Você está na página 1de 30

Monday,

October 22, 2007

Part III

Department of
Energy
10 CFR Part 430
Energy Conservation Program for
Consumer Products: Test Procedure for
Residential Central Air Conditioners and
Heat Pumps; Final Rule
pwalker on PROD1PC71 with RULES3

VerDate Aug<31>2005 17:58 Oct 19, 2007 Jkt 214001 PO 00000 Frm 00001 Fmt 4717 Sfmt 4717 E:\FR\FM\22OCR3.SGM 22OCR3
59906 Federal Register / Vol. 72, No. 203 / Monday, October 22, 2007 / Rules and Regulations

DEPARTMENT OF ENERGY B. Background subject to this Program (covered


C. Summary of the Test Procedure products) include central air
10 CFR Part 430 Revisions conditioners and heat pumps, the
II. Discussion of Comments
subject of today’s final rule.
[Docket No. EE–RM/TP–02–002] A. Frost Accumulation Test Duration
B. Multiple-Split Systems Under EPCA, the Program consists of
RIN 1904–AB55 C. Defining ‘‘Repeatable’’ for Cyclic Tests three parts: Testing, labeling, and the
D. Outdoor Air Test Conditions for Units Federal energy conservation standards.
Energy Conservation Program for Having a Two-Capacity Compressor DOE, in consultation with the National
Consumer Products: Test Procedure E. Air Volume Rate Less Than Institute of Standards and Technology
for Residential Central Air Manufacturer’s Specified Value (NIST), is authorized to establish or
Conditioners and Heat Pumps F. Updating References to Industry amend test procedures as appropriate
Standards
AGENCY: Department of Energy. G. Maximum and Minimum Speed Values
for each of the covered products. (42
for Calculating NQ and NE U.S.C. 6293) The purpose of these test
ACTION: Final rule. procedures is to measure energy
H. Using the Default or Tested Value of
SUMMARY: The Department of Energy Cyclic-Degradation Coefficient efficiency, energy use, or estimated
(DOE) is amending its test procedure for I. Guidance on the Inclusion of Pre- annual operating cost of a covered
Production Units in the Sample product during a representative, average
residential central air conditioners and Population
heat pumps. This final rule implements use cycle or period of use. The test
J. Clarification of the Sample Population procedure must not be unduly
test procedure changes for small-duct, Used To Validate the Rated Seasonal
high-velocity systems, two-capacity Energy Efficiency Ratio and Heating
burdensome to conduct. (42 U.S.C.
units, and updates references to the Seasonal Performance Factor of Heat 6293(b)(3))
current American Society of Heating, Pumps If a test procedure is amended, DOE
Refrigerating, and Air-Conditioning K. Clarification of the Definition of a is required to determine to what extent,
Engineers (ASHRAE) standards. Today’s ‘‘Highest-Sales-Volume Combination’’ if any, the proposed new test procedure
L. Upper Limit on the Difference Between would alter the measured energy
rule also clarifies issues associated with Calculated and Tested Seasonal Energy
sampling tested systems and rating efficiency of any covered product as
Efficiency Ratio and Heating Seasonal
untested split-system combinations. determined under the existing test
Performance Factor Values
M. Clarification of the Published Ratings procedure. (42 U.S.C. 6293(e)(1)) If DOE
DATES: This rule is effective April 21,
for Untested Split-System Combinations determines that an amended test
2008. Incorporation by reference of
N. Ratings That Are Based on Using a procedure would alter the measured
certain publications in the final rule is
Particular Furnace or Ducted Air Mover energy efficiency of a covered product,
approved by the Director of the Federal
O. Revisions to the Definition of ‘‘Coil DOE is required to amend the applicable
Register as of April 21, 2008. Family’’ energy conservation standard with
ADDRESSES: You may review copies of III. Summary of Other Additions, Changes, respect to such test procedure. In
all materials related to this rulemaking and Corrections to the Department of
determining any such amended energy
at the U.S. Department of Energy, Energy Residential Central Air
Conditioner and Heat Pump Test conservation standard, DOE is required
Forrestal Building, Room 1J–018 to measure the energy efficiency or
Procedure
(Resource Room of the Building energy use of a representative sample of
IV. Effect of Test Procedure Revisions on
Technologies Program), 1000 Compliance With Standards covered products that minimally
Independence Avenue, SW., V. Procedural Requirements comply with the existing standard. The
Washington, DC, (202) 586–9127, A. Review Under Executive Order 12866 average efficiency or energy use of this
between 9 a.m. and 4 p.m., Monday B. Review Under the Regulatory Flexibility representative sample, tested using the
through Friday, except Federal holidays. Act
amended test procedure, constitutes the
Please call Ms. Brenda Edwards-Jones at C. Review Under the Paperwork Reduction
Act of 1995 amended standard. (42 U.S.C.
the above telephone number for 6293(e)(2)) DOE has determined that
additional information regarding D. Review Under the National
Environmental Policy Act of 1969 today’s amended test procedure does
visiting the Resource Room. Please note: E. Review Under Executive Order 13132 not alter the measured efficiency or
DOE’s Freedom of Information Reading F. Review Under Executive Order 12988 measured energy use of minimally
Room (formerly Room 1E–190 at the G. Review Under the Unfunded Mandates compliant central air conditioners and
Forrestal Building) is no longer housing Reform Act of 1995 heat pumps.
rulemaking materials. H. Review Under the Treasury and General
Beginning 180 days after a test
FOR FURTHER INFORMATION CONTACT: Government Appropriations Act, 1999
I. Review Under Executive Order 12630 procedure for a covered product is
Michael G. Raymond, U.S. Department prescribed, no manufacturer,
J. Review Under the Treasury and General
of Energy, Office of Energy Efficiency Government Appropriations Act, 2001 distributor, retailer, or private labeler
and Renewable Energy, EE–2J, 1000 K. Review Under Executive Order 13211 may make representations with respect
Independence Avenue, SW., L. Review Under Section 32 of the Federal to the energy use, efficiency, or cost of
Washington, DC 20585–0121, (202) 586– Energy Administration Act of 1974 energy consumed by such product,
9611, e-mail: M. Congressional Notification except as reflected in tests conducted
michael.raymond@ee.doe.gov; or VI. Approval of the Office of the Secretary according to the DOE procedure. (42
Francine Pinto, Esq., U.S. Department of I. Introduction U.S.C. 6293(c)(2)) Any manufacturer,
Energy, Office of the General Counsel, distributor, retailer, or private labeler
GC–72, 1000 Independence Avenue, A. Authority may petition the Secretary of Energy for
SW., Washington, DC 20585–0121, (202) Part B of Title III of the Energy Policy an extension of not more than 180 days
pwalker on PROD1PC71 with RULES3

586–9507, e-mail: and Conservation Act (EPCA) to test and make representations in
Francine.Pinto@hq.doe.gov. established the Energy Conservation accordance with the amended DOE test
SUPPLEMENTARY INFORMATION: Program for Consumer Products Other procedure. (42 U.S.C. 6293(c)(3)) In
I. Introduction Than Automobiles (Program). (42 U.S.C. addition, all existing waivers
A. Authority 6291 et seq.) The products currently concerning residential multi-split

VerDate Aug<31>2005 17:58 Oct 19, 2007 Jkt 214001 PO 00000 Frm 00002 Fmt 4701 Sfmt 4700 E:\FR\FM\22OCR3.SGM 22OCR3
Federal Register / Vol. 72, No. 203 / Monday, October 22, 2007 / Rules and Regulations 59907

systems terminate on the effective date capacity/stage and at an outdoor Energy-Efficient Economy (ACEEE),
of today’s final rule. temperature of 35 degrees Fahrenheit Sanyo Fisher Service Corporation
(°F); (5) implementing modifications (Sanyo), Lennox International (Lennox),
B. Background
and additions that specifically address and the China WTO/TBT National
A final rule published on October 11, elements unique to testing and rating Notification and Enquiry Center (China).
2005, updated and completely re- modulating multi-split systems; (6) The comments and the DOE response to
organized the DOE residential central allowing indoor capacities used in them are discussed below. References to
air conditioner and heat pump test calculating Seasonal Energy Efficiency section numbers within this document
procedure. 70 FR 59122. During this Ratio (SEER) and Heating Seasonal refer to the section numbers of
prior rulemaking, a few issues were Performance Factor (HSPF) to be Appendix M to Subpart B of 10 CFR
identified too late in the process to corrected for duct losses; (7) defining part 430–Uniform Test Method for
allow them due consideration. DOE the term ‘‘standard air;’’ (8) changing the Measuring the Energy Consumption of
investigated these issues and considered outdoor temperature conditions used for Central Air Conditioners and Heat
additional topics that could further one of the low-capacity, steady-state, Pumps (Appendix M).
improve the testing and rating process. cooling mode tests on a two-capacity
As a result of these efforts, DOE issued A. Frost Accumulation Test Duration
unit; (9) renaming ‘‘Cooling and Heating
a Notice of Proposed Rulemaking on Certified Air Volume Rates’’ to ‘‘Full- DOE proposed shortening the
July 20, 2006 (hereafter referred to as the Load Air Volume Rates;’’ (10) modifying maximum test interval of a Frost
July 2006 proposed rule). 71 FR 41320. the criterion for using an air volume rate Accumulation Test from 12 hours to 6
Although the majority of the proposed less than the manufacturer’s specified hours when testing a two-capacity heat
changes pertained to the test procedure value; (11) updating the references to pump at low capacity. ARI supported
set forth in appendix M to subpart B of current versions of the Air-Conditioning DOE’s proposal to lessen the test
Title 10, Code of Federal Regulations, and Refrigeration Institute (ARI) and burden, but recommended that the
Part 430 (10 CFR part 430), DOE also ASHRAE standards; (12) adding maximum duration be further shortened
proposed revisions to sections of language to better explain the SEER and to 3 hours. (ARI, No. 21 at p. 2)1 ARI
subparts B and F of 10 CFR part 430 that HSPF calculation steps for variable- stated that ‘‘preliminary testing done by
concern the sampling of tested units and speed equipment; and (13) adding text manufacturers shows a variation in
the ratings of untested split-system to clarify the provision to use the HSPF of less than one tenth 2 when the
combinations. 10 CFR 430.24 and default value of the cyclic-degradation test is reduced from 12 to 3 hours.’’
430.62. DOE held a public meeting on coefficient if it is lower than the tested (ARI, Id.) In a follow-up
the July 2006 proposed rule on August value. communication, ARI clarified that its 3-
23, 2006. Today’s final rule also amends hour recommendation applies to all
On October 10, 2006, DOE published sections 430.2, 430.24 and 430.62 of 10 Frost Accumulation Tests, not just the
a Federal Register notice correcting two CFR part 430, as follows: (1) It expands test at low-capacity. (ARI, No. 25 at p.
inadvertent omissions in the July 2006 the options for meeting the data 2) ARI provided a table showing the
proposed rule. 71 FR 59410. These submission requirements when percentage of the total interval allocated
omissions contained the regulatory verifying an alternative rating method to defrosting for cycles lasting 6, 7, 8, 9,
language governing the criterion for (ARM); (2) it clarifies the sample and 10 minutes; percentages were
using an air volume rate that is less than population to be used to validate the calculated for complete (frost + defrost)
the manufacturer’s specified value: One rated SEER and rated HSPF of a heat intervals ranging from 1 hour to 12
case covered air conditioners and heat pump; (3) it clarifies the definition of a hours. As an example, for tests lasting
pumps, the other case covered heating- ‘‘highest-sales-volume combination’’ 12, 6, and 3 hours, the percentages of
only heat pumps. This change was (HSVC); (4) it clarifies DOE’s role in time spent defrosting are 1.1, 2.2, and
described in the preamble of the July verifying ratings for untested split 4.4 percent, respectively, if the defrost
2006 proposed rule, but was not system combinations; (5) it clarifies how lasts 8 minutes in all cases. (ARI, No. 25
included in the regulatory language. In to apply the ARM to obtain published at p. 3) In addition to recommending
addition to publishing the corrected ratings for untested, split-system that any change be applied to all Frost
regulatory language in the Federal combinations; (6) it adds the Accumulation Tests, Nordyne and
Register, the omitted regulatory requirement that ratings for an air Carrier recommended manufacturers be
language was distributed at the August conditioner or heat pump tested with a given the option of using either the
23, 2006, public meeting. furnace or similar ducted air mover procedure specified in ASHRAE
include the model number of the air Standard 37 (which uses a maximum
C. Summary of the Test Procedure test interval of 3 hours) or the algorithm
mover as part of the overall equipment
Revisions specified in the DOE test procedure.
model number; (7) it clarifies the
The revisions adopted in today’s final responsibilities of private labelers; (8) it (Nordyne, No. 19 at p. 2; Carrier, No. 17
rule include the following changes to adds the statutory definition of ‘‘private
appendix M of Subpart B of 10 CFR part labeler;’’ and (9) it adds definitions for 1 A notation in the form ‘‘ARI, No.21 at p. 2’’

430: (1) Adding new testing identifies a written comment the Department has
terms, including ‘‘indoor unit’’, received and has included in the docket of this
requirements for small-duct, high- ‘‘outdoor unit’’, and ‘‘ARM/simulation rulemaking. This particular notation refers to a
velocity systems; (2) reinstating the adjustment factor.’’ comment (1) by the Air-Conditioning and
optional testing to determine the cyclic- Refrigeration Institute (ARI), (2) in document
degradation coefficient (CD) of a two- II. Discussion of Comments number 21 in the docket of this rulemaking
(maintained in the Resource Room of the Building
capacity unit when cycling on and off In addition to the comments received Technologies Program), and (3) appearing on page
at high capacity; (3) shortening the at the August 23, 2006, public meeting, 2 of document number 21. Likewise, ‘‘Public
pwalker on PROD1PC71 with RULES3

maximum duration of the Frost DOE received written comments to the Hearing Tr., p. 178,’’ for example, would refer to
Accumulation Tests; (4) allowing the July, 2006 proposed rule from ARI, page 178 of the transcript of the ‘‘Public Meeting
on Test Procedures for Central Air Conditioners’’
use of default equations to approximate Nordyne, Mitsubishi, Fujitsu General held in Washington, DC, August 23, 2006.
the capacity and power of a two- Limited (Fujitsu), Carrier Corporation 2 This means an absolute variation in HSPF of 0.1,

capacity unit when operating at low- (Carrier), the American Council for an such as between 8.1 and 8.2.

VerDate Aug<31>2005 17:58 Oct 19, 2007 Jkt 214001 PO 00000 Frm 00003 Fmt 4701 Sfmt 4700 E:\FR\FM\22OCR3.SGM 22OCR3
59908 Federal Register / Vol. 72, No. 203 / Monday, October 22, 2007 / Rules and Regulations

at p. 2) In summary, the stakeholders B. Multiple-Split Systems ARI 1230. ARI, Sanyo, Fujitsu,
recommended applying changes to all DOE received comments on issues Mitsubishi, and Daikin AC (Americas),
Frost Accumulation Tests (not just to related to the testing and rating of Inc. (Daikin) urged DOE to adopt Draft
the one low-capacity test, as proposed), multiple-split air-conditioning systems ARI Standard 1230, ‘‘Performance
reducing the maximum duration to 3 (multi-split systems), including: (1) Rating of Multi-Split Air-Conditioning
hours instead of 6 hours, and adding an Rating multi-split systems based on and Heat Pump Equipment’’ in lieu of
alternative test method. SEER (if they compete primarily with the proposed rule. (ARI, No. 21 at p. 3;
DOE believes that if all three changes ducted central air conditioners), or Sanyo, No. 15 at pp. 2–3; Fujitsu, No.
were adopted, the HSPF ratings of heat rating them based on EER (if they 13 at p. 3; Mitsubishi, No. 20 at pp. 4–
pumps would be changed, since the compete with room air conditioners) 5; Public Hearing Tr., pp. 153–154)
ASHRAE Standard 37 ‘‘T’’ Test (SEER or EER); (2) adopting a separate China recommends that DOE not cover
Procedure may terminate after 0, 1, 2, or multi-split systems within the
test procedure for multi-split systems,
3 complete cycles whereas the DOE residential central air conditioner and
such as Draft ARI Standard 1230 (ARI
Frost Accumulation Test is either 0 or heat pump test procedure until all the
1230); (3) allowing one or more indoor
1 complete cycle. The different cycles in technical issues have been resolved.
coils to turn off during any test, if
the ASHRAE and DOE test methods can (China, No. 14 at p. 1) Copeland
representative of normal operation
yield different average heating capacity recommends that DOE review and
(Coils active during test); (4) allowing
and power consumption results at the consider the approaches being taken by
the manufacturer to specify the
DOE-specified 35 °F dry-bulb/33 °F wet- China and the European Union on how
compressor speed used during the
bulb outdoor test conditions which to test and rate multi-split systems.
minimum-speed, intermediate-speed
would affect the HSPF rating. As for (Public Hearing Tr., p. 64) Nordyne
shortening the maximum test time to 3 and maximum-speed tests (Compressor
speed); (5) extending multi-split system supports the changes proposed in the
hours, such a change may benefit heat July 2006 proposed rule to cover multi-
pumps (i.e., give a higher average test procedure changes to one-to-one
ducted systems (One-to-one split systems as an interim solution, but
heating capacity) that initiate a defrost states that further study is needed for a
of the outdoor coils between 3 and 6 applicability); and (6) adding the term
‘‘tested combination’’ within 10 CFR long term solution. (Nordyne, No. 19 at
hours after the start of the test. In such p. 2) Lennox, on the other hand,
cases, the heat pump’s average heating 430.2 for determining the combination
of indoor units to be tested when testing believes that multi-split systems should
capacity will not account for the energy be rated using the current test procedure
used for defrosting. By not accounting a multi-split outdoor unit, and the
appropriate rating of the tested for central air conditioners and central
for the defrost energy, the shorter test air conditioning heat pumps. (Lennox,
time would overstate the heating combination (Tested combination).
SEER or EER. DOE received several No. 22 at p. 2) Sanyo and Fujitsu point
capacity and HSPF. Thus, DOE will not out that the test procedure does not
reduce the maximum test duration by comments on whether multi-split
systems compete primarily with ducted address units that can simultaneously
the additional 3 hours or add the cool and heat; the test procedure does
ASHRAE Standard 37 procedure as an residential central air conditioners and
heat pumps and as such, should be not specify how many indoor units are
alternate test method as part of this final turned off during a given test; and
rule. rated based on SEER and HSPF, or if
they compete with room air doubts whether the current DOE tests
DOE agrees with comments
conditioners and should be rated in for variable-speed systems can
recommending the same maximum limit
terms of EER and COP. Trane argues approximate the unit’s ‘‘performance
for all Frost Accumulation Tests. The
that residential size multi-split systems map.’’ 3 (Sanyo, No. 15 at pp. 2–3;
low-capacity Frost Accumulation Test is
projected to be the most likely of the 35 compete for the same markets as ducted Fujitsu, No. 13 at pp. 2–3; Public
°F tests to approach the proposed 6-hour residential central systems: both serve Hearing Tr., pp. 94–95, 110)
limit, followed by the required Frost multiple rooms, one ducts air whereas DOE is not convinced that residential-
Accumulation Test at the intermediate the second ‘‘ducts’’ refrigerant. (Public size multi-split systems require a
speed when testing a variable-speed Hearing Tr., p. 178) Carrier and ACEEE separate test procedure from the current
heat pump. All other Frost support rating conventional central air test procedure found in Appendix M.
Accumulation Tests are more likely to conditioners and heat pumps and multi- While it is true that the current test
build frost and are likely to result in the split systems using the same procedure fails to account for the energy
unit defrosting in less time than it descriptors. (Carrier, No. 17 at p. 1 and savings derived from a simultaneous
would at the intermediate speed. Thus, ACEEE, No. 16 at p. 3) According to cooling and heating mode, the current
triggering the 6-hour limit is less likely Mitsubishi, ‘‘ductless split-systems, test procedure is adaptable and DOE
when applied to these other cases. including ductless multi-split systems, believes the tests for variable-speed
Finally, DOE concludes that 6 hours are used for room or spot cooling systems in Appendix M offer a
offers a sufficiently long duration for applications while the rest of the USE reasonable starting point for producing
evaluating performance in all cases. As [unitary small equipment] equipment energy efficiency and energy use
noted in the July 2006 proposed rule, if (i.e., central systems) is applied in a estimates. Once data become available
a heat pump has not defrosted in 6 ducted environment for multiple rooms that provides insight as to the energy
hours, it is either not building frost or or whole houses.’’ (Mitsubishi, No. 20 at use and efficiency benefits of
is completely frosted and probably has p. 3) DOE believes residential-size simultaneous cooling and heating, and
been so for more than half of the multi-split systems compete with alternative or additional tests to
interval. In both cases, the benefits from ducted central systems and that the estimate these benefits are formulated,
continuing to run the test past 6 hours consumer will be best served if multi- DOE will then consider further
pwalker on PROD1PC71 with RULES3

are minimal. Therefore, DOE reduces split systems can be compared with
3 Performance map refers to a plot that shows the
the maximum duration of all Frost central air conditioners and central air-
effect of compressor speed, number of indoor unit
Accumulation Tests from 12 hours to 6 conditioning heat pumps. Therefore, turned on versus off, and outdoor temperature
hours. This change appears in section DOE concludes that SEER and HSPF are conditions on the unit’s space conditioning
3.9 of Appendix M. better descriptors than EER and COP. capacity and power consumption.

VerDate Aug<31>2005 18:36 Oct 19, 2007 Jkt 214001 PO 00000 Frm 00004 Fmt 4701 Sfmt 4700 E:\FR\FM\22OCR3.SGM 22OCR3
Federal Register / Vol. 72, No. 203 / Monday, October 22, 2007 / Rules and Regulations 59909

amendments to the test procedure. To evaluate the effect of such an or nominal rated speed because
Accordingly, DOE is not adopting a new algorithm, Fujitsu conducted performance at that compressor speed is
test procedure and energy efficiency and simulations in which it modeled the used in sizing and selling the product.
energy use ratings will continue to be performance of a unit if operated at the ARI and Sanyo supported DOE’s
based on the test procedure found in DOE test procedure cooling mode proposal to allow the manufacturer to
Appendix M. conditions. Fujitsu considered cases specify the compressor speed used for
Regarding the stakeholder where the number of indoor units the minimum-speed and intermediate-
recommendation to adopt draft ARI turned on for the two minimum speed speed tests. (ARI, No. 21 at p. 2; Sanyo,
Standard 1230, the current draft (as and one intermediate speed tests No. 15 at p. 2) Sanyo and ARI,
distributed in June 2007), is less changed. Fujitsu reported results for moreover, both believe that test
complete for residential multi-split three cases: the first case, all four indoor laboratories must accept the task of
systems than the DOE test procedure in units are on for all tests; the second providing test facilities that can
today’s final rule. For example, ARI case, three indoor units are on for the maintain steady test room conditions
Standard 1230 (June 2007 draft) lacks intermediate speed test and two indoor and accurately measure capacity at very
information on how to conduct units are on for the minimum speed low loads. (ARI, No. 21 on pp. 2–3;
intermediate speed tests, whether any tests; and the third case, two indoor Sanyo, No. 15 on p. 2)
indoor units are to be turned off for part- units are on for the intermediate-speed Regarding the maximum and
load tests, how to interpolate EER and test and one indoor unit is on for the minimum compressor speed issue, DOE
COP in the intermediate speed range, minimum speed tests. (Fujitsu, No. 13 at reviewed test procedure waivers
and generally how to calculate SEER pp. 1–2) Using the simulated data, processed in the 1980’s, and the 1988
and HSPF. Furthermore, ARI has not Fujitsu reported that the first case yields test procedure rulemaking that first
finalized ARI Standard 1230 and, as the highest SEER. In comparison, added coverage for air conditioners and
such it cannot be incorporated by Fujitsu reported that the SEER drops by heat pumps having a variable-speed
reference since it could be amended 4.7 percent for the second case and by compressor. (53 FR 8304, March 14,
prior to being adopted in final form. 11.6 percent for the third case. Fujitsu 1988) None of these actions explicitly
Therefore, for the reasons discussed concluded that the number of operating defined maximum and minimum
above, DOE is not adopting ARI indoor units may have a great impact on compressor speed. Instead, the
Standard 1230 (June 2007 draft) in the result, and that the operating ranges manufacturer was allowed to define
today’s final rule. in Table 1 were not appropriate. these speeds for its particular units. The
As for considering changes that are evolution to include maximum and
modeled on the approaches taken in TABLE 1.—APPROACH TO REGULATING minimum compressor speeds among
China and the European Union, DOE those elements that are ‘‘conducted in
THE NUMBER OF ACTIVE INDOOR
sees their potential use as limited given accordance with the manufacturer’s
the current EPCA requirement to UNITS instructions’’ occurred because of the
calculate annual measures of energy (Example Case of a Multi-Split System Having test laboratory’s need for a mechanism
consumption. The European Union 4 Identical Indoor Units) to override the unit’s normal controls,
HVAC trade association, Eurovent, lists so that the compressor can be forced to
Number of
ratings for residential-size multi-splits Percentage output relative to operating operate at fixed speeds for the DOE-
that are based on full load EER and COP full load capacity specified lab tests. As part of today’s
indoor units
and their European SEER (ESEER) is final rule, DOE considered adopting a
thus far limited to liquid chilling 75% to 100% ........................ 4 specific definition for maximum speed
packages, not unitary air conditioners 50% to 75% .......................... 3 and requiring additional lab verification
(i.e., residential central air conditioners 25% to 50% .......................... 2 tests, but has decided against it because
and central air conditioning heat 0% to 25% ............................ 1 there is no compelling technical
pumps). The ESEER is actually a (DOE, No. 12.3 at p. 12) argument for doing so. The current
variation of ARI Standard 340/360’s approach effectively allows the
IPLV, which is used to quantify the part- DOE recognizes that when field manufacturer to de-rate the unit’s
load performance of larger, non- installed, a multi-split system will often maximum capacity in order to raise its
residential systems. An IPLV equivalent operate with one or more of its indoor performance descriptor. As long as that
is also used in China. Neither units turned off. In an effort to have the de-rated capacity is used for sizing the
international resource explicitly DOE test procedure capture this part- particular multi-split combination, then
addresses the number of indoor units to load operating mechanism, today’s final the practice is acceptable. DOE,
be turned off during a given part-load rule requires that at least one indoor however, does not agree with
test; such information would be unit must be turned off for tests substituting ‘‘nominal’’ or ‘‘rated’’
necessary in order to get an accurate conducted at minimum compressor compressor speed for ‘‘maximum’’
measure of equipment efficiency for speed. In addition, the manufacturer compressor speed, as that will not allow
comparison purposes. may elect to have one or more indoor for test results that can be used to
Coils active during test. Concerning units turned off for tests conducted at generate a performance map
the issue of whether one or more indoor the intermediate compressor speed. In representing how particular multi-split
units should be turned off during any all cases, the manufacturer specifies the combinations will operate in the field.
given test, Daikin commented that you particular indoor unit(s) that is turned The DOE test procedure will continue
cannot rely on the unit’s controls to off. to require variable-speed systems to be
make the decision when operated in a Compressor speed. ARI, Sanyo, tested at their minimum compressor
laboratory environment. (Public Hearing Fujitsu, and Mitsubishi opposed DOE’s speed. Manufacturers will be relied
pwalker on PROD1PC71 with RULES3

Tr., p. 62) Given this, DOE offered, at proposed definition of maximum upon to provide the independent testing
the public meeting, an algorithm for compressor speed. (ARI, No. 21 at p. 2; laboratory with a means for conducting
specifying the number of indoor units Sanyo, No. 15 at p. 2; Fujitsu, No. 13 at tests at this speed. Minimum speed may
that are turned on for a given test. This p. 2; Mitsubishi, No. 20 at p. 4) They not be the absolute minimum speed at
algorithm is shown in Table 1, below. recommended using the rated capacity which the compressor can operate, but

VerDate Aug<31>2005 18:36 Oct 19, 2007 Jkt 214001 PO 00000 Frm 00005 Fmt 4701 Sfmt 4700 E:\FR\FM\22OCR3.SGM 22OCR3
59910 Federal Register / Vol. 72, No. 203 / Monday, October 22, 2007 / Rules and Regulations

it is expected to be a speed below which intermediate-speed tests and then use that matches the outdoor unit than it is
the compressor would rarely operate. linear fits for calculating COP and EER to restrict selection to units from the
DOE concurs with Sanyo and ARI and within the intermediate-speed operating highest sales model family, for cases
expects test laboratories to measure range. Adopting these two changes for where both criteria cannot be met. As
performance over the wide modulation variable-speed one-to-one units would for Copeland’s statement that the
range that is characteristic of multi- create a second compliance path that definition includes references to the
splits. Thus, to the issue of what would likely cause different SEER and capacity of the outdoor unit and the
compressor speed to use when HSPF ratings than the current test cumulative capacities of the indoor
conducting minimum speed and procedure. Therefore, in adopting these units even though no prescriptions are
maximum speed tests, DOE is changes, DOE is not extending them to given to evaluate these capacities, DOE
maintaining the current test procedure variable-speed one-to-one units. agrees but nonetheless will allow their
language in sections 3.2.4 and 3.6.4 of Although DOE expects the current test use in this particular definition.
Appendix M. procedure to yield the higher ratings for Manufacturers are able to estimate the
DOE adopts the July 2006 proposed one-to-one units, it will rely on the rated capacities of the separate
change of allowing the manufacturer to waiver process if any manufacturer components without conducting the
specify the compressor speed used for seeks to adopt these two multi-split test rigorous testing associated with ARI
the cooling and heating intermediate procedure changes for use in rating Standards 410 (‘‘Forced-Circulation Air-
speed/capacity tests. This change variable-speed one-to-one units. Cooling and Air-Heating Coils’’) and 540
provides the manufacturer an Tested combination. On the issue of (‘‘Performance Rating of Positive
opportunity to select and verify the the ‘‘tested combination’’—the Displacement Refrigerant Compressors
peak-efficiency of the unit being tested. equipment configuration that can be and Compressor Units’’) on each new
Coupled with this change, and as also tested in the laboratory and thereby model. Finally, the last element of the
proposed in the July 2006 notice, provide a common basis for proposed definition of ‘‘tested
steady-state efficiency (EER and COP) comparison—Sanyo, Fujitsu, combination’’ will be changed from ‘‘all
over the intermediate-speed range shall Mitsubishi, and ARI recommended have the same external static pressure’’
be calculated using piece-wise linear deleting the requirement that the to ‘‘all be subject to the same minimum
fits: a line connecting the minimum- selected indoor units ‘‘represent the external static pressure requirement
and intermediate-speed balance points highest-sales-volume type models’’ and (i.e., 0 inches of water column for non-
and a line connecting the intermediate- replacing it with ‘‘represent the highest ducted, see Table 2 in Appendix M for
and maximum-speed balance points. sales model family.’’ (Sanyo, No. 15 at ducted indoor units) while being
One-to-one applicability. Carrier p. 3; Fujitsu, No. 13 at p. 4; Mitsubishi, configurable to produce the same static
noted the need for transparency in No. 20 at pp. 5 and 6; ARI, No. 21 at pressure at the exit of each outlet
testing and manufacturer test results so p. 6) In addition, Sanyo, Fujitsu, plenum when manifolded as per section
that interested parties can verify the Mitsubishi, and ARI recommended that 2.4.1 of Appendix M.’’ This additional
performance claims without having to provisions be made in the event that information is provided so that the test
consult the manufacturer. (Carrier, No. five of the largest model indoor coils laboratory may conduct the lab testing
17 at p. 2) Trane and ARI pointed out from the selected model family cannot by manifolding the outlets of all the
that any steps introduced to facilitate provide a cumulative indoor capacity indoor units together and using one
testing and rating modulating multi- that is more than 95 percent of the airflow measuring apparatus to
split systems should also be allowed for outdoor unit’s nominal capacity. As to determine the cumulative air volume
modulating one-to-one ducted systems references in the proposed definition rate.
to promote comparability. (Public that a manufacturer will know the At the August 23, 2006, public
Hearing Tr., pp. 87 and 118; ARI, No. 21 capacity of each indoor unit and each meeting, DOE restated its proposed
at p. 3) With respect to Carrier’s outdoor unit, Copeland Corporation interim solution for assigning SEER and
comment, variable-speed systems do not (Copeland) questioned how the HSPF ratings for untested multi-split
lend themselves to being tested by a manufacturer would determine combinations. This interim solution—to
third party who does not have the component capacities. (Public Hearing assign the rating measured for the tested
cooperation of the outdoor unit Tr., pp. 217–221) Finally, with regard to combination to every other combination
manufacturer. Third-party certification the proposal that all of the tested indoor using the same outdoor unit—was
programs thus become especially units ‘‘have the same external static included as part of the March 24, 2006,
important as they offer the primary pressure,’’ Trane asked how to interpret Federal Register notice that published a
pathway for independent verification. that requirement if testing a ducted petition for waiver from the residential
For those multi-split products that are multi-split system having indoor units package air conditioner and heat pump
not covered by a third-party certification that have different minimum external test procedures that was received from
program, DOE can request from the static pressure requirements. (Public Mitsubishi Electric and Electronics
manufacturer the information needed to Hearing Tr., p. 229) USA, Inc. (Case No. CAC–012). 71 FR
conduct such testing along with DOE accepts the stakeholder 14858. This provision was not in the
reviewing the lab test results maintained recommendation of substituting the July 2006 proposed rule, but was
by the manufacturer, that substantiate phrase ‘‘represent the highest sales discussed at the public meeting and
the multi-split system’s ratings. 10 CFR model family’’ for the originally relevant comments were received in the
430.62(d). proposed wording, ‘‘represent the course of the waiver process. Lennox
Of the changes being implemented highest sales volume type models,’’ and Copeland commented that the rated
today to allow testing and rating of because it has essentially the same system’s combination of indoor units
residential modulating multi-split meaning, but is clearer. Although it is could be very different from those in the
pwalker on PROD1PC71 with RULES3

systems, two changes could be applied more an issue with commercial multi- tested system, and the ratings agreement
to variable-speed one-to-one units. split systems, DOE accepts the proposed would be poor in this case. (Public
Together, these two changes would wording to clarify the tested Hearing Tr., pp. 245–246)
allow the manufacturer to specify the combination since it is more important Because of the difficulty of
compressor speed used for the to obtain a cumulative indoor capacity prescribing similarity of indoor unit

VerDate Aug<31>2005 17:58 Oct 19, 2007 Jkt 214001 PO 00000 Frm 00006 Fmt 4701 Sfmt 4700 E:\FR\FM\22OCR3.SGM 22OCR3
Federal Register / Vol. 72, No. 203 / Monday, October 22, 2007 / Rules and Regulations 59911

combinations, and with the belief that a that the time-integrated air temperature cooling mode tests. The three low-
rating that reflects the ‘‘highest sales difference across the indoor unit for capacity tests are conducted at different
model family’’ is better than no rating, consecutive ‘‘on’’ cycles must change by outdoor dry bulb temperatures (i.e.,
DOE is including this ratings provision 0.05 °F hr or less while the other was steady-state, wet-coil test at 95 °F
in the final rule, with the additional for the average system power outdoor dry bulb temperature (the A1
stipulation that multi-split consumption for the complete ‘‘OFF/ Test); the steady-state, dry-coil test at 82
manufacturers must test two or more ON’’ interval to change by 10 watts or °F (the C1 Test); and the cyclic, dry-coil
combinations with each outdoor unit less from one cycle to the next. test at 82 °F (the D1 Test)). The July 2006
unless they have an approved ARM (in ARI, Sanyo, Carrier, and Nordyne
commented that repeatability should be proposal was to have all three of these
which case, they only need to test one tests replaced by equivalent tests
combination). 10 CFR 430.24(m)(2). One addressed by ASHRAE’s Standards
Project Committee (SPC) 116, ‘‘Method conducted at an outdoor dry bulb
system shall be tested using only non-
ducted indoor units that meet the of Testing for Rating Seasonal Efficiency temperature of 67 °F.
definition of a tested combination. The of Unitary Air Conditioners and Heat ARI, Carrier, and Nordyne supported
second system shall be tested using only Pumps,’’ not by the DOE test procedure replacing the A1 Test with the steady-
ducted indoor units that meet the (ARI, No. 21 at p. 3; Sanyo, No. 15 at state, wet-coil, F1 Test at 67 °F because
definition of a tested combination. The p. 5; Carrier, No. 17 at p. 2; Nordyne, the change will close a potential
rating given to any untested multi-split No. 19 at p. 2) Finally, ACEEE supports loophole in the current test procedure.
system combination having the same DOE’s efforts to capture the essence of (ARI, No. 21 at p. 3; Carrier, No. 17 at
outdoor unit and all non-ducted indoor industry best practices for cyclic testing. p. 2; Nordyne, No. 19 at p. 2) This
units shall be set equal to the rating of (ACEEE, No. 16 at p. 4) loophole allowed manufacturers a way
the tested system having all non-ducted DOE recognizes that variability is
to increase the measured SEER by
indoor units. The rating given to any inherent in testing products for energy
efficiency, including central air disproportionately increasing the
untested multi-split system combination electrical power consumption during
having the same outdoor unit and all conditioners and central air
conditioning heat pumps. In order to the A1 Test. ACEEE supported the
ducted indoor units shall be set equal to change in the temperature in the A1 test,
the rating of the tested system having all reduce test variability and increase
repeatability of test results, DOE has set but expressed its concern that the
ducted indoor units. Finally, the rating
specific requirements for test set-up and change may downgrade the importance
given to any untested multi-split system
combination having the same outdoor measurement to reduce variability. of high temperature performance.
unit and a mix of non-ducted and However, even with these requirements, (ACEEE, No. 16 at p. 4) ARI, Carrier, and
ducted indoor units shall be set equal to test variability remains. Furthermore, Nordyne commented that the change in
the average of the ratings for the two DOE notes that the less repeatable the the C1 and D1 tests is unnecessary since
required tested combinations. 10 CFR test, either more units need to be tested these tests are optional and the changes
430.24(m)(2)(ii). Furthermore, DOE to support an energy efficiency rating will do very little to improve the
notes that it is including a provision for that is representative of the units true accuracy of SEER. (ARI, No. 21 at p. 3;
the use of an alternate rating method. energy efficiency or, if less testing is Carrier, No. 17 at p. 2; Nordyne, No. 19
While DOE is not aware of any done, the product must be rated at p. 2) Carrier also expressed its
algorithms appropriate for rating the conservatively (i.e., lower energy concern that products designed and
energy efficiency of untested multi-split efficiency rating).4 Test variability can tested under the current methodology
system combinations, DOE expects that be further reduced by, for example, may have to be re-rated as a result of the
as more laboratory test data and field including more specific requirements in proposal. (Carrier, No. 17 at p. 2) In
use data become available, such the DOE test procedures as well as terms of the test procedure, Carrier is
algorithms will be developed. through industry actions, such as concerned that a different cyclic-
Today’s final rule contains a minor ASHRAE Standard 116. However, degradation coefficient (CD) may result
update that was introduced in the July changes to the DOE test procedures to
2006 proposed rule, removing the limit from replacing the C1 and D1 Tests with
deal with test variability could increase
on having only one indoor test room. No equivalent tests at 67°F.
the burden and cost of testing. Since the
comments were received on this purpose of this requirement was to Collectively, the three proposed
proposed change. reduce variability and there are changes make the test conditions for
Today’s final rule sufficiently alternative approaches manufacturers two-capacity units consistent with the
addresses issues that led to the can take to reduce variability, DOE is test conditions specified for variable-
requesting and granting of test not adopting the cyclic changes speed systems. Implementing all three
procedure waivers for several models of proposed. Therefore, as part of today’s changes would result in a more normal
residential multi-split systems. final rule, DOE makes no changes on test progression for most two-capacity
Therefore, all existing waivers defining repeatability during cyclic units: all wet coil tests followed by the
concerning residential modulating tests. dry coil test; start with high capacity
multi-split systems terminate on the tests and end with the low capacity
effective date of today’s final rule. D. Outdoor Air Test Conditions for Units
Having a Two-Capacity Compressor tests; and start at 95 °F, progress to 82
Multi-split manufacturers may use the °F, and then end with 67 °F. These
waiver process described in 10 CFR The July 2006 proposed rule included benefits, however, cannot be realized
430.27 to petition for modification of provisions that dealt with the outdoor
because of the possibility of causing a
today’s test procedure, if necessary. test conditions for three low-capacity
change in the SEER ratings of some two-
C. Defining ‘‘Repeatable’’ for Cyclic 4 SEER and HSPF values, per the sampling plan
capacity units. Thus, DOE agrees with
pwalker on PROD1PC71 with RULES3

Tests in 10 CFR 430.24, are to be based on the lower 90 the general position of the comments
The July 2006 proposed rule percent confidence limit of the true mean divided that the proposal to change the outdoor
by 0.95 (as opposed to the sample mean), thus the test conditions for the two optional dry-
contained two provisions that further more variability in test results, the more likely that
defined repeatable performance during a product’s SEER and HSPF ratings will have to be coil CD tests (C1 and D1 tests) is not
cyclic tests. One was the requirement reduced from the true mean. warranted.

VerDate Aug<31>2005 19:03 Oct 19, 2007 Jkt 214001 PO 00000 Frm 00007 Fmt 4701 Sfmt 4700 E:\FR\FM\22OCR3.SGM 22OCR3
59912 Federal Register / Vol. 72, No. 203 / Monday, October 22, 2007 / Rules and Regulations

Therefore, today’s final rule replaces blowers that are affected by this change G. Maximum and Minimum Speed
the A1 Test with the F1 Test, as be as generic as possible so as not to Values for Calculating NQ and NE
proposed. The F1 Test requires an impede product innovation. (Public Rheem inquired as to whether the
outdoor dry bulb temperature of 67 °F, Hearing Tr., pp. 132–133) minimum and maximum speed
and for those few cases where it applies, quantities needed to evaluate Appendix
DOE agrees with ACEEE that the
an outdoor wet bulb temperature of 53.5 M equations 4.1.3–1 and 4.1.3–3 are to
proposed language could limit
°F. The amendments discussed above be determined directly from additional
are found in sections 3.2.3 and 4.1.3 of innovation since the proposed
amendment was intended to apply to lab testing or from interpolating data
Appendix M. from required tests lab tests at 67 °F, 82
designs that are not adequately
E. Air Volume Rate Less Than addressed by the current air volume °F, and 95 °F. (NIST, No. 24 at p. 2) In
Manufacturer’s Specified Value requirements. Since it is impossible to response, for cooling performance, DOE
In the July 2006 proposed rule, and predict what product designs may enter modified section 4.1.4 to explicitly state
the October 10, 2006, correction notice, the marketplace, specifying the designs that the capacities and Q̇ck=1 (87) and
DOE proposed modifications to the subject to the new provisions may, in Q̇ck=2 (87), which are used as part of the
criteria for using an air volume rate that algorithm for approximating the slope of
fact, limit innovation. Therefore, in
is less than the manufacturer’s specified the intermediate compressor speed
response to ACEEE’s comment, DOE
value. The proposal was made to (k=v) capacity curve, are determined by
restructured the air volume criteria to
account for the variability in fan motors, evaluating equations 4.1.3–1 and 4.1.3–
indicate that the change applies to all 3, respectively, for Tj = 87. Similar
housings, and wheels. In brief, the designs, except variable-speed,
proposed set-up process for the test direction is provided for determining
constant-air-volume-rate blowers. In this the power consumption quantities Ėck=1
procedure provides for making
way, the variable-speed, constant- (87) and Ėck=2 (87) that appear within
incremental adjustments in the indoor
volume-rate blowers, which the existing the section 4.1.4 equation for NE. For
fan speed until the indoor unit provides
an external static pressure that is equal test procedure adequately addresses, heating performance, such direction
to or greater than the applicable DOE continue to be subject to the existing already exists within the section on
minimum (i.e., 0.1, 0.15, or 0.20 inch of requirement. calculating the HSPF for a variable-
water column, if a non-small-duct, high- F. Updating References to Industry speed heat pump, with regard to the
velocity (SDHV) system), while source of the minimum speed quantities
Standards
operating at the manufacturer-specified at 35 °F.
air volume rate or, if needed, at the air The July 2006 proposed rule included This change does not affect the
volume rate between 95 percent and 100 updates to references to current industry calculated SEER. The revised text is
percent that produces the corresponding test standards, including ASHRAE found following the equation for NE in
DOE minimum static pressure value. Standard 23–2005, ‘‘Methods of Testing section 4.1.4 of Appendix M.
For comparison, the current algorithm for Rating Positive Displacement H. Using the Default or Tested Value of
in the DOE test procedure does not Refrigerant Compressors and Cyclic-Degradation Coefficient
allow the air volume rate to be reduced Condensing Units,’’ ASHRAE Standard
from 100 percent for the case where the Carrier asked if the manufacturer
37–2005, ‘‘Methods of Testing for Rating elects to run the optional tests, and the
external static pressure is less than
Electrically Driven Unitary Air- resulting CD exceeds the 0.25 default
specified by the test procedure. The
Conditioning and Heat Pump value, is the manufacturer obligated to
proposed criteria apply to all ducted
blower-coil systems, except those Equipment,’’ and ASHRAE Standard use the tested value. (Public Hearing Tr.,
having a variable-speed motor that is 116–1995 (RA2005), ‘‘Methods of p. 31) The current test procedure
controlled based on maintaining a Testing for Rating Seasonal Efficiency of addresses this scenario for most cases
constant air volume rate. The proposed Unitary Air Conditioners and Heat where a CD is used in the SEER and
criteria include two cases where the test Pumps.’’ Nordyne commented in HSPF calculations. Specifically,
laboratory is instructed to operate at an support of this proposal. (Nordyne, No. sections 4.1.1, 4.1.2.1, 4.1.3.1, 4.1.4.1,
air volume rate less than that specified 19 at p. 2) 4.2.1, and 4.2.3.1, direct that if the
by the manufacturer: (1) If the highest In addition, subsequent to the optional test(s) are not conducted, the
indoor fan speed setting cannot yield publication of the July 2006 proposed cooling (heating) cyclic-degradation
the DOE-specified external static rule, ARI released an updated version of coefficient, CDc (CDh), is to be set to the
pressure minimum while supplying the ARI Standard 210/240, ‘‘Performance default value of 0.25. If the optional
manufacturer-specified air volume rate, test(s) are conducted, CDc (CDh) must to
Rating of Unitary Air-Conditioning and
and (2) if the manufacturer’s specified be set to the lower of: the value
Air-Source Heat Pump Equipment.’’ The
air volume rate yields a ratio higher calculated per the test or the default
updated version of ARI Standard 210/ value of 0.25. In response to Carrier’s
than 37.5 standard cubic feet per minute
240 included references to the DOE test comment, DOE has added similar
(scfm) per 1000 Btu/h.
Nordyne, Carrier and Rheem procedure as amended by the final rule wording to sections 4.1.3.3 and 4.2.3.3,
supported the proposed criteria for published on October 11, 2005. This the only sections that did not include
using an air volume rate that is less than latest version of ARI Standard 210/240 the clarifying language found in the
the manufacturer’s specified value. had not been released at the time that sections referenced above.
(Nordyne, No. 19 at p. 2; Carrier, No. 17 the content of the July 2006 proposed Furthermore, in reviewing the
at p. 3; Public Hearing Tr., p. 135; and rule had been finalized. Since the organization of the current test
Public Hearing Tr., pp. 134–135) ACEEE updated test procedures do not affect procedure while considering this
pwalker on PROD1PC71 with RULES3

commented that since the proposed the measure of efficiency and provide update, DOE found that the information
language specified which product manufacturers with current test would be better placed in the earlier
designs would be subject to this standards, DOE moves today to adopt sections (within section 3) with the
requirement, they recommended that the 2006 version of ARI Standard 210/ instructions as to which tests to conduct
the wording for the types of indoor 240. based on the type of equipment (i.e.,

VerDate Aug<31>2005 19:03 Oct 19, 2007 Jkt 214001 PO 00000 Frm 00008 Fmt 4701 Sfmt 4700 E:\FR\FM\22OCR3.SGM 22OCR3
Federal Register / Vol. 72, No. 203 / Monday, October 22, 2007 / Rules and Regulations 59913

single-speed, two-capacity, variable- J. Clarification of the Sample Population proposal was made in recognition that
speed, etc). Therefore, language has Used To Validate the Rated Seasonal coil-only units represent the
been added in the test procedure to Energy Efficiency Ratio and Heating overwhelming majority of installations
clarify that if the tested cyclic- Seasonal Performance Factor of Heat of central air conditioners and, as such,
degradation coefficient is higher than Pumps the highest-sales-volume should reflect
the default value, the default value is to DOE proposed that a manufacturer standard practice. The proposal also
be used to calculate SEER and HSPF. must include the cooling and heating minimizes instances where the highest-
(see sections 3.2.1, 3.2.2.1, 3.2.3, 3.2.4, results from each heat pump of the sales volume combination of a split-
3.5.3, 3.6.1, 3.6.2, 3.6.3, 3.6.4, 3.8.1, sample population when obtaining the system air conditioner could be defined
4.1.3.3, and 4.2.3.3). certified SEER and HSPF ratings. This as one with a ‘‘blower-coil’’ in order to
requirement disallows testing multiple meet Federal minimum energy
I. Guidance on the Inclusion of Pre- heat pumps and then using a subset of efficiency standards and then have the
Production Units in the Sample results for assigning the certified SEER outdoor unit combined with coil-only
Population rating and a different subset of results indoor units where the combination
for determining the certified HSPF would not meet the Federal energy
As part of the July 2006 proposed efficiency standards.
rule, DOE proposed that only pre- rating. The proposal provided one
ACEEE, Carrier and ARI agreed that
production units fabricated using the exception, which would allow
some clarification to the test procedure
additional testing in just one mode,
same tooling used for the eventual full- was needed in order to avoid such
cooling or heating, if the manufacturer
production units could be used as part situations. (ACEEE, No. 16 at p. 5; ARI,
elected to discontinue testing in the
of the tested sample population to No. 21 at p. 4; Public Hearing Tr., pp.
other mode at some point in the sample
obtain the certified ratings of full- 208–209) ACEEE supported the goal of
sequence.
production units. ACEEE, Nordyne, and Carrier not having outdoor units installed with
ARI, Nordyne, and Carrier supported the intent of clarifying the coil-only indoor units where the
sample population used for determining combination does not meet the energy
commented that the proposed wording
heat pump ratings. (ACEEE, No. 16 at p. efficiency standard. (ACEEE, No. 16 at
is too narrow, and recommended that
5; Nordyne, No. 19 at p. 3; Carrier, No. p. 5) Instead of the proposed text, ARI
the current regulatory language not be
17 at p. 2) Carrier and the ACEEE, and Carrier recommended that DOE
changed. (ARI, No. 21 at p. 4; Nordyne, adopt the wording from the 2006 ARI
No. 19 at p. 3; Carrier, No. 17 at p. 2) however, recommended deleting the
exception, noting that additional testing Certification Program Operational
ARI and Trane explained that the Manual for Unitary Air Conditioners &
tooling used for pre-production units is is insignificant as compared to the
potential for misrepresented ratings. Air-Source Unitary Heat Pumps (Rated
often different than that used for Below 65,000 Btu/h Cooling). (ARI, No.
production units. (Public Hearing Tr., (Carrier, No. 17 at p. 2; ACEEE, No. 16
at p. 5) 21 at p. 4; Public Hearing Tr., pp. 208–
pp. 192–193) Trane stated that pre- 209) Carrier and ARI commented that
DOE is aware of the testing burden on
production units must have the same the proposed exception for outdoor
manufacturers, but agrees with Carrier
configuration as the production unit to units that prevent installations with
and the ACEEE that this particular
be included in the sample population, coil-only units with a proprietary
attempt at marginally reducing the test
while Carrier suggested using wording burden is not worthwhile. Thus, today’s interface should be eliminated because
such as that in the ARI Certification final rule adopts the proposal that all it is not enforceable. Nordyne strongly
Program Operational Manual to define units of the sample population must be objected to the entire proposal, stating
the configuration (e.g., same tested in both the cooling and heating that it restricts a manufacturer’s use of
compressor, same air flow, etc.). (Public modes and the results used for technology. (Nordyne, No. 19 at pp. 3–
Hearing Tr., pp. 192, 198–199) Rheem determining the heat pump’s certified 4) Moreover, to implement such a
commented that the ARI internal SEER and HSPF ratings without change, Nordyne asserted that DOE
process handles ratings derived from adopting the proposed exception for needs to analyze the impact of
pre-production units by making the additional testing. minimally compliant units. Nordyne,
model subject to certification testing however, did note its support for the
K. Clarification of the Definition of a proposed exception for blower coils
immediately after production starts.
‘‘Highest-Sales-Volume Combination’’ having a proprietary interface.
(Public Hearing Tr., p. 202)
DOE proposed amendments to the ARI and Carrier recommended the
DOE agrees that the proposed following alternative text to the July
definition of the Highest-Sales-Volume
criterion is too narrow, and that 2006 proposed rule:
Combination (HSVC) to require that a
different tooling can yield equivalent HSVTC, Highest-sales-volume Tested
single-speed, split-system air
machinery. Moreover, DOE believes that conditioner must include the coil-only Combination. For Unitary Air-Conditioners
spot checks conducted under an indoor unit likely to have the largest below 14 SEER, the HSVTC must be an RCU-
industry certification program, such as A-C combination, except for through-the-wall
volume of retail sales with the particular and ductless equipment (RCU-A-CBO). For
the ARI Certification Program, provide a model of outdoor unit. Proposed 10 CFR Unitary Air-Conditioners 14 SEER and above,
safeguard against the performance of the 430.24(m)(2). In addition, DOE every outdoor model number must have a
production unit deviating appreciably proposed exceptions to this requirement coil-only rating. Coil-only ratings offered for
from ratings derived from testing pre- to provide for equipment designed sale must be publicly viewable. Coil-only
production units. For these reasons, exclusively for blower-coil installations: ratings not offered for sale are viewable only
DOE is not amending the existing mini-splits; multi-splits; small-duct, to ARI staff. Non-viewable ratings fall under
pwalker on PROD1PC71 with RULES3

requirements and will continue to allow all compliance guidelines except the
high-velocity systems; through-the-wall
challenge procedure. If a non-publicly
manufacturers to test pre-production units; and condensing units having viewable rating falls below NAECA
units. features (e.g., proprietary interfaces) that minimum, then the manufacturer must
prevent their installation with third- submit a coil-only rating that meets NAECA
party, coil-only indoor units. This minimum and is verified through ARI testing.

VerDate Aug<31>2005 17:58 Oct 19, 2007 Jkt 214001 PO 00000 Frm 00009 Fmt 4701 Sfmt 4700 E:\FR\FM\22OCR3.SGM 22OCR3
59914 Federal Register / Vol. 72, No. 203 / Monday, October 22, 2007 / Rules and Regulations

Until then, the Basic Model Group ratings July 2006 proposed rule. DOE believes combination. The proposed approach
will not be listed in the ARI directory. that its proposal, which is adopted in applied to untested combinations
Historically, the highest sales volume today’s final rule, increases the offered by system manufacturers and by
combination for most split-system air likelihood that the outdoor unit, in independent coil manufacturers (ICM’s).
conditioners has had a coil-only indoor combination with any compatible ACEEE commented in support of the
unit. Both the June 2006 proposed rule indoor unit, will meet the federal energy proposal to limit the difference between
and the ARI alternative maintain this efficiency standards. This is because the calculated and tested SEER and HSPF
historical practice. DOE, however, proposal which is adopted today values. (ACEEE, No. 16 at p. 5) Carrier
believes ARI’s approach is arbitrary and ensures that the tested combinations, and Nordyne also supported the DOE
results in uncertainties to upon which most ratings are based, proposal for SEER ratings but Carrier
manufacturers. Furthermore, DOE reflect the outdoor-indoor combinations does not believe a similar cap is
believes it would be difficult to most likely to be sold. Furthermore, this required for HSPF ratings. (Carrier, No.
implement the above ARI algorithm. language does not limit technology 17 at p. 3; Nordyne, No. 19 at p. 4)
With the ARI approach, the options to manufacturers, since the test Using data from the September 2006
manufacturer may have to re-test in a procedure allows for representations of ARI Online Directory, Carrier found that
coil-only configuration after having other than the highest-sales-volume the proposed 5 percent SEER limit
tested in a blower-coil configuration, if combination. would affect the ratings of 1.05 percent
the expected SEER of 14 or higher is not With regard to Nordyne’s comment of OEM coil-only combinations and
that DOE needs to analyze the impact of 13.87 percent of ICM coil-only
realized in laboratory testing. In
the clarifications on minimally combinations. (Carrier, No. 17 at p. 4) At
addition, if DOE were to adopt the ARI
compliant units, DOE fails to see how the public meeting, Carrier offered
alternative and the minimum energy
the clarification in the definition will similar statistics to show that ICM’s, in
efficiency standards were amended,
alter the rating of a particular split- general, rate condenser-coil
DOE would have to modify the
system air conditioner. The clarification combinations employing the same
requirement, since the new minimum
ensures that the highest-sales-volume condenser at higher efficiencies than the
could be higher than the 14 SEER
split-system air conditioner—which is OEM’s. Carrier also offered statistics to
requirement in the ARI alternative.
subject to testing—yields ratings show that a small number of ICM’s
Conversely, in formulating the approach
reflective of the outdoor-indoor provide most of the ratings that are more
proposed in the July 2006 proposed combinations most likely to be sold. For
rulemaking, DOE first considered than 5 percent higher than the OEM
split-system air conditioners
requiring that all split-system air rating for the highest-sales combination.
‘‘representative’’ and ‘‘highest sales’’
conditioners be tested with a coil-only (Public Hearing Tr., p. 265) Carrier also
historically equate to coil-only indoor
indoor unit. DOE recognized, however, cites the September 2006 NIST ‘‘Survey
units. Only mini-splits, multi-splits, and
that in addition to the exceptions such of SEER Ratings for Independent Coil
through-the-wall units can currently
as equipment designed exclusively for Manufacturer Mixed Systems’’ as
argue for an exception, since, in these
blower-coil installations, other demonstrating the need to address the
cases, the outdoor units would be sold
exceptions would have to be recognized. issue. (Carrier, No. 17 at p. 3)
in combination with specific indoor
These other exceptions include two- units which would include a fan and a Lennox disagrees with the June 2006
capacity and variable-speed units, coil. proposal. Lennox points out that the
because they are always much more Therefore, DOE is adopting the proposed 5 percent limit is not
efficient than 14 SEER, and do not risk language of the July 2006 proposed rule, technically supported and that the
having a coil-only combination that to require that the highest sales volume practical limit is more likely 13 percent
would not meet the DOE efficiency combination of a single-speed, split- than 5 percent. Lennox notes that the
standards. Therefore, DOE applied the system air conditioner must include the NIST report referenced above states that
coil-only requirement only to split coil-only indoor unit likely to have the ‘‘maximum gains in SEER associated
system air conditioners having a single- largest volume of retail sales with the with coil capacity and improved
speed compressor. particular model of outdoor unit. The expansion devices are approximately 10
Returning to the issue of listed only change from the proposed rule is percent and 2.5 percent, respectively.’’
exceptions, DOE agrees with ARI and to limit the exceptions to mini-splits, (Lennox, No. 22 at p. 1) Lennox reports
Carrier that the proposed exception for multi-splits, and through-the-wall units. that an independent laboratory tested
combinations that prevent applications two different condensing units having
with third-party coil-only indoor units L. Upper Limit on the Difference 13 SEER HSVC ratings with an alternate,
would be prohibitively difficult to Between Calculated and Tested non-HSVC, evaporator coil. According
define, verify, and enforce. DOE Seasonal Energy Efficiency Ratio and to Lennox, the non-HSVC tested
believes that its proposal to substitute Heating Seasonal Performance Factor combinations produced SEER ratings
the words ‘‘mini-splits’’ and ‘‘multi- Values 7.9 and 11.8 percent higher than the
splits’’ for ‘‘ductless equipment,’’ is DOE proposed setting a 5 percent 13.0 SEER rating of the HSVC units.
somewhat more comprehensive because limit on the amount that a rating for an Lennox argues that data analysis
it includes ducted multi-split systems. untested split-system combination conducted by Carrier is incomplete and
Finally, SDHV manufacturers, at could exceed the rating of the that having to test combinations that are
present, only manufacture indoor coils corresponding HSVC. 71 FR 41330, July projected to exceed the 5 percent limit
and do not manufacture outdoor units. 20, 2006. The proposed limit only will be overly burdensome. Lennox
Since SDHV manufacturers do not offer applied to applications where both further stated that the combination of
for sale complete systems, they are not combinations used coil-only indoor DOE approval of the ARM,
pwalker on PROD1PC71 with RULES3

subject to specifying HSVC’s. Thus, units. Ratings based on testing are not governmentally enforceable penalties
SDHV systems do not need to be subject to the 5 percent limit. for overrating, and an industry-
included as an exception. Manufacturers seeking a rating that sponsored certification program ‘‘ensure
As to Nordyne’s objections, DOE exceeds the 5 percent limit can do so by a reasonable level of rating integrity and
stands by its position as stated in the testing the particular coil-only result in a full availability of cost

VerDate Aug<31>2005 17:58 Oct 19, 2007 Jkt 214001 PO 00000 Frm 00010 Fmt 4701 Sfmt 4700 E:\FR\FM\22OCR3.SGM 22OCR3
Federal Register / Vol. 72, No. 203 / Monday, October 22, 2007 / Rules and Regulations 59915

effective, higher efficiency combinations untested combination ratings is the ARM without the adjustment/tuning
for consumers.’’ (Lennox, No. 22 at p. 2) warranted. However, DOE finds, from a factor. The purpose is to limit the
ARI commented that the DOE review of the data and comments amount of manufacturer’s ‘‘tuning’’ of
proposed 5 percent upper limit is received, that the ratings of some non- ARMs, without resubmitting the ARM
arbitrary and will unduly penalize HSVCs are higher that what would seem for DOE review in accordance with 10
manufacturers who participate in the warranted. DOE supports the steps CFR 430.24(m)(5). DOE is concerned
ARI certification program. Furthermore, recently implemented by ARI’s that the ‘‘tuned’’ ARMs will result in a
ARI commented that inconsistent certification program to more frequently different model than the one the
ratings for untested split-system check combinations having suspect Department had reviewed and approved
combinations have been discussed at ratings. Moreover, DOE is amending the under 10 CFR 430.24(m)(5). The
length with the appropriate ARI test procedure to emphasize its right to changes were proposed to improve the
committees for quite some time, and, obtain information that is the basis for current regulatory language that states
based on these discussions, significant any manufacturer’s rating. DOE will the ARM must be used to obtain
changes were made to strengthen the require documentation to justify ratings ‘‘representative values of the measures
credibility of the ARI certification more than 6 percent higher that the of energy consumption.’’ 10 CFR
program. (ARI, No. 21 at p. 5) For rated efficiency of the HSVC unit. If 430.24(m)(2)(ii).
example, ARI commented that coil-only DOE questions the rating, the ARI commented that ‘‘untested’’
combinations (system manufacturers manufacturer will be responsible for combinations are subject to verification
and ICMs) with SEER ratings that are 6 verifying the ARM, and supplying to testing in the ARI Certification Program
percent above the SEER rating of the DOE the ARM used and furnishing the and so placing a limit on the adjustment
highest-sales-volume tested specific input parameters used for each factor is unwarranted for combinations
combination are automatically subject to condenser-evaporator combination, the listed in the ARI directory. (ARI, No. 21
testing as part of the ARI certification energy efficiency rating of the HSVC, at p. 5) Carrier commented that any
program. (ARI, No. 21 at p. 5) the energy efficiency results of the adjustment based on actual testing to be
The analysis conducted by Carrier ARM, and the rated energy efficiency of not only allowable but desirable.
and NIST certainly justifies further the units in question. Furthermore, the (Carrier, No. 17 at p. 3) Nordyne was
scrutiny of ratings of untested manufacturer must be prepared to willing to consider the concept of a
combinations of split-system central air provide the information source and/or maximum allowable adjustment but
conditioners. The SEER ratings reported justification for any input parameter. stated that the exact values and the
by Lennox raise a few questions, while In summary, DOE is not adopting the specific wording needed further review.
suggesting that the proposed mechanism proposed 5 percent limit on the (Nordyne, No. 19 at p. 4)
and 5 percent limit may not be maximum amount that a rating for an In reviewing its files of ARMs that
adequate, but Lennox doesn’t offer an untested coil-only split-system can DOE has approved, DOE finds that none
alternative. For example, how much of exceed the rating of the HSVC. Instead, reference an ARM/simulation
the ratings difference is a result of the DOE will evaluate the improvements adjustment factor, or equivalent. Yet,
better performance of the mixed system available through using new and the use of such adjustment factors
indoor units? How much of the ratings improved ARMs and the results from appears to be common. This situation,
difference results from the HSVC rating internal changes made as part of the ARI along with the fact that most
being conservative ‘‘ i.e., although rated Certification Program. DOE will give manufacturers’ ARMs have not been
at 13.0, the tested SEER of the HSVCs follow-up priority to individual updated in many years, and that most,
is likely higher? If the percent combinations having questionably high if not all, of the models upon which the
differences reported by Lennox had ratings (for example, a coil-only system ARMs were based have been removed
been based on the measured SEER of the having a rating that exceeds the rating from the marketplace because they did
HSVC, the respective magnitudes would of a coil-only highest sales volume not meet the 13 SEER standard leads
likely have been less, possibly much combination by more than 6 percent). DOE to conclude that it is likely some
less. The text that sets forth DOE’s authority ARMs need the adjustment factor in
As for Lennox’s comment that the to examine ratings for untested split order to correctly predict the efficiency
NIST report supports a higher system combinations is found in 10 CFR of untested combinations.
percentage, DOE notes that the NIST 430.24(m)(5) of today’s rule. In view of the foregoing, DOE is
analysis only commented on the effect amending 10 CFR 430.24(m)(5) to
of increased coil capacity and an M. Clarification of the Published Ratings require published ratings for an
improved expansion device, two factors for Untested Split-System Combinations untested split-system combination to be
that increase SEER. The impact of the DOE proposed amendments to 10 CFR equal to, or lower than, the value
larger coil on compressor power 430.24(m)(4) to require published calculated using the DOE-approved
consumption, however, was believed ratings for an untested split-system ARM. The practice of ‘‘tuning’’ an ARM
negligible even though it too would combination to be equal to, or lower or computer simulation by using
typically increase. Thus, for the nominal than, the value calculated using the laboratory data from tests on the HSVC
case where a power increase DOE-approved ARM. 71 FR 41336. The or any other split-system combination
accompanies the capacity gain, the proposed language specifically tested in accordance with the sample
maximum SEER increase predicted by recognized that a manufacturer may use plan of 10 CFR 430.24(m), and then
the long-standing NIST ARM is in the 9 laboratory data from the HSVC testing to using the tuned ARM to calculate the
to 10 percent range, higher than the 5 adjust or ‘‘tune’’ its ARM, or a ratings for untested combinations that
percent limit proposed in the NOPR, but simulation subcomponent, when use the same outdoor unit, is now
less than the maximum increase stated calculating the ratings for untested referenced in 10 CFR 430.24(m)(4).
pwalker on PROD1PC71 with RULES3

by Lennox. combinations that use the same outdoor DOE, however, is not adopting a limit
Upon consideration of the above unit. Under the proposal, the amount of on how much the SEER/HSPF rating,
comments, DOE believes that its 5 adjustment is limited to a 5 percent calculated using an ARM, may exceed
percent limit, as proposed, is deficient. increase in the calculated rating the rating obtained without using the
DOE still believes that more scrutiny of compared to the rating obtained using adjustment factor.

VerDate Aug<31>2005 17:58 Oct 19, 2007 Jkt 214001 PO 00000 Frm 00011 Fmt 4701 Sfmt 4700 E:\FR\FM\22OCR3.SGM 22OCR3
59916 Federal Register / Vol. 72, No. 203 / Monday, October 22, 2007 / Rules and Regulations

N. Ratings That Are Based on Using a define coil circuitry. Trane responded surrounding ambient to 0.5 inches of
Particular Furnace or Ducted Air Mover that if this coil differentiating feature water column or less. If the particular
DOE proposed having manufacturers were deleted then it wouldn’t have to be test setup permits, the outlet air
document those published ratings that defined. (Public Hearing Tr., p. 297) damper box used for cyclic tests can
In considering the comments double as the adjustable air damper.
are based on a complete system
received, DOE finds the proposed This change is found in section
consisting of a coil-only air conditioner
amendments to the definition cause 2.5.4.3 of Appendix M.
or heat pump and a particular model of
more confusion than the existing
furnace. The model number of the Optional high-capacity cyclic-
definition, therefore, DOE is not
furnace would be published, most likely degradation coefficient (CD). Today’s
amending the definition of coil circuitry
in addition to the indoor unit model at this time. final rule reinstates the optional high-
number. capacity cyclic-degradation coefficient
ACEEE supported the measure, as III. Summary of Other Additions, (CD) testing for two-capacity units that
originally proposed. (ACEEE, No. 16 at Changes, and Corrections to the lock out low-capacity operation at
p. 5) Nordyne and ARI also supported Department of Energy Residential outdoor temperatures where the unit is
the measure but suggest replacing the Central Air Conditioner and Heat Pump otherwise projected to modulate
word ‘‘furnace’’ with a more generic Test Procedure between low and high capacities/
term so that the requirement is extended The following discussion summarizes compressor stages. In lieu of testing, the
to all indoor air movers. (Nordyne, No. revisions that were proposed in the July default value for the high-capacity CD
19 at p. 4; ARI, No. 21 at p. 6) Nordyne 2006 proposed rule and received no will be the value of the low-capacity CD.
suggests using ‘‘indoor blower’’ and ARI substantive comments. The specific change is reflected in
suggests ‘‘ducted air mover.’’ Small-duct, high-velocity (SDHV) sections 3.2.3, 3.4, 3.5, 3.5.3, 3.6.3, 3.8,
DOE accepts the recommendation of systems. Today’s final rule adopts the 3.8.1, 4.1.3.3, and 4.2.3.3 of Appendix
using generic wording to clearly convey following five changes that apply M.
the equipment components that exclusively to small-duct, high-velocity Two-capacity heat pump default
contribute to the published rating, and (SDHV) systems: equations. Instead of conducting the
selects the description ‘‘ducted air —The minimum external-static-pressure laboratory test, default equations are
mover.’’ DOE adopts revised text for 10 levels that must be equaled or now provided to approximate the
CFR 430.62(a)(4)(i) and (ii) that exceeded during the first test on any performance of a two-capacity heat
explicitly states that the model number SDHV system will be 1.0 inches of pump operating at low capacity and
of the ducted air mover, if applicable, water column higher than the 35 °F outdoor temperature. The default
must be included among the minimum that is required of non- equations appear in section 3.6.3 of
manufacturer’s model numbers SDHV units. For example, for Appendix M.
submitted on the certification report to equipment having rated cooling
DOE. Compared to the wording Duct loss correction. Except as noted
capacities from 29,000 to 42,500 Btu/ below, DOE adopts the practice of
proposed in the July 2006 proposed h, the minimum external static
rule, today’s revision is simpler, in that applying a duct loss correction to the
pressure is 1.15 inches of water cooling and heating capacities
it does not repeat text from 10 CFR column for SDHV systems, compared
430.62(a)(4) in sections 430.62(a)(4)(i) determined using the indoor air
to 0.15 inches of water column for enthalpy method. The losses occur
and (a)(4)(ii). conventional blower-coil systems. within the section of insulated duct that
O. Revisions to the Definition of ‘‘Coil This change is found in section extends between the outlet of the indoor
Family’’ 3.1.4.1.1 of Appendix M. unit and the test facility’s outlet
—All balance dampers or restrictor
DOE proposed minor modifications to temperature grid. The correction,
devices on or inside the unit must be
the existing definition of ‘‘coil family,’’ however, does not apply to the two
set fully open or on the lowest
to improve its readability and make it indoor capacities used for calculating a
restriction setting. This change is
easier to understand. 71 FR 41335. cyclic-degradation coefficient, CD. The
found in section 2.2 of Appendix M.
Nordyne and Rheem asked for —The size of the duct connected to the change affects sections 3.3, 3.4, 3.7,
clarifications to the proposed language. outlet of the indoor unit must not 3.9.1, and 3.11 of Appendix M and is
(Nordyne, No. 19 at p. 4) exceed prescribed limits. This change implemented by referencing sections
Concerning Nordyne’s comment, DOE is found in section 2.4.1 of Appendix 7.3.3.3 and 7.3.4.3 of ASHRAE Standard
had no intention other than to offer a M. 37–2005 for cooling and heating tests,
few editorial improvements, and to —When a closed-loop, air-enthalpy test respectively.
heighten awareness of the definition apparatus is used on the indoor side, Air volume. DOE adopts the definition
among stakeholders, given the related the test laboratory must limit the of ‘‘standard air’’ as given in ASHRAE
discussion of ARMs. As proposed, DOE airflow resistance on the inlet-side of Standard 37–2005. This change affects
viewed the substantive content of the the indoor blower-coil to a maximum section 1.37 of Appendix M and causes
definition as adequate for the purpose of value of 0.1 inches of water column. standard air volume rates to be
designating what split systems may be The balance of the airflow resistance expressed in terms of dry air, not moist
used for verifying an ARM. There was must be imposed on the outlet-side of air. DOE replaces the proper names
no change proposed to the definition of the indoor blower. This change is containing the words ‘‘Certified Air
‘‘coil family’’ with respect to coil found in section 3.1.4.1.1 of Volume Rate’’ with ‘‘Full-load Air
circuitry. In both the current and Appendix M. Volume Rate.’’ The change will
proposed test procedures, ‘‘coil —The test setup must include an eliminate confusion over whether the
pwalker on PROD1PC71 with RULES3

circuitry’’ is included in a list of design adjustable air damper that is air volume rates specified in the test
features that affect heat exchanger positioned immediately upstream of procedure are certified values, which
performance. In responding to the the airflow measuring apparatus that they are not. This change appears in
question raised by Rheem, NIST asked limits the differential pressure numerous places within the DOE test
attendees at the public meeting how to between the inside of the duct and the procedure, mostly in section 3 and

VerDate Aug<31>2005 18:36 Oct 19, 2007 Jkt 214001 PO 00000 Frm 00012 Fmt 4701 Sfmt 4700 E:\FR\FM\22OCR3.SGM 22OCR3
Federal Register / Vol. 72, No. 203 / Monday, October 22, 2007 / Rules and Regulations 59917

Tables 3 to 6 and Tables 9 to 12 of and power curves when the heat pump ratings of two-capacity systems. Since
Appendix M. is operated at the intermediate two-capacity systems are inherently
ARMs. DOE adopts revised language compressor speed, k = v. These more energy efficient, DOE concludes
for 10 CFR 430.24(m)(6) that describes intermediate speed slopes are derived that these amendments would only
the specific information the from the slopes of the minimum and affect higher efficiency systems and,
manufacturer must include in its maximum speed curves, weighting each therefore, not require DOE to amend its
submittal when requesting DOE’s accordingly. The terms NQ and NE are energy conservation standards.
approval of the manufacturer’s ARM. the weighting factors for the maximum The change to allow the use of default
The revision expands the options speed slopes. equations instead of conducting a low-
regarding the data used to evaluate and In the October 2005 final rule, section capacity Frost Accumulation Test will
verify the ARM and provides a 4.2.4 of Appendix M, the equations for negatively impact the measured HSPF.
compliance path for manufacturers who MQ and ME each consist of the sum of DOE estimates that the HSPF could be
offer indoor units from only one coil two expressions in square brackets. In as much as 0.3 point lower if the default
family. the right-hand bracketed expression of equations are used to obtain the value
Definitions. DOE incorporates the both equations, the divisor line is too corresponding to climate Region IV and
definition for ‘‘private labelers’’ from long. It should not extend under NQ in the minimum design-heating
EPCA, 42 U.S.C. 6291(15) into 10 CFR the equation for MQ, nor should it requirement instead of testing. This
430.2. Definitions for the terms ‘‘indoor extend under NE in the equation for ME. change will not affect the HSPF of a
unit,’’ ‘‘outdoor unit,’’ and ‘‘ARM/ The divisor line is being shortened so currently rated heat pump because use
simulation adjustment factor’’ have also that the equation returns to its format of the default equations is optional and
been added. Under 10 CFR established in the 1988 revision of the DOE understands manufacturers test
430.24(m)(5), DOE adopts revised test procedure. (53 FR 8304, March 14, products instead of using the default
language to specify that the 1988). The same misprint did not occur value and, therefore, there is no change
requirements also apply to private within the comparable cooling mode as a result of today’s revisions.
labelers, and not just to manufacturers. equations. Changing the maximum duration of
For example, private labelers, like all Frost Accumulation Tests from 12
manufacturers, are responsible for IV. Effect of Test Procedure Revisions hours to 6 hours is expected to only
ensuring that reported ratings for on Compliance With Standards affect the average space heating capacity
untested split-system combinations are In amending a test procedure, section and power at 35 °F by causing a
based on a DOE-approved ARM. 323(e) of EPCA directs DOE to minimal, systematic increase in the
October 2005 final rule. In addition, determine to what extent, if any, the test derived HSPF for the rare case where
DOE is correcting two errors that were procedure would alter the measured the heat pump remains completely
mistakenly introduced in the test energy efficiency of the covered product frosted beyond 6 hours. DOE believes
procedure final rule published on and if the amended test procedure alters such a situation is extremely unlikely,
October 11, 2005. 70 FR 59122. The the measured efficiency, the Secretary is especially for tests at full-load.
October 2005 final rule incorrectly to amend the applicable energy DOE does not expect that adopting the
specifies the outdoor test conditions conservation standard to the extent the practice of applying a duct loss
used for the optional low-capacity amended test procedure changes the correction to the cooling and heating
heating-mode cyclic test for two- energy efficiency of products that capacities determined using the indoor
capacity heat pumps. The temperatures minimally comply with the existing air enthalpy method to cause an
for this test are incorrectly specified in standard. (42 U.S.C. 6293(e)) In increase in SEER or HSPF. This is
the October 2005 final rule as 62 °F db/ recognition of this requirement, the July because the test procedure is simply
56.5°F wb. These temperatures should 2006 proposed rule requested comments catching up with current practice.
have remained as they were, with the on whether any of the proposed changes Making the definition of ‘‘standard
values 47°F db/43°F wb. This error was would affect the measures of energy air’’ consistent with the definition in
unfortunately not discovered until after efficiency, and, if so, to what extent, ASHRAE Standard 37–2005 will have
the final rule became effective on April when tested under the current test no effect on the SEER and HSPF as
10, 2006. DOE has been informed that procedure. DOE received no comments calculated using the October 2005 final
several new models of two-capacity heat in response. The issue was also raised rule. 70 FR 59122 (October 11, 2005).
pumps have been rated for HSPF based at the public hearing, and DOE again Finally, changing the one steady-state,
on conducting the low-capacity heating received no comments that any models low-capacity cooling-mode test
mode cyclic test at 62 °F db/56.5 °F wb. would fail to meet the standard when condition from 95 °F to 67 °F for two-
In implementing the test condition tested using the new test procedure. capacity units is projected to change the
correction, DOE will not require that Since DOE did not receive comments on calculated SEER very minimally—
these affected models of two-capacity this issue, and based on the discussion within ± 0.1 SEER point—in most cases.
heat pumps be retested and rerated below, DOE concludes that the However, the reduction in SEER could
since the difference in energy efficiency amendments to the central air be very considerable if the power
is very slight, (i.e., tenths of HSPF). This conditioner and central air conditioning consumption during the 95 °F test at low
correction appears in section 3.6.3b and test procedures adopted in today’s final capacity is increased in an effort to
Table 11 of Appendix M. rule do not change the measure of obtain lower estimates, through
The second correction affects two energy efficiency of central air extrapolation, of the power
equations used for calculating the HSPF conditioners and central air consumption for low-capacity at
of a variable-speed heat pump. Within conditioning heat pumps that minimally temperatures less than 82 °F. In general,
section 4.2.4 of Appendix M of the final comply with the existing standard. the impact of the change will be
pwalker on PROD1PC71 with RULES3

rule published on October 11, 2005, the Therefore, amendments to the existing measurable if the unit’s electrical power
terms NQ and NE are incorrectly energy efficiency standard are not draw increases atypically at higher
positioned within the equations for MQ required. outdoor temperatures when operating at
and ME, respectively. MQ and ME Some revisions in today’s final rule low capacity. However, two-capacity
correspond to the slopes of the capacity are expected to slightly change the compressors are inherently more energy

VerDate Aug<31>2005 17:58 Oct 19, 2007 Jkt 214001 PO 00000 Frm 00013 Fmt 4701 Sfmt 4700 E:\FR\FM\22OCR3.SGM 22OCR3
59918 Federal Register / Vol. 72, No. 203 / Monday, October 22, 2007 / Rules and Regulations

efficient and are not used in minimally Paperwork Reduction Act. (44 U.S.C. Executive Order 12988 specifically
compliant units, and, therefore, DOE 3501 et seq.) requires that Executive agencies make
concludes that this amendment to the every reasonable effort to ensure that the
D. Review Under the National
test procedure will not change the regulation: (1) Clearly specifies the
Environmental Policy Act of 1969
energy efficiency of marginally preemptive effect, if any; (2) clearly
compliant units. DOE has determined that this rule specifies any effect on existing Federal
falls into a class of actions that are law or regulation; (3) provides a clear
V. Procedural Requirements categorically excluded from review legal standard for affected conduct
A. Review Under Executive Order 12866 under the National Environmental while promoting simplification and
Policy Act of 1969 (42 U.S.C. 4321 et burden reduction; (4) specifies the
Today’s regulatory action is not a seq.) and DOE’s implementing retroactive effect, if any; (5) adequately
‘‘significant regulatory action’’ under regulations at 10 CFR part 1021. This defines key terms; and (6) addresses
section 3(f) of Executive Order 12866, rule amends an existing rule without other important issues affecting clarity
Regulatory Planning and Review, 58 FR changing its environmental effect, and, and general draftsmanship under any
51735 (October 4, 1993). Accordingly, therefore, is covered by the Categorical guidelines issued by the Attorney
this action was not subject to review Exclusion in paragraph A5 to subpart D, General. Section 3(c) of Executive Order
under the Executive Order by the Office 10 CFR part 1021. Accordingly, neither 12988 requires Executive agencies to
of Information and Regulatory Affairs in an environmental assessment nor an review regulations in light of applicable
the Office of Management and Budget. environmental impact statement is standards in section 3(a) and section
required. 3(b) to determine whether they are met
B. Review Under the Regulatory
Flexibility Act E. Review Under Executive Order 13132 or it is unreasonable to meet one or
Executive Order 13132, ‘‘Federalism,’’ more of them. DOE has completed the
The Regulatory Flexibility Act (5 required review and determined that, to
U.S.C. 601 et seq.) requires preparation 64 FR 43255 (August 4, 1999) imposes
certain requirements on agencies the extent permitted by law, this rule
of an initial regulatory flexibility meets the relevant standards of
analysis for any rule that by law must formulating and implementing policies
or regulations that preempt State law or Executive Order 12988.
be proposed for public comment, unless
the agency certifies that the rule, if that have federalism implications. The G. Review Under the Unfunded
promulgated, will not have a significant Executive Order requires agencies to Mandates Reform Act of 1995
economic impact on a substantial examine the constitutional and statutory
authority supporting any action that Title II of the Unfunded Mandates
number of small entities. As required by Reform Act of 1995 (Pub. L. 104–4)
Executive Order 13272, Proper would limit the policymaking discretion
of the States and to carefully assess the (UMRA) requires each Federal agency to
Consideration of Small Entities in assess the effects of Federal regulatory
Agency Rulemaking, 67 FR 53461 necessity for such actions. The
Executive Order also requires agencies actions on State, local, and Tribal
(August 16, 2002), DOE published governments and the private sector. For
procedures and policies on February 19, to have an accountable process to
ensure meaningful and timely input by a proposed regulatory action that may
2003, to ensure that the potential result in the expenditure by State, local
impacts of its rules on small entities are State and local officials in the
development of regulatory policies that and Tribal governments, in the
properly considered during the aggregate, or by the private sector of
rulemaking process. (68 FR 7990) The have federalism implications. On March
14, 2000, DOE published a statement of $100 million or more (adjusted annually
DOE procedures and policies are for inflation), section 202 of UMRA
available on the Office of General policy describing the intergovernmental
consultation process it will follow in the requires a Federal agency to publish
Counsel’s Web site: http:// estimates of the resulting costs, benefits,
www.gc.doe.gov. development of such regulations. (65 FR
13735) DOE examined this final rule and other effects on the national
DOE reviewed today’s final rule under and determined that it does not have a economy. (2 U.S.C. 1532(a),(b)) UMRA
the provisions of the Regulatory substantial direct effect on the States, on also requires a Federal agency to
Flexibility Act and the procedures and the relationship between the national develop an effective process to permit
policies published on February 19, government and the States, or on the timely input by elected officers of State,
2003. 68 FR 7990. DOE certified in the distribution of power and local, and Tribal governments on a
July 20, 2006, proposed rule that the responsibilities among the various proposed ‘‘significant intergovernmental
proposed rule would not impose a levels of government. Executive Order mandate,’’ and requires an agency plan
significant economic impact on a 13132 requires no further action. for giving notice and opportunity for
substantial number of small entities. (66 timely input to potentially affected
FR 6780) DOE received no comments on F. Review Under Executive Order 12988 small governments before establishing
this issue, and after considering the Regarding the review of existing any requirements that might
potential small entity impact of this regulations and the promulgation of significantly or uniquely affect small
final rule, DOE affirms the certification new regulations, section 3(a) of governments. On March 18, 1997, DOE
that this rule will not have a significant Executive Order 12988, ‘‘Civil Justice published a statement of policy on its
economic impact on a substantial Reform’’ 61 FR 4729 (February 7, 1996), process for intergovernmental
number of small entities. imposes on Federal agencies the general consultation under UMRA (62 FR
C. Review Under the Paperwork duty to adhere to the following 12820) (also available at http://
Reduction Act of 1995 requirements: (1) Eliminate drafting www.gc.doe.gov). The rule published
errors and ambiguity; (2) write today contains neither an
pwalker on PROD1PC71 with RULES3

This rulemaking imposes no new regulations to minimize litigation; and intergovernmental mandate, nor a
information or record keeping (3) provide a clear legal standard for mandate that may result in an
requirements. Accordingly, Office of affected conduct rather than a general expenditure of $100 million or more in
Management and Budget (OMB) standard and promote simplification any year, so these requirements do not
clearance is not required under the and burden reduction. Section 3(b) of apply.

VerDate Aug<31>2005 17:58 Oct 19, 2007 Jkt 214001 PO 00000 Frm 00014 Fmt 4701 Sfmt 4700 E:\FR\FM\22OCR3.SGM 22OCR3
Federal Register / Vol. 72, No. 203 / Monday, October 22, 2007 / Rules and Regulations 59919

H. Review Under the Treasury and energy supply, distribution, or use Issued in Washington, DC, on September
General Government Appropriations should the proposal be implemented, 27, 2007.
Act, 1999 and of reasonable alternatives to the Alexander A. Karsner,
Section 654 of the Treasury and action and their expected benefits on Assistant Secretary, Energy Efficiency and
energy supply, distribution, and use. Renewable Energy.
General Government Appropriations
Act, 1999 (Pub. L. 105–277) requires Today’s regulatory action would not For the reasons set forth in the
Federal agencies to issue a Family have a significant adverse effect on the preamble, Part 430 of Chapter II of Title
Policymaking Assessment for any rule supply, distribution, or use of energy 10, Code of Federal Regulations is
that may affect family well-being. This and, therefore, is not a significant amended as set forth below:
rule would not have any impact on the energy action. Accordingly, DOE has not
PART 430—ENERGY CONSERVATION
autonomy or integrity of the family as prepared a Statement of Energy Effects.
PROGRAM FOR CONSUMER
an institution. Accordingly, DOE has
L. Review Under Section 32 of the PRODUCTS
concluded that it is not necessary to
prepare a Family Policymaking Federal Energy Administration Act of
1974 ■ 1. The authority citation for part 430
Assessment. continues to read as follows:
I. Review Under Executive Order 12630 Under section 301 of the Department Authority: 42 U.S.C. 6291–6309; 28 U.S.C.
DOE has determined, under Executive of Energy Organization Act (Pub. L. 95– 2461 note.
Order 12630, ‘‘Governmental Actions 91), the Department of Energy must
■ 2. Section 430.2 is amended in
and Interference with Constitutionally comply with section 32 of the Federal
subpart A by adding definitions of
Protected Property Rights,’’ 53 FR 8859 Energy Administration Act of 1974
‘‘ARM/simulation adjustment factor,’’
(March 18, 1988), that this regulation (FEAA), as amended by the Federal
‘‘indoor unit,’’ ‘‘outdoor unit,’’ ‘‘private
would not result in any takings which Energy Administration Authorization
labeler,’’ and ‘‘tested combination,’’ in
might require compensation under the Act of 1977. (15 U.S.C. 788) Section 32
alphabetical order, to read as follows:
Fifth Amendment to the United States provides in essence that, where a
Constitution. proposed rule contains or involves use § 430.2 Definitions.
of commercial standards, the notice of * * * * *
J. Review Under the Treasury and proposed rulemaking must inform the ARM/simulation adjustment factor
General Government Appropriations public of the use and background of means a factor used as part of a DOE-
Act, 2001 such standards. This final rule updates approved alternative rating method
Section 515 of the Treasury and references to the most recent versions of (ARM) to improve the accuracy of the
General Government Appropriations four commercial standards, as discussed calculated ratings for untested split-
Act, 2001 (44 U.S.C. 3516 note) requires in section II.F of this preamble. system central air conditioners or heat
agencies to review most disseminations The Department has evaluated these pumps. The adjustment factor
of information to the public under standards and is unable to conclude associated with each outdoor unit must
guidelines established by each agency whether they fully comply with the be set such that it reduces the difference
pursuant to general guidelines issued by between the SEER (HSPF) determined
requirements of section 32(b) of the
OMB. OMB’s guidelines were published using the ARM and a split-system
FEAA, i.e., that they were developed in
at 67 FR 8452 (February 22, 2002), and combination tested in accordance with
a manner which fully provides for
DOE’s guidelines were published at 67 § 430.24(m)(1). The ARM/simulation
public participation, comment and
FR 62446 (October 7, 2002). DOE has adjustment factor is an integral part of
review. As required by section 32(c) of
reviewed today’s notice under the OMB the ARM and must be a DOE-approved
and DOE guidelines and has concluded the FEAA, the Department has
consulted with the Attorney General element in accordance with 10 CFR
that it is consistent with applicable 430.24(m)(4) to (m)(6).
policies in those guidelines. and the Chairman of the Federal Trade
Commission concerning the impact of * * * * *
K. Review Under Executive Order 13211 these four standards on competition, Indoor unit means a component of a
Executive Order 13211, ‘‘Actions and neither recommended against split-system central air conditioner or
Concerning Regulations That incorporation of these standards. heat pump that is designed to transfer
Significantly Affect Energy Supply, heat between the refrigerant and the
M. Congressional Notification indoor air, and which consists of an
Distribution, or Use,’’ 66 FR 28355 (May
22, 2001), requires Federal agencies to indoor coil, a cooling mode expansion
As required by 5 U.S.C. 801, DOE will
prepare and submit to OIRA, a device, and may include an air moving
report to Congress on the promulgation
Statement of Energy Effects for any device.
of today’s rule prior to its effective date.
proposed significant energy action. A The report will state that it has been * * * * *
‘‘significant energy action’’ is defined as Outdoor unit means a component of
determined that the rule is not a ‘‘major
any action by an agency that a split-system central air conditioner or
rule’’ as defined by 5 U.S.C. 804(2).
promulgated or is expected to lead to heat pump that is designed to transfer
promulgation of a final rule, and that: VI. Approval of the Office of the heat between the refrigerant and the
(1) Is a significant regulatory action Secretary outdoor air, and which consists of an
under Executive Order 12866, or any outdoor coil, compressor(s), an air
successor order; and (2) is likely to have The Secretary of Energy has approved moving device, and in addition for heat
a significant adverse effect on the publication of this final rule. pumps, a heating mode expansion
supply, distribution, or use of energy, or List of Subjects in 10 CFR Part 430 device, reversing valve, and defrost
pwalker on PROD1PC71 with RULES3

(3) is designated by the Administrator of controls.


OIRA as a significant energy action. For Administrative practice and * * * * *
any proposed significant energy action, procedure, Energy conservation, Private labeler means an owner of a
the agency must give a detailed Household appliances, Incorporation by brand or trademark on the label of a
statement of any adverse effects on reference. consumer product which bears a private

VerDate Aug<31>2005 17:58 Oct 19, 2007 Jkt 214001 PO 00000 Frm 00015 Fmt 4701 Sfmt 4700 E:\FR\FM\22OCR3.SGM 22OCR3
59920 Federal Register / Vol. 72, No. 203 / Monday, October 22, 2007 / Rules and Regulations

label. A consumer product bears a § 430.23 Test procedures for the coil that is likely to have the largest
private label if: measurement of energy and water volume of retail sales with the particular
(1) Such product (or its container) is consumption. model of condensing unit. For mini-
labeled with the brand or trademark of * * * * * split condensing units that are designed
a person other than a manufacturer of (m) * * * to always be installed with more than
such product; (5) All measures of energy one indoor unit, a ‘‘tested combination’’
(2) The person with whose brand or consumption must be determined by the as defined in 10 CFR 430.2 shall be used
trademark such product (or container) is test method as set forth in appendix M for tests pursuant to paragraph (m)(1) of
labeled has authorized or caused such to this subpart; or by an alternative this section. For multi-split systems,
product to be so labeled; and rating method set forth in § 430.24(m)(4) each model of condensing unit shall be
(3) The brand or trademark of a as approved by the Assistant Secretary tested with two different sets of indoor
manufacturer of such product does not for Energy Efficiency and Renewable units. For one set, a ‘‘tested
appear on such label. Energy in accordance with combination’’ composed entirely of non-
* * * * * § 430.24(m)(5). ducted indoor units shall be used. For
Tested combination means a multi- * * * * * the second set, a ‘‘tested combination’’
split system with multiple indoor coils composed entirely of ducted indoor
having the following features: ■ 5. Section 430.24 is amended in units shall be used. Components of
(1) The basic model of a system used subpart B by revising paragraph (m) to similar design may be substituted
as a tested combination shall consist of read as follows: without requiring additional testing if
one outdoor unit, with one or more the represented measures of energy
§ 430.24 Units to be tested.
compressors, that is matched with consumption continue to satisfy the
between 2 and 5 indoor units; for multi- * * * * * applicable sampling provisions of
split systems, each of these indoor units (m)(1) For central air conditioners and paragraphs (m)(1)(i) and (m)(1)(ii) of this
shall be designed for individual heat pumps, each single-package system section. However, for any split-system
operation. and each condensing unit (outdoor unit) air conditioner having a single-speed
(2) The indoor units shall— of a split-system, when combined with compressor, the condenser-evaporator
(i) Represent the highest sales model a selected evaporator coil (indoor unit) coil combination selected for tests
family, or another indoor model family or a set of selected indoor units, must pursuant to paragraph (m)(1) of this
if the highest sales model family does have a sample of sufficient size tested in section shall include the indoor coil-
not provide sufficient capacity (see ii); accordance with the applicable only unit that is likely to have the
(ii) Together, have a nominal capacity provisions of this subpart. The largest volume of retail sales with the
that is between 95% and 105% of the represented values for any model of particular model of outdoor unit. This
nominal capacity of the outdoor unit; single-package system, any model of a coil-only requirement does not apply to
(iii) Not, individually, have a capacity tested split-system combination, any split-system air conditioners that are
that is greater than 50% of the nominal model of a tested mini-split system only sold and installed with blower-coil
capacity of the outdoor unit; combination, or any model of a tested indoor units, specifically mini-splits,
(iv) Operate at fan speeds that are multi-split system combination must be multi-splits, and through-the-wall units.
consistent with the manufacturer’s assigned such that — This coil-only requirement does not
specifications; and (i) Any represented value of estimated
(v) All be subject to the same apply to any split-system heat pumps.
annual operating cost, energy For every other split-system
minimum external static pressure consumption or other measure of energy
requirement (i.e., 0 inches of water combination that includes the same
consumption of the central air model of condensing unit but a different
column for non-ducted, see Table 2 in conditioner or heat pump for which
Appendix M to Subpart B of this part for model of evaporator coil and for every
consumers would favor lower values other mini-split and multi-split system
ducted indoor units) while being must be no less than the higher of:
configurable to produce the same static that includes the same model of
(A) The mean of the sample; or condensing unit but a different set of
pressure at the exit of each outlet (B) The upper 90-percent confidence
plenum when manifolded as per section evaporator coils, whether the evaporator
limit of the true mean divided by 1.05; coil(s) is manufactured by the same
2.4.1 of Appendix M. (ii) Any represented value of the manufacturer or by a component
* * * * * energy efficiency or other measure of manufacturer, either—
§ 430.22 [Amended]
energy consumption of the central air (i) A sample of sufficient size,
conditioner or heat pump for which comprised of production units or
■ 3. Section 430.22 is amended as consumers would favor higher values representing production units, must be
follows: must be no greater than the lower of: tested as complete systems with the
■ a. Paragraph (b)(5)2. is amended by (A) The mean of the sample; or resulting ratings for the outdoor unit-
removing ‘‘23–1993’’ and adding in its (B) The lower 90-percent confidence indoor unit(s) combination obtained in
place ‘‘23–2005.’’ limit of the true mean divided by 0.95;
■ b. Paragraph (b)(5)3. is amended by
accordance with paragraphs (m)(1)(i)
(iii) For heat pumps, all units of the and (m)(1)(ii) of this section; or
removing ‘‘37–1988’’ and adding in its sample population must be tested in (ii) The representative values of the
place ‘‘37–2005.’’ both the cooling and heating modes and
■ c. Paragraph (b)(5)8. is amended by
measures of energy efficiency must be
the results used for determining the heat assigned as follows,
removing ‘‘116–1995’’ and adding in its
pump’s certified SEER and HSPF ratings (A) Using an alternative rating method
place ‘‘116–1995 (RA 2005).’’
in accordance with paragraph (m)(1)(ii) (ARM) that has been approved by DOE
■ d. Paragraph (b)(8) is amended by
of this section. in accordance with the provisions of
removing ‘‘210/240–2003’’ and adding
pwalker on PROD1PC71 with RULES3

(2) For split-system air conditioners paragraphs (m)(4) through (m)(6) of this
in its place ‘‘210/240–2006.’’
and heat pumps, the condenser- section; or
■ 4. Section 430.23 is amended in evaporator coil combination selected for (B) For multi-split systems composed
subpart B by revising paragraph (m)(5) tests pursuant to paragraph (m)(1) of entirely of non-ducted indoor units, set
to read as follows: this section shall include the evaporator equal to the system tested in accordance

VerDate Aug<31>2005 17:58 Oct 19, 2007 Jkt 214001 PO 00000 Frm 00016 Fmt 4701 Sfmt 4700 E:\FR\FM\22OCR3.SGM 22OCR3
Federal Register / Vol. 72, No. 203 / Monday, October 22, 2007 / Rules and Regulations 59921

with paragraph (m)(1) of this section section. Thereafter, apply the ARM ducted systems, etc.) must be stated in
whose tested combination was entirely using the derived adjustment factor(s) the documentation.
non-ducted indoor units; only when determining the ratings for (iii) Complete test data from
(C) For multi-split systems composed untested combinations having the same laboratory tests on four mixed (i.e., non-
entirely of ducted indoor units, set outdoor unit. highest-sales-volume combination)
equal to the system tested in accordance (5) Manufacturers or private labelers systems per each ARM.
with paragraph (m)(1) of this section who elect to use an ARM for (A) The four mixed systems must
whose tested combination was entirely determining measures of energy include four different indoor units and
ducted indoor units; and consumption under paragraphs at least two different outdoor units. A
(D) For multi-split systems having a (m)(2)(ii)(A) and (m)(4) of this section particular model of outdoor unit may be
mix of non-ducted and ducted indoor must submit a request for DOE to review tested with up to two of the four indoor
units, set equal to the mean of the the ARM. Send the request to the units. The four systems must include
values for the two systems — one Assistant Secretary of Energy Efficiency two low-capacity mixed systems and
having the tested combination of all and Renewable Energy, 1000 two high-capacity mixed systems. The
non-ducted units and the second having Independence Avenue, SW., low-capacity mixed systems may have
the tested combination of all ducted Washington, DC 20585–0121. Approval any capacity. The rated capacity of each
indoor units — tested in accordance must be received from the Assistant high-capacity mixed system must be at
with paragraph (m)(1) of this section. Secretary to use the ARM before the least a factor of two higher than its
(3) Whenever the representative ARM may be used for rating split- counterpart low-capacity mixed system.
values of the measures of energy system central air conditioners and heat The four mixed systems must meet the
consumption, as determined by the pumps. If a manufacturer has a DOE- applicable energy conservation standard
provisions of paragraph (m)(2)(ii) of this approved ARM for products also in § 430.32(c) in effect at the time of the
section, do not agree within 5 percent of distributed in commerce by a private rating.
the representative values of the labeler, the ARM may also be used by
measures of energy consumption as (B) The four indoor units must come
the private labeler for rating these from at least two different coil families,
determined by actual testing, the products. Once an ARM is approved,
representative values determined by with a maximum of two indoor units
DOE may contact a manufacturer to coming from the same coil family. Data
actual testing must be used to comply learn if their ARM has been modified in
with section 323(c) of the Act or to for two indoor units from the same coil
any way and to verify that the ARM is
comply with rules under section 324 of family, if submitted, must come from
being applied as approved. DOE will
the Act. testing with one of the ‘‘low-capacity
give follow-up priority to individual
(4) The basis of the ARM referred to mixed systems’’ and one of the ‘‘high
combinations having questionably high
in paragraph (m)(2)(ii) of this section capacity mixed systems.’’ A mixed
ratings (e.g., a coil-only system having a
must be a representation of the test data system indoor coil may come from the
rating that exceeds the rating of a coil-
and calculations of a mechanical vapor- same coil family as the highest-sales-
only highest sales volume combination
compression refrigeration cycle. The volume-combination indoor unit (i.e.,
by more than 6 percent).
major components in the refrigeration (6) Each request to DOE for approval the ‘‘matched’’ indoor unit) for the
cycle must be modeled as ‘‘fits’’ to of an alternative rating method must particular outdoor unit. Data on mixed
manufacturer performance data or by include: systems where the indoor unit is now
graphical or tabular performance data. (i) The name, mailing address, obsolete will be accepted towards the
Heat transfer characteristics of coils may telephone number, and e-mail address ARM-validation submittal requirement
be modeled as a function of face area, of the official representing the if it is from the same coil family as other
number of rows, fins per inch, manufacturer. indoor units still in production.
refrigerant circuitry, air-flow rate and (ii) Complete documentation of the (C) The first two sentences of
entering-air enthalpy. Additional alternative rating method to allow DOE paragraph (m)(6)(iii)(B) of this section
performance-related characteristics to be to evaluate its technical adequacy. The do not apply if the manufacturer offers
considered may include type of documentation must include a indoor units from only one coil family.
expansion device, refrigerant flow rate description of the methodology, state In this case only, all four indoor coils
through the expansion device, power of any underlying assumptions, and must be selected from this one coil
the indoor fan and cyclic-degradation explain any correlations. The family. If approved, the ARM will be
coefficient. Ratings for untested documentation should address how the specifically limited to applications for
combinations must be derived from the method accounts for the cyclic- this one coil family.
ratings of a combination tested in degradation coefficient, the type of (iv) All product information on each
accordance with paragraph (m)(1) of this expansion device, and, if applicable, the mixed system indoor unit, each
section. The seasonal energy efficiency indoor fan-off delay. The requestor must matched system indoor unit, and each
ratio (SEER) and/or heating seasonal submit any computer programs— outdoor unit needed to implement the
performance factor (HSPF) ratings for an including spreadsheets—having less proposed ARM. The calculated ratings
untested combination must be set equal than 200 executable lines that for the four mixed systems, as
to or less than the lower of the SEER implement the ARM. Longer computer determined using the proposed ARM,
and/or HSPF calculated using the programs must be identified and must be provided along with any other
applicable DOE-approved alternative sufficiently explained, as specified related information that will aid the
rating method (ARM). If the method above, but their inclusion in the initial verification process.
includes an ARM/simulation submittal package is optional. (v) If request for approval is for an
adjustment factor(s), determine the Applicability or limitations of the ARM updated ARM, manufacturers must
pwalker on PROD1PC71 with RULES3

value(s) of the factors(s) that yield the (e.g., only covers single-speed units identify modifications made to the ARM
best match between the SEER/HSPF when operating in the cooling mode, since the last submittal, including any
determined using the ARM versus the covers units with rated capacities of 3 ARM/simulation adjustment factor(s)
SEER/HSPF determined from testing in tons or less, not applicable to the added since the ARM was last approved
accordance with paragraph (m)(1) of this manufacturer’s product line of non- by DOE.

VerDate Aug<31>2005 17:58 Oct 19, 2007 Jkt 214001 PO 00000 Frm 00017 Fmt 4701 Sfmt 4700 E:\FR\FM\22OCR3.SGM 22OCR3
59922 Federal Register / Vol. 72, No. 203 / Monday, October 22, 2007 / Rules and Regulations

(7) Manufacturers that elect to use an ■ b. In section 2, Testing Conditions: ■ 8. Section 3.1.4.2b is amended by
alternative rating method for ■ 1. Sections 2.1a, 2.2a, 2.2b, 2.2.3, revising the equation for minimum
determining measures of energy 2.2.5, 2.4.1, and 2.4.2 are revised to read external static pressure to read as set
consumption under paragraphs as set forth below. forth below.
(m)(2)(ii)(A) and (m)(4) of this section ■ 2. Section 2.3.1b is amended by ■ 9. Section 3.1.4.2c is amended by
must either subject a sample of their removing ‘‘Certified’’ and adding in its removing ‘‘Certified’’ and adding in its
units to independent testing on a regular place ‘‘Full-load.’’ place ‘‘Full-load.’’
basis, e.g., through a voluntary ■ 3. Section 2.5.3 is amended by ■ 10. Section 3.1.4.3a is amended by
certification program, or have the revising the first sentence to read as set revising the ‘‘Cooling Intermediate Air
representations reviewed and certified forth below. Volume Rate’’ equation to read as set
■ 4. New section 2.5.4.3 is added to read forth below.
by an independent state-registered
professional engineer who is not an as set forth below. ■ 11. Section 3.1.4.3b is amended by
■ 5. Section 2.6a is amended by adding revising the ‘‘Ev Test DPst ’’ equation to
employee of the manufacturer. The
in the first sentence ‘‘(RA05)’’ after read as set forth below.
registered professional engineer is to
‘‘116–95.’’ ■ 12. Section 3.1.4.4 is amended by
certify that the results of the alternative ■ 6. Section 2.6b is amended in the
rating procedure accurately represent removing ‘‘Certified’’ and adding in its
second sentence, and in the last place ‘‘Full-load.’’
the energy consumption of the unit(s). sentence, by removing ‘‘37–88’’ and ■ 13. Section 3.1.4.4.1 is amended by
The manufacturer is to keep the adding in its place ‘‘37–2005;’’ and by removing ‘‘Certified’’ and adding in its
registered professional engineer’s removing ‘‘ARI Standard 210/240– place ‘‘Full-load’’ in three locations.
certifications on file for review by DOE 2003’’ and adding in its place ‘‘ARI ■ 14. Section 3.1.4.4.2 is amended by
for as long as said combination is made Standard 210/240–2006’’ in the second removing ‘‘Certified’’ and adding in its
available for sale by the manufacturer. sentence. place ‘‘Full-load’’ and revising the
Any proposed change to the alternative ■ 7. Section 2.7 is amended by ‘‘Heating Certified Air Volume Rate’’
rating method must be approved by removing ‘‘ARI Standard 210/240– equation to read as set forth below.
DOE prior to its use for rating. 2003’’ and adding in its place ‘‘ARI ■ 14a. Section 3.1.4.4.2a is amended by
(8) Manufacturers who choose to use Standard 210/240–2006.’’ removing ‘‘Certified’’ and adding in its
computer simulation or engineering ■ 8. Section 2.10.2 is amended in the place ‘‘Full-load.’’
analysis for determining measures of third and fourth sentences, by removing ■ 15. Section 3.1.4.4.2b is amended by
energy consumption under paragraphs ‘‘37–88’’ and adding in its place ‘‘37– removing ‘‘Certified’’ and adding in its
(m)(2)(ii)(A) and (m)(4) through (m)(7) 2005.’’ place ‘‘Full-load’’ in three locations, and
of this section must permit ■ 9. Section 2.10.3 is amended in the revising the ‘‘Heating Certified DPst’’
representatives of the Department of second sentence, by removing ‘‘7.6.2,’’ equation to read as set forth below.
Energy to inspect for verification and adding in its place ‘‘7.5.2,’’ and by ■ 16. Section 3.1.4.4.2c is amended by
purposes the simulation method(s) and removing ‘‘37–88’’ and adding in its removing ‘‘Certified’’ and adding in its
computer program(s) used. This place ‘‘37–2005’’ in the second and place ‘‘Full-load’’ in three locations.
inspection may include conducting third sentences. ■ 17. Sections 3.1.4.4.3 and 3.1.4.4.3a
simulations to predict the performance ■ 10. Section 2.11a is amended in the are revised to read as set forth below.
of particular outdoor unit ‘‘ indoor unit first sentence, by removing ‘‘37–88’’ and ■ 17a. Sections 3.1.4.4.3b is amended by
combinations specified by DOE, adding in its place ‘‘37–2005.’’ revising the first sentence to read as set
analysis of previous simulations ■ 11. Section 2.13 is amended in the forth below.
conducted by the manufacturer, or both. second sentence, by removing ‘‘37–88’’ ■ 18. Amend sections 3.1.4.4.3b,

* * * * * and adding in its place ‘‘37–2005.’’ 3.1.4.4.3c and 3.1.4.4.4 by removing


■ c. In section 3, Testing Procedures: ‘‘Certified’’ and adding in its place
Appendix M—[Amended] ■ 1. Section 3.1.1 is amended by ‘‘Full-load.’’
revising the seventh sentence to read as ■ 19. Section 3.1.4.5a is amended by
■ 6. Appendix M to subpart B of part revising the ‘‘Heating Minimum Air
set forth below.
430 is amended: ■ 2. Section 3.1.3 is amended by Volume Rate’’ equation to read as set
■ a. In section 1. Definitions:
removing ‘‘ARI Standard 210/240– forth below.
■ 1. Section 1.3 is amended by
2003’’ and adding in its place ‘‘ARI ■ 20. Section 3.1.4.5b is amended by
removing ‘‘210/240–2003’’ and adding Standard 210/240–2006.’’ revising the ‘‘H01, H11, H21, H31, Test
in its place ‘‘210/240–2006’’; and by ■ 3. Section 3.1.4.1 is amended by DPst’’ equation to read as set forth below.
removing ‘‘2003’’ and adding in its removing ‘‘Certified’’ and adding in its ■ 21. Section 3.1.4.5d is amended by
place ‘‘2006.’’ place ‘‘Full-load.’’ removing Certified and adding in its
■ 2. Section 1.5 is amended by ■ 4. Section 3.1.4.1.1, from its title to place Full-load in two locations.
removing ‘‘23–93’’ and adding in its the end of paragraph a., and Table 2, are ■ 22. Section 3.1.4.6a is amended by
place ‘‘23–2005’’; and by removing revised to read as set forth below. revising the ‘‘Heating Intermediate Air
‘‘1993’’ and adding in its place ‘‘2005.’’ ■ 4a. Section 3.1.4.1.1b is amended by Volume Rate’’ equation to read as set
■ 3. Section 1.6 is amended by revising the first sentence to read as set forth below.
removing ‘‘37–88’’ and adding in its forth below. ■ 23. Section 3.1.4.6b is amended by
place ‘‘37–2005’’; and by removing ■ 5. Amend sections 3.1.4.1.1b and revising the ‘‘H2v Test DPst’’ equation to
‘‘1988’’ and adding in its place ‘‘2005.’’ 3.1.4.1.1c by removing ‘‘Certified’’ and read as set forth below.
■ 4. Section 1.12 is amended by adding adding in its place ‘‘Full-load.’’ ■ 24. Section 3.1.4.7 is amended by
‘‘RA(05)’’ after ‘‘116–95’’; and adding ■ 6. Section 3.1.4.1.2 is amended by revising the ‘‘Heating Nominal Air
‘‘and reaffirmed in 2005’’ after ‘‘1995.’’ removing ‘‘Certified’’ and adding in its Volume Rate’’ equation and the ‘‘H1N
pwalker on PROD1PC71 with RULES3

■ 5. Section 1.35 is amended by place ‘‘Full-load’’ in two locations. Test DPst’’ equation to read as set forth
removing ‘‘certified’’ and adding in its ■ 7. Section 3.1.4.2a is amended by below.
place ‘‘full-load.’’ revising the ‘‘Cooling Minimum Air Vol. ■ 25. Section 3.1.5 is amended in the
■ 6. Section 1.37 is revised to read as set Rate’’ equation to read as set forth first sentence by removing ‘‘37–88’’ and
forth below. below. adding in its place ‘‘37–2005.’’

VerDate Aug<31>2005 17:58 Oct 19, 2007 Jkt 214001 PO 00000 Frm 00018 Fmt 4701 Sfmt 4700 E:\FR\FM\22OCR3.SGM 22OCR3
Federal Register / Vol. 72, No. 203 / Monday, October 22, 2007 / Rules and Regulations 59923

■ 26. Section 3.1.6 is amended in the ■ 45. Section 3.6.1 is amended by ■ 1. Sections 4.1.2.1a and 4.1.2.1d are
first and second sentences, by removing revising the second, third, and fourth amended by removing ‘‘Certified’’ and
‘‘7.8.3.1 and 7.8.3.2’’ and adding in its sentences to read as set forth below. adding in its place ‘‘Full-load.’’
place ‘‘7.7.2.1 and 7.7.2.2,’’ and in the ■ 46. Table 9 to Section 3.6.1 is ■ 2. Section 4.1.3 is amended by
first sentence, by removing ‘‘37–88’’ and amended by removing ‘‘Certified’’ and revising the introductory text, equations
adding in its place ‘‘37–2005,’’ and by adding in its place ‘‘Full-load’’ in three 4.1.3–1 and 4.1.3–2, the paragraph
adding a new sentence after the second locations. preceding equation 4.1.3–3, and
sentence, to read as set forth below. ■ 47. Section 3.6.2 is amended by equation 4.1.3–3 to read as set forth
■ 27. Section 3.1.7 is amended by revising the introductory text to read as below.
removing ‘‘certified’’ and adding in its set forth below. ■ 3. Section 4.1.3.3 is amended by
place ‘‘Full-load’’ in four locations. ■ 48. Table 10 to Section 3.6.2 is revising the equation for PLFj and the
■ 28. Section 3.1.9 is amended by amended by removing ‘‘Certified’’ and text following the equation to read as set
removing ‘‘Certified’’ and adding in its adding in its place ‘‘Full-load’’ in three forth below.
place ‘‘Full-load.’’ locations. ■ 4. Section 4.1.4 is amended by
■ 28a. Section 3.2.1 is amended by
■ 49. Section 3.6.3 is revised as set forth revising everything except for the
revising the fourth sentence to read as below. equations for calculating MQ and ME, to
set forth below. ■ 50. Table 11 to section 3.6.3 is revised
■ 29. Table 3 to Section 3.2.1 is
read as set forth below.
as set forth below. ■ 5. Section 4.1.4.1 is amended by
amended by removing ‘‘certified’’ and
■ 51. Section 3.6.4 is amended by revising the second sentence after the
adding in its place ‘‘full-load’’ in three
revising the third, fourth, and fifth explanation of terms in the equations
locations in the last column.
■ 29a. Section 3.2.2.1 is amended by
sentences of paragraph a. and adding a (‘‘Use Equations 4.1.3–1 and 4.1.3–2,
revising the third sentence to read as set new paragraph c. to read as set forth respectively, to evaluate Q̇ck=1 (Tj)’’ and
forth below. below. Ėck=1 (Tj) to read as set forth below.
■ 30. Table 4 to Section 3.2.2.1 is ■ 52. Table 12 to section 3.6.4 is revised ■ 6. Section 4.1.4.2 is amended by
amended by removing ‘‘certified’’ and to read as set forth below. revising the equation numbers
adding in its place ‘‘full-load’’ in two ■ 53. Section 3.7a is amended in the referenced in the descriptions of the
locations in the last column. fifth sentence by removing ‘‘Table 5 of quantities T1 and Tv, revising the
■ 31. Section 3.2.2.2 is amended by ASHRAE Standard 37–88’’ and adding equation numbers referred to in the
removing ‘‘Certified’’ and adding in its in its place ‘‘Table 3 of ASHRAE equations for EERk=1 (T1) and EERk=v
place ‘‘Full-load.’’ Standard 37–2005,’’ and in the sixth (Tv), and adding text at the end of the
■ 32. Sections 3.2.3a is revised as set sentence, by removing ‘‘Table 5’’ and section to read as set forth below.
forth below. adding in its place ‘‘Table 3.’’ ■ 7. Section 4.2.3.3 is amended by
■ 33. Section 3.2.3b is amended by ■ 54. Section 3.7b is amended by revising the equation for PLFj and the
removing ‘‘Certified’’ and adding in its revising the first sentence to read as set text following the equation to read as set
place ‘‘Full-load.’’ forth below. forth below.
■ 34. Section 3.2.3d is revised as set ■ 55. The title of section 3.8 is revised ■ 8. The Section 4.2.4 equations for MQ
forth below. to read as set forth below. and ME are revised to read as set forth
■ 35. Table 5 to section 3.2.3 is revised ■ 56. The introductory text and the first below.
as set forth below. equation of section 3.8.1 are revised to ■ 9. Section 4.2.4.2 is amended by
■ 36. Section 3.2.4.a is amended by read as set forth below.
revising the third sentence to read as set adding text at the end of the section to
■ 57. Section 3.9c is revised to read as read as set forth below.
forth below. set forth below.
■ 37. Section 3.2.4b is amended by The additions and revisions read as
■ 58. Section 3.9f is amended by
removing ‘‘Certified’’ and adding in its follows:
revising the fifth sentence and adding a
place ‘‘Full-load.’’ parenthetical immediately following it Appendix M to Subpart B of Part 430—
■ 38. Table 6 to section 3.2.4 is revised Uniform Test Method for Measuring the
to read as set forth below.
as set forth below. Energy Consumption of Central Air
■ 59. Section 3.9.1a is amended by
■ 39. Section 3.2.4 is amended by
adding a new sentence at the end of the Conditioners and Heat Pumps
adding a new paragraph (c) as set forth
section directly before section 3.9.1.b to * * * * *
below.
■ 40. Section 3.3b is amended in both
read as set forth below. 1. Definitions
■ 60. Section 3.9.2b is amended by
the first and second sentences, by * * * * *
removing ‘‘Table 5,’’ and adding in its replacing ‘‘Certified’’ with ‘‘Full-load.’’
1.37 Standard air means dry air
■ 61. Section 3.11 is amended by
place ‘‘Table 3,’’ and in the first having a mass density of 0.075 lb/ft3.
sentence by removing ‘‘37–88’’ and removing the introductory text
following the paragraph heading, which * * * * *
adding in its place ‘‘37–2005.’’ 2. Testing Conditions
■ 41. Section 3.3c is amended in the is republished below.
first sentence by removing ‘‘section ■ 62. Section 3.11.1.3b is revised to read * * * * *
7.3.3.1 of ASHRAE Standard 37–88,’’ as set forth below. 2.1 Test room requirements. a. Test
and adding in its place ‘‘sections 7.3.3.1 ■ 63. Section 3.11.2a is amended by using two side-by-side rooms, an indoor
and 7.3.3.3 of ASHRAE Standard 37– revising the seventh sentence to read as test room and an outdoor test room. For
2005.’’ set forth below. multiple-split air conditioners and heat
■ 42. The titles of sections 3.4 and 3.5 ■ 64. Section 3.11.2b is revised to read pumps (see Definition 1.30), however,
are revised as set forth below. as set forth below. use as many available indoor test rooms
pwalker on PROD1PC71 with RULES3

■ 43. Section 3.4b is revised to read as ■ 65. Section 3.11.3 is revised to read as as needed to accommodate the total
set forth below. set forth below. number of indoor units. These rooms
■ 44. Section 3.5.3 is amended by ■ d. In section 4, CALCULATIONS OF must comply with the requirements
revising the introductory text to read as SEASONAL PERFORMANCE specified in sections 8.1.2 and 8.1.3 of
set forth below. DESCRIPTORS: ASHRAE Standard 37–2005

VerDate Aug<31>2005 17:58 Oct 19, 2007 Jkt 214001 PO 00000 Frm 00019 Fmt 4701 Sfmt 4700 E:\FR\FM\22OCR3.SGM 22OCR3
59924 Federal Register / Vol. 72, No. 203 / Monday, October 22, 2007 / Rules and Regulations

(incorporated by reference, see small-duct, high-velocity systems, packaged systems, the indoor coil may
§ 430.22). configure all balance dampers or be located in the outdoor test room.)
* * * * * restrictor devices on or inside the unit b. For systems having multiple indoor
2.2 Test unit installation to fully open or lowest restriction. coils, attach a plenum to each indoor
requirements. a. Install the unit * * * * * coil outlet. Connect two or more outlet
according to section 8.2 of ASHRAE 2.2.3 Special requirements for multi- plenums to a single common duct so
Standard 37–2005 (incorporated by split air conditioners and heat pumps, that each indoor coil ultimately
reference, see § 430.22). With respect to and systems composed of multiple connects to an airflow measuring
interconnecting tubing used when mini-split units (outdoor units located apparatus (section 2.6). If using more
testing split systems, however, follow side-by-side) that would normally than one indoor test room, do likewise,
the requirements given in section 6.1.3.5 operate using two or more indoor creating one or more common ducts
of ARI Standard 210/240–2006 thermostats. For any test where the within each test room that contains
(incorporated by reference, see system is operated at part load (i.e., one multiple indoor coils. At the plane
§ 430.22). When testing triple-split or more compressors ‘‘off’’, operating at where each plenum enters a common
systems (see Definition 1.44), use the the intermediate or minimum duct, install an adjustable airflow
tubing length specified in section 6.1.3.5 compressor speed, or at low compressor damper and use it to equalize the static
of ARI Standard 210/240–2006 capacity), the manufacturer shall pressure in each plenum. Each outlet air
(incorporated by reference, see § 430.22) designate the particular indoor coils that temperature grid (section 2.5.4) and
to connect the outdoor coil, indoor are turned off during the test. For airflow measuring apparatus are located
compressor section, and indoor coil variable-speed systems, the downstream of the inlet(s) to the
while still meeting the requirement of manufacturer must designate at least common duct.
exposing 10 feet of the tubing to outside one indoor unit that is turned off for all
tests conducted at minimum compressor c. For small-duct, high-velocity
conditions. When testing split systems
speed. For all other part-load tests, the systems, install an outlet plenum that
having multiple indoor coils, connect
manufacturer shall choose to turn off has a diameter that is equal to or less
each indoor fan-coil to the outdoor unit
zero, one, two, or more indoor units. than the value listed below. The limit
using: (a) 25 feet of tubing, or (b) tubing
The chosen configuration shall remain depends only on the cooling Full-Load
furnished by the manufacturer,
unchanged for all tests conducted at the Air Volume Rate (see section 3.1.4.1.1)
whichever is longer. If they are needed
same compressor speed/capacity. For and is effective regardless of the flange
to make a secondary measurement of
any indoor coil that is turned off during dimensions on the outlet of the unit (or
capacity, install refrigerant pressure
a test, take steps to cease forced airflow an air supply plenum adapter accessory,
measuring instruments as described in
through this indoor coil and block its if installed in accordance with the
section 8.2.5 of ASHRAE Standard 37–
outlet duct. Because these types of manufacturer’s installation
2005 (incorporated by reference, see
systems will have more than one indoor instructions).
§ 430.22). Refer to section 2.10 of this
Appendix to learn which secondary fan and possibly multiple outdoor fans d. Add a static pressure tap to each
methods require refrigerant pressure and compressor systems, references in face of the (each) outlet plenum, if
measurements. At a minimum, insulate this test procedure to a single indoor rectangular, or at four evenly distributed
the low-pressure line(s) of a split-system fan, outdoor fan, and compressor means locations along the circumference of an
with insulation having an inside all indoor fans, all outdoor fans, and all oval or round plenum. Create a
diameter that matches the refrigerant compressor systems that are turned on manifold that connects the four static
tubing and a nominal thickness of 0.5 during the test. pressure taps. Figure 1 shows two of the
inch. * * * * * three options allowed for the manifold
b. For units designed for both 2.2.5 Additional refrigerant charging configuration; the third option is the
horizontal and vertical installation or requirements. Charging according to the broken-ring, four-to-one manifold
for both up-flow and down-flow vertical ‘‘manufacturer’s published configuration that is shown in Figure 7a
installations, the manufacturer must instructions,’’ as stated in section 8.2 of of ASHRAE Standard 37–2005
specify the orientation used for testing. ASHRAE Standard 37–2005 (incorporated by reference, see
Conduct testing with the following (incorporated by reference, see § 430.22). See Figures 7a, 7b, 7c, and 8
installed: § 430.22), means the manufacturer’s of ASHRAE Standard 37–2005
(1) the most restrictive filter(s); installation instructions that come (incorporated by reference, see § 430.22)
(2) supplementary heating coils; and packaged with the unit. * * * for the cross-sectional dimensions and
(3) other equipment specified as part * * * * * minimum length of the (each) plenum
of the unit, including all hardware used 2.4.1 Outlet plenum for the indoor and the locations for adding the static
by a heat comfort controller if so unit. a. Attach a plenum to the outlet of pressure taps for units tested with and
equipped (see Definition 1.28). For the indoor coil. (NOTE: for some without an indoor fan installed.

Maximum diameter* of
Cooling full-load air volume rate outlet plenum
(scfm) (inches)

≤500 ..................................................................................................................................................................................... 6
501 to 700 ............................................................................................................................................................................ 7
701 to 900 ............................................................................................................................................................................ 8
901 to 1100 .......................................................................................................................................................................... 9
pwalker on PROD1PC71 with RULES3

1101 to 1400 ........................................................................................................................................................................ 10


1401 to 1750 ........................................................................................................................................................................ 11
*If the outlet plenum is rectangular, calculate its equivalent diameter using (4A)/P, where A is the area and P is the perimeter of the rectan-
gular plenum, and compare it to the listed maximum diameter.

VerDate Aug<31>2005 17:58 Oct 19, 2007 Jkt 214001 PO 00000 Frm 00020 Fmt 4701 Sfmt 4700 E:\FR\FM\22OCR3.SGM 22OCR3
Federal Register / Vol. 72, No. 203 / Monday, October 22, 2007 / Rules and Regulations 59925

2.4.2 Inlet plenum for the indoor the pressure in the receiving chamber of a. For all ducted units tested with an
unit. Install an inlet plenum when the airflow measuring apparatus is no indoor fan installed, except those
testing a coil-only indoor unit or a more than 0.5 inch of water higher than having a variable-speed, constant-air-
packaged system where the indoor coil the surrounding test room ambient. In volume-rate indoor fan. The second
is located in the outdoor test room. Add lieu of installing a separate damper, use requirement applies exclusively to the A
static pressure taps at the center of each the outlet air damper box of sections 2.5 or A2 Test and is met as follows.
face of this plenum, if rectangular, or at and 2.5.4.1 if it allows variable 1. Achieve the Cooling Full-load Air
four evenly distributed locations along positioning. Also apply these steps to Volume Rate, determined in accordance
the circumference of an oval or round any conventional indoor blower unit with the previous paragraph;
plenum. Make a manifold that connects that creates a static pressure within the 2. Measure the external static
the four static-pressure taps using one of receiving chamber of the airflow pressure;
the three configurations specified in measuring apparatus that exceeds the 3. If this pressure is equal to or greater
section 2.4.1. See Figures 7b, 7c, and test room ambient pressure by more than the applicable minimum external
Figure 8 of ASHRAE Standard 37–2005 than 0.5 inches of water column. static pressure cited in Table 2, this
(incorporated by reference, see § 430.22) * * * * * second requirement is satisfied. Use the
for cross-sectional dimensions, the 3. Testing Procedures current air volume rate for all tests that
minimum length of the inlet plenum, require the Cooling Full-load Air
and the locations of the static-pressure * * * * *
3.1.1 Primary and secondary test Volume Rate.
taps. When testing a ducted unit having
methods. * * * 4. If the Table 2 minimum is not
an indoor fan (and the indoor coil is in
For this capacity comparison, use the equaled or exceeded,
the indoor test room), the manufacturer
has the option to test with or without an Indoor Air Enthalpy Method capacity 4a. reduce the air volume rate until
inlet plenum installed. Space that is calculated in section 7.3 of the applicable Table 2 minimum is
limitations within the test room may ASHRAE Standard 37–2005 equaled or
dictate that the manufacturer choose the (incorporated by reference, see § 430.22) 4b. until the measured air volume rate
latter option. If used, construct the inlet (and, if testing a coil-only unit, do not equals 95 percent of the air volume rate
plenum and add the four static-pressure make the after-test fan heat adjustments from step 1, whichever occurs first.
taps as shown in Figure 8 of ASHRAE described in section 3.3, 3.4, 3.7, and 5. If the conditions of step 4a occur
Standard 37–2005 (incorporated by 3.10 of this Appendix). * * * first, this second requirement is
reference, see § 430.22). Manifold the * * * * * satisfied. Use the step 4a reduced air
four static-pressure taps using one of the 3.1.4.1.1 Cooling Full-Load Air volume rate for all tests that require the
three configurations specified in section Volume Rate for Ducted Units. The Cooling Full-load Air Volume Rate.
2.4.1. Never use an inlet plenum when manufacturer must specify the Cooling 6. If the conditions of step 4b occur
testing a non-ducted system. Full-load Air Volume Rate. Use this first, make an incremental change to the
* * * * * value as long as the following two set-up of the indoor fan (e.g., next
2.5.3 Section 6.5.2 of ASHRAE requirements are satisfied. First, when highest fan motor pin setting, next
Standard 37–2005 (incorporated by conducting the A or A2 Test highest fan motor speed) and repeat the
reference, see § 430.22) describes the (exclusively), the measured air volume evaluation process beginning at above
method for fabricating static-pressure rate, when divided by the measured step 1. If the indoor fan set-up cannot
taps. * * * indoor air-side total cooling capacity be further changed, reduce the air
* * * * * must not exceed 37.5 cubic feet per volume rate until the applicable Table 2
2.5.4.3 Minimizing air leakage. For minute of standard air (scfm) per 1000 minimum is equaled. Use this reduced
small-duct, high-velocity systems, Btu/h. If this ratio is exceeded, reduce air volume rate for all tests that require
install an air damper near the end of the the air volume rate until this ratio is the Cooling Full-load Air Volume Rate.
interconnecting duct, just prior to the equaled. Use this reduced air volume b. For ducted units that are tested
transition to the airflow measuring rate for all tests that call for using the with a variable-speed, constant-air-
apparatus of section 2.6. To minimize Cooling Full-load Air Volume Rate. The volume-rate indoor fan installed. * * *
air leakage, adjust this damper such that second requirement is as follows: * * * * *

TABLE 2.—MINIMUM EXTERNAL STATIC PRESSURE FOR DUCTED SYSTEMS TESTED WITH AN INDOOR FAN INSTALLED
Minimum external resistance 3
(Inches of water)
Rated Cooling 1 or Heating 2 Capacity
(Btu/h) Small-duct, high-
All other systems velocity sys-
tems 4,5

Up Thru 28,800 ................................................................................................................................................ 0.10 1.10


29,000 to 42,500 .............................................................................................................................................. 0.15 1.15
43,000 and Above ........................................................................................................................................... 0.20 1.20
1 For air conditioners and heat pumps, the value cited by the manufacturer in published literature for the unit’s capacity when operated at the A
or A2 Test conditions.
2 For heating-only heat pumps, the value the manufacturer cites in published literature for the unit’s capacity when operated at the H1 or H1
2
Test conditions.
pwalker on PROD1PC71 with RULES3

3 For ducted units tested without an air filter installed, increase the applicable tabular value by 0.08 inch of water.
4 See Definition 1.35 to determine if the equipment qualifies as a small-duct, high-velocity system.
5 If a closed-loop, air-enthalpy test apparatus is used on the indoor side, limit the resistance to airflow on the inlet side of the indoor blower coil
to a maximum value of 0.1 inch of water. Impose the balance of the airflow resistance on the outlet side of the indoor blower.

VerDate Aug<31>2005 17:58 Oct 19, 2007 Jkt 214001 PO 00000 Frm 00021 Fmt 4701 Sfmt 4700 E:\FR\FM\22OCR3.SGM 22OCR3
59926 Federal Register / Vol. 72, No. 203 / Monday, October 22, 2007 / Rules and Regulations

* * * * * 3.1.4.2 Cooling Minimum Air


Volume Rate. a. * * *

Cooling Minimum Fan Speed


Cooling Minimum Air Vol. Rate = Cooling Full-load Air Vol. Raate × ,
A 2 Test Fan Speed

* * * b. * * *

2
 Cooling Minimum Air Volume Rate 
A1 , B1 , C1 , F1 , & G1 Test ∆Pst = ∆Pst , A2 ×   ,
 Cooling Full-load Air Volume Rate 

* * * * * 3.1.4.3 Cooling Intermediate Air


Volume Rate. a. * * *

E V Test Fan Speed


Cooling Intermediate Air Vol. Rate = Cooling Full-load Air Vool. Rate × ,
A 2 Test Fan Speed

* * * b. * * *

2
 Cooling Intermediate Air Volume Rate 
E V Test ∆Pst = ∆Pst , A2 ×   ,
 Cooling Full-load Air Volume Rate 

* * * * * Volume Rates are different due to


3.1.4.4.2 Ducted heat pumps where indoor fan operation. a. * * *
the Heating and Cooling Full-load Air

H1 or H12 Test Fan Speed


Heating Full-load Air Volume Rate = Cooling Full-load Air Vollume Rate × ,
A or A 2 Test Fan Speed

ER22OC07.070</MATH>
* * * b. * * *

2
 Heating Full-load Air Volume Rate 
Heating Full-load ∆Pst = Cooling Full-load ∆Pst ×   ,

ER22OC07.069</MATH>
 Cooling Full-load Air Volume Rate 

* * * * * heating-only heat pump’s rated heating 6. If the conditions of step 4b occur


3.1.4.4.3 Ducted heating-only heat capacity, use the current air volume rate first, make an incremental change to the
ER22OC07.068</MATH>
pumps. The manufacturer must specify for all tests that require the Heating set-up of the indoor fan (e.g., next
the Heating Full-load Air Volume Rate. Full-load Air Volume Rate. highest fan motor pin setting, next
a. For all ducted heating-only heat 4. If the Table 2 minimum is not highest fan motor speed) and repeat the
pumps tested with an indoor fan equaled or exceeded, evaluation process beginning at above
installed, except those having a step 1. If the indoor fan set-up cannot
4a. reduce the air volume rate until
ER22OC07.067</MATH>

variable-speed, constant-air-volume-rate be further changed, reduce the air


the applicable Table 2 minimum is
indoor fan. Conduct the following steps volume rate until the applicable Table 2
equaled or
only during the first test, the H1 or H12 minimum is equaled. Use this reduced
Test. 4b. until the measured air volume rate
equals 95 percent of the manufacturer- air volume rate for all tests that require
1. Achieve the Heating Full-load Air the Heating Full-load Air Volume Rate.
ER22OC07.066</MATH>

Volume Rate. specified Full-load Air Volume Rate,


pwalker on PROD1PC71 with RULES3

2. Measure the external static whichever occurs first. b. For ducted heating-only heat
pressure. 5. If the conditions of step 4a occurs pumps that are tested with a variable-
3. If this pressure is equal to or greater first, use the step 4a reduced air volume speed, constant-air-volume-rate indoor
than the Table 2 minimum external rate for all tests that require the Heating fan installed. * * *
ER22OC07.065</MATH>

static pressure that applies given the Full-load Air Volume Rate. * * * * *

VerDate Aug<31>2005 17:58 Oct 19, 2007 Jkt 214001 PO 00000 Frm 00022 Fmt 4701 Sfmt 4700 E:\FR\FM\22OCR3.SGM 22OCR3
Federal Register / Vol. 72, No. 203 / Monday, October 22, 2007 / Rules and Regulations 59927

3.1.4.5 Heating Minimum Air


Volume Rate. a. * * *

Heating Minimum Fan Speed


Heating Minimum Air Vol. Rate = Heating Full-load Air Vol. Rate × ,
H12 Test Fan Speed

* * * b. * * *

2
 Htg Minimum Air Vol. Rate 
H01 , H11 , H 21 , H31 , Test ∆Pst = ∆Pst, H12 ×   ,
 Htg Full-load Air Vol. Rate 

* * * * * 3.1.4.6 Heating Intermediate Air


Volume Rate. a. * * *

H 2V Test Fan Speed


Heating Intermediate Air Volume Rate = Heating Full-load Air Volume Rate × ,
H12 Test Fan Speed

* * * b. * * *

2
 Heating Intermediate Air Volume Rate 
H 2V Test ∆Pst ∆Pst , H12 ×   ,
 Heating Full-load Air Volume Rate 

* * * * * 3.1.4.7 Heating Nominal Air Volume


Rate. * * *

H1N Test Fan Speed

ER22OC07.077</MATH>
me Rate ×
Heating Nominal Air Volume Rate = Heating Full-load Air Volum ,
H12 Test Fan Speed

2
 Heating Nominal Air Volume Rate 

ER22OC07.076</MATH>
H1N Test ∆Pst = ∆Pst , H12 ×   ,
 Heating Full-load Air Volume Rate 

ER22OC07.075</MATH>
* * * * * assign CDc the default value of 0.25. d. If a two-capacity air conditioner or
3.1.6 * * * (Note: In the first * * * heat pump locks out low-capacity
printing of ASHRAE Standard 37–2005, * * * * * operation at higher outdoor
the second IP equation for Qmi should temperatures, then use the two optional
read, 3.2.3 Tests for a unit having a two-
capacity compressor. (See Definition dry-coil tests, the steady-state C2 Test
ER22OC07.074</MATH>
1.45.) and the cyclic D2 Test, to determine the
1097CA n Pv v′n .) * * * a. Conduct four steady-state wet coil
cooling-mode cyclic-degradation
coefficient that only applies to on/off
* * * tests: the A2, B2, B1, and F1 Tests. Use
the two optional dry-coil tests, the cycling from high capacity, CDc(k=2). If
* * * * * the two optional tests are conducted but
steady-state C1 Test and the cyclic D1
ER22OC07.073</MATH>

3.2.1 * * * If the two optional tests


Test, to determine the cooling-mode yield a tested CDc(k=2) that exceeds the
are conducted but yield a tested CDc that
exceeds the default CDc or if the two cyclic-degradation coefficient, CDc. If the default CDc(k=2) or if the two optional
optional tests are not conducted, assign two optional tests are conducted but tests are not conducted, assign CDc(k=2)
CDc the default value of 0.25. * * * yield a tested CDc that exceeds the the default value. The default CDc(k=2)
default CDc or if the two optional tests is the same value as determined or
ER22OC07.072</MATH>

* * * * *
assigned for the low-capacity cyclic-
pwalker on PROD1PC71 with RULES3

3.2.2.1 * * * If the two optional are not conducted, assign CDc the
tests are conducted but yield a tested default value of 0.25. Table 5 specifies degradation coefficient, CDc [or
CDc that exceeds the default CDc or if the test conditions for these six tests. equivalently, CDc(k=1)].
two optional tests are not conducted, * * * * *
ER22OC07.071</MATH>

VerDate Aug<31>2005 17:58 Oct 19, 2007 Jkt 214001 PO 00000 Frm 00023 Fmt 4701 Sfmt 4700 E:\FR\FM\22OCR3.SGM 22OCR3
59928 Federal Register / Vol. 72, No. 203 / Monday, October 22, 2007 / Rules and Regulations

TABLE 5.—COOLING MODE TEST CONDITIONS FOR UNITS HAVING A TWO-CAPACITY COMPRESSOR
Air entering indoor unit Air entering outdoor unit
temperature (°F) temperature (°F) Compressor
Test description Cooling air volume rate
capacity
Dry bulb Wet bulb Dry bulb Wet bulb

A2 Test—required ................................ 80 67 95 1 75 High ............. Cooling Full-Load.2


(steady, wet coil)
B2 Test—required ................................ 80 67 82 1 65 High ............. Cooling Full-Load.2
(steady, wet coil)
B1 Test—required ................................ 80 67 82 1 65 Low ............. Cooling Minimum.3
(steady, wet coil)
C2 Test—optional ................................ 80 (4) 82 ...................... High ............. Cooling Full-Load.2
(steady, dry-coil)
D2 Test—optional ................................ 80 (4) 82 ...................... High ............. (5)
(cyclic, dry-coil)
C1 Test—optional ................................ 80 (4) 82 ...................... Low .............. Cooling Minimum.3
(steady, dry-coil)
D1 Test—optional ................................ 80 (4) 82 ...................... Low .............. (6)
(cyclic, dry-coil)
F1 Test—required ................................ 80 67 67 1 53.5 Low ............. Cooling Minimum.3
(steady, wet coil)
1 The specified test condition only applies if the unit rejects condensate to the outdoor coil.
2 Definedin section 3.1.4.1.
3 Defined in section 3.1.4.2.
4 The entering air must have a low enough moisture content so no condensate forms on the indoor coil. DOE recommends using an indoor air
wet-bulb temperature of 57 °F or less.
5 Maintain the airflow nozzle(s) static pressure difference or velocity pressure during the ON period at the same pressure or velocity as meas-
ured during the C2 Test.
6 Maintain the airflow nozzle(s) static pressure difference or velocity pressure during the ON period at the same pressure or velocity as meas-
ured during the C1 Test.

3.2.4 Tests for a unit having a specified for a minimum compressor minimum cooling-mode speeds. The
variable-speed compressor. a. * * * If speed, at least one indoor unit must be manufacturer should prescribe an
the two optional tests are conducted but turned off. The manufacturer shall intermediate speed that is expected to
yield a tested CDc that exceeds the designate the particular indoor unit(s) yield the highest EER for the given EV
default CDc or if the two optional tests that is turned off. The manufacturer Test conditions and bracketed
are not conducted, assign CDc the must also specify the compressor speed compressor speed range. The
default value of 0.25. * * * used for the Table 6 EV Test, a cooling- manufacturer can designate that one or
c. For multiple-split air conditioners mode intermediate compressor speed more indoor units are turned off for the
and heat pumps (except where noted),
that falls within 1⁄4 and 3⁄4 of the EV Test.
the following procedures supersede the
difference between the maximum and * * * * *
above requirements: For all Table 6 tests

TABLE 6.—COOLING MODE TEST CONDITION FOR UNITS HAVING A VARIABLE-SPEED COMPRESSOR
Air entering indoor unit Air entering outdoor unit
temperature (°F) temperature (°F) Compressor
Test description Cooling air volume rate
speed
Dry bulb Wet bulb Dry bulb Wet bulb

A2 Test—required .......................... 80 67 95 1 75 Maximum .......... Cooling Full-Load2


(steady, wet coil)
B2 Test—required .......................... 80 67 82 1 65 Maximum .......... Cooling Full-Load2
(steady, wet coil)
EV Test—required .......................... 80 67 87 1 69 Intermediate ..... Cooling Intermediate 3
(steady, wet coil)
B1 Test—required .......................... 80 67 82 1 65 Minimum ........... Cooling Minimum 4
(steady, wet coil)
F1 Test—required ........................... 80 67 67 1 53.5 Minimum ........... Cooling Minimum 4
(steady, wet coil)
G1 Test 5—optional ......................... 80 (6) 67 ...................... Minimum ........... Cooling Minimum 4
(steady, dry-coil)
I1 Test 5—optional .......................... 80 (6) 67 ...................... Minimum ........... (6)
(cyclic, dry-coil)
1 The specified test condition only applies if the unit rejects condensate to the outdoor coil.
2 Definedin section 3.1.4.1.
pwalker on PROD1PC71 with RULES3

3 Definedin section 3.1.4.3.


4 Defined in section 3.1.4.2.
5 The entering air must have a low enough moisture content so no condensate forms on the indoor coil. DOE recommends using an indoor air
wet bulb temperature of 57°F or less.
6 Maintain the airflow nozzle(s) static pressure difference or velocity pressure during the ON period at the same pressure difference or velocity
pressure as measured during the G1 Test.

VerDate Aug<31>2005 19:03 Oct 19, 2007 Jkt 214001 PO 00000 Frm 00024 Fmt 4701 Sfmt 4700 E:\FR\FM\22OCR3.SGM 22OCR3
Federal Register / Vol. 72, No. 203 / Monday, October 22, 2007 / Rules and Regulations 59929

* * * * * ‘‘(k=2)’’ to the coefficient if it degradation coefficient, CDh. If this


3.4 Test procedures for the optional corresponds to a two-capacity unit optional test is conducted but yields a
steady-state dry-coil cooling-mode tests cycling at high capacity. If the two tested CDh that exceeds the default CDh
(the C, C1, C2, and G1 Tests). optional tests are conducted but yield a or if the optional test is not conducted,
* * * * * tested CDc that exceeds the default CDc assign CDh the default value of 0.25. Test
b. Denote the resulting total space or if the two optional tests are not conditions for the seven tests are
cooling capacity and electrical power conducted, assign CDc the default value specified in Table 10. If the optional H21
derived from the test as Q̇ss,dry and Ėss,dry. of 0.25. The default value for two- Test is not performed, use the following
With regard to a section 3.3 deviation, capacity units cycling at high capacity, equations to approximate the capacity
do not adjust Q̇ss,dry for duct losses (i.e., however, is the low-capacity coefficient, and electrical power of the heat pump
do not apply section 7.3.3.3 of ASHRAE i.e., CDc(k=2)=CDc. Evaluate CDc using at the H21 test conditions:
Standard 37–2005 (incorporated by the above results and those from the * * * * *
reference, see § 430.22)). In preparing section 3.4 dry-coil steady-state test. 3.6.3 Tests for a heat pump having a
for the section 3.5 cyclic tests, record * * * * * two-capacity compressor (see Definition
the average indoor-side air volume rate,
Ô 1.45), including two-capacity, northern
3.6.1 * * * Conduct the optional
V, specific heat of the air, Cp,a heat pumps (see Definition 1.46). a.
High Temperature Cyclic (H1C) Test to
(expressed on dry air basis), specific
determine the heating mode cyclic- Conduct one Maximum Temperature
volume of the air at the nozzles, v′n,
degradation coefficient, CDh. If this Test (H01), two High Temperature Tests
humidity ratio at the nozzles, Wn, and
optional test is conducted but yields a (H12 and H11), one Frost Accumulation
either pressure difference or velocity
tested CDh that exceeds the default CDh Test (H22), and one Low Temperature
pressure for the flow nozzles. For units
or if the optional test is not conducted, Test (H32). Conduct an additional Frost
having a variable-speed indoor fan (that
assign CDh the default value of 0.25. Test Accumulation Test (H21) and Low
provides either a constant or variable air
conditions for the four tests are Temperature Test (H31) if both of the
volume rate) that will or may be tested
specified in Table 9. * * * following conditions exist:
during the cyclic dry coil cooling mode
test with the indoor fan turned off (see * * * * * 1. Knowledge of the heat pump’s
section 3.5), include the electrical 3.6.2 Tests for a heat pump having a capacity and electrical power at low
power used by the indoor fan motor single-speed compressor and a variable- compressor capacity for outdoor
among the recorded parameters from the speed, variable-air-volume-rate indoor temperatures of 37°F and less is needed
30-minute test. fan: capacity modulation correlates with to complete the section 4.2.3 seasonal
3.5 Test procedures for the optional outdoor dry bulb temperature. Conduct performance calculations; and
cyclic dry-coil cooling-mode tests (the five tests: two High Temperature Tests 2.The heat pump’s controls allow
D, D1, D2, and I1 Tests). (H12 and H11), one Frost Accumulation low-capacity operation at outdoor
* * * * * Test (H22), and two Low Temperature temperatures of 37°F and less.
3.5.3 Cooling-mode cyclic- Tests (H32 and H31). Conducting an If the above two conditions are met,
degradation coefficient calculation. Use additional Frost Accumulation Test an alternative to conducting the H21
the two optional dry-coil tests to (H21) is optional. Conduct the optional Frost Accumulation is to use the
determine the cooling-mode cyclic- High Temperature Cyclic (H1C1) Test to following equations to approximate the
degradation coefficient, CDc. Append determine the heating mode cyclic- capacity and electrical power:

Determine the quantities Q̇hk=1 (47) tested CDh that exceeds the default CDh capacity is conducted but yields a tested
and Ėhk=1 (47) from the H11 Test and or if the optional test is not conducted, CDh (k=2) that exceeds the default CDh
evaluate them according to Section 3.7. assign CDh the default value of 0.25. If (k=2) or if the optional test is not
Determine the quantities Q̇hk=1 (17) and a two-capacity heat pump locks out low conducted, assign CDh the default value.
Ėhk=1 (17) from the H31 Test and capacity operation at lower outdoor The default CDh (k=2) is the same value
evaluate them according to Section 3.10. temperatures, conduct the optional High as determined or assigned for the low-
b. Conduct the optional High Temperature Cyclic Test (H1C2) to capacity cyclic-degradation coefficient,
Temperature Cyclic Test (H1C1) to determine the high-capacity heating- CDh [or equivalently, CDh (k=1)]. Table
determine the heating-mode cyclic-
mode cyclic-degradation coefficient, CDh 11 specifies test conditions for these
degradation coefficient, CDh. If this
(k=2). If this optional test at high nine tests.
optional test is conducted but yields a

TABLE 11.—HEATING MODE TEST CONDITIONS FOR UNITS HAVING A TWO-CAPACITY COMPRESSOR
Air entering indoor unit Air entering outdoor unit
temperature (°F) temperature (°F) Compressor
Test description Heating air volume rate
capacity
Dry bulb Wet bulb Dry bulb Wet bulb
pwalker on PROD1PC71 with RULES3

H01 Test .............................................. 70 60(max) 62 56.5 Low .............. Heating Minimum.1


(required, steady)
H12 Test .............................................. 70 60(max) 47 43 High ............. Heating Full-Load.2
(required, steady)
ER22OC07.078</MATH>

VerDate Aug<31>2005 17:58 Oct 19, 2007 Jkt 214001 PO 00000 Frm 00025 Fmt 4701 Sfmt 4700 E:\FR\FM\22OCR3.SGM 22OCR3
59930 Federal Register / Vol. 72, No. 203 / Monday, October 22, 2007 / Rules and Regulations

TABLE 11.—HEATING MODE TEST CONDITIONS FOR UNITS HAVING A TWO-CAPACITY COMPRESSOR—Continued
Air entering indoor unit Air entering outdoor unit
temperature (°F) temperature (°F) Compressor
Test description Heating air volume rate
capacity
Dry bulb Wet bulb Dry bulb Wet bulb

H1C2 Test ............................................ 70 60(max) 47 43 High ............. (3)


(optional, cyclic)
H11 Test .............................................. 70 60(max) 47 43 Low ............. Heating Minimum.1
(required)
H1C1 Test ............................................ 70 60(max) 47 43 Low .............. (4)
(optional, cyclic)
H22 Test .............................................. 70 60(max) 35 33 High ............. Heating Full-Load.2
(required)
H21 Test5,6 ........................................... 70 60(max) 35 33 Low ............. Heating Minimum.1
(required)
H32 Test .............................................. 70 60(max) 17 15 High ............. Heating Full-Load.2
(required, steady)
H31 Test 5 ............................................ 70 60(max) 17 15 Low .............. Heating Minimum. 1
(required, steady)
1 Defined in section 3.1.4.5.
2 Defined in section 3.1.4.4.
3 Maintain the airflow nozzle(s) static pressure difference or velocity pressure during the ON period at the same pressure or velocity as meas-
ured during the H12 Test.
4 Maintain the airflow nozzle(s) static pressure difference or velocity pressure during the ON period at the same pressure or velocity as meas-
ured during the H11 Test.
5 Required only if the heat pump’s performance when operating at low compressor capacity and outdoor temperatures less than 37°F is need-
ed to complete the section 4.2.3 HSPF calculations.
6 If table note #5 applies, the section 3.6.3 equations for Q̇ k=1 (35) and Ė k=1 (17) may be used in lieu of conducting the H2 Test.
h h 1

3.6.4 Tests for a heat pump having a c. For multiple-split heat pumps within 1⁄4 and 3⁄4 of the difference
variable-speed compressor. a. * * * (only), the following procedures between the maximum and minimum
Conduct the optional Maximum supersede the above requirements. For heating-mode speeds. The manufacturer
Temperature Cyclic (H0C1) Test to all Table 12 tests specified for a should prescribe an intermediate speed
determine the heating mode cyclic- minimum compressor speed, at least that is expected to yield the highest COP
degradation coefficient, CDh. If this one indoor unit must be turned off. The for the given H2V Test conditions and
optional test is conducted but yields a manufacturer shall designate the bracketed compressor speed range. The
tested CDh that exceeds the default CDh particular indoor unit(s) that is turned manufacturer can designate that one or
or if the optional test is not conducted, off. The manufacturer must also specify more specific indoor units are turned off
assign CDh the default value of 0.25. Test the compressor speed used for the Table
for the H2V Test.
conditions for the eight tests are 12 H2V Test, a heating-mode
specified in Table 12. * * * intermediate compressor speed that falls * * * * *

TABLE 12.—HEATING MODE TEST CONDITIONS FOR UNITS HAVING A VARIABLE-SPEED COMPRESSOR
Air entering indoor unit Air entering outdoor unit
temperature (°F) temperature (°F)
Test description Compressor speed Heating air volume rate
Dry bulb Wet bulb Dry bulb Wet bulb

H01 Test ....................... 70 60(max) 62 56.5 Minimum ............................. Heating Minimum.1


(required, steady)
H0C1 Test .................... 70 60(max) 62 56.5 Minimum ............................. (2)
(optional, steady)
H12 Test ....................... 70 60(max) 47 43 Maximum ............................ Heating Full-Load.3
(required, steady)
H11 Test ....................... 70 60(max) 47 43 Minimum ............................. Heating Minimum.1
(required, steady)
H1N Test ...................... 70 60(max) 47 43 Cooling Mode Maximum .... Heating Nominal.4
(optional, steady)
H22 Test ....................... 70 60(max) 35 33 Maximum ............................ Heating Full-Load.3
(optional)
H2V Test ...................... 70 60(max) 35 33 Intermediate ....................... Heating Intermediate.5
(required)
H32 Test ....................... 70 60(max) 17 15 Maximum ............................ Heating Full-Load.3
(required, steady)
pwalker on PROD1PC71 with RULES3

1 Definedin section 3.1.4.5.


2 Maintainthe airflow nozzle(s) static pressure difference or velocity pressure during an ON period at the same pressure or velocity as meas-
ured during the H01 Test.
3 Defined in section 3.1.4.4.
4 Defined in section 3.1.4.7.
5 Defined in section 3.1.4.6.

VerDate Aug<31>2005 17:58 Oct 19, 2007 Jkt 214001 PO 00000 Frm 00026 Fmt 4701 Sfmt 4700 E:\FR\FM\22OCR3.SGM 22OCR3
Federal Register / Vol. 72, No. 203 / Monday, October 22, 2007 / Rules and Regulations 59931

* * * * * indicated by instructions provided by measurements as specified in sections


3.7 Test procedures for steady-state the manufacturer. If the heat pump has 7.3.4.2 and 7.3.3.4.3 of the same
Maximum Temperature and High not undergone a defrost after 6 hours, ASHRAE Standard. Adjust the outdoor-
Temperature heating mode tests (the immediately conclude the test and use side capacity according to section
H01, H1, H12, H11, and H1N Tests). a. the results from the full 6-hour period 7.3.3.4 of ASHRAE Standard 37–2005
* * * to calculate the average space heating (incorporated by reference, see § 430.22)
b. Calculate indoor-side total heating capacity and average electrical power to account for line losses when testing
capacity as specified in sections 7.3.4.1 consumption. split systems. Use the outdoor unit fan
and 7.3.4.3 of ASHRAE Standard 37– For heat pumps that turn the indoor power as measured during the official
2005 (incorporated by reference, see fan off during the defrost cycle, take test and not the value measured during
§ 430.22). * * * steps to cease forced airflow through the the preliminary test, as described in
* * * * * indoor coil and block the outlet duct section 8.6.2 of ASHRAE Standard 37–
3.8 Test procedures for the optional whenever the heat pump’s controls 2005 (incorporated by reference, see
cyclic heating mode tests (the H0C1, cycle off the indoor fan. If it is installed, § 430.22), when calculating the capacity.
H1C, H1C1 and H1C2 Tests). use the outlet damper box described in 3.11.2 If using the Compressor
* * * * * section 2.5.4.1 to affect the blocked Calibration Method as the secondary
3.8.1 Heating mode cyclic- outlet duct. test method.
degradation coefficient calculation. Use * * * * *
the results from the optional cyclic test a. * * * Otherwise, conduct the
f. * * * Sample measurements used
and the required steady-state test that calibration tests according to ASHRAE
in calculating the air volume rate (refer
were conducted at the same test Standard 23–05 (incorporated by
to sections 7.7.2.1 and 7.7.2.2 of
conditions to determine the heating- reference, see § 430.22), ASHRAE
ASHRAE Standard 37–2005
mode cyclic-degradation coefficient CDh. Standard 41.9–2000 (incorporated by
(incorporated by reference, see
Add ‘‘(k=2)’’ to the coefficient if it reference, see § 430.22), and section 7.4
§ 430.22)) at equal intervals that span 10
corresponds to a two-capacity unit of ASHRAE Standard 37–2005
minutes or less. (Note: In the first
cycling at high capacity. For the below (incorporated by reference, see
printing of ASHRAE Standard 37–2005,
calculation of the heating mode cyclic § 430.22).
the second IP equation for Qmi should
degradation coefficient, do not include read: .) b. Calculate space cooling and space
the duct loss correction from section heating capacities using the compressor
7.3.3.3 of ASHRAE Standard 37–2005 calibration method measurements as
(incorporated by reference, see § 430.22) 1097CA n Pv v′n .) * * * specified in section 7.4.5 and 7.4.6
in determining Q̇hk(Tcyc) (or qcyc). If the respectively, of ASHRAE Standard 37–
* * * * *
optional cyclic test is conducted but 3.9.1 Average space heating capacity 2005 (incorporated by reference, see
yields a tested CDh that exceeds the and electrical power calculations. § 430.22).
default CDh or if the optional test is not a. * * * 3.11.3 If using the Refrigerant-
conducted, assign CDh the default value To account for the effect of duct losses Enthalpy Method as the secondary test
of 0.25. The default value for two- between the outlet of the indoor unit method. Conduct this secondary method
capacity units cycling at high capacity, and the section 2.5.4 dry-bulb according to section 7.5 of ASHRAE
however, is the low-capacity coefficient, temperature grid, adjust Q̇hk(35) in Standard 37–2005 (incorporated by
i.e., CDh (k=2) = CDh. The tested CDh is accordance with section 7.3.4.3 of reference, see § 430.22). Calculate space
calculated as follows: ASHRAE Standard 37–2005 cooling and heating capacities using the
(incorporated by reference, see refrigerant-enthalpy method
COPcyc § 430.22). measurements as specified in sections
1−
COPss ( Tcyc ) * * * * * 7.5.4 and 7.5.5, respectively, of the same
ChD = 3.11 Additional requirements for the ASHRAE Standard.
1 − HLF secondary test methods. * * * * * *
* * * 3.11.1 If using the Outdoor Air
Enthalpy Method as the secondary test 4. Calculations of Seasonal
* * * * * Performance Descriptors
3.9 * * * method.
c. The official test period begins when * * * * * * * * * *
the preliminary test period ends, at 3.11.1.3 Official test. 4.1.3 SEER calculations for an air
defrost termination. The official test * * * * * conditioner or heat pump having a two-
ER22OC07.080</MATH>
period ends at the termination of the b. For space cooling tests, calculate capacity compressor. Calculate SEER
next occurring automatic defrost cycle. capacity from the outdoor air-enthalpy using Equation 4.1–1. Evaluate the
When testing a heat pump that uses a measurements as specified in sections space cooling capacity, Q̇ck=1 (Tj), and
time-adaptive defrost control system 7.3.3.2 and 7.3.3.3 of ASHRAE Standard electrical power consumption, Ėck=1 (Tj),
(see Definition 1.42), however, manually 37–2005 (incorporated by reference, see of the test unit when operating at low
ER22OC07.079</MATH>

initiate the defrost cycle that ends the § 430.22). Calculate heating capacity compressor capacity and outdoor
official test period at the instant based on outdoor air-enthalpy temperature Tj using,
ER22OC07.098</MATH>
pwalker on PROD1PC71 with RULES3

ER22OC07.096</MATH>

VerDate Aug<31>2005 17:58 Oct 19, 2007 Jkt 214001 PO 00000 Frm 00027 Fmt 4701 Sfmt 4725 E:\FR\FM\22OCR3.SGM 22OCR3
59932 Federal Register / Vol. 72, No. 203 / Monday, October 22, 2007 / Rules and Regulations

where Q̇ck=1 (82) and Ėck=1 (82) are calculated as specified in section 3.3. when operating at high compressor
determined from the B1 Test, Q̇ck=1 (67) Evaluate the space cooling capacity, capacity and outdoor temperature Tj
and Ėck=1 (67) are determined from the Q̇ck=2 (Tj), and electrical power using,
F1 Test, and all four quantities are consumption, Ėck=2 (Tj), of the test unit

* * * * * optional tests are conducted, set CDc and all four quantities are calculated as
4.1.3.3 * * * (k=2) to the lower of: specified in section 3.3. Evaluate the
a. the CDc (k=2) value calculated as space cooling capacity, Q̇ck=2 (Tj), and
per section 3.5.3; or electrical power consumption, Ėck=2 (Tj),
PLFj = 1 − CcD (k = 2) ⋅ 1 − X k = 2 (Tj )  , b. the section 3.5.3 default value for of the test unit when operating at
CDc (k=2) . maximum compressor speed and
the part load factor, dimensionless.
* * * * * outdoor temperature Tj. Use Equations
Obtain the fraction bin hours for the 4.1.4 SEER calculations for an air 4.1.3–3 and 4.1.3–4, respectively, where
cooling season, conditioner or heat pump having a Q̇ck=2 (95) and Ėck=2 (95) are determined
variable-speed compressor. Calculate from the A2 Test, Q̇ck=2 (82) and Ėck=2
nj SEER using Equation 4.1–1. Evaluate the (82) are determined from the B2 Test,
, space cooling capacity, Q̇ck=1 (Tj), and and all four quantities are calculated as
N
electrical power consumption Ėck=1 (Tj), specified in section 3.3. Calculate the
from Table 16. Use Equations 4.1.3–3 of the test unit when operating at space cooling capacity, Q̇ck=v (Tj), and
and 4.1.3–4, respectively, to evaluate minimum compressor speed and electrical power consumption, Ėck=v (Tj),
Q̇ck=2 (Tj) and Ėck=2 (Tj). If the optional outdoor temperature Tj. Use Equations of the test unit when operating at
C2 and D2 Tests described in section 4.1.3–1 and 4.1.3–2, respectively, where outdoor temperature Tj and the
3.2.3 and Table 5 are not conducted, set Q̇ck=1 (82) and Ėck=1 (82) are determined intermediate compressor speed used
CDc (k=2) equal to the default value from the B1 Test, Q̇ck=1 (67) and Ėck=1 during the section 3.2.4 (and Table 6) EV
specified in section 3.5.3. If these (67) are determined from the F1 Test, Test using,

ER22OC07.087</MATH>
ER22OC07.086</MATH>
where Q̇ck=v (87) and Ėck=v (87) are Approximate the slopes of the k = v electrical power input curves, MQ and
determined from the Ev Test and intermediate speed cooling capacity and ME, as follows: * * *
calculated as specified in section 3.3. where,

ER22OC07.085</MATH>
ER22OC07.084</MATH>
Use Equations 4.1.3–1 and 4.1.3–2 for Tj 3 and 4.1.3–4 for Tj = 87°F to determine
= 87°F to determine Q̇ck=l (87) and Ėck=l Q̇ck=2 (87) and Ėck=2 (87), respectively.
(87), respectively. Use Equations 4.1.3– Calculating Equation 4.1–1 quantities

ER22OC07.083</MATH>
q c (Tj ) ec (Tj )
and
N N
ER22OC07.097</MATH>

differs depending upon whether the test 4.1.4.3) in responding to the building 4.1.4.1 * * * Use Equations 4.1.3–1
unit would operate at minimum speed load. Use Equation 4.1–2 to calculate and 4.1.3–2, respectively, to evaluate
(section 4.1.4.1), operate at an the building load, BL(Tj), for each Q̇ck=l (Tj) and Ėck=l (Tj).
intermediate speed (section 4.1.4.2), or temperature bin. 4.1.4.2 * * *
operate at maximum speed (section
ER22OC07.082</MATH>
pwalker on PROD1PC71 with RULES3

A = EER k =2 (T2 ) − B ⋅ T2 − C ⋅ T22


ER22OC07.081</MATH>

VerDate Aug<31>2005 17:58 Oct 19, 2007 Jkt 214001 PO 00000 Frm 00028 Fmt 4701 Sfmt 4725 E:\FR\FM\22OCR3.SGM 22OCR3
Federal Register / Vol. 72, No. 203 / Monday, October 22, 2007 / Rules and Regulations 59933

where, Determine T1 by equating Equations section 3.2.4 EV Test, provides a space


T1 = the outdoor temperature at which 4.1.3–1 and 4.1–2 and solving for cooling capacity that is equal to the
the unit, when operating at minimum outdoor temperature. Tv = the outdoor building load (Q̇ck=v (Tv) = BL(Tv)), °F.
compressor speed, provides a space temperature at which the unit, when Determine Tv by equating Equations
cooling capacity that is equal to the operating at the intermediate 4.1.4–1 and 4.1–2 and solving for
building load (Q̇ck=l (Tl) = BL(T1)), °F. compressor speed used during the outdoor temperature. * * *

* * * * * procedures supersede the above For each temperature bin where Tl < Tj
For multiple-split air conditioners requirements for calculating EERk=i (Tj). < Tv,
and heat pumps (only), the following

EER k = v (Tv ) − EER k =1 (T1 )


EER k =i (Tj ) = EER k =1 (T1 ) + ⋅ (Tj − T1 ).
Tv − T1

* * * * * 4.2.3.3 * * *

PLFj = 1 − ChD ( k = 2 ) ⋅ 1 − X k = 2 (Tj )  .

If the optional H1C2 Test described in If this optional test is conducted, set CDh Determine the low temperature cut-
section 3.6.3 and Table 11 is not (k=2) to the lower of: out factor, d (Tj), using Equation 4.2.3–
conducted, set CDh (k=2) equal to the a. the CDh (k=2) value calculated as 3.

ER22OC07.094</MATH>
default value specified in section 3.8.1. per section 3.8.1; or
* * * * *
b. the section 3.8.1 default value for
CDh (k=2). 4.2.4 * * *

ER22OC07.093</MATH>
ER22OC07.092</MATH>
* * * * * For multiple-split heat pumps (only), COPhk=i (Tj). For each temperature bin
ER22OC07.091</MATH>
4.2.4.2 * * * the following procedures supersede the where T3 > Tj > Tvh,
above requirements for calculating

COPhk = v ( Tvh ) − COPhk =1 ( T3 )


ER22OC07.090</MATH>

COPhk =i ( Tj ) = COPhk =1 ( T3 ) + ⋅ ( Tj − T3 ) .
Tvh − T3

For each temperature bin where Tvh ≥ Tj


ER22OC07.089</MATH>

> T4,
pwalker on PROD1PC71 with RULES3

ER22OC07.088</MATH>

VerDate Aug<31>2005 17:58 Oct 19, 2007 Jkt 214001 PO 00000 Frm 00029 Fmt 4701 Sfmt 4700 E:\FR\FM\22OCR3.SGM 22OCR3
59934 Federal Register / Vol. 72, No. 203 / Monday, October 22, 2007 / Rules and Regulations

COPhk = 2 ( T4 ) − COPhk = v ( Tvh )


COPhk =i ( Tj ) = COPhk = v ( Tvh ) + ⋅ ( Tj − Tvh ) .’’
T4 − Tvh

* * * * * installation that includes a particular ratio and heating seasonal performance


■ 7. Section 430.62 is amended in model of ducted air mover (e.g., furnace, factor are based on an installation that
subpart F by revising paragraphs (a)(4)(i) air handler, blower kit, etc.), the model includes a particular model of ducted
and (ii) to read as follows: number of this ducted air mover must air mover (e.g., furnace, air handler,
be included among the model numbers blower kit, etc.), the model number of
§ 430.62 Submission of data. this ducted air mover must be included
listed on the certification report.
(a) * * * among the model numbers listed on the
(4) * * * (ii) Central air conditioning heat
certification report.
(i) Central air conditioners, the pumps, the seasonal energy efficiency
ratio and heating seasonal performance * * * * *
seasonal energy efficiency ratio. For
central air conditioners whose seasonal factor. For central air conditioning heat [FR Doc. 07–5142 Filed 10–19–07; 8:45 am]
energy efficiency ratio is based on an pumps whose seasonal energy efficiency BILLING CODE 6450–01–P
pwalker on PROD1PC71 with RULES3

ER22OC07.095</MATH>

VerDate Aug<31>2005 17:58 Oct 19, 2007 Jkt 214001 PO 00000 Frm 00030 Fmt 4701 Sfmt 4700 E:\FR\FM\22OCR3.SGM 22OCR3

Você também pode gostar