APPENDIX 2(b)

MSAN SYSTEM PHYSICAL CHECKLIST


ACCESS NETWORK MANAGEMENT

Preventive Maintenance Checklist


Access Equipment
CENTRAL OFFICE TERMINAL (COT)
CONTRACT NO.

_________________________

MSAN ID

_________________________

MSAN TYPE

_________________

EXCHANGE NAME

_________________________

DATE

_________________

TEST GEAR:

Ste
p

No.

Item

1.
2.
3.
4.
5.
6.
7.
8.
9.

Multimeter
Earth tester
Data Logger/Thermometer/Hydrometer
Vacuum
Blower
Drill (optional)
Tool Kit
Thermoscanner/Thermosensor (if applicable)
Laptop

Maintenance Descriptions
A. ENVIRONMENT HEALTH CHECK

Room Condition

Expected Result

Series No.
(If applicable)

Status

Reading & remarks

MSAN SYSTEM PHYSICAL CHECKLIST


ACCESS NETWORK MANAGEMENT

1.1

1.2

Check the rooms air-conditioning


units are working.

Check the room temperature is


maintained at 25C 35C.

Air-Cond are
working.
25C 30C if
aircond
or
25C 35C if
none aircond

APPENDIX 2(b)

OK
Not OK

OK
Not OK

OK

1.3

Check the room humidity is


maintained at 60%

60%

1.4

Check the equipment surrounding


is generally clean, dry, proper
cabling and labeling.

Clean, dry, proper


cabling and
labeling.

OK

1.5

Ensure equipment and room is


locked properly.

Room is locked /
log book is used.

OK

Clean, dry and


dust-free.

OK

Not OK

Reading : __________C

Reading : __________%

Not OK

Not OK

B. EQUIPMENT HEALTH CHECK


2
2.1

MSAN Shelf / Equipment


Check and ensure equipment is
clean and dry, free from dust, spider
webs and other particles.
Verify equipment operating
temperature is maintained < 50C.

2.2

2.3

(The threshold for equipment is


55C. Put lower temperature for
precaution)
Check all fans are working.
State no of faulty fan (if any)

< 50C input

All fans are working

2.4

Check and ensure the fan blades at


each sub-rack are clean.

All fan are clean

2.5

Ensure the ventilation filter is clean


and in-place (if any)

Filter is clean and


in place

Ste
p

Maintenance Descriptions

2.6

Clear visible alarms and state type


of faulty/missing card (if any).

Expected Result
Alarms cleared.
Faulty cards
replaced.

Not OK

OK
Not OK

OK
Not OK

Reading : _________ C

Faulty Fan : ______unit

OK
Not OK
OK
Not OK
Status

Reading & remarks


Type Faulty card:

OK

_________________

Not OK

Type Missing card:


_________________

MSAN SYSTEM PHYSICAL CHECKLIST


ACCESS NETWORK MANAGEMENT

APPENDIX 2(b)

Screen capture
alarm/event history
(compulsory)

2.7

Check and ensure all cables and


connectors are in good
arrangement and labeling.

Good arrangement
and cabling.

OK

2.8

Check and ensure all E1 cables are


properly inserted and unshakable.

Good arrangement,
labeling and fixed.

OK

3
3.1

3.2

Not OK
Not OK

System Redundancy
Verify control card is 1+1 or 1+0

1+1 or 1+0

Verify fiber cable is 1+1 or 1+0

1+1
or
1+0 (no spare fiber)
or
1+0 (spare fiber
hanging and not
connected)

1+1
1+0
1+1
1+0 (no
spare fiber)
1+0
(spare fiber
hanging
and not
connected)

Protection Switch

4.1

Check the condition of Protection


switch board.

Switch board is
healthy.

OK

4.2

Make the system run on protection


switch board if switch board is in
working condition.

System runs on
protection switch
board.

OK

4.3

Changeover Controller card by


using GUI or CLI using 'swap'
command as in TM list with PMW (if
any).
(Applicable for 1+1 uplink fiber).

4.4

Switch off Power card at every shelf


one by one.

Ste
p

Maintenance Descriptions

5
5.1

Standby Controller
Card becomes
active and service
should not affect.
All cards in the
particular shelf
should be working
with one Power
card.
Expected Result

Not OK

Not OK

OK
Not OK

OK
Not OK

Status

Database Backup
Check that login to RT from COT
(remote login) is successful.

Successful login to
RT from COT.

OK
Not OK

Reading & remarks

MSAN SYSTEM PHYSICAL CHECKLIST


ACCESS NETWORK MANAGEMENT

5.2

Perform database backup on


cross-connect information and
configuration.

Successful backup.

5.3

Save the database in suitable


media storage and send a copy.

Backup copy.

Verify uplink fiber for error.

No error.

6.2

Verify subtending (downlink) fiber


for error.

No error.

POWER RELATED HEALTH CHECK

Power Supply

7.1

Check DC supply voltage to


MSAN.

-48V ~ -54Vdc

7.2

Check Power Distribution Box


(PDB) has correct fuse rating for
MSAN operation.

Minimum 25 Amp.

7.3

Check that MSAN is properly


earthed to the ground via MGB.

Directly Connected
from MSAN to MGB.

7.4

Check earth reading at MGB.

<10 ohm

7.5

Measure Earth Continuity reading


between MGB and MSAN shelf
with Multimeter.

<1 ohm

Tighten all MCB, DC cable


(incoming from rectifier) at
equipment rack.
(Please use proper tool,
insulator screw driver).

7.7

OK
Not OK
OK
Not OK

Error and alarm

6.1

7.6

APPENDIX 2(b)

Check the condition of cable


lug/connector at AC/DC Cable
using Thermoscanner/
thermosensor (if applicable).

OK
Not OK
OK
Not OK

OK
Not OK
OK
Not OK
OK
Not OK
OK
Not OK
OK
Not OK

MCB, DC cable
(incoming from
rectifier) tightens.

OK

Cable lug/connector
is in good condition.

OK

Temperature < 38C

Not OK

Not OK

Reading : _________C

Additional Remarks (if any)


____________________________________________________________________________________
____________________________________________________________________________________
____________________________________________________________________________________
____________________________________________________________________________________

MSAN SYSTEM PHYSICAL CHECKLIST


ACCESS NETWORK MANAGEMENT

APPENDIX 2(b)

____________________________________________________________________________________

Disclaimer : Vendor & RNO to comply OSH Requirement as stated in


http://www.dosh.gov.my/Informasi/Akta/AktaKeselamatan.pdf

Prepared by (Vendor)

Verified by (TM Personnel)

Signature :

Signature :

Name :

Name :

Designation :

Designation :

Date:

Date:

Preventive Maintenance Checklist


Access Equipment

APPENDIX 2(b)

MSAN SYSTEM PHYSICAL CHECKLIST


ACCESS NETWORK MANAGEMENT

REMOTE TERMINAL (RT)


CONTRACT NO.

_________________________

MSAN ID

_________________________

MSAN TYPE

_________________

EXCHANGE NAME

_________________________

DATE

_________________

TEST GEAR:

No
.
1.
2.
3.
4.
5.
6.
7.
8.
9.

Item
Multimeter
Earth tester
Data Logger/Thermometer/Hydrometer
Vacuum
Blower
Drill (optional)
Tool Kit
Thermoscanner/Thermosensor (if applicable)
Laptop

Series No.
(If applicable)

MSAN SYSTEM PHYSICAL CHECKLIST


ACCESS NETWORK MANAGEMENT
Step

Maintenance Descriptions

Expected Result

Status

APPENDIX 2(b)

Reading & remarks

A. ENVIRONMENT HEALTH CHECK


1.

Indoor Cabinet (IDC) / Outdoor Cabinet (ODC) Condition

1.1

Check the IDCs air-conditioning


units are working.

1.2

Check the IDCs temperature is


maintained at 25C 35C.

Air-Cond are
working.
25C 30C if
aircond
or
25C 35C if
none aircond

OK
Not OK

OK
Not OK

Reading : __________C

a) Surrounding
Temperature

1.3

Check the ODC temperature. ODC


ventilation unit are working.

Difference between
Ambient
(surrounding) and
inside temperature
< 100C.

_____C
OK
Not OK

b) Inside Temperature
_____C
(b) (a) = ______C
c) Battery compartment
______C

OK

1.4

Check the IDC / ODC humidity is


maintained 60%.

60%

1.5

Check and ensure the ODC fan is


working and the fan blades are
clean.

Fan is working with


clean blades.

OK

1.6

Ensure no condensation and rust at


the ODC.

Condensation and
rust free.

OK

1.7

Check the IDC / ODC surrounding


is generally clean.

Externally and
Internally clean.

OK

1.8

Check and ensure the IDC / ODC


is equipped with proper cabling and
labeling.

Proper cabling and


labeling done.

OK

1.9

Check the IDC / ODC is correctly


labeled according to NE ID.

Correct Labeling.

1.10

Ensure IDC / ODC is properly


locked.

IDC / ODC is
locked.

Step

Maintenance Descriptions

Expected Result

Not OK

Not OK

Reading : ________%

Faulty Fan : ______unit

Not OK

Not OK

Photo required for any


issued.

Not OK
OK
Not OK
OK
Not OK
Status

Reading & remarks

MSAN SYSTEM PHYSICAL CHECKLIST


ACCESS NETWORK MANAGEMENT
1.11

1.12

Check and ensure cable inlet are


properly sealed after external cable
are led in.

Cable entry
properly sealed
with appropriate
sealant compound.

Check and ensure the gap between


cabinet base and cabinet plinth are
properly sealed.

Gap must be
properly sealed
with silicon sealant
and screws tighten
to prevent from
water/insect/rodent
entering.

APPENDIX 2(b)

OK
Not OK

OK
Not OK

OK

1.13

Check and ensure all Tag Block are


in good arrangement.

Good arrangement

1.14

Check the gas/lightning arrestor at


MDF block.

Arrestor is good.

1.15

Verify and repair any faulty port


based on TM list (if any) and
update status on TM list.

All faulty port


should be ready for
service.

OK

Clean, dry and dust


free.

OK

Not OK
OK
Not OK

Not OK

No of bad port: _______

B. EQUIPMENT HEALTH CHECK


2
2.1

MSAN Shelf / Equipment


Check and ensure equipment is
clean and dry, free from dust,
spider webs and other particles.
Verify equipment operating
temperature is maintained < 50C.

2.2

Not OK

OK

(The threshold for equipment is


55C. Put lower temperature for
precaution)

< 50C input

2.2

Check the fans at each sub-rack


are working.

All fans are


working.

OK

2.3

Check the fan blades at each subrack are clean.

Fan blades are


clean.

OK

2.4

Ensure Fan Alarm appear in EMS


when Fan removed (including Heat
Exchanger (if any)).

Fan Alarm
Appeared.

OK

Step

Maintenance Descriptions

Expected Result

Not OK

Not OK

Reading : ________ C

Faulty Fan : ______unit

Not OK

Not OK
Status

Screen capture
alarm/event history
(compulsory)
Reading & remarks

MSAN SYSTEM PHYSICAL CHECKLIST


ACCESS NETWORK MANAGEMENT

APPENDIX 2(b)

Type Faulty card:


_________________
2.5

3
3.1

Clear visible alarms and state type


of faulty/missing card (if any).

Alarms cleared.
Faulty cards
replaced.

Verify control card is 1+1 or 1+0

1+1 or 1+0

Verify fiber cable is 1+1 or 1+0

1+0 (no spare fiber)


or
1+0 (spare fiber
hanging and not
connected)

Not OK

1+1
1+0 (no
spare fiber)
1+0
(spare fiber
hanging
and not
connected)

Protection Switch
Switch board is
healthy.

OK

4.2

Make the system run on protection


switchboard if Switch board is in
working condition.

System runs on
protection switch
board.

OK

Changeover Controller card by


using GUI or CLI using 'swap'
command as in TM list with PMW
(if any).
(Applicable for 1+1 uplink fiber).

Step
5

Screen capture
alarm/event history
(compulsory)

1+0

Check the condition of Protection


Switch board.

4.4

_________________

1+1

4.1

4.3

Type Missing card:

System Redundancy

1+1 or

3.2

OK

Switch off Power card at every


shelf one by one

Maintenance Descriptions
Database Backup

Standby Controller
Card becomes
active and service
should not affect.
All cards in the
particular shelf
should be working
with one Power
card.
Expected Result

Not OK

Not OK

OK
Not OK

OK
Not OK

Status

Reading & remarks

APPENDIX 2(b)

MSAN SYSTEM PHYSICAL CHECKLIST


ACCESS NETWORK MANAGEMENT

5.1

Check that login to COT from RT


(remote login) is successful.

Successful login to
COT from RT.

5.2

Perform database backup on


cross-connect information and
configuration.

Successful backup.

5.3

Save the database in suitable


media storage and send a copy.

Backup copy.

OK
Not OK
OK
Not OK
OK
Not OK

Error and alarm

6.1

Verify uplink fiber for error.

No error.

6.2

Verify subtending (downlink) fiber


for error.

No error.

OK
Not OK
OK
Not OK

C. POWER RELATED HEALTH CHECK


7

Power Supply

7.1

Check AC supply voltage to


Rectifier.

176 V 280 Vac @


50 Hz 60 Hz

7.2

Measure DC supply voltage from


rectifier to Access Equipment circuit
breaker with multimeter.

-48V ~ -54Vdc

7.3

Measure DC voltage from circuit


breaker to shelf with multimeter.

-48V ~ -54Vdc

7.4

Check the physical amount of


rectifier installed and the
model/brand.

OK
Not OK
OK
Not OK
OK
Not OK

Reading : _________V

Reading : _________V

Reading : _________V
Quantity : _______

OK

Max

Not OK

Current : _______

: _______

Model/Brand : _______
7.5

Ensure rectifier has correct fuse


rating for Access Equipment
operation.

7.6

Check rectifier loading via display


module/controller

7.7

Take out rectifier module and blow


all dust at rectifier modules and its
housing.

Clean, dry and dust


free.

Step

Maintenance Descriptions

Expected Result

Minimum 25 Amp

OK
Not OK
OK
Not OK

Reading : _______Amp

Reading : ______Amp

OK
Not OK
Status

Reading & remarks

MSAN SYSTEM PHYSICAL CHECKLIST


ACCESS NETWORK MANAGEMENT

APPENDIX 2(b)

Check the condition of rectifier.


7.8

Rectifier is able to auto-switch if


faulty (only 2+N module).
Ensure Rectifier Alarm appear in
EMS when Rectifier removed.

Rectifier able to
auto-switch and
Alarm appeared.

OK

OK

7.9

Check the AC Power surge arrestor


/ protector.

Surge arrestor is
good is in green
color (good).

7.10

Check that MSAN is properly


earthed to the ground via MGB
using Multimeter.

Connected to MGB.

7.11

Measure continuity between


Access Equipment shelf and MGB
using multimeter.

<1 ohm

7.12

Measure continuity between MGB


and last reference earth point using
multimeter.

<1 ohm

7.13

Measure continuity between AC


MGB and DC MGB using
multimeter.

<1 ohm

7.14

Measure earth resistance reading


at the last earth reference point
using earth tester.

<10 ohm

8
8.1

8.2

8.3

Not OK
OK
Not OK
OK
Not OK
OK
Not OK
OK
Not OK

OK
Not OK

Reading : _______ohm

Reading : _______ohm

Reading : _______ohm

Reading : _______ohm

Battery
OK

Check battery quantity in unit.

Not OK
OK

Check battery brand and model.

Measure the output DC voltage at


battery terminals (total voltage).

Not OK

Voltage >50V

(Offload Off Battery Breaker)


Step

Not OK

Screen capture
alarm/event history
(compulsory)

Maintenance Descriptions

Expected Result

OK
Not OK
Status

Quantity : _______Unit

Brand : ______
Model : ______
Rating : _____AH ___V

Reading : ______V

Reading & remarks

APPENDIX 2(b)

MSAN SYSTEM PHYSICAL CHECKLIST


ACCESS NETWORK MANAGEMENT
Inspect the physical condition of
battery. Record if theres any:
a) Evidence of corrosion at
terminals, connectors and
racks.(clean and apply grease).
8.4

b) Check for any loose


connection between cells.
(tighten battery terminal).

If not ok :
Battery in good
condition.

OK

_________________

Not OK

_________________
_________________
____________________

c) Cracks in cells or leakage of


electrolyte.
d) Replace the battery if its found
damaged.

8.5

If battery is in good condition


(refer to 8.4) and output DC
voltage as in 8.3 OK, execute
BOL test for 15 minutes.
(Make sure to check every 5
minute and voltage reading not
drop below 46 V)

8.6

Tighten all MCB, AC/DC cable


(incoming to rectifier) and rectifier
module in equipment cabinet.
(Please use proper tool,
insulator screw driver).

8.7

Check the condition of cable


lug/connector at AC/DC Cable
using Thermoscanner/
thermosensor (if applicable).

Additional Remarks (if any)

Battery-on-load is
supported.

Reading after BOL test :


_________V
OK

Alarm BOL appear at


EMS.

Not OK

MCB, AC cable
(incoming to rectifier)
and rectifier tighten.

OK

Cable lug/connector
is in good condition.

OK

Temperature < 38C

Screen capture
alarm/event history
(compulsory)

Not OK

Not OK

Reading : _________C

MSAN SYSTEM PHYSICAL CHECKLIST


ACCESS NETWORK MANAGEMENT

APPENDIX 2(b)

____________________________________________________________________________________
____________________________________________________________________________________
____________________________________________________________________________________
____________________________________________________________________________________
PRI CONTACT = 1800889947
Press 2 - Bahasa Melayu
Press 4 - NFM

Disclaimer : Vendor & RNO to comply OSH Requirement as stated in


http://www.dosh.gov.my/Informasi/Akta/AktaKeselamatan.pdf

Prepared by (Vendor)

Verified by (TM Personnel)

Signature :

Signature :

Name :

Name :

Designation :

Designation :

Date:

Date: