Loss of Field Protection

Power Automation

Power Transmission and Distribution

Consequences of Excitation Failures


Power Automation
Progress. Its that simple.

Influence Quantities:
? type of construction of the generator
? design of the excitation
? grid conditions
? magnitude of delivered active power
? type of the voltage and power regulator
Consequences:
? rotor acceleration
? local overheating in the rotor and stator
? over-voltages in the rotor
? mechanical shocks onto the foundation
? grid starts oscillating

Power Automation

Power Transmission and Distribution

Relation of Current and Voltage in a Synchronous


Generator
Power Automation
Progress. Its that simple.

Simplified equivalent circuit:


X

VP

ZL

machine equation:

VP = V - I jX

cylindrical-rotor machine:
(turbo generator)

X~Xd; VP = V- jXd I

salient-pole machine:
(hydro generator)
exact:

X:=Xq; Xd

Vector diagram:
Re
Vp

I jX
V
Iexc

?
?
V / jX

? = rotor angle
? = load angle

Im

reduced:

VP = V - j(XdId + XqIq)
VP ~ V - jXqI

Power Automation

Power Transmission and Distribution

Possible Design of the Generator Capability Diagram


Power Automation
Progress. Its that simple.

Definition:

Preferred design

+Q
(Var)

+P
(W)

Operating
area
over excited

under excited

+P
(W)

Static
stability
limit

under
excited

Operating
area

over
excited

+Q
(Var)

Static stability
limit

Power Automation

Power Transmission and Distribution

Capability Curve of a Turbo Generator


Power Automation

0,85

type of generator:

0,8

0,85

0,9

MW

0,95

0,975

0,975

0,95

0,9

Progress. Its that simple.

nominal apparent power SN


=
nominal voltage
VN =
nominal current
IN
=
nominal frequency
fN
=
power factor
cos ? N =
cold-air temperature
Tx
=

220
200
180

0,8

TLRI 108/46
200
MVA
15.750 kV
7.331 kA
50.0
Hz
0.8
40.00 C

0,7

160
140

0,7

0,6

120

0,6

100
80

0,4

60

0,4

40

cosphi

cosphi

0,2

0,2

MVAr 140 120 100 80

60

underexcited

40 20

20

40

Q
60 80 100 120 140 160 180 MVAr
overexcited

Power Automation

Power Transmission and Distribution

Load Diagram of a Synchronous Machine (Cylindricalrotor Machine)


Power Automation
Progress. Its that simple.

steady
state
stability
limit

dynamic
stability
limit

turbine limit
stator limit

theoretically
limit

VP If
SN

rotor limit

?N

?N

VN
; ? SN
X 'd

VN
Xd

underexcited

Xd: synchronous reactance


Xd: transient reactance
overexcited

The generator capability curve describes


the stability limits of the generator
Power Automation

Power Transmission and Distribution

Per Unit Capability Diagram of a Synchronous Generator


in the Case of Undervoltage (V = 0.9 VN)
Power Automation
Progress. Its that simple.

P [p.u]
1

Stability
limit

0.85

V=1; I=1;
V=0.9; I= 1.11

overexcited

underexcited
0.81/xd

Q [p.u]

1/xd

In the case of an under-voltage the generator capability curve


moves to right and reduces the stability limits of the generator

Power Automation

Power Transmission and Distribution

Conclusions for the Protection Design


Power Automation
Progress. Its that simple.

1. The generator capability curve describes in the


underexcitation region the stability limit of a generator
2. In the case of an undervoltage the stability becomes
much more critical (moves to active power axis)

A good underexcitation protection should consider both facts


(1 and 2)
The transformation of the generator diagram into the
admittance diagram is the solution, because:

? its direct proportional to the per unit generator diagram


(only the reactive axis must be multiplied by -1)
? the settings can be easy read out from the generator diagram
? it considers right the undervoltage behaviour

Power Automation

10

Power Transmission and Distribution

Definitions for Converting the Generator


Diagram into the Admittance Diagram
Power Automation
Progress. Its that simple.

Complex Power:

S ? V ?I

Admittance:

S? P ? jQ

I
Y?
V

Y ? G ? jB

G: Conductance
B: Susceptance

Transformation:
?

P - jQ
I ?V
S*
Y?
?
?
?
?
2
2
V
V
V ?V
+

P
G? 2
V
Q
B? - 2
V

Q
P
j
V2
V2
+

Note: In the per unit calculation is VN = 1

In the per unit


representation
the diagrams
are the same,
only there is a
phase shift in
the reactive
part of 180

Power Automation

11

Power Transmission and Distribution

Additional Solutions for the Underexcitation


Protection
Power Automation
Progress. Its that simple.

a) Excitation Current (IEXC)


- stabile for over-excitation
- insecure for under-excitation (IEXC can be smaller than IEXC, N)

b) Direct Measuring of the Rotor Angle (? )


stability limit depends on ? or 2 ?
- transversal reactance cannot be neglected with small excitation of
turbogenerators (Xq is also depending from 2 ? )

- steady

c) Reactive power I-QI>, Impedance I-ZI<


- the

reactive power protection gets more insensitive when voltage


decreases (at V<VN the stability limit curve moves to right)
- Impedance criterion is used by the competitors
(Stability limit can not be clear seen - see notes beyond )

Power Automation

12

Power Transmission and Distribution

Underexcitation Protection with the Criterion


Admittance Y>
Power Automation
Progress. Its that simple.

char.3

char.2

char.1
G[p.u.]

? Admittance calculation guarantees


a right behaviour, if the voltages
decreases
? 3 independent characteristics and 3
timer
? characteristic 1,2 is adaptated on
the steady state curve;

?3

B[p.u.] x
d3

1
x d1

?2
1
x d2

? additional inquiry of the field voltage


(release a short trip time)

?1

? characteristic 3 is adaptated on the


dynamic stability limit curve
? blocking of the protection at V<25%
VN

Settings: Can direct read out from the generator diagram

1
1
x d1 ? x
d

? 1 = 80

1
1
x d2 ? 0.9 ? xd1

? 2 = 90

1
2
x d3 ? 1 or ? x d

? 3 = 100 or 110

Power Automation

13

Power Transmission and Distribution

Reactions from the Protection


Power Automation
Progress. Its that simple.

Combination of
?

stator criterion (straight line characteristics)

rotor criterion (DC undervoltage in the excitation circuit)

Case no. 1:

only rotor criterion fulfilled:


no alarm, no trip

Case no. 2:

only stator criterion fulfilled ( char. 1,2):


only alarm, eventually long-time delayed trip (e.g. 10s)

Case no. 3:

rotor and stator criterion fulfilled (char. 1,2):


alarm and short-time delayed trip (e.g. <0,5s - 1s)

Case no. 4:

stator criterion fulfilled (char. 3):


alarm and short-time delayed trip (e.g. <0,3s)

Power Automation

14

Power Transmission and Distribution

Conversion of the Reactive Power into 1/xd


Power Automation
Progress. Its that simple.

Example: Generator capability diagram (figure 9)


Generator:
Stability limit:

CT, VT: knV =

SN = 200 MVA
VN = 15,75 kV
Q = 90 MVAr

16kV / 100V
3
3

knl = 8000A/1A

1. Calculation the longitudinal reactance :


Xd ?

?U ?
? N?
? 3?
?
?

Q
3

2
U
? N ? 2,76?
Q

xd ? X d ?

3 IN
? 2,22 or
UN

x d ? SN ? 2,22
Q

2. Conversion into secondary values :

xdsek ? xd

U ?I
UN,G ?INsek ?knl
? xd N,G pN,W ? 2,38
UNsek ?I N,G?knU
I N,G?UpN,W

3. Setting value for Char. 1:


1
1 ? 0,42 ?
? 0,42 ,
x
xdsek
d1

? 1 ? 80?
Power Automation

15

Power Transmission and Distribution

Measuring Algorithm
Power Automation
Progress. Its that simple.

1) Filtering of the input values


iL
vL

I L1 , I L2 , I L3 ,

V L1 , V L2 , V L3 ,

7UM6

I L ? I rL ? j I iL ,
V L ? VrL ? j ViL ,

2) Calculation of the positive sequence values

GS
3~
iL1,2,3

fourier filter
(50Hz)

uL1,2,3

symmetr.
comp.

I1
V1

3) Calculation of the complex power


I1

S?U I*

V1

S? P? jQ

4) Calculation of the admittance values


S

Y ?

S
2
U1

Y ?

1
1
? j
? G ? jB
R
X

Power Automation

16

Power Transmission and Distribution

Underexcitation Protection with Criterion Impedance


I-ZI<
Power Automation
Progress. Its that simple.

Generator diagram is transferred in the impedance plan (e.g. X=V2/Q).


(Stability limit is represented as a circular arc.)
? characteristic: Offset-MHO

X[p.u.]
R[p.u.]

? characteristic 1, tdelay ? 0...0.3 s (for high


load generator and field failure)

0.5 xd

? tripping zone inside the circle

Char.1

? characteristic 2, tdelay ? 0.5 - 3 s (for low


load generator, section field voltage failure)

xd
Char.2

approximation
of stability
limit

Summary:
? Measuring principle is from the electro-

Relay settings according


IEEE C37.102-1995

mechanical relays, because impedance


measuring elements were only available
? circle characteristic is a compromise for

adaptation to the generator stability curve


Power Automation

17

Power Transmission and Distribution

Transformation of Criterion Impedance I-ZI<


into the Admittance plan
Power Automation
Progress. Its that simple.

Transformation rule:
A circle without zero crossing inverted becomes again a circle

Impedance plane
X[p.u.]

Admittance plane

1
Y?
Z

G[p.u.]

R[p.u.]
0.5 xd

Char.1

B[p.u.]

xd

2
1
?
2 ?x d ? x ,d x d

Char. 2

2
x ,d

2
?1
,
2 ? xd

Power Automation

18

Power Transmission and Distribution

Setting Example for Impedance and Admittance Principle


Power Automation
Progress. Its that simple.

Settings: 501- Generator xd= 0,27; xd = 1,81


Diameter= 1

0,5 Xd = 0,13

Admittance Plane
Impedance Plane

2.5

1.25

0.33
0.67

0
1
1.33

1.25

1.67
2

2.5
1

0.5

0.5

2.5

1.75

0.25

0.5

1/Xd = 0,55
Diameter: Xd = 1,81

All values are in per unit

2/Xd = 1,1

Power Automation

19

Power Transmission and Distribution

Both Measuring Principle in the Admittance Plane


Power Automation
Progress. Its that simple.

Impedance principle

Admittance principle
Admittance Plane

Trajectory in the
case of underexcitation
with 100% excitation
loss

Generator
diagram
0

Settings:
xd = 0,27
xd = 1,81

2/Xd = 7,4

Note:
B-axis is for mathematical
reasons multiplied by -1

1/Xd = 0,55

Power Automation

20

Power Transmission and Distribution

Turbo generators: Pick-up Conditions of Different


Relay Characteristics in the Admittance Plane
Power Automation
Progress. Its that simple.

1
R

II

5,5
1

2,5

?
2
X?
d

2
X
d

Power Automation

21

Power Transmission and Distribution

Dynamic Test on a Network Model with RTDS


Fault Record
Power Automation
Progress. Its that simple.

Test condition: P=160 MW Q=25 MVar; If = 1,87 If0; Voltage regulator failure: V= 1,05
0,8
Relay settings: Char 1 = 0.55 ? 80, 10s; Char 2 = 0.51 ? 90, 10s; Char 3 =1.1 ? 110, 0s

Power Automation

22

Power Transmission and Distribution

Dynamic Test on a Network Model with RTDS


Calculated Symmetrical Components
Power Automation
Progress. Its that simple.
3
9.512 ?10

4
1 ?10

in V in V
Prim. Spannung
Voltage

7500
U0
U1
U2

i
i

5000

i
2500

0.354

Strom in A in A
Prim. Current

1.229

?10 4

I0
I1
I2

0
4
1.5 ?10 94.986

500

1000

1500

2000

2500
3
2.483 ?10

ta

i
Zeit in ms

4
1 ?10

i
i

0.086

5000

0
94.986

500

1000

1500
ta

i ms
Time
in
Zeit in ms

2000

2500
2.483

?10 3

Power Automation

23

Power Transmission and Distribution

Dynamic Test on a Network Model with RTDS


Results in the Impedance Plane
Power Automation
Progress. Its that simple.

Reactance in Ohm

0.5

0.5

Load
point

0.5

XZ( p )

XZS ( p )

1.5

All
impedances
are primary
values

2.5 2.5

1.5
1.5

0.5

0.5

R ?RZ( p ) ?RZS ( p )
i

1.5

Resistance in Ohm

2
2

Power Automation

24

Power Transmission and Distribution

Dynamic Test on a Network Model with RTDS


Results in the Admittance Plane
Power Automation
Progress. Its that simple.
150

150

100
G1

Load
point

Ch1 ( l )
Ch2 ( l )
Ch3 ( m )
50

250
237.814

200

150

100
B1 ?l ?l ?m
i

Scaling in percent - related to primary values

50

50
12.87

X calculation every 50ms

Power Automation

25

Power Transmission and Distribution

Dynamic Test on a Network Model with RTDS


RMS Fault Record - Low Load Condition
Power Automation
Progress. Its that simple.

Test condition: P=40 MW Q=25 MVar; If = 1,4 If0; Voltage regulator failure: V= 1,05
0,7
Relay settings: Char 1 = 0.55 ? 80, 10s; Char 2 = 0.51 ? 90, 10s; Char 3 =0.9 ? 100, 0s

Power Automation

26

Power Transmission and Distribution

Dynamic Test on a Network Model with RTDS


Result in the Impedance Plane
Power Automation
Progress. Its that simple.
3.339

Load
point

Reactance
in in
Ohm
Primrwiderstand
Ohm

X1

Im( Z( p ) )

Generator oscillates
near pickup characteristic

Im( ZS ( p ) )

2
1.103

R1 ?Re ( Z( p ) ) ?Re( ZS ( p ) )
i
Primrwiderstan
in Ohm
Ohm
Resistance in

7
6.446

Power Automation

27

Power Transmission and Distribution

Dynamic Test on a Network Model with RTDS


Result in the Admittance Plane
Power Automation
Progress. Its that simple.

50

50

Leitwerte in Prozent

40

Underexcited
region for 3.2 s

30

G( i )
Ch1 ( l )
Ch2 ( l )

20

Load
point

Ch3 ( m )

Oscillating near
the characteristic

10

0
5
100
100

80

60

40

20

20

B ( i ) ?l ?l ?m
Leitwerte in Prozent

Scaling in percent - related to primary values

12.066

X calculation every 20ms

Power Automation

28