Escolar Documentos
Profissional Documentos
Cultura Documentos
STEVEN BELLONE
SUFFOLK COUNTY EXECUTIVE
SUFFOLK COUNTY
DEPARTMENT OF HEALTH SERVICES
DIVISION OF ENVIRONMENTAL QUALITY
12/1/09
TABLE OF CONTENTS
Section
Page
I.
INTRODUCTION .........................................................................................................................1
II.
III.
IV.
V.
VI.
VII.
VIII.
IX.
X.
XI.
XII.
XIII.
XIV.
XV.
XVI.
XVII.
XX.
XXI.
XXII.
12/1/09
12/1/09
LIST OF TABLES
TABLE 1 PROJECT DENSITY LOADING RATES & DESIGN SEWAGE FLOW RATES .................12
TABLE 2 MINIMUM HORIZONTAL SEPARATION DISTANCES ...................................................21
LIST OF FIGURES
FIGURE 1 SINGLE UNIT SEPTIC TANK
FIGURE 2 TWO UNIT SEPTIC TANK
FIGURE 3 MULTIPLE UNIT SEPTIC TANK (3 & 4 Units)
FIGURE 4 MULTIPLE UNIT SEPTIC TANK (5 & 6 Units)
FIGURE 5 SINGLE UNIT GREASE TRAP
FIGURE 6 MULTIPLE UNIT GREASE TRAP
FIGURE 7 LEACHING POOL DESIGN AND CONSTRUCTION DETAILS
FIGURE 8 LEACHING POOL ARRANGEMENT/LAYOUT
FIGURE 9 ACCESS/JUNCTION MANHOLE
ii
12/1/09
LIST OF APPENDICIES
APPENDIX A STANDARDS FOR CONSTRUCTION OF MODIFIED SEWAGE DISPOSAL SYSTEMS
AND SMALL COMMUNITY SEWERAGE SYSTEMS
APPENDIX B STANDARDS FOR APPROVAL AND CONSTRUCTION OF SEWAGE COLLECTION
SYSTEMS AND TREATMENT WORKS
APPENDIX C REQUIREMENTS OF DEPARTMENT OF HEALTH SERVICES AND
RESPONSIBILITIES OF LICENSED DESIGN PROFESSIONALS IN INSPECTING ON-LOT SEWAGE
TREATMENT SYSTEMS OR COLLECTION SYSTEMS
ii
12/1/09
STANDARDS FOR
APPROVAL OF PLANS AND CONSTRUCTION FOR
SEWAGE DISPOSAL SYSTEMS FOR
OTHER THAN SINGLE FAMILY RESIDENCES
I.
INTRODUCTION
These are the Suffolk County Department of Health Services Standards for the Administration of Section 502, of
Article 5 (Sewage Disposal), Sections 607-609 of Article 6 and Sections 705, 706, 709-716 of Article 7 of the
Suffolk County Sanitary Code.
The purpose of these standards is to provide a means for achieving protection of the groundwater from excessive
contaminant loading and to assure a safe, sanitary means of disposing of wastewater. Diseases such as infectious
hepatitis, typhoid fever and dysentery can be transmitted by water, food, insects, pets, and toys contaminated by
human waste. Properly designed, maintained and operated sewage disposal systems minimize the possibility of
disease transmission and the potential for contamination of ground and surface waters.
These standards apply to commercial, industrial, multiple residential or other buildings and only address sewage as
herein defined. Other solid, liquid or gaseous emissions or discharges are subject to a separate review and approval
by the Department. For details relating to single family residences, refer to Standards - Approval of Plans and
Construction - Sewage Disposal Systems for Single-Family Residences.
II.
AASHTO H-20 Loading. AASHTO is the American Association of State Highway and Transportation Officials.
H-20 refers to the manufacture of sewage disposal system components and access covers capable of withstanding
a 16,000 lb/sq. ft. live load, caused by traffic conditions. H-20 loading simulates the load due to a 20 ton truck.
Acre. Forty Three Thousand Five Hundred Sixty (43,560) square feet.
Adjusted Gross Land Area. Gross land area of a parcel minus area of regulated freshwater or tidal wetlands and
ponds or other underwater lands.
Alternative Sewage Disposal System. A subsurface sewage disposal system which contains design elements not
explicitly described herein or components that are arranged differently than shown in the conventional layouts of
these standards.
Apartment. A premises occupied by an individual or family which is leased or rented from a corporation, entity, or
another individual. Apartments are considered Multiple Residential Units.
ASTM. American Society for Testing and Materials.
Page 1
12/1/09
Page 2
12/1/09
Gross Floor Area. The floor area of all levels, within the exterior walls of a building or enclosed structure.
Unfinished and/or mechanical spaces within cellars and attics are not included in the gross floor area.
Groundwater. The subsurface water occupying the zone of saturation below the established water table.
Groundwater Management Zone. Any one of the areas delineated in Suffolk County by the "Long Island
Comprehensive Waste Treatment Management Plan (L.I. 208 Study)," as revised by the "Long Island Groundwater
Management Plan", and subsequent revisions adopted by the Suffolk County Board of Health identifying differences
in regional hydrogeologic and groundwater quality conditions. The boundaries of the Groundwater Management
Zones are set forth on a map adopted by the Board filed in the Office of the Commissioner of Health in Hauppauge,
New York.
Groundwater Monitoring Well. A well introduced into a particular aquifer for the purpose of obtaining samples
of the groundwater for chemical analysis.
Highest Recorded Groundwater. The highest recorded groundwater elevation based upon the historic data of
both the Department of Health Services and the United States Geological Survey.
Hydraulic Load. The sum of the density load and kitchen/gray load for a particular use of a building on a parcel
expressed in terms of gallons per day per applicable unit.
Invert Elevation. The lowest elevation of the inside of a sewer line, water line, or other piping.
Kitchen/gray Load. The volume of sewage discharged from food preparation and service areas, or other gray
water uses from a building expressed in terms of gallons per day per applicable unit which are omitted from the
Density Load.
Leaching Area. The sidewall absorption area in a leaching pool below the inlet pipe, distribution pool below the
outlet pipe, or the bottom surface area of a recharge bed. The area of the bottom of leaching pools is not included
in leaching area.
Leaching Pool. A covered pit with a perforated reinforced concrete wall through which effluent from septic tanks
or sewage treatment systems will infiltrate the surrounding soil.
Liquid Depth. The depth measured from the bottom of a septic tank or grease trap to the outlet invert elevation.
Manhole. A watertight chamber used for smooth redirection of sewage flow and/or to provide access to sewer
lines.
Modified Subsurface Sewage Disposal System. An On Site Sewage Treatment system (treatment works)
which includes processes capable of meeting applicable discharge standards and where the Design Sewage Flow
does not exceed 15,000 gallons per day.
Page 3
12/1/09
Multiple Residential Projects. All residential construction other than detached single-family housing units each
on its own separate lot. Examples include two-family houses, apartment complexes, town homes, condominiums,
co-ops, mobile home parks, or other similar arrangements.
Municipal Sewage Treatment System. A system utilized for the collection and disposal of sewage, or other
waste of a liquid nature, including the various devices for the treatment (treatment works) of such wastes, serving a
municipal sewer district.
NEC. National Electrical Code published by the National Fire Protection Association.
NEMA. The National Electrical Manufacturers Association.
NYSDEC. The New York State Department of Environmental Conservation.
Occupancy Rating. The maximum number of persons permitted to occupy an establishment as determined by the
appropriate agency.
On - Site Sewage Treatment System. A treatment system (treatment works) located on the same parcel as the
building(s) it serves which includes processes capable of meeting applicable discharge standards.
Perched Groundwater. Groundwater which is separated from the main body of groundwater by an aquiclude (e.g.
a clay lens).
Planned Retirement Community (PRC). A multiple residential project in which each unit is required by law or
regulation to be occupied by at least one resident per unit who is 55 years of age or older.
Population Density Equivalent. An expression of the quantity of domestic sewage in terms of the calculated
population per unit area. (The calculated yield in gallons per day).
PVC pipe. A type of flexible thermoplastic pipe, manufactured from ethylene and chlorine, which may be used for
sewer lines.
Rooming House. A building arranged or used for lodging for compensation, where group sleeping
accommodations are provided in one room, or a series of rooms, and shared bathroom and kitchen areas may be
provided.
SCDPW. The Suffolk County Department of Public Works
Standard Dimension Ratio (SDR). The ratio of the outside pipe diameter to the pipe wall thickness.
SEQRA. State Environmental Quality Review Act - a process that requires the consideration of environmental
factors in the planning stages of a proposed action(s).
Septic Tank. A watertight chamber used for the settling, stabilizing and anaerobic decomposition of sewage.
Page 4
12/1/09
Sewage. Water-carried wastes from residences, institutions, businesses, commercial and industrial buildings and
establishments or a combination thereof, together with such ground, surface, and storm water as may inadvertently
be present. The admixture of industrial wastes or other wastes shall not be considered sewage for purposes of these
standards except where otherwise indicated. "Industrial wastes" and "other wastes" have the meaning as defined in
Environmental Conservation Law Sections 17-0105(5) and (6).
Sewage Disposal System. Any plumbing or conveyances which are capable of receiving a discharge of sewage.
This includes, but is not limited to, sewer lines, septic tanks, leaching pools, sumps, grease traps, tile fields, holding
tanks, treatment works, outfalls and connecting piping. The term may also refer to a part of a larger disposal
system.
Sewage Pump. Any type of device designed for the purpose of pumping sewage or other liquid wastes. Some
examples of sewage pumps may include the following:
1.
Grinder Pump. A type of submersible sewage pump used to cut, shred, or reduce in size, solids
found in raw sewage.
2.
Positive Displacement Pump. A type of pump capable of pumping raw sewage or liquids at a
constant rate while utilizing various pressure heads.
3.
Submersible Sewage Pump. A type of pump designed to operate while submerged in sewage.
4.
Vacuum Pump. A type of pump capable of pumping air or a mixture of air and liquid.
Sewage Pump Station. A structure that contains pumps, piping, and other equipment used for the purpose of
receiving, temporarily storing, and pumping sewage.
Sewage Recharge Bed. A designated area exposed to the atmosphere where treated wastewater is distributed for
the purpose of infiltrating the surrounding soil.
Sewage Treatment Plant (STP).
A sewage treatment system (treatment works) which includes processes
capable of meeting applicable discharge standards and where the Design Sewage Flow rate exceeds 15,000 gpd.
Sewage Treatment System. Is a sewage disposal system consisting of a sewage collection system and treatment
works.
Sewer Line. A pipe designed to convey sewage. Examples include the following:
1.
House Connection. The gravity sewer line which extends from the face of the building to the
sewage disposal or sewer system.
2.
Lateral or Branch Sewer Line. The gravity sewer line used to collect sewage from one or more
building sewers or house connections.
Page 5
12/1/09
3.
Main Sewer Line. The gravity sewer line used to collect sewage from one or more lateral or branch
sewer lines.
4.
Sewage Force Main. A sewer line designed to receive the sewage discharged from a pumping
station and convey it under pressure to the point of discharge.
Sewer System. (Also referred to as sewage collection system, public sanitary sewer, municipal sewage disposal
system, privately owned communal sewerage system, and communal sewage disposal system) Pipe lines, conduits,
pumping stations, and force mains, and all other constructions, devices, and appliances appurtenant thereto, used for
conducting sewage to a point of ultimate disposal.
SPDES (State Pollutant Discharge Elimination System) Permit. A permit, issued by the NYSDEC,
authorizing discharges of 1,000 gallons per day or greater to the ground or surface waters of New York State.
Stormwater Recharge Basin. A designated area exposed to the atmosphere where stormwater is collected and
distributed for the purpose of infiltrating the surrounding soil.
Suffolk County Sewer Agency (Sewer Agency). The agency responsible for directing the means and method of
sewage disposal for projects involving multiple ownership where the Suffolk County Health Department has
determined that sewage treatment is required.
Thrust Block or Restraint. A device used to resist thrust forces due to changes in alignment or direction of force
mains.
Treatment Works. A facility designed for the purpose of removing certain constituents from sewage by mechanical,
chemical or biological means, and stabilizing, and disposing of sewage.
USGS. United States Geological Survey. (Also, the NYS Building Code makes reference to the USC&GS United States Coast and Geodetic Survey.)
Valve Chamber. A separate concrete box or chamber used to contain and access valving for the purpose of flow
control or to isolate pumping units without having to enter the pump station.
Wet Well. The portion of a sewage pump station that receives and temporarily stores sewage.
III.
The installation of a sewage disposal system(s) is prohibited by the Suffolk County Sanitary Code
unless a permit to construct has been issued by the Commissioner.
2.
The construction of a new building or an addition to an existing building is prohibited unless the
proposed sewage disposal system(s) serving such building has been approved by the Department
Page 6
12/1/09
and/or the existing sewage disposal system(s) have been approved by the Department for the
additional use.
Page 7
IV.
12/1/09
3.
The construction of a building or building addition without plumbing or additional sewage disposal
facilities is prohibited unless sewage disposal system(s) serving such facilities have been certified to the
Department by a licensed design professional as capable of accepting
sewage flows generated by the use of such new facilities and such facilities conform to the density
load requirements of the Department.
4.
A change in use or renovation to an existing building that may affect the Density Load or Design
Sewage Flow is prohibited unless the proposed sewage disposal system(s) serving such building has
been approved by the Department and/or the existing sewage disposal systems have been approved
by the Department for the additional use.
5.
The occupancy of a building(s) and/or the use of a sewage disposal system(s) is prohibited without
(final) approval by the Department.
6.
The installation of conventional subsurface sewage disposal system(s) or alternative sewage disposal
system(s) is prohibited when the site to be developed is within the boundaries of a municipal sewer
district or is served by an on-site/community sewage treatment system.
Page 8
b)
12/1/09
2.
V.
b)
A SPDES permit issued by the New York State Department of Environmental Conservation or
its agent is required for all discharges to groundwater where the design sewage flows (total
hydraulic load) are 1,000 gallons per day or greater.
c)
Sewer district approval is required from Suffolk County Department of Public Works for county
sewer districts or the appropriate agency for other sewer districts.
Page 9
2.
12/1/09
3.
VI.
2.
3.
Other Requirements
For further information, refer to Instructions for Obtaining Final Health Department Approval
of Constructed Projects for Other Than Single-Family Residences Form WWM-019 and
Appendix C of these standards.
VII.
A population density equivalent estimate must be made in order to determine the type of sewage disposal system
required for a project, and to determine if a project meets the density requirements of Article 6 of the Suffolk
County Sanitary Code. There are two alternative acceptable methods for determining population density equivalent,
a Calculation Method, or a Yield Map Method.
Page 10
1.
12/1/09
Calculation Method
a)
Commercial Projects
Population density equivalent is calculated by multiplying the adjusted gross lot area in acres
(43,560 sq.ft./acre) by 600 gallons per day/acre (300 gallons per day per acre in Groundwater
Management Zones III, V, or VI, or where a community water supply is not being provided).
Adjusted gross lot area is obtained by subtracting the area of regulated freshwater wetlands,
tidal wetlands, ponds, or other underwater lands from the land area as delineated and shown on
official surveys and site plans.
b)
2.
Page 11
12/1/09
The population density equivalent, in gallons / day, is obtained by multiplying the number of building
lots by 300 gallons / lot / day.
IX.
The Design Sewage Flow for a project is derived from the hydraulic load rates shown in Table 1 below. For a
mixed type building(s) such as office/warehouse, the design sewage flow rate should be calculated as the sum of all
hydraulic loads for each individual use within the building(s). The Design Sewage Flow may be apportioned
appropriately if more than one sewage disposal system is being proposed or modified.
Page 12
12/1/09
TABLE 1 - PROJECT DENSITY LOADING RATES & DESIGN SEWAGE FLOW RATES
(Based upon gross floor area in square feet (sf) unless otherwise noted)
Structure Use
Density Load
Kitchen/Gray Load
Hydraulic Load
FOOD SERVICE
Bar (in restaurant)
Bar, Tavern, Disco
10 gpd/seat
5 gpd/seat
15 gpd/seat
10 gpd/occupant1
5 gpd/occupant1
15 gpd/occupant1
5 gpd/seat
See Primary use + 5
gpd/seat
2.5 gpd/seat
7.5 gpd/seat
Primary use + 7.5
gpd/seat
Cafeteria/Continental
Breakfast
(not open to public)
2.5 gpd/seat
Snack Bar
0.12 gpd/sf
Juice Bar
2.5 gpd/seat
Catering Hall
Outside Patio Dining
Restaurant
5 gpd/seat
5 gpd/seat
2.5 gpd/seat
10 gpd/seat
10 gpd/seat
20 gpd/seat
30 gpd/seat
0.03 gpd/sf
0.12 gpd/sf
0.15 gpd/sf
0.03 gpd/sf
0.02 gpd/sf
0.05 gpd/sf
0.04 gpd/sf
0.02 gpd/sf
0.06 gpd/sf
5 gpd/occ
2.5 gpd/occ
7.5 gpd/occ
Bar (outdoor/seasonal)
Cafeteria
(open to public)
2.5 gpd/seat
Convenience
store/Market/Farm Stand
Commercial Bakery
Wine/Beer Tasting (in a
winery/brewery only)
GENERAL INDUSTRIAL
3
General Industrial
Greenhouse
0.04 gpd/sf
0.03 gpd/sf
0.04 gpd/sf
0.03 gpd/sf
MEDICAL
Drug Rehabilitation
Mental Health Residence
Hospital
Nursing Home
Assisted Living
Medical office space
Dialysis Center
75 gpd/bed
75 gpd/bed
300 gpd/bed
150 gpd/bed
110 gpd/bed
0.10 gpd/sf
0.10 gpd/sf
See note 5
See note 5
See note 5
See note 5
See note 5
N/A
Dialysis process water4
Veterinary6
0.10 gpd/sf + 10
gpd/animal boarding
N/A
Page 13
75 gpd/bed
75 gpd/bed
300 gpd/bed
150 gpd/bed
110 gpd/bed
0.10 gpd/sf
0.10 gpd/sf
0.10 gpd/sf + 10
gpd/animal boarding
12/1/09
MUNICIPAL SERVICES
Library, firehouse,
precinct, museum, art
gallery
(w/ meeting rooms)
Library, firehouse,
precinct, museum, art
gallery
0.03 gpd/sf + 5
gpd/occupant1 for
meeting rooms
2.5 gpd/occupant1
0.03 gpd/sf + 5
gpd/occupant1 + 2.5
gpd/occupant1
0.03 gpd/sf
2.5 gpd/occupant1
OFFICE
Non-medical office space 0.06 gpd/sf
0.06 gpd/sf
RECREATION
5 gpd/occupant1 + 5
gpd/shower/occupant +
Food service7
100 gpd/court or alley+
Food service7
15 gpd/parking space +
Food service7
15 gpd/skater1 + 5
gpd/specator1 + Food
service7
15 gpd/parking space +
Food service7
Bath house/comfort
station
5 gpd/occupant1
5 gpd/shower/occupant1 +
Food service7
Bowling alley/tennis
court/racquetball
Food service7
Miniature golf
15 gpd/parking space
Food service7
15 gpd/skater1 + 5
gpd/specator1
Food service7
Recreation
15 gpd/parking space
Food service7
Spa/Fitness Center/
Karate/Dance/etc.
0.1 gpd/sf
0.1 gpd/sf
Food service7
Marina
10 gpd/boat slip
Food service7
OTB
5 gpd/person
Food service7
Theater
3 gpd/seat
Food service7
Horse Farm6
0.04 gpd/sf + 10
gpd/stall
Camp Ground
10 gpd/camper
5 gpd/shower/camper
Billiard Hall
5 gpd/occ
2.5 gpd/occ
Spa/Fitness Center/
Karate/Dance/etc.
(w/o showers & amenities)
RESIDENTIAL
Single Family Residence
Two Family Residence
Rooming house
300 gpd
600 gpd
75 gpd/bed
300 gpd
600 gpd
75 gpd/bed
Page 14
Motel/Hotel unit up to
400 sq.ft. gross floor
area w/o kitchenette
(w/kitchenette see
Housing Unit)
Motel/Hotel unit > 400
sq.ft. gross floor area
w/o kitchenette
(w/kitchenette see
Housing Unit)
Housing Unit8 up to 600
sq.ft. gross floor area
Housing Unit8 between
601-1200 sq.ft. gross
floor area
Housing Unit8 > 1200
sq.ft. gross floor area
PRC unit up to 600 sq.ft.
gross floor area
PRC unit between 6001600 sq.ft. gross floor
area
PRC unit between 16002000 sq.ft. gross floor
area
PRC unit > 2000 sq.ft.
gross floor area
12/1/09
100 gpd/unit
100 gpd/unit
150 gpd/unit
150 gpd/unit
150 gpd/unit
150 gpd/unit
225 gpd/unit
225 gpd/unit
300 gpd/unit
300 gpd/unit
100 gpd/unit
100 gpd/unit
150 gpd/unit
150 gpd/unit
225 gpd/unit
225 gpd/unit
300 gpd/unit
300 gpd/unit
RETAIL
Dry store
Wet store w/o Food
(Hair salon, nail salon, pet
shop w/o animal boarding,
etc.)
Car Dealership
Massage/Tanning
Tattoo Parlor
0.03 gpd/sf
0.03 gpd/sf
0.03 gpd/sf
0.07 gpd/sf
0.1 gpd/sf
0.03 gpd/sf for
showroom/offices + 0.04
gpd/sf for
maintenance/storage
areas
0.03 gpd/sf
0.03 gpd/sf
SCHOOL
Boarding school/
Dormitory
Day School
75 gpd/capita1
2.5 gpd/capita1
77.5 gpd/capita1
5 gpd/capita1
2.5 gpd/capita1
7.5 gpd/capita1
MISCELLANEOUS
Car Wash
Laundromat
0.04 gpd/sf
0.03 gpd/sf
Page 15
0.04 gpd/sf
0.03 gpd/sf
Funeral Home
House of Worship
(w/ meeting rooms)
House of Worship
(w/o meeting rooms)
Public Storage9
Animal boarding6
Winery/Brewery
1
2
4
5
6
7
8
9
12/1/09
0.05 gpd/sf
1.5 gpd/seat + 5
gpd/occupant1 for
meeting rooms
2.5 gpd/occupant1
1.5 gpd/seat
2.5 gpd/occupant1
0.04 gpd/sf
0.03 gpd/sf + 10
gpd/animal
0.04 gpd/sf
Winery/Brewery process
water4
0.05 gpd/sf
1.5 gpd/seat + 5
gpd/occupant1 + 2.5
gpd/occupant1
1.5 gpd/seat + 2.5
gpd/occupant1
0.04 gpd/sf
0.03 gpd/sf + 10
gpd/animal
0.04 gpd/sf
Occupancy ratings can be determined using New York State Uniform Fire Prevention and Building Code as a guide.
Single Service means disposable plates, silverware & cups. Takeout seating is for waiting patrons and is not convertible to
full seating or for density credit at full service restaurants.
General industrial buildings may contain up to 15% related office space without applying a proportionate office density
loading or flow rating to the space. If office space exceeds 15% of gross floor area, then a proportionate office density
loading or flow rating must be applied to the entire office space.
Process waters require a separate permit and disposal facilities Consult Department.
A grease trap shall be provided for this installation which is sized at 20 gpd/bed.
A separate sewage disposal system shall be provided for wastewater generated from animal boarding, horse stalls, or
kennel areas.
Food (kitchen) flow is added according to the type of food service in the establishment.
Motel/Hotel with Kitchenettes, Cottages, Apartments, Condominiums, Mobile Homes, Trailers, or Co-Ops.
Public storage density and/or design flow may be reduced if restrictive covenants are recorded on the parcel.
Note: The above table is subject to amendment from time to time as data becomes available to the Department. The table will be
republished as an addendum to these standards if and when revised.
Page 16
X.
12/1/09
2.
If the Density Load for a project exceeds the Population Density Equivalent then the installation of a
sewage treatment system will be required. Sewage treatment systems are broken down into the
following categories:
i.
Page 17
ii.
12/1/09
iii.
b)
ii.
12/1/09
Page 19
12/1/09
the GLUMRB - Recommended Standards for Wastewater Facilities - 2004 Edition, or the
latest revision, and Appendix B.
XI.
2.
In any area subject to imminent erosion, which cannot be controlled so as to protect the sewage
disposal system(s);
d)
In areas where the highest recorded groundwater level is less than one foot below the original
ground surface;
e)
In areas with existing slopes greater than 15%, unless the site can be properly graded in
accordance with these standards. Refer to Section XXI - Final Grading and Backfilling;
f)
In areas where the existing subsoils contain meadow mat, bog, silts, clays, or other impervious
material extending below the groundwater table;
g)
In areas where the groundwater conditions are not conducive to the proper functioning of
subsurface sewage disposal systems;
h)
Where topography concentrates runoff onto or into the area where the system is proposed;
i)
In any area or under any part of a building, or other improvements that does or may prevent
reasonable access for repair or maintenance of the system.
j)
In any area which may reasonably be expected to create a public health risk.
Page 20
3.
12/1/09
4.
a)
On land owned in fee by the applicant (except for Community or Municipal Sewage Treatment
Systems);
b)
On the same parcel as the building(s) to be serviced (except for Community or Municipal
Sewage Treatment Systems);
c)
d)
In accordance with the minimum separation distances presented in Table 2 of these standards;
e)
In accordance with the minimum separation distances and other conditions listed in Appendix
A and Appendix B as applicable.
b)
5.
Page 21
12/1/09
a)
Sewage disposal systems shall be located to maximize distances to public water supply wells. If
the department determines that insufficient distance exists to protect the well, further treatment
may be required.
b)
c)
Boundaries of wetlands, surface waters and flood zones shall be shown accurately on surveys
and site plans. Wetlands are not regulated directly by the Department, only through standards
and regulations of the NYSDEC, NYSDOH, and various other government agencies.
Page 22
12/1/09
Leaching
Pool 3
Sewer Line,
Force Main
10 ft.
10 ft.
5 ft.
5 ft.
10 ft.
5 ft.
10 ft.
10 ft.
10 ft. 4
Underground Utilities
5 ft.
5 ft.
5 ft.
75 ft.
100 ft.
50 ft.
200 ft.
200 ft.
50 ft.
100 ft.
150 ft.
50 ft.
7
8
20 ft.
20 ft.
10 ft.
5 ft.
10 ft.
5 ft.
Leaching Pool
8 ft.
8 ft.
10 ft. 7
5 ft.
8 ft.
5 ft.
Property Lines
5 ft.
10 ft.
5 ft.
Swimming Pool
20 ft.
20 ft.
5 ft.
10 ft.
10 ft.
5 ft.
20 ft.
20 ft.
10 ft.
25 ft.
25 ft.
25 ft.
Bluffs
65 ft.
65 ft.
65 ft.
Increased distance between leaching pools and private wells may be required based upon the depth of the well(s) involved
and the direction of groundwater flow. Refer to Standards For The Design Of Individual Water Supply Systems.
Discharges from treatment works shall be located down gradient of the well or out of the groundwater flow path towards the
well. Precise groundwater flow direction measurements may be required.
Significant discharges (generally greater than 5,000 gpd or those in proximity to wells) are subject to a separate site review
by the department.
Leaching pools for treatment works have different distance requirements. See Appendix A and Appendix B for distance
requirements for leaching pools or recharge beds associated with modified subsurface sewage disposal systems and
treatment works, respectively.
Water and sewer lines may be in the same trench if the water line is placed on an undisturbed bench or shelf so that the
bottom of the water main is at least 18 inches higher than the top of the sewer and the sewer is not subject to settling,
vibration, superimposed loads, or frost action.
A minimum of 10 foot separation is required between water service line/laterals/mains and the edge of all stormwater
drainage leaching structures.
A minimum of 5 foot separation is required between water service line/laterals/mains and the edge of allstormwater drainage
non-leaching structures and associated piping.
Sewer piping between clusters of leaching pools may be installed at lesser separation distances.
Multiple unit septic tanks and grease traps shall be considered one structure and therefore individual components may be
installed at lesser separation distances.
Page 23
XII.
12/1/09
Subsoil conditions shall be shown on the plans. The nature of the soil shall be determined by excavation of one or
more test holes at the site of the proposed subsurface sewage disposal system. The soil investigation shall be subject
to the following conditions:
1.
Test Holes/Borings
The soils in the test holes/borings shall be classified using the ASTM Unified Soil Classification
System (ASTM D-2487) as a reference. The test holes/borings shall be carried to a depth of three
feet in excess of the proposed leaching pool bottom or seventeen feet, whichever is greater. In the
case where unacceptable soil is encountered, the test hole/boring must be carried until a strata of six
feet of clean sand is reached (defined as SP or SW by ASTM standards). If groundwater is
encountered less than seventeen feet from grade, then the test hole/boring must be extended a
minimum of six feet into groundwater.
A test hole/boring log and grade elevation at the test hole shall be indicated on the plans. The log shall
also indicate the date, time, and person responsible for the test hole. If groundwater is encountered,
the groundwater elevation measured during the test hole/boring and the highest recorded groundwater
elevation shall be shown.
2.
3.
4.
5.
Page 24
12/1/09
Unsuitable soils shall be removed and replaced with clean sand for a diameter six feet greater than the
leaching pool (three foot collar) extending down until a hydraulic connection is established with a
minimum six foot stratum of acceptable material. In cases where clean sand
Page 25
12/1/09
cannot be encountered, a design for an alternative sewage disposal system may be required in
accordance with Section XXV of these standards.
XIV.
General
All conventional subsurface and/or alternative sewage disposal systems shall contain a septic tank as
part of the overall sanitary disposal system design.
2.
Location
Septic tanks shall be located below grade and outside the building in either paved or unpaved areas.
Septic tanks shall be located in areas that are easily accessible for routine inspection and maintenance.
Refer to Section XI for additional siting requirements.
3.
The minimum outside diameter cylindrical septic tank shall be 8 feet and the maximum
outside diameter shall be 12 feet.
ii.
The minimum liquid depth of any cylindrical septic tank shall be 4 feet. Liquid depth is the
effective depth of the tank below the outlet pipe.
iii.
Eight (8) foot diameter tanks shall have a maximum liquid depth of 5 feet.
iv.
Ten (10) foot diameter tanks shall have maximum liquid depth of 6 feet.
Page 26
v.
12/1/09
Twelve (12) foot diameter tanks shall have a maximum liquid depth of 7 feet.
Page 27
vi.
b)
12/1/09
There shall be a maximum number of three (3) outlet pipes from the septic tank. All outlet
pipes shall be set at the same elevation.
c)
Units shall be connected with three (3) - 8 inch diameter pipes placed such that the center
lines of the pipes are 18 inches below the liquid level of the tank. The three connecting
pipes shall be spaced 20 inches on centers. Each unit shall have the same diameter and
liquid depth.
4.
i.
When three or more individual septic tanks are utilized within one system, they shall be
placed on a common reinforced concrete slab at least 6 inches thick.
ii.
All units shall be connected with two (2) 8 inch diameter pipes placed such that the center
lines of the pipes are 18 inches below the liquid level of the tank. Each connecting pipe set
shall be spaced 20 inches on centers.
iii.
Each unit shall have the same diameter and liquid depth.
All septic tank components (i.e. slabs, domes, covers, etc.) shall be constructed of precast
reinforced concrete and designed to be traffic bearing to meet the requirements of AASHTO H20 loading.
b)
All units shall be provided with two openings with a minimum diameter of 20 inches positioned
over the inlet and outlet pipes. A watertight and insect-proof adjustable and locking cast iron
frame and cover shall be installed at grade over each opening.
c)
Extension Collars (chimneys) may be used for the purpose of bringing the cast iron covers to
grade provided that they are firmly affixed in place. The extension collar (chimney) shall be of
reinforced precast concrete at least 24 inches in diameter and shall not exceed 2 feet in height.
d)
The top slab or dome of the septic tank shall be located a maximum of 2.5 feet below grade.
Page 28
12/1/09
e)
There shall be a minimum 1 foot air space measured from the outlet invert(s) to the bottom of the
septic tank top slab or dome.
f)
Precast concrete sections shall be sealed with one(1) - inch butyl rubber joint sealant which
conforms to ASTM C-990.
g)
The outlet invert(s) shall be six inches below the lowest inlet invert. All outlet inverts shall be
installed at the same level.
h)
The outlet pipe(s) from the tank shall be provided with a drop tee extending eighteen inches into
the liquid. The outlet(s) shall be located at the maximum flow path from the inlet.
i)
All sewer pipes shall penetrate the vertical sidewall of the septic tank(s) and shall be sealed with
grout. There shall be no penetrations within domes.
j)
All single unit septic tanks shall be divided into two compartments, the inlet compartment to have
50 - 75 percent of the total capacity. The traverse wall separating compartments shall extend
from the bottom to at least 6 inches above the liquid level and be constructed of reinforced
precast concrete.
k)
The opening in the traverse wall shall be 8 inches in height and at least 24 inches wide. The
center shall be 18 inches below the liquid level. There shall be a minimum of 4 inch air gap at the
top of the traverse wall.
l)
Whenever practical, septic tanks shall not be located within groundwater. For installations that
are placed in groundwater, the bottom and side portion, up to 18 inches above the highest
recorded groundwater elevation, of the septic tank shall be monolithically constructed. In cases
where this is not practicable, the septic tank shall be water-proofed up to 18 inches above the
highest recorded groundwater elevation and leak tested to ensure tightness prior to operation.
Maximum permissible leak rate is inch in 8 hours.
m) Septic tanks shall be installed in accordance with the manufacturers recommendation. Allseptic
tanks shall be installed at level in all directions (with a maximum tolerance in any direction of +/one quarter inch) on a minimum three inch bed of properly graded and compacted sand which is
free of rock and pea gravel.
XV.
General
All restaurants and/or food preparation establishments are required to install a grease trap for the
kitchen or food preparation area. A grease trap is considered part of the equipment necessary to
obtain a permit to operate a food establishment pursuant to Article 13 of the Suffolk County Sanitary
Page 29
12/1/09
Code. Grease traps should be cleaned and maintained on a regular basis in order to insure proper
functioning and insect free performance.
2.
Location
Grease traps shall be located below grade and outside the building preceding the septic tank or sewer
line. Only discharges from the kitchen or food preparation areas may be piped to grease traps.
Grease traps shall be located in areas that are easily accessible for routine inspection and
maintenance. Refer to Section XI for additional siting requirements.
3.
b)
4.
The minimum outside diameter cylindrical grease trap shall be 8 feet and the maximum
outside diameter shall be 12 feet.
ii.
The liquid depth shall be a minimum of 5 feet and shall not exceed 7 feet depending
upon diameter.
The minimum outside diameter cylindrical grease trap shall be 10 feet and the maximum
outside diameter shall be 12 feet.
ii.
The liquid depth shall be a minimum of 5 feet and shall not exceed 7 feet depending
upon diameter.
iii.
iv.
Units shall be connected in series by utilizing one 6 inch diameter drop tee pipe.
v.
There shall be a 6 inch drop between the inlet and outlet pipes of each unit. Each
succeeding unit shall have a liquid depth of 6 inches less than the preceding unit.
All grease trap components (i.e. slabs, domes, covers, etc.) shall be constructed of precast
reinforced concrete and designed to be traffic bearing to meet the requirements of AASHTO
H-20 loading.
Page 30
5.
12/1/09
b)
All units shall be provided with two openings with a minimum diameter of 20 inches positioned
over the inlet and outlet pipes. A watertight and insect-proof adjustable and locking cast iron
frame and cover shall be installed at grade over each opening.
c)
Extension Collars (chimneys) may be used for the purpose of bringing the cast iron covers to
grade provided that they are firmly affixed in place. The extension collar (chimney) shall be of
reinforced precast concrete at least 24 inches in diameter and shall not exceed 2 feet in height.
d)
The top slab or dome of the grease trap shall be located a maximum of 2.5 feet below grade.
e)
There shall be a minimum 1 foot air space measured from the outlet invert(s) to the bottom of
the grease trap top slab or dome.
f)
The base section of all units (bottom slab and minimum of 1 foot of sidewall) shall be
monolithically cast.
g)
Precast concrete sections shall be sealed with one (1) - inch butyl rubber joint sealant which
conforms to ASTM C-990.
h)
The outlet pipe(s) from each grease trap unit shall be 6 inch in diameter to the inlet of the septic
tank or sewer main. Each outlet shall be provided with a 6 inch diameter drop tee extending to
1 foot above the bottom of the tank. The outlet(s) shall be braced as required and located at
the maximum practicable distance from the inlet.
i)
All sewer pipes shall penetrate the vertical sidewall of the grease trap(s) and shall be sealed
with grout. There shall be no penetrations within domes.
j)
Whenever practical, grease traps shall not be located in groundwater. For installations that are
placed in groundwater, the bottom and side portion, up to 18 inches above the highest
recorded groundwater elevation, of the grease traps shall be monolithically constructed. In
cases where this is not practicable, the grease traps shall be water-proofed up to 18 inches
above the highest recorded groundwater elevation and leak tested to ensure tightness prior to
operation. Maximum permissible leak rate is inch in 8 hours.
Exceptions
While the requirement to install a grease trap at establishments served by community sewers shall not
be waived, the design, location, capacity and construction details for the unit shall be determined by
the appropriate sewer authority.
Page 31
XVI.
12/1/09
General
Leaching pools are used as part of conventional subsurface or alternative sewage disposal system,
and on-site and community sewage treatment systems to infiltrate effluent into the surrounding soil.
2.
Location
Leaching pools must be installed in areas that are easily accessible for routine inspection, maintenance,
replacement or expansion. Refer to Section XI for additional requirements concerning the locationof
leaching pools.
3.
4.
Leaching pool systems shall be designed on the basis of sidewall area to receive one full days
hydraulic design flow. The required sidewall leaching area is computed from the outside wall
area below the inlet pipe for satellite pools and below the outlet pipe for distribution pools. The
pool bottom area is not to be included in the leaching area computation.
b)
c)
The maximum hydraulic leaching rate of 1.5 gal/sq.ft./day shall be used for Conventional
Subsurface Sewage Disposal Systems.
d)
The maximum hydraulic leaching rate of 5 gal/sq.ft./day shall be used for On-Site and
Community Sewage Treatment Systems without positive filtration processes.
e)
The maximum hydraulic leaching rate of 10 gal/sq.ft./day shall be used for On-Site and
Community Sewage Treatment Systems with positive filtration processes.
f)
The maximum hydraulic leaching rate for alternative sewage disposal systems shall be
determined in accordance with the requirements of Section XXV of these standards.
All leaching pools shall have an outside diameter of eight feet or ten feet.
b)
When more than one leaching pool is used, all pools shall be the same size and depth, except
the distribution pool, which may differ.
c)
When a distribution pool is used, all outlet pipes shall be set at the same elevation and be at
least three inches below the inlet pipe. All outlets shall be provided with an 18 inch drop tee.
Page 32
5.
12/1/09
d)
The maximum permissible depth of a precast concrete leaching pool is twenty five feet from
finished grade. The minimum permissible effective depth of any leaching pool shall be three
feet.
e)
The minimum vertical separation distance from the bottom of the leaching pools to the highest
recorded groundwater elevation shall be 3 feet for all new leaching pools installed after the
effective date of this standard. Previously installed leaching pools that do not meet this criteria
may be accepted by the Department on a case-by-case basis.
f)
All leaching pools (i.e. slabs, domes, covers, etc.) shall be constructed of precast reinforced
concrete and designed to be traffic bearing to meet the requirements of AASHTO H-20
loading.
g)
All leaching pools shall be provided with one opening with a minimum diameter of 20 inches. A
watertight and insect-proof adjustable and locking cast iron frame and cover shall be installed at
grade over each opening.
h)
Extension Collars (chimneys) may be used for the purpose of bringing the cast iron covers to
grade provided that they are firmly affixed in place. The extension collar (chimney) shall be of
reinforced precast concrete at least 24 inches in diameter and shall not exceed 2 feet in height.
i)
The top slab or dome of the leaching pool shall be located a maximum of 2.5 feet below grade.
j)
All sewer pipes shall penetrate the vertical sidewall of the leaching pool and shall be sealed with
grout. There shall be no penetrations within domes.
A maximum of 3 leaching pools are permitted to be piped directly from the septic tank.
b)
When 4 or more leaching pools are required, a distribution leaching pool or a distribution
manhole shall be used to apportion the flow to the satellite leaching pools.
c)
A maximum of 4 satellite leaching pools shall be piped from a distribution pool or manhole to
form one leaching pool cluster.
d)
When more than 5 leaching pools are required, multiple leaching pool clusters shall be
provided. The leaching pool clusters may be piped directly from the septic tank or from
distribution pools or manholes as required.
e)
When multiple clusters are utilized, each cluster shall be equipped with a gate or ball valve to
allow for isolation and resting. Each valve shall be outfitted with a traffic bearing cover that is
accessible for operation from grade.
Page 33
6.
12/1/09
Installation Requirements
a)
b)
Unsuitable soils shall be removed and replaced with clean sand for a diameter six feet greater
than the leaching pool (three foot collar) extending down until a hydraulic connection is
established with a minimum six foot stratum of acceptable material.
c)
In cases where clean sand cannot be encountered, a design for an alternative sewage disposal
system may be required in accordance with Section XXV of these standards.
d)
The bottom and sidewall area of the leaching pools shall be free of debris before backfilling.
General
Manholes are used as part of a sewage disposal and collection systems to distribute equal volumes of
sewage, to allow for access, or to collect and re-distribute sewage.
2.
3.
Location
a)
Manholes shall be provided on gravity sewer lines wherever there is a grade change or
alignment change further than 10 feet from building foundations as measured along the pipe.
b)
Manholes shall be provided on gravity sewer lines at intervals not exceeding 400 feet.
c)
Manholes shall be provided at the junctions and at the ends of lateral or main sewer lines.
d)
Building sewer connections shall not be piped directly to a collection system manhole, but shall
be connected to the main line via a wye connection.
All manholes (i.e. slabs, covers, etc.) shall be constructed of precast reinforced concrete and
designed to be traffic bearing to meet the requirements of AASHTO H-20 loading.
b)
All manholes shall be constructed in accordance with ASTM C-478 (latest revision).
c)
All manholes shall be provided with an opening with a minimum diameter of 20 inches. A
watertight and insect-proof adjustable and locking cast iron frame and cover shall be installed at
grade over each opening.
Page 34
4.
12/1/09
d)
Extension Collars (chimneys) may be used for the purpose of bringing the cast iron covers to
grade provided that they are firmly affixed in place. The extension collar (chimney) shall be of
reinforced precast concrete at least 24 inches in diameter and shall not exceed 2 feet in height.
e)
The top slab of the manhole shall be located a maximum of 2.5 feet below grade.
f)
The base section of all manholes (bottom slab and minimum of 1 foot of sidewall) shall be
monolithically cast.
g)
Precast concrete sections shall be sealed with one(1) - inch butyl rubber joint sealant which
conforms to ASTM C-990.
h)
The bottom of all manholes shall be coved or benched. The bench shall be the same width as
the diameter of the pipe and shall extend upward at least three-quarters of the diameter of the
pipe.
i)
All sewer pipe penetrating the manhole shall be accomplished with a cast- in place flexible
rubber sleeve that conforms to ASTM C-923 and stainless steel tightening devices. For cases
where a new penetration is being made into an existing manhole, a link seal may be substituted
for the rubber boot.
j)
If the manhole is more than four feet in depth, manhole steps shall be provided every twelve
(12) inches. The steps shall be constructed of copolymer polypropylene coated 2 inch steel
reinforcing bar. The access opening shall be provided over the manhole steps.
k)
Whenever practical, manholes shall not be located in groundwater. For installations that are
placed in groundwater, the bottom and side portion, up to 18 inches above the highest
recorded groundwater elevation, of the manhole shall be monolithically constructed. In cases
where this is not practicable, the manhole shall be water-proofed up to 18 inches above the
highest recorded groundwater elevation and leak tested to ensure tightness prior to operation.
Maximum permissible leak rate is inch in 8 hours.
Types of Manholes
Manholes can be broken into 4 general categories. In addition to the items in Section C above, each
category shall conform to the following requirements:
a)
ii.
For pipe diameters of 24 inches or greater, the minimum inside diameter of the manhole
shall be 5 feet.
Page 35
b)
c)
d)
12/1/09
iii.
A minimum drop of 0.1 foot shall be provided between the inlet and lowest outlet invert
elevation.
iv.
The maximum change in elevation between the inlet and outlet invert shall be no greater than
2 feet.
ii.
A drop manhole is required to be provided when the difference in elevation between the
inflow and outflow sewer line is greater than 2 feet.
iii.
The drop pipe shall be securely attached to the sidewall of the manhole with stainless steel
straps.
All outlets from the distribution manhole shall be set at the same elevation.
ii.
A minimum drop of 0.1 foot shall be provided between the inlet and outlet invert elevations.
ii.
iii.
A minimum drop of 0.1 foot shall be provided between the inlet and outlet invert elevations.
iv.
A 12 inch deep sample retention area shall be provided below the outlet invert elevation.
Gravity sewer lines and fittings shall meet or exceed ASTM standard D-3034 for PVC sewer
pipe with a minimum SDR 35 rating, unless otherwise indicated.
b)
PVC pipe and fittings shall be provided with integral bells and spigots and rubber sealing rings.
The sealing rings shall meet the requirements of ASTM standard F-477. All sewer lines shall be
straight, and couplings shall be securely installed and be watertight.
c)
All sewer lines shall have a minimum diameter of four (4) inches.
Page 36
d)
2.
3.
12/1/09
Where practical, gravity sewer lines shall not be installed in groundwater. For installations that
are placed in groundwater, the sewer piping shall be constructed of pressure rated piping and
tested to ensure tightness prior to operation. Maximum permissible leak rate is inch in 8
hours.
Internal building plumbing shall be designed in accordance with applicable building codes and is
outside the jurisdiction of the Department.
b)
It is the preference of the Department that all individually owned buildings, residences, or
premises be plumbed separately and serviced with an independent house connection to the
exterior sanitary services.
c)
The use of common house connections shall be permitted provided that the internal plumbing is
designed to accommodate multiple sewer connections in accordance with good engineering
practice and applicable building codes. In addition, restrictive covenants shall be placed upon
the property notifying the owner and/or homeowners association of their responsibility for the
operation and maintenance of the internal sewer appurtenances; including, but not limited to, the
repair, replacement, and cleaning of the internal piping within the structure.
House Connections
a)
A house connection is defined as the portion of the gravity sewer line which extends from the
face of the building to the sewage disposal or sewer system.
b)
There shall be a minimum two foot length of cast-iron sewer line extending through the
foundation.
c)
House connections shall have a minimum diameter of 4 inches, unless otherwise noted.
d)
House connections serving two or more commercial or multiple residential units shall have a
minimum diameter of 6 inches.
e)
House connections shall have a minimum pitch of one-quarter inch per foot.
f)
Slip ring connectors of the proper type shall be used at the cast iron joint. If required, a flexible
PVC coupling with stainless steel bands may be used to connect cast iron pipe to PVC house
Connections. The flexible coupling and bands shall conform to ASTM C1173.
g)
All house connections shall be provided with a clean-out at the face of the building.
Page 37
h)
4.
5.
12/1/09
House connections shall be straight. There shall be no bends in sewer lines to the septic tank or
grease trap. If bends are unavoidable, then the following additional criteria shall apply:
i.
For bends greater than 10 feet from the building foundation as measured along the length of
the sewer pipe, an approved manhole will be required where the pipe changes direction.
ii.
For bends within 10 feet of the building foundation measured along the length of the sewer
pipe, no fittings greater than 45 degrees shall be installed. If a directional change greater
than 45 degrees is required, a minimum of five foot length of pipe shall be installed between
fittings. The maximum permitted change in alignment of the sewer line shall be 90 degrees
as measured along the axis of the starting pipe.
iii.
Cleanouts are required at any bend within 10 feet from the building or every 75 feet along
the length the house connection. Refer to Figure #13.
Sewer main and lateral sewers shall have a uniform slope and be laid with a straight alignment,
without bends. When required, approved manholes may be utilized where sewers change
direction or slope.
b)
House or building sewers shall be connected to main or lateral sewers with approved wye
fittings.
c)
Sewers shall be provided with manholes at intervals not to exceed 400 feet. See Section XVII
for manhole location requirements.
d)
Sewer main and lateral sewers shall have a minimum diameter of eight inches, and shall have a
minimum slope of 0.4%. Ten inch diameter sewers shall have a minimum slope of 0.28%.
e)
Sewer main and lateral sewers that have less than 2 foot of cover or are not placed on virgin soil
shall be constructed of ductile iron pipe.
f)
Sewer main and lateral sewers that have between 2 foot and 4 foot of cover shall be constructed
of DR18 or ductile iron pipe.
g)
Sewer main and lateral sewers that have over 4 foot of cover may utilize SDR35 pipe.
The width of trenches shall be adequate to allow sewer pipe to be laid and joined properly and
to allow bedding and haunching to be placed and compacted to adequately support the pipe.
Page 38
6.
12/1/09
b)
The embedment material around the PVC pipe shall be installed in layers not exceeding six
inches. The embedment material shall be Class I, Class II, or Class III. Class I material shall
conform to the following standards: minimum particle size 3/4 inches, not less than 50% weight
of material shall pass the 3/8 inch sieve. Class II material is defined as coarse sands and gravels
with maximum particle size of 40 mm (1/2 inches), including variously graded sands and gravels
containing small percentages of fines, generally granular and non-cohesive, either wet or dry.
Unified Soil Classification types GW, CP, SW, SP are included in this Class. Class III material
is defined as fine sand and clayey gravels, including fine sands, sand clay mixtures, and gravel clay mixtures. All backfill material within one foot horizontally and one foot above the crown of
the pipe shall be placed by hand and requires hand compaction.
c)
Each layer of Class II and class III material shall be compacted to a minimum density of ninetyfive (95) percent of maximum density of the soil as determined by the Standard Procter Test
AASHTO designation T-99.
d)
For additional requirements concerning the installation of PVC sewer pipe, refer to ASTM
standard D-2321 Underground Installation of Thermoplastic Pipe for Sewers and Other
Gravity- Flow Applications.
Testing
Deflection testing of every section of sewer main or lateral sewers, constructed of PVC, is required
by the Department. The total vertical wall deflection of the PVC pipe, as determined by testing not
earlier than 30 days after placement and compaction of the final backfill, shall not exceed four (4)
percent of the inside pipe diameter. The deflection shall be checked by manually pulling a GO - NO
GO deflection testing mandrell through the pipe. The contractor shall conduct the tests under the
observation of the certifying engineer / architect.
7.
Certification
For projects that involve a sewage collection system, a licensed engineer / architect shall certify that
all material, method of construction, installation, and testing of the sewer pipe meet the
requirements of these standards as well as plans approved by the Department. Refer to Appendix C
of these standards.
XIX.
Parallel Installation
a)
Sewers shall be laid at least 10 feet horizontally from any existing or proposed water main or
lateral. The distance shall be measured edge to edge.
b)
If it is not practical to maintain a horizontal separation of ten feet, the department may allow a
deviation on a case-by-case basis. Such deviation may allow for the installation of the sewer to
Page 39
12/1/09
be a minimum of 5 feet to a water main or lateral, provided that the bottom of water main or
lateral is at least 18 inches above the top of the sewer line.
c)
2.
If the vertical separation as described in item 2 above cannot be obtained, the department may
allow a deviation on a case-by-case basis. Such deviation may allow for the installation of the
sewer to be a minimum of 5 feet to a water main or lateral, provided that the bottom of the water
main or lateral is at least 12 inches above the top of the sewer line and both are constructed of
pressure rated pipe.
Crossings
a)
The crossing of water and sewer lines should be avoided unless proven absolutely necessary.
b)
c)
i.
sewer lines shall be laid below the water line and provide a separation of at least 18 inches
between the bottom of the water line and the top of the sewer line; and
ii.
sewer line joints shall be at least 10 feet from the point of crossing; and
iii.
when it is not practical to obtain an 18 inch separation, both the water and sewer lines shall
be constructed of pressure pipe and have a minimum separation of 12 inches between the
bottom of the water line and the top of the sewer line.
adequate structural support shall be provided for the sewer to maintain line and grade; and
ii.
water line and sewer line joints shall be at least ten feet from the point of crossing; and
iii.
the entire length of sewer line between adjacent manholes or other sanitary structures shall
be constructed of materials and joints that are equivalent to water main standards of
construction; and
iv.
a vertical separation of at least 18 inches shall be provided between the bottom of the
sewer line and the top of the water line. In the event that this distance cannot be
maintained, the department may allow a deviation on a case-by-case basis. In no case shall
the separation distance be less than 12 inches between the bottom of the sewer line and the
top of the water line.
Page 40
XX.
XXI.
12/1/09
Sewers shall be laid at least 5 feet horizontally from any existing or proposed drainage line. The
distance shall be measured edge to edge.
2.
In the event that the drainage line must cross over the sewer line, the sewer line must be constructed
of ductile iron pipe unless a separation distance of 18 or more inches is maintained.
3.
In the event that the sewer line must cross over the drainage line, the sewer line shall be constructed of
ductile iron pipe for a distance of 3 feet horizontally into virgin soil.
4.
If perimeter roof drainage piping is installed near the face of the building, all house connections must
be constructed of ductile iron pipe for 10 feet from the building.
2.
Retaining Walls
a)
In cases where the grading and slopes indicated in paragraph A. above, the utilization of retaining
walls shall be required. In such cases, the retaining walls shall be designed by a licensed design
professional in accordance with good engineering practice and applicable building codes. All
retaining walls shall be shown as part of a grading and plot plan.
b)
Retaining walls that are located within 20 feet of the sewage disposal system shall be
constructed of reinforced concrete.
ii.
No part of the sewage disposal system shall be placed closer than 10 feet from a retaining
wall.
Page 41
iii.
12/1/09
If the leaching pools are located closer than 20 feet from the retaining wall, waterproofing
will be required to prevent the seepage of leachate through the wall.
Page 42
12/1/09
General Requirements
Sewage disposal systems should be designed to flow by gravity. Only when absolutely necessary
should pump stations be used. In such cases, the sewage pump station plans shall be prepared by a
licensed design professional and must be reviewed and approved by the Department. In addition,
construction and installation of sewage pump stations must be certified by a licensed professional
engineer. For additional information concerning sewage pump stations refer to GLUMRB Recommended Standards for Wastewater Facilities -2004 edition (or latest revision) and
NYSDEC - Design Standards for Wastewater Treatment Works - 1988 edition (or latest
revision).
2.
3.
Location
a)
Sewage pump stations and valve chambers must be located in an area that is easily accessible
for proper operation and routine maintenance. Security fencing shall be provided around pump
station installations. Refer to Section XI for additional requirements concerning the location of
sewage pump stations.
b)
Whenever practical, pumping stations that are utilized as lift stations within conventional on-site
sewage disposal systems shall be located after the septic tank. In no instance shall the pump
station be located prior to the grease trap.
c)
All sewage pump station components are to be constructed of precast reinforced concrete and
designed to be traffic bearing that meets the requirements of AASHTO H-20. Concrete
pumping stations shall have a minimum inside diameter of four (4) feet. Pump stations may be
constructed of other materials provided that they are water-tight, non-corrodible, and structurally
sound.
b)
The bottom and side portion, up to 18 inches above the inlet invert, of the station shall be
monolithically constructed. In cases where this is not practicable, the pumping station shall be
water-proofed up to 18 inches above the invert and leaked tested to ensure tightness prior to
operation. Maximum permissible leak rate is inch in 8 hours.
c)
Inlet sewer pipes penetrating the sidewall of the pump station shall be provided with cast-inplace rubber sleeves with stainless steel tightening devices or with a flexible rubber sleeve that
conforms to ASTM C-923.
Page 43
4.
12/1/09
d)
Pump station wet well volume shall be sized to prevent excessive retention of sewage while
preventing frequent cycling of pumps. Minimum cycle times between 15 and 30 minutes are
recommended.
e)
The floor of the wet well shall be sloped toward the pump units to prevent the deposition of
sewage solids.
f)
Precast concrete sections shall be sealed with one (1) - inch butyl rubber joint sealant which
conforms to ASTM C-990.
g)
The maximum permissible depth of a pump station from grade shall be 30 feet.
Mechanical Requirements
a)
Duplex submersible sewage pumps that are automatically alternated shall be provided. A handoff-automatic (HOA) switch shall also be provided for each pump. Each pump shall be capable
of meeting the anticipated peak sewage design hydraulic flow rate.
b)
In some cases, where the pump station is receiving raw sewage, grinder type sewage pumps
may be required.
c)
Pumps shall be readily removable and replaceable without dewatering the wet well or
disconnecting any piping in the wet well. Stainless steel guide rails together with slide away
flanges, or quick disconnect couplings shall be provided for this purpose.
d)
Pump discharge piping within the pumps station shall be constructed of ductile iron or stainless
steel piping.
e)
Pump stations shall have adequate ventilation, by providing an intake fan that forces fresh air into
the bottom of the lift station. The intake fan shall be capable of providing 12 air changes per
hour for continuous operation or 30 air changes per hour for intermittent operation. An exhaust
vent shall also be provided to remove sewer gases. Odor control equipment may be required
for the exhaust vent.
f)
A hinged and lockable (non-skid) aluminum or stainless steel door shall be provided to allow
accessibility to the pumps.
g)
A non-corrodible ladder with safety climb device shall be provided for access to the pumping
station.
h)
A hinged and lockable (non-skid) aluminum or stainless steel door shall be provided to allow
access to the ladder.
i)
Each pump shall be equipped with a stainless steel chain or cable. In addition, a pump lifting
device shall be provided on-site to facilitate the removal of the pumps.
Page 44
j)
12/1/09
There shall be no physical interconnection between any potable water supply and a sewage
pumping station or any of its components.
Page 45
5.
6.
12/1/09
Electrical Requirements
a)
All electrical components, including pumps, fans, and wiring, shall be explosion proof and
conform to the requirements for Class I, Division 1, Group D of the National Electrical Code.
b)
There shall be no electrical splices, junction boxes, or connections of any kind in the sewage wet
well. Junction boxes shall be located within a NEMA 4X enclosure outside of the pump station
wet well.
c)
The pump station shall be provided with a minimum of 5 pump control switches. These include:
a) Low Level Alarm, b) Pumps Off, c) Lead Pump On, d) Lag Pump On, e) High
Water Alarm. Encapsulated mercury filled float switches shall be used for this purpose. A
hand-off-automatic (HOA) switch shall also be provided.
d)
Pump stations shall be provided with a dialer alarm that is activated by the low level and high
level alarms.
e)
Alternative pump control devices, such as, a mutlitrode or bubbler system may be accepted in
lieu of float controls. If an alternative device is utilized, a redundant high level float and low level
float must be provided. The high level alarm shall activate the dialer alarm and operate the
pumps throughout the throw of the float. The low level alarm shall activate the dialer alarm.
f)
Pump station control panels should be located within a building or other enclosure when
possible. If required, control panels may be located outside of buildings, provided that the
controls are located within a NEMA 4X rated enclosure that is placed within another NEMA
3R box.
g)
If pump control panel(s) are not within line of sight of the pumping station, then the pumps shall
be outfitted with local disconnect switches at the pump station in lieu of a junction box.
h)
When pump stations are serving Multiple Residential Type projects, a permanent emergency
power generator set with an automatic transfer switch shall be provided at the site. For other
types of projects, consult the Department. All equipment and installation shall conform to the
requirements of the National Electrical Code.
i)
A permanent light fixture shall be provided in the pump station wet well.
Valve Chamber
a)
The valve chamber shall be constructed of precast reinforced concrete and designed to be traffic
bearing that meets the requirements of AASHTO H-20.
b)
Each pump shall be provided with a check and shut-off or isolation valve located within a
separate chamber, outside of the pump station.
Page 46
7.
12/1/09
c)
The piping within the valve vault shall be constructed of ductile iron or stainless steel piping.
d)
A hinged and lockable aluminum or stainless steel door with a non-skid surface shall be provided
over the valve chamber to allow accessibility to all valving.
e)
If necessary, access steps, constructed of polypropylene coated 2 inch steel bar shall be
provided to access all valving from finished grade.
f)
Certification
For projects that involve a sewage pumping station, a licensed design professional shall certify that all
materials, method of construction, installation, and testing of the sewer pipe and equipment meet the
requirements of these standards as well as plans approved by the Department. Refer to Appendix C
of these standards.
8.
Exceptions
The Department may accept pump station designs which vary from the standards in cases of small
sewage flows provided that the licensed design professional submits engineering justification
acceptable to the Department.
Materials
Force mains may be constructed of either PVC and /or ductile iron in accordance with the following
criteria:
a)
Plastic (PVC) sewer pipe used for force mains that have a diameter less than 4 inches shall be
constructed of schedule 40 or 80 PVC pipe and meet the requirements of ASTM standard D1785. Fittings shall have bell push-on joints and rubber sealing rings constructed of ductile iron,
grade 65-45-12, in accordance with ASTM standard A-536. The rubber sealing rings shall
meet the requirements of ASTM standard F- 477.
b)
Plastic (PVC) sewer pipe and fittings used for force mains that have a diameter of four (4) inches
or greater shall have a minimum rating of SDR-18 and meet or exceed the requirements of the
AWWA C-900 standard. Rubber sealing rings shall meet ASTM F-477.
Page 47
c)
2.
3.
4.
12/1/09
Ductile iron pipe shall conform to AWWA C-150 and C-151 standards and have a minimum
class 52 designation. Ductile iron push-on-joints used with this pipe shall conform to AWWA
C-111; fittings shall meet AWWA C-110 and C-153 standards.
Design
a)
Force mains shall be designed to provide a minimum flow velocity of 2 feet per second and a
maximum velocity of 7 feet per second. No force main shall have an inside diameter of less than
two (2) inches.
b)
Force mains used to pump raw sewage shall have a minimum diameter of 4 inches, unless
grinder pumps are used.
c)
Thrust blocks or restraints shall be provided where applicable throughout the length of a force
main and shall be designed to contain the resultant thrust forces. Thrust blocks and restraints
shall conform to AWWA C-600 standards.
d)
Force mains shall be located a minimum of 4.5 feet below finished grade to protect against
freezing. In certain cases, force mains may have less soil cover, provided the line is pitched so
that sewage is not retained in the line between pump cycles.
Installation Requirements
a)
The width of trenches shall be adequate to allow sewer pipe to be laid and joined properly and
to allow bedding and haunching to be placed and compacted to adequately support the pipe.
Refer to Section XVIII, paragraph E concerning the material used for embedment around PVC
pressure pipe.
b)
For additional requirements concerning the installation of PVC pressure pipe, refer to ASTM
standard D-2774 "Practice for Underground installation of Thermoplastic Pressure Piping".
c)
Force mains constructed of ductile iron pipe shall be installed in accordance with AWWA C600 standard.
Testing
Force mains shall be pressure tested at 200 psi for a minimum of 30 minutes to assure water tightness
prior to backfilling. The contractor shall conduct the test in the presence of the certifying design
professional.
5.
Certification
A licensed design professional shall certify that all material, methods of construction, installation and
testing meet the requirements of these standards as well as plans approved by the Department. Refer
to Appendix C of these standards.
Page 48
6.
12/1/09
Exceptions
The Department may accept force main designs which vary from the standards in cases of small
sewage flows provided that the licensed design professional submits engineering justification
acceptable to the Department.
Pump-out units may be portable or permanent, and should include a vacuum pump or a positive
displacement type of pump to empty marine vessel and boat holding tank wastes. Pump-out
units may be electrically or manually operated. If pump-out units are electrically operated, then
all electrical components must be explosion proof, and meet NEC requirements.
b)
All pump-out units shall be provided with a flexible suction hose and dripless nozzle.
c)
All mechanical and electrical components must be adequately protected from freezing.
d)
Pump-discharge piping or force mains must be constructed of materials and joints that meet
water main standards. The force main may be constructed of Type 1, Grade 1, schedule 80
PVC sewer pipe, or PVC pressure rated SDR 18 pipe.
e)
All pump-out units should be provided with a non-potable water service and an approved
backflow prevention device for rinsing the onboard holding tanks.
f)
g)
The minimum capacity of any holding tank shall be 1000 gallons, but a greater volume may be
required, as determined by the Department.
h)
Holding tanks shall be made watertight and leak tested to ensure tightness prior to operation.
Maximum permissible leak rate is inch in 8 hours.
Page 49
12/1/09
i)
Holding tanks shall not have an outlet pipe but shall be provided with a hinged and locking
access port. A locking cast iron frame and cover shall be provided at finished grade over the
access port. Both the access port and access cover shall be watertight and insect proof.
j)
Holding tanks shall be properly vented, and shall be equipped with a liquid level float switch,
high water level alarm and auto dialer or other acceptable automatic notification system.
k)
All mechanical and electrical equipment shall meet the requirements of the NEC.
Holding tank wastes must be pumped out on a routine basis by a licensed scavenger vehicle and
discharged to an acceptable treatment facility.
b)
4. Certification Required
A design professional shall supervise the installation of pump-out facilities and certify that the systems
are constructed in accordance with the approved plans and applicable codes.
5. Exceptions
a)
For cases where a municipal sewer is available, the marine vessel, bus, or RV waste can be
pumped directly to the sewer system in lieu of providing an on-site holding tank.
b)
For cases were NYSDEC approval is required, the Department may consider alternative
designs for pump-out facilities.
General
The sewage disposal systems addressed thus far in these Standards are considered conventional or
typical systems and may be used on sites with adequate soil percolation and vertical/horizontal
separation distances unless otherwise prohibited. For sites that are not suitable for such systems, the
use of alternative systems may be permitted by the Department without need for a variance if the
design meets the conditions listed in section XXV.2 and is acceptable to the Department. The
Department reserves the right to require a variance to utilize an alternative system from the Board of
Review at any time in conformance with section XXVIII.
2.
Design Considerations
Page 50
12/1/09
In addition to the typical plan requirements, applications for alternative designs shall include the
following:
3.
a)
b)
It is clearly demonstrated that the proposed system is physically equivalent or better than the
conventional systems, in respect to storage capacity, leaching area, land area utilization, grading,
accessibility, maintainability, reparability, life expectancy, effluent quality and reliability.
c)
An engineering report shall be submitted that defines the disposal system and determines that the
proposed design is most suitable for the building site and that the proposed sanitary system will
function properly without causing any health hazard and will minimize the impact on the
surrounding environment.
d)
The design engineer shall supervise the installation of the system and certify that the system was
constructed in accordance with the approved plans. An inspection log shall be maintained and a
copy submitted to the Department if requested.
Clustered Leaching Systems - a leaching system that consists of shallow pools that are
clustered to minimize the space requirement. Maximum effective depth of leaching rings shallnot
exceed 3 feet and can be located a minimum of 2 feet above the highest recorded groundwater
elevation. Refer to figure #14.
b)
Chamber Leaching System - a leaching system that consists of plastic chambers in lieu
of concrete leaching pools and can be located a minimum of 2 feet above the highest
recorded groundwater elevation.
c)
Diffusion Well Systems - a leaching system that utilizes wicks and other appurtenances to
minimize the effects of poor soils.
Abandonment In-Place - existing systems shall be abandoned by removing all residual sewage
wastes by a licensed waste hauler, removing the top of the structure(s), backfilling with suitable sand
and gravel material, and properly compacting.
Page 51
12/1/09
2.
Abandonment by Removal - existing systems may also be abandoned by removing all residual
sewage wastes by a licensed waste hauler, removing the entire structure(s), backfilling with suitable
sand and gravel material, and properly compacting.
3.
Abandonment of Sewer Piping - the associated sewer piping shall be cut and capped as a means of
abandonment. The Department should be contacted for further abandonment requirements, if future
construction is contemplated in the area of the abandoned septic system.
4.
Certification Required - the abandonment of existing sewage disposal systems, either in-place, or by
removal, must be certified by either a licensed design professional or licensed contractor as indicated
by the Department on the Permit to Construct. For projects served by municipal sewer districts, the
appropriate municipal agency with jurisdiction should also be contacted.
XXVIII. VARIANCES
1.
The Commissioner of the Department of Health Services, on written application, may grant a
variance, in accordance with Section 220 of Article 2 of the Suffolk County Sanitary Code, from a
specific provision of these Standards in a particular case, subject to appropriate conditions, where
such variance is in harmony with the general purpose and intent of the Standards, and when such
application for a variance has been considered by a Review Board appointed by the Commissioner.
2.
The Commissioner may impose more stringent requirements in a specific case when necessary to
insure an adequate and satisfactory sewage and waste disposal system or to protect a sensitive
habitat.
Page 52
12/1/09
Page 53
COUNTY OF SUFFOLK
STEVE LEVY
SUFFOLK COUNTY EXECUTIVE
SUFFOLK COUNTY
DEPARTMENT OF HEALTH SERVICES
DIVISION OF ENVIRONMENTAL QUALITY
STANDARDS FOR APPROVAL OF PLANS
AND CONSTRUCTION FOR
SEWAGE DISPOSAL SYSTEMS FOR
OTHER THAN SINGLE-FAMILY RESIDENCES
APPENDIX A
STANDARDS FOR CONSTRUCTION OF MODIFIED SUBSURFACE
SEWAGE DISPOSAL SYSTEMS AND SMALL COMMUNITY
SEWERAGE SYSTEMS
December 1, 2009
Linda Mermelstein, M.D., M.P.H.
Acting Commissioner of Health Services
Vito Minei, P.E.
Director of Environmental Quality
12/1/09
TABLE OF CONTENTS
Section
Page
A1.
GENERAL/APPLICABILITY ......................................................................................................1
A2.
A3.
A4.
A5.
A6.
A7.
A8.
A9.
A10.
A11.
A12.
LIST OF TABLES
TABLE A1 MINIMUM SEPARATION DISTANCES ...........................................................................3
TABLE A2 MODIFIED SEPARATION DISTANCES .........................................................................5
LIST OF FIGURES
FIGURE A1 TYPICAL MONITORING WELL ...................................................................................10
Appendix A
Page i
12/1/09
APPENDIX A
STANDARDS FOR CONSTRUCTION OF MODIFIED SUBSURFACE SEWAGE DISPOSAL
SYSTEMS AND SMALL COMMUNITY SEWERAGE SYSTEMS
A1.
GENERAL / APPLICABILITY
This appendix sets forth standards for both modified subsurface sewage disposal systems (MSSDS), also
known as denitrification systems, and for small community sewerage systems (SCSS) that do not exceed
15,000-gpd total design flow. Standards for collection systems (sewer mains) and for larger sewage
treatment plants are not included herein. Refer to latest edition of Recommended Standards For Wastewater
Facilities GLUMRB, to Suffolk County Department of Public Works, and to Appendix B of these
standards for sewer main and treatment plant requirements. These standards are applicable only for
technologies that have received prior approval by New York State Department of Environmental
Conservation for use within Suffolk County. The standards do not address the method of obtaining such
approval.
These standards serve as a supplement to Standards For Approval Of Plans And Construction For
Sewage Disposal Systems For Other Than Single Family Residences (the STANDARDS) and include
minimum separation distances from process tanks and leaching pools to buildings, property lines, and
surface water. The statutory authority for this appendix can be found in Article 6 Section 760-603 and 607
of the Suffolk County Sanitary Code.
Definitions of terms used herein can be found in the STANDARDS and in Article 6. When used in this
appendix, a small community sewerage system is defined as a community sewerage system with a total
design sewage flow of less than or equal to 15,000 gpd. The standards in this appendix apply to both
MSSDS and SCSS. All plans for construction of new MSSDS and SCSS as well as plans to upgrade or
expand existing systems must meet these requirements.
An MSSDS may be approved as a method of sewage disposal for a single parcel provided the construction
project is not located in a realty subdivision or development as defined by Article 6 of the Suffolk County
Sanitary Code where such subdivision or development was approved by the Department after January 1,
1981. The total design flow must be at least 450-gpd and cannot exceed 15,000-gpd and the total nitrogen in
the effluent stream cannot exceed 10 mg/l. Projects with a modified subsurface sewage disposal system
must also connect to a community water supply.
A2.
SUBMISSION REQUIREMENTS
Refer to Application Requirements For Sewage Disposal Facilities & Water Supply Systems For Other
Than Single Family Residences, (WWM-003) for application procedures.
Appendix A
Page 1 of 10
A3.
12/1/09
Modified subsurface sewage disposal systems and small community sewage systems shall be located to
ensure that they do not cause contamination of drinking water supply wells. They shall be located to prevent
airborne spread of pathogens and minimize nuisance odors and noise. Refer to the STANDARDS for
additional information concerning the location and siting of sewage treatment facilities.
The following criteria also apply to these sites:
1.
Modified subsurface sewage disposal systems and small community sewerage systems shall be
located to maximize distances to drinking water supply wells. To protect the drinking water
supply, all projects will undergo a separate site review within the Suffolk County Department
of Health Services (SCDHS). If the SCDHS determines that insufficient distance exists to
protect wells, or there is a preferred placement because of groundwater flow direction, further
measures, including but not limited to relocation, effluent disinfection or additional sewage
treatment may be required.
2.
Modified subsurface sewage disposal systems and small community sewerage systems shall be
located so as to maximize distances to freshwater wetlands, tidal wetlands, ponds, streams, and
other surface waters, provided the minimum separation distances in Tables A1 and A2, are
met.
3.
Modified subsurface sewage disposal systems and small community sewerage systems shall be
located in an area that is easily accessible for purposes of maintenance and / or replacement of
sewage treatment or disposal facilities. Additionally, treatment and disposal facilities shall not
be located within areas used for parking, easements or rights-of-way. Adequate security
fencing shall be provided around all sewage treatment components.
4.
A buffer area of one hundred (100) feet shall be provided surrounding the area of the facilities
including the expansion area. The buffer area shall be measured as a radius from the
outermost dimensions of the tanks and expansion area. There shall be no substantial human
use of the buffer area. Swimming pools, tennis courts or other recreational enhancements,
parking lots, mailboxes or other building amenities shall not be located within the buffer area.
This area shall be used exclusively for plantings that serve to screen the facilities from view.
Effluent leaching pools may be placed in the buffer area.
5.
Modified subsurface sewage disposal systems and small community sewerage systems shall be
located as far as possible from human habitation, surface water, and areas of substantial use by
the public. Separation distances, as listed in Table A1 below, are considered to be the
minimum allowable and are based upon a typical system that is properly designed,
constructed, well operated and judiciously maintained. Reasonable efforts should be made to
ensure maintenance of these minimum separation distances, including evaluating alternative
site layouts and changing density load.
Appendix A
Page 2 of 10
12/1/09
**
To
HABITABLE
*
Building
200 ft.
25 ft.
To NONHABITABLE
Building
To Area of
Substantial
Human Use
(Buffer Area)
100 ft.
25 ft.
To Property
Lines
To Surface
Water
150 ft.
25 ft.
100 ft.
May Be
Included
For purposes of this appendix, HABITABLE buildings include those buildings intended for permanent or transient residency
or recreational use, and commercial buildings in substantial use by the public (i.e., condos, apartments, co-ops, PRC, assisted
living, townhouses, hotels, motels, community clubhouses, office buildings, retail stores, restaurants, etc.).
The minimum separation distances found in TABLE 2 of the (main body of the) STANDARDS also apply to modified
subsurface sewage disposal systems and small community sewerage systems.
6.
A4.
THAT
MAY
WARRANT
REDUCED
The separation distances as defined in Section A3 above can be reduced when special site conditions
exist or when the design of the modified subsurface sewage disposal system or small community
sewerage system is enhanced beyond the level otherwise required by these standards, as defined in
paragraph A4.2 below.
1.
Appendix A
Page 3 of 10
2.
12/1/09
b)
Venting
Location and height of exhaust air ventilation shall be designed to minimize impacts to
habitable areas.
c)
Noise Attenuation
Noise attenuation is required when reduced separation distances are requested. Blowers
and exhaust fans shall be placed in an enclosure designed with a rating sufficient to
attenuate noise levels from the equipment to a maximum of 50 dbA as measured at a
distance of twenty-five (25) feet from the equipment.
3.
Addition of all of the above enhancements shall allow the separation distance from enclosed
process tanks, expansion area, and/or exhaust air discharge location to be reduced to a
minimum of seventy-five (75) feet to habitable buildings, as previously defined, and fifty (50)
feet to non-habitable buildings, such as separate garages or maintenance type buildings. A
buffer area of fifty (50) feet minimum is required. Swimming pools, parking areas, mailboxes,
playgrounds, tennis courts, or any other amenities shall not be placed within the fifty foot
buffer area. This buffer area may be reduced when special site conditions are present as
described in paragraph A4.1 above.
This area shall be used for plantings that serve to screen the facilities from view. Effluent leaching
pools may be placed in the buffer area. Modified distance requirements are summarized in Table A2
below.
Appendix A
Page 4 of 10
12/1/09
**
**
***
To
HABITABLE
*
Building
75 ft.
25 ft.
To NONHABITABLE
Building
To Area of
Substantial
Human Use
(Buffer Area)
50 ft.
50 ft.
25 ft.
May Be
Included
To Property
Lines
To Surface
Water
75 ft.***
25 ft.
For purposes of this appendix, HABITABLE buildings include those buildings intended for permanent or transient
residency or recreational use, and commercial buildings in substantial use by the public (i.e., condos, apartments, co-ops,
PRC, assisted living, townhouses, hotels, motels, community clubhouses, office buildings, retail stores, restaurants, etc.).
The minimum separation distances found in TABLE 2 of the (main body of the) STANDARDS also apply to modified
subsurface sewage disposal systems and small community sewerage systems.
May be reduced to twenty-five (25) feet when special site conditions as noted in paragraph A4.1 are present and when
reduced distance does not interfere with future building setbacks for off-site vacant parcels.
When a distance reduction is made for a multiple ownership project such as a condominium, the offering
plan shall contain language indicating that special risks are present due to the reduction in distance.
Any reduction in the distances prescribed in Table A2, will require a variance from the SCDHS Board
of Review.
A5.
FINAL RECHARGE
Effluent from the treatment facility shall be piped to subsurface pre-cast concrete leaching pools in
accordance with provisions in the STANDARDS. The maximum hydraulic leaching rate of 5 gal./sq.ft./day
shall be used without positive filtration. Alternative designs for effluent disposal may be submitted for
review by the SCDHS.
A6.
An adequate area shall be available to allow for a minimum of one hundred percent (100%)
expansion/replacement of the modified subsurface sewage disposal systems and small community sewerage
treatment and disposal facilities. The area provided for expansion/replacement shall be contiguous to the
planned location of treatment and disposal facilities. Required buffer area shall be located outside of the
expansion/replacement area for processes. Leaching pools and required expansion/replacement area for
Appendix A
Page 5 of 10
12/1/09
leaching may be placed within the buffer area provided that applicable separation distances listed in the
tables are maintained. Deepening of leaching pools is not permitted in lieu of providing
expansion/replacement area.
A7.
LABORATORY REQUIREMENTS
All modified subsurface sewage disposal systems and small community sewerage systems shall provide the
means necessary for proper process control and operation. An area for laboratory facilities shall be provided
in a building on the plant site. The laboratory shall be equipped with bathroom facilities and shall be heated
and ventilated to provide an indoor temperature of at least 70 degrees F when the outside temperature is 0
degrees F.
A8.
The SCDHS reserves the right to require all remedial actions necessary; including but not limited to
enclosing of odor and noise causing facilities and the installation of odor and emissions control equipment
should nuisance conditions arise during actual plant operation. Approval of sewage treatment facility site
location and design shall not be interpreted as relieving the owners from responsibility for remedial action
should nuisance conditions arise in the future.
A9.
A State Pollutant Discharge Elimination System (SPDES) permit, issued by the New York State Department
of Environmental Conservation (NYSDEC), or its agent, is required prior to the issuance of a permit to
construct. A SPDES permit is necessary when the project design sewage flow (total hydraulic load) is 1,000
gpd or greater. These permits require monitoring of the system influent, and effluent for flow and total
nitrogen. Other parameters and sampling requirements may be imposed.
A10.
MONITORING WELLS
1.
Applicability
Monitoring wells are designed to provide a means of obtaining shallow groundwater quality
samples in proximity to sewage treatment plant effluent discharges to assure that SPDES
permit conditions are being met, to determine whether such conditions are adequate to protect
groundwater, and other purposes determined by the commissioner of the SCDHS.
2.
Siting / Location
The applicants engineer shall include the location of all proposed and /or existing monitoring
wells on the site plans together with the direction of groundwater flow. The required array of
monitoring wells must provide a means of determining plant discharges on a continuous basis,
and shall include the following:
Appendix A
Page 6 of 10
12/1/09
a)
One (1) well up gradient of the effluent disposal facilities to monitor ambient groundwater
quality. This well should be located at least 50 feet up gradient of any such facilities,
beyond the influence of mounding at the water table caused by the recharged effluent.
b)
One (1) well down gradient of the effluent disposal facilities to monitor the impact of
recharged effluent. These wells should be located no more than twenty-five (25) feet
down gradient of disposal facilities.
The adequacy of proposed monitoring well arrays will be determined by the SCDHS based
upon information contained in the plan submission, and on groundwater flow direction. The
SCDHS reserves the right to require the installation of additional monitoring wells at any time.
Access to all wells by the SCDHS and by the NYSDEC during normal working hours shall be
assured.
3.
Specifications / Construction
Monitoring wells shall conform to the following standards:
A11.
a)
b)
c)
Screen Length: 15 feet minimum; may be greater depending upon the fluctuation in the
local groundwater elevation.
d)
Filter Pack: Silica sand, uniformity coefficient < 1.7, effective size > 0.35", 2 feet above
the top of the screen.
e)
Grouting: Grouting of the annular space above the filter pack is desirable, but not
required; when included, a seal of fine silica sand - 2 inches thick- must be placed
between the filter pack and grouting.
f)
Caps: Wells finished above grade must be protected by a 4-inch inside diameter steel
casing secured with concrete collars and unthreaded, lockable caps. Wells finished
below grade must be protected by suitable roadway, service or meter boxes (minimum 6
inches inside diameter).
g)
Inspection
All sewage treatment and disposal system components must be inspected by the SCDHS to
ensure conformance with the approved plans, reports and specifications. No portion of the
system shall be backfilled until such time as the SCDHS has accepted the installation. A
schedule for constructing the various components of the project shall be submitted to the
SCDHS prior to the start of construction. A revised schedule will be required if anticipated
construction is delayed more than two (2) weeks.
Appendix A
Page 7 of 10
2.
12/1/09
Testing
The project engineer, and /or contractor shall perform tests of the sewage treatment system in
accordance with the following criteria:
3.
a)
Force mains shall be pressure tested for a minimum of 30 minutes @ 200 psi, or as
recommended by the pipe manufacturer.
b)
Operation of all system components, including pumps, process equipment and electrical
components.
c)
Engineers Certification
The project engineer shall certify that all sewage treatment system components have been
constructed in accordance with approved plans, reports, specifications, and standards issued by
the SCDHS. Refer to Appendix C of these standards for further information.
4.
Manufacturers Certification
The project engineer shall submit Manufacturer(s) Start-Up Reports (MSR) for all major
components. For example: pump station, generator set, process equipment, and flow
meters.
5.
As - Built Plans
"As Built" plans shall be submitted to the SCDHS for review and approval. These plans
shall include all of the items listed in Instructions For Obtaining Final Health Department
Approval Of Constructed Projects For Other Than Single Family Residences, (WWM019)
6.
Shop Drawings
Shop drawings of the major mechanical and electrical components shall be submitted to the
SCDHS. For example, pumps, process equipment, and generator set.
7.
Appendix A
Page 8 of 10
A12.
12/1/09
In accordance with Article 2 and Article 6 of the Suffolk County Sanitary Code, the foregoing are the
standards of the Suffolk County Department of Health Services for Appendix A of the Standards For
Approval Of Plans And Construction For Sewage Disposal Systems For Other Than Single-family
Residences. These Standards are adopted December 1, 2009 and are effective for applications received
after January 1, 2010.
Appendix A
Page 9 of 10
12/1/09
Figure A1
Appendix A
Page 10 of 10
COUNTY OF SUFFOLK
STEVE LEVY
SUFFOLK COUNTY EXECUTIVE
SUFFOLK COUNTY
DEPARTMENT OF HEALTH SERVICES
DIVISION OF ENVIRONMENTAL QUALITY
STANDARDS FOR APPROVAL OF PLANS
AND CONSTRUCTION FOR
SEWAGE DISPOSAL SYSTEMS FOR
OTHER THAN SINGLE-FAMILY RESIDENCES
APPENDIX B
STANDARDS FOR APPROVAL AND CONSTRUCTION
OF SEWAGE COLLECTION SYSTEMS AND
TREATMENT WORKS
December 1, 2009
Linda Mermelstein, M.D., M.P.H.
Acting Commissioner of Health Services
Vito Minei, P.E.
Director of Environmental Quality
12/1/09
TABLE OF CONTENTS
Section
Page
B1.
B2.
B3.
B4.
B5.
B6.
B7.
B8.
TESTING REQUIREMENTS......................................................................................................10
B9.
B10.
B11.
LIST OF TABLES
TABLE B1 REQUIRED MINIMUM SEPARATION DISTANCES ......................................................6
TABLE B2 PIPE COLOR CODING .......................................................................................................6
TABLE B3 REQUIRED TEST EQUIPMENT .......................................................................................8
LIST OF FIGURES
FIGURE B1 TYPICAL MONITORING WELL ...................................................................................15
Appendix B
Page i
12/1/09
APPENDIX B
STANDARDS FOR APPROVAL AND CONSTRUCTION OF
SEWAGE COLLECTION SYSTEMS AND TREATMENT WORKS
B1.
ENGINEERING REPORTS
Construction projects which include treatment works and/or large collection systems for sanitary wastes
require supplemental design review and approval by the department prior to approval to construct being
issued on the remainder of the project.
Design information is submitted to the department in the form of engineers reports and plans and
specifications. The departments review is conducted in two phases. The first phase is the submission of the
engineering report. Following approval of this report, the second phase begins with submissions of plans
and specifications. A copy of the final plans and specifications will be stamped with an approval stamp and
returned to the authorized engineer. Projects with Suffolk County Sewer Agency contracts require review
and approval by Suffolk County Department of Public Works in addition to Health Department review and
approval.
All submitted documents shall bear the original seal and signature of an engineer licensed and registered to
practice in New York State. Documents submitted shall be accompanied with a letter from the applicant
authorizing the engineer to submit documents. Documents shall include a project application per WWM003, SCDHS submission instructions.
Designs shall conform to the GLUMRB Recommended Standards for Sewage Works (Ten State
Standards) except where the requirements following allow differences. The project engineering report shall
conform to the outline presented in Chapter 10 of the aforementioned standards. For small non-municipal
type sewage treatment plants, a less elaborate report is usually acceptable. However, as a minimum, the
information outlined below shall be included in the report.
The engineering report is reviewed to evaluate whether: a proper basis for design has been established; the
design criteria of the GLUMRB (Ten States) standards and Suffolk County Department of Health Services
standards have been utilized; and the design has a reasonable expectation of meeting its objective.
The engineering report shall include:
1.
Project name and description, including location, size and type of development and/or service
area and future additions.
2.
Appendix B
A detailed site plan drawn accurately to scale of the planned development showing all
property lines, topography, existing and proposed structures, rights-of-way, easements
and proposed treatment plant site location. Scale shall not exceed 1 inch = 100 feet.
Page 1 of 15
3.
12/1/09
b)
c)
d)
A detailed sewage treatment plant site plan of a scale no greater than 1 inch = 50 feet
containing all information necessary to judge the suitability of the site location proposed.
Typically, the plan must clearly detail an area of at least 500 feet surrounding the
proposed plant site and must show all property lines, property ownership, property
zoning, existing and future structures, rights-of- way, easements, water supply wells,
surface water bodies, wetlands areas, storm water recharge facilities and utilities. Site
plans shall bear the original seal and signature of a licensed professional engineer or
architect registered for practice in the State of New York. The proposed STP shall not be
located underneath the surface of the ground, such as under a parking lot, etc.
b)
4.
A flow schematic of the proposed STP including piping and pumps, chemical additions, sludge
system, recycle and return lines, etc.
5.
A hydraulic profile through the STP from the influent sewer invert to the end of the effluent
discharge pipe.
6.
A statement of the effluent requirements to be met by the proposed treatment plant. In the case
of discharge to groundwater, standards require that a Total Nitrogen (as N) concentration of 10
mg/l not be exceeded. Refer to NYSDEC Effluent Standards and/or Limitations for
Discharges to Class GA Waters (6NYCRR 703.6).
7.
Present and future population to be served and corresponding average daily and maximum
hourly flows to the treatment plant.
8.
9.
Appendix B
a)
Indicate the design criteria used for sizing of the treatment units.
b)
Page 2 of 15
10.
A detailed discussion of the total air requirements at the STP. Indicate the size and number of
blowers to be provided. In the case of the activated sludge process, the report shall show that
sufficient air will be available for BOD reduction and conversion of the influent nitrogen to
nitrate. Additional air shall be provided for the surge tank, digester, airlift pumps, sand filter
backwash air scour, etc.
11.
Detailed calculations for sizing of chemical storage tanks and feed equipment. The chemicals
usually provided are sodium hypochlorite, methanol and caustic soda. Storage of chemicals
shall conform to Article 12 of the Suffolk County Sanitary Code.
12.
13.
B2.
12/1/09
a)
Potable water to the treatment plant and pump station, protected by an approved reduced
pressure backflow prevention device.
b)
Emergency standby power to maintain flow throughout the plant and for operation of
other critical equipment.
c)
An observation well in the vicinity of the leaching pools for monitoring groundwater.
d)
e)
Laboratory facilities, including a lab bench with sink and test equipment to perform the
required daily tests.
f)
A control building to house the laboratory facility and the chemical feeders.
g)
h)
TREATMENT UNITS
Typical biological nitrification - denitrification treatment processes used in Suffolk County are Extended
Aeration Activated Sludge or Rotating Biological Contactors followed by Deep Bed Filters but other
processes may be approved. The Deep Bed Filter accomplishes denitrification and solids removal and is
equipped with an automatic backwash system. The influent to the filter is inoculated with a carbon source
(methanol).
The total required clarifier and filter areas shall be divided among two or more units. Multiples of other
treatment units may also be required.
Preliminary treatment devices shall be designed to remove or reduce in size large suspended or floating
solids; to remove heavy inorganic solids; and to remove excess amounts of oils and grease.
Appendix B
Page 3 of 15
12/1/09
Flow equalization shall be provided to dampen the diurnal flow variation, and thus achieve a constant or
nearly constant flow rate through the downstream treatment processes. Separate equalization basins are
required.
Facilities for disinfection of the sewage effluent shall be provided and designed in accordance with Ten
State Standards.
Facilities for waste sludge handling and storage shall be provided and designed in accordance with Ten State
Standards. For small size plants, an aerobic digester is usually provided. The report must also address final
sludge disposal.
A control building shall be provided to house the laboratory facility and the chemical feeders. In addition,
an enclosure shall also be provided for the blowers and electrical panel to protect the equipment from
adverse weather and to reduce noise impact on the environment.
In the case of effluent recharge to groundwater, final disposal facilities may consist of subsurface leaching
pools or a minimum of 4 recharge beds. The maximum allowable design rate for tertiary filtered effluent is
10 gpd per sf of pool sidewall area or bed bottom area (5 gpd per sf for unfiltered effluent). This rate is
conditioned on acceptable soil conditions being encountered.
A minimum of 100 percent expansion/replacement area shall be provided for the sewage treatment plant and
for future leaching facilities. This plant expansion area may be modified for small private plants if the
property is fully developed.
B3.
The site location for wastewater treatment facilities shall be selected to insure that public health hazards are
not caused by airborne spread of pathogens and contamination of water supply wells. Care shall also be
exercised to insure that neighboring resources are not degraded and that usage of neighboring properties are
not impaired.
To protect the public water supply and the benefits that freshwater wetlands, tidal wetlands, ponds, streams
and other surface waters provided, all projects within 1500 feet of a public water supply well or projects
containing wetlands or surface waters will undergo a separate site review. The following criteria apply to
these sites:
1.
Wastewater treatment facilities shall be located to maximize distances to public water supply
wells. If the department determines that insufficient distance exists to protect the well, further
measures may be required.
2.
Appendix B
Page 4 of 15
3.
12/1/09
A buffer area of one hundred (100) feet shall be provided surrounding the area of the facilities
including the expansion area. The buffer area shall be measured as a radius from the
outermost dimensions of the tanks and expansion area. There shall be no substantial human
use of the buffer area. Swimming pools, tennis courts or other recreational enhancements,
parking lots, mailboxes or other building amenities shall not be located within the buffer area.
This area shall be used exclusively for plantings that serve to screen the facilities from view.
Effluent leaching pools may be placed in the buffer area.
Separation distances, as hereinafter listed in Table 1, are considered to be the minimum allowable and are
based upon a typical system being well operated and judiciously maintained. Every reasonable effort should
be expended to provide separation distances in excess of those tabulated. The Department reserves the right
to require all remedial actions necessary; including but not limited to, enclosing of odor causing facilities
and the installation of adequate ventilation and odor destruction equipment should objectionable conditions
arise during actual plant operation. Approval of water pollution control plant site location and design shall
not be interpreted as relieving the owner from responsibility for remedial action should objectionable
conditions arise in the future.
Below are separation distances which shall be maintained between water pollution control plant units and
tenantable structures, and between water pollution control plant units and property lines of developed or
buildable property. Where neighboring properties are currently vacant, separation distances shall be
measured to the pertinent setback distance required by present zoning.
Where the tabulated separation distances are shown for enclosed facilities, those reduced distances are based
upon inclusion within the enclosure of noise control, proper ventilation and positive odor removal devices.
Ventilation systems shall be designed to maintain a negative pressure inside the enclosure with respect to the
outside ambient environment of sufficient magnitude to prevent the inadvertent escape of noxious odors.
Special emphasis should be placed on architectural detail to insure a tight enclosure.
Positive odor removal shall be taken to include ozonation, thermal incineration, oxidation by chemical
oxidants, adsorption on sorptive media, or any like process which removes and/or destroys the odorous
constituents of the ventilated gases. Use of masking agents shall not be permitted.
Appendix B
Page 5 of 15
12/1/09
DISTANCE TO
PROPERTY LINES
400' 3
350' 3
200' 2,3
150' 3
400' 3
300' 3
25'
25'
Leaching Pools
Chemical Storage
1
2
3
Enclosed building designation requires ventilation, odor and noise control devices in accordance with good engineering
practice.
Non-residential structures located on the same parcel may qualify for lesser distances.
100 foot buffer to areas of substantial human use is to be included in this distance.
B4.
It shall be a requirement for all sewage treatment plants that process piping be color coded and identified
with stenciled markings. Identification markings shall be stenciled at suitable locations on the piping and
lettering shall be of such size to allow easy identification.
Unless otherwise approved, lettering shall be 2 inches high and spaced at no greater than 10'-0" between
identifying markings. Color coding and identification markings shall be as follows:
TABLE B2 PIPE COLOR CODING
SERVICE
COLOR
MARKING
Sludge
Brown
SL
Gas
Potable Water
Blue
C.W.
Sewage
Gray
Appendix B
Page 6 of 15
12/1/09
SERVICE
Chlorine or Hypochlorite
Compressed Air
COLOR
Yellow
CL
Green
Chemical
Orange
Fire Protection
Red
B5.
MARKING
L - Lime
F Ferric
M Methanol
Na - Caustic
P Polymer
X at 12 inch
intervals
LABORATORY REQUIREMENTS
All wastewater treatment facilities shall provide the means necessary for proper process control and
operation. An area for laboratory facilities shall be provided in a building on the plant site. The building
may also house process equipment, lavatory facilities, storage rooms, etc; however, the laboratory shall be
isolated from other equipment and housed in an enclosure by means of partition walls and doors. The
laboratory shall be heated and ventilated to provide an indoor temperature of at least 70 degrees F when the
outside temperature is 0 degrees F. At least two duplex GFI 120V electric outlets shall be located in close
proximity to laboratory benches. Outlets shall be located to allow operation of all electrical laboratory
equipment on laboratory benches and tables. Lighting shall be provided to produce a light intensity of at
least 50 foot-candles over the entire laboratory area and at least 100 foot-candles over laboratory benches.
Laboratories shall be equipped with ample bench and storage space to allow safe storage of equipment
and reagents. The following storage and work space shall be supplied:
1.
1 - 60"L x 30"D x 36"H bench with at least 3 storage drawers and cupboard. The
bench top shall be of corrosion resistant material;
2.
3.
4.
5.
1 lab sink manufactured of corrosion resistant material, equipped with 2 goose neck
faucets suitable for heavy duty laboratory service, and serviced with hot and cold
running water.
Appendix B
Page 7 of 15
12/1/09
6.
7.
Facilities and an ample supply of test equipment shall be provided to perform the following tests at the STP
for day to day operational control:
TABLE B3 - REQUIRED TEST EQUIPMENT
TEST
EQUIPMENT REQUIRED
1.
Settleable solids
Imhoff cones
2.
Dissolved oxygen
3.
Ammonia nitrogen
Color comparitor
4.
Nitrite nitrogen
Color comparitor
5.
Nitrate nitrogen
Color comparitor
6.
TKN
Color comparitor
7.
pH
pH meter
8.
SVI
9.
Color comparitor
10.
Color comparitor
11.
Temperature
Laboratory thermometer
Other tests on STP effluent parameters as listed in the discharge permit (SPDES permit) are to be performed
by an approved outside laboratory and submitted monthly to authorities listed in the permit.
B6.
MONITORING WELLS
1.
Applicability
Monitoring wells are designed to provide a means of obtaining shallow groundwater quality
samples in proximity to sewage treatment plant effluent discharges to assure that SPDES
permit conditions are being met, to determine whether such conditions are adequate to protect
groundwater, and other purposes determined by the commissioner of the SCDHS.
2.
Siting / Location
The applicants engineer shall include the location of all proposed and /or existing monitoring
wells on the site plans together with the direction of groundwater flow. The required array of
monitoring wells must provide a means of determining plant discharges on a continuous basis,
and shall include the following:
Appendix B
Page 8 of 15
12/1/09
a)
One (1) well up gradient of the effluent disposal facilities to monitor ambient groundwater
quality. This well should be located at least 50 feet up gradient of any such facilities,
beyond the influence of mounding at the water table caused by the recharged effluent.
b)
Two (2) wells down gradient of the effluent disposal facilities to monitor the impact of
recharged effluent. These wells should be located no more than twenty-five (25) feet
down gradient of disposal facilities.
The adequacy of proposed monitoring well arrays will be determined by the SCDHS based upon
information contained in the plan submission, and on groundwater flow direction. The SCDHS
reserves the right to require the installation of additional monitoring wells at any time. Access to all
wells by the SCDHS and by the NYSDEC during normal working hours shall be assured.
3.
Specifications / Construction
Monitoring wells shall conform to the following standards:
B7.
a)
b)
c)
Screen Length: 15 feet minimum; may be greater depending upon the fluctuation in the
local groundwater elevation.
d)
Filter Pack: Silica sand, uniformity coefficient < 1.7, effective size > 0.35", 2 feet above
the top of the screen.
e)
Grouting: Grouting of the annular space above the filter pack is desirable, but not
required; when included, a seal of fine silica sand - 2 inches thick- must be placed
between the filter pack and grouting.
f)
Caps: Wells finished above grade must be protected by a 4-inch inside diameter steel
casing secured with concrete collars and unthreaded, lockable caps. Wells finished
below grade must be protected by suitable roadway, service or meter boxes (minimum 6
inches inside diameter).
g)
RECHARGE DESIGN
Effluent from the treatment facility shall be piped to subsurface pre-cast concrete leaching pools in
accordance with provisions in the STANDARDS or to recharge beds. Alternative designs for effluent
disposal may be submitted for review by the SCDHS.
Recharge pools shall be designed on the basis of 10 gallons per day per square foot of sidewall area for
filtered effluent or 5 gallons per day per square foot of sidewall area for unfiltered effluent. An area shall be
set aside for future 100% expansion/replacement of the pools.
Appendix B
Page 9 of 15
12/1/09
Recharge beds shall be designed on the basis of 10 gallons per day per square foot of bottom area for
filtered effluent or 5 gallons per day per square foot of bottom area for unfiltered effluent. An area shall be
set aside for future 100% expansion/replacement of the beds.
Beds shall be a maximum of four (4) feet in depth including freeboard, shall be equipped with access ramps
for ease of cleaning and shall be equipped with splash pads at the ends of influent piping.
Beds shall be separated into four independent areas valved to allow alternate dosing.
For further information regarding recharge bed design consult the Department.
B8.
TESTING REQUIREMENTS
All testing shall be scheduled and conducted by the contractor prior to the operation of the plant. The
Department of Health Services shall be given at least 48 hours notice prior to the start of any phase of the
testing procedure. All testing shall be witnessed and reported by the engineer certifying construction.
Prior to testing, during the entire testing procedure, and prior to putting the plant into operation, all tanks,
piping and appurtenances shall be cleaned and flushed of all debris, grease, oil, water and other deleterious
materials. At no time shall the discharge from the flushing operation be allowed to pass through any
equipment.
Prior to approval of any sewage treatment plant or pump station, all tanks, piping and appurtenances shall
pass the following tests.
1.
Appendix B
Page 10 of 15
12/1/09
After each individual tank has passed the 8 hour leakage test, all tanks within each complex
shall be filled with water to the normal operating level. Elevations shall be obtained around
the periphery at the same locations as prior to the leak test. Before and after elevations shall
be reported to the department.
2.
Wet Wells
Wet wells shall be filled to the maximum operating level or one foot above the crown of the
influent pipe whichever is higher and tested as outlined above.
3.
4.
Piping
In addition to flushing all pipe lines, the following requirements apply:
5.
a)
Air system - prior to connection of diffusers and air lifts to the main piping, the system
shall be run at maximum obtainable air flow to insure that all dust, dirt, scale, debris, etc.,
are scoured from the system. Piping shall be tested according to manufacturers
specifications.
b)
Other - Prior to operation, a piping system shall be tested and leaks repaired according to
manufacturers specification.
Equipment
All wiring and installation of appurtenances shall be completed prior to the testing of a piece
of equipment. All machinery and equipment shall be put in service and tested under the
supervision and direction of a representative of its manufacturer who has complete knowledge
and responsibility for the equipment and is capable of making any adjustments and/or
replacements required. All miscellaneous systems (alarm, remote telemetry, etc.) shall be
tested from all access points. All required testing equipment shall be furnished by the
contractor.
All blowers, pumps, generators, etc. shall be tested in place to insure that they do indeed
conform to the requirements of the contract specifications. All motors shall be tested to insure
that they do not exceed their name plate rating over the range of normal operation.
Appendix B
Page 11 of 15
12/1/09
Engine generator sets shall be tested at full load conditions by simulating a utility power
failure. All equipment which might normally be at load under power failure shall be in
operation during this test.
After testing is completed to the satisfaction of the engineer and the Department, the
manufacturers shall certify to:
a)
b)
The satisfactory compliance with testing requirements in accordance with design and
approved specifications.
c)
One copy of the above noted certification(s) on the manufacturers letterhead shall be supplied
to the Department by the certifying engineer.
B9.
A State Pollutant Discharge Elimination System (SPDES) permit, issued by the New York State
Department of Environmental Conservation (NYSDEC), or its agent, is required prior to the issuance of a
permit to construct. A SPDES permit is necessary when the project design sewage flow is 1,000 gpd or
greater. These permits require monitoring of the system influent, and effluent for flow and total nitrogen.
Other parameters and sampling requirements may be imposed.
B10.
Inspection
All sewage treatment and disposal system components must be inspected by the SCDHS to
ensure conformance with the approved plans, reports and specifications. No portion of the
system shall be backfilled until such time as the SCDHS has accepted the installation. A
schedule for constructing the various components of the project shall be submitted to the
SCDHS prior to the start of construction. A revised schedule will be required if anticipated
construction is delayed more than two (2) weeks.
2.
Engineers Certification
The project engineer shall certify that all sewage treatment system components have been
constructed in accordance with approved plans, reports, specifications, and standards issued by
the SCDHS. Refer to Appendix C of these standards for further information.
3.
Manufacturers Certification
The project engineer shall submit Manufacturer(s) Start-Up Reports (MSR) for all major
components. For example: pump station, generator set, process equipment, and flow meters.
Appendix B
Page 12 of 15
4.
12/1/09
As - Built Plans
"As Built" plans shall be submitted to the SCDHS for review and approval. These plans
shall include all of the items listed in Instructions For Obtaining Final Health Department
Approval Of Constructed Projects For Other Than Single Family Residences, (OWM019)
5.
Shop Drawings
Shop drawings of the major mechanical and electrical components shall be submitted to the
SCDHS. For example, pumps, process equipment, and generator set.
6.
Appendix B
Page 13 of 15
B11.
12/1/09
In accordance with Article 2 and Article 6 of the Suffolk County Sanitary Code, the foregoing are the
standards of the Suffolk County Department of Health Services for Appendix B of the Standards For
Approval of Plans And Construction For Sewage Disposal Systems For Other Than Single-family
Residences. These Standards are adopted December 1, 2009 and are effective for applications received after
January 1, 2010.
Appendix B
Page 14 of 15
12/1/09
Figure B1
Appendix B
Page 15 of 15
COUNTY OF SUFFOLK
STEVE LEVY
SUFFOLK COUNTY EXECUTIVE
SUFFOLK COUNTY
DEPARTMENT OF HEALTH SERVICES
DIVISION OF ENVIRONMENTAL QUALITY
STANDARDS FOR APPROVAL OF PLANS
AND CONSTRUCTION FOR
SEWAGE DISPOSAL SYSTEMS FOR
OTHER THAN SINGLE-FAMILY RESIDENCES
APPENDIX C
REQUIREMENTS OF DEPARTMENT OF HEALTH SERVICES
AND RESPONSIBILITIES OF LICENSED DESIGN PROFESSIONALS
IN INSPECTING SEWAGE TREATMENT WORKS OR
COLLECTION SYSTEMS
December 1, 2009
Linda Mermelstein, M.D., M.P.H.
Acting Commissioner of Health Services
Vito Minei, P.E.
Director of Environmental Quality
12/1/09
TABLE OF CONTENTS
Section
Page
C1.
GENERAL .....................................................................................................................................1
C2.
C3.
C4.
LIST OF FORMS
FORM C1 AUTHORIZATION OF LICENSED PROFESSIONAL ENGINEER OR
REGISTERED ARCHITECT........................................................................................................2
FORM C2 CERTIFICATION OF CONSTRUCTED WORKS BY DESIGN PROFESSIONAL ..........3
Appendix C
Page i
12/1/09
APPENDIX C
REQUIREMENTS OF DEPARTMENT OF HEALTH SERVICES
AND RESPONSIBILITIES OF LICENSED DESIGN PROFESSIONALS
IN INSPECTING SEWAGE TREATMENT WORKS
OR COLLECTION SYSTEMS
C1.
GENERAL
The Suffolk County Department of Health Services requires that installation of sewage treatment works
and collection systems be certified by a licensed professional engineer or registered architect as
compliance of construction with Department standards.
The Suffolk County Department of Health Services prefers that the duties of construction inspection be
carried out by the architect or engineer responsible for designing the project. However, an independent
licensed professional engineer or registered architect is acceptable to the Department provided that the
design professional and the owner authorize the choice. In order to assure impartiality, the inspecting
personnel must have no financial or other vested interest in the construction contractor or installer. In
cases where the design professional acts as contractor, the inspecting personnel must be independent.
This appendix contains samples of certificates and log sheets to be used in the certification procedure. All
are to be submitted to the Department at time of application for final approval except for Authorization of
Design Professional which must be submitted prior to commencing construction. Certain larger projects
require pre-job meetings prior to commencing construction. Authorization may be submitted to the
Department at this meeting.
Appendix C
Page 1 of 6
12/1/09
collection system
SECT.
BLOCK
LOT
employed
authorized
retained
Name
Name of Firm
a licensed Professional Engineer
a registered Architect
to perform controlled inspection work for the above specified installation.
Signature
(owner or officer of corporation)
Print Name
Title
Date
Address
Statement of L.P.E. or R.A. preparing plans (if inspecting engineer is different):
Name of licensed P.E. or R.A. preparing plans
Address
I hereby certify that
the L.P.E .
the R.A.
(name)
engaged by the owner to perform the controlled inspection of the above specified installation is acceptable to me.
Signature
Date
(Affix seal)
Date
(Affix seal)
Appendix C
Page 2 of 6
12/1/09
SECT.
BLOCK
LOT
Project Name
Applicants Name
ITEMS BEING CERTIFIED (Check all that apply)
Sewer Lines and Sewage Collection System Components
Retaining Walls (approved as part of the sewage disposal system)
Sewage Pump Station / Valve Chamber
Subsurface Sewage Disposal System
Sewage Treatment Plant
Water Supply System
Abandonment of Preexisting Sewage Disposal System and /or Water Supply
Other
As the Licensed Professional Engineer or Architect I, or qualified personnel under my direct supervision, have
inspected the work specified above in accordance with the New York State Education Law, and (check one)
I hereby certify that all material and work conforms to approved plans and permit conditions, and with
guidelines issued pursuant to the Suffolk County Sanitary Code. (Attach any inspection or test reports
required by the Department.)
I hereby certify that all material and work conforms to approved plans and permit conditions, and with
guidelines issued pursuant to the Suffolk County Sanitary Code, except as described in my attached
addendum. (Also attach any inspection or test reports required by the Department.)
Engineers / Architects signature
Print Name
Date
(Affix seal)
License Number
This certification shall not be used in lieu of inspections required by personnel of the Department
Appendix C
Page 3 of 6
C2.
12/1/09
The inspecting personnel are responsible to complete inspection of all aspects of a sewage treatment plant
and or pump stations. The following schedule outlines the major components to be inspected. The
inspector shall submit a log with his certification indicating that each component or segment was
satisfactorily completed, date, time and length of each inspection, and initials of the person performing the
inspection.
1.
Concrete forms and reinforcing steel shall be inspected for proper placement.
2.
All placement of concrete shall be inspected. Six test cylinders shall be taken for each 50
cu. yds. of concrete required. Weather conditions and temperature shall be recorded during
placement of concrete. 1, 4 Detention time of concrete in each truck shall be recorded as
well.
3.
4.
a)
b)
c)
Emergency Generator
d)
Inspection and leak testing of all tanks to assure that tanks are installed and sealed in
accordance with manufacturers specifications.1, 3
b)
5.
Infiltration tests for tanks and wet well situated below groundwater level.
6.
7.
8.
9.
10.
Proper backfilling.1, 2
Appendix C
Page 4 of 6
11.
Final grading.
12.
Proper fencing.
13.
14.
15.
12/1/09
Should any unforeseen field conditions necessitate changes on the plans and/or specifications, the
inspecting personnel shall notify the Department immediately.
1
2
3
4
C3.
Requires full time presence of inspecting design professional or qualified personnel under a design professionals supervision during
installation.
Sieve analysis to assure that sand and gravel is clean and conforms to specifications.
Leak testing of all watertight chambers. See Appendix B for leak test requirements for watertight chambers.
Requires call-in to Department 48 hr. prior to commencement of installation.
The inspecting personnel are responsible to complete inspection of all aspects of a collection system. The
following schedule outlines the major components to be inspected. The inspector shall submit a log with
his certification indicating that each component or segment was satisfactorily completed, date, time and
length of each inspection, and initials of the person performing the inspection.
1.
All sewer piping (installation and grade). Inspection of piping shall assure that all pipe is of
proper size, type and class; that construction is according to specifications and installed
properly; that pipe is run at proper slope and alignment; and that all joints are properly
constructed; that the invert elevations of pipes at all crossings (sewer-water, sewer-drainage
and water-drainage) are maintained in accordance with plans approved for construction.
2.
3.
4.
5.
House connections.
6.
Should any unforeseen field conditions necessitate changes on the plans and/or specifications, the
inspecting personnel shall notify the Department immediately.
1
Requires full time presence of inspecting design professional or qualified personnel under a design professionals supervision during
installation.
Requires call-in to Department 48 hr. prior to commencement of installation.
Appendix C
Page 5 of 6
C4.
12/1/09
In accordance with Article 2 and Article 6 of the Suffolk County Sanitary Code, the foregoing are the
standards of the Suffolk County Department of Health Services for Appendix C of the Standards for
Approval of Plans and Construction for Sewage Disposal Systems for Other Than Single-family
Residences. These Standards are adopted December 1, 2009 and are effective for applications received
after January 1, 2010.
Appendix C
Page 6 of 6