GUARANTEED TECHNICAL PARTICULARS

Sl. No. Particulars

Specification

1 MVA, 6.6/.725 KV

VOLTAMP

IS 2026,
Part I 1977
Part II - 1977
Part III 1981
Part IV 1977
IS11171-1985

Type

Three phase, core type, cast


resin dry type

Application

Input transformer to VFD for


Motor

1
2
3
4
5
6
7
8
9
10
11
12

Duty
Degree of Protection of Enclosure
Voltage HV/LV
Frequency
No. of phase
Continuous rating
Conductor
Insulation class
Cooling
Winding connection
Vector group
Neutral grounding

13

System earthing

14

Percentage impedance

Indoor, installed in room


IP 42
6.6 / 0.725 kV
50 Hz
3
1000/500-500 KVA
Copper
Class H or Better
Air Natural
Delta / Star
Dyn11d0
Effectively earthed
HV-Unearthed
LV-Effectively earthed
6.25%
HV- Cable end box suitable for
termination of XLPE aluminium
cables, with air insulated
disconnecting chamber

15

Termination
LV- Cable end box suitable for
termination of XLPE aluminium
cables, with air insulated
disconnecting chamber

16

Temperature rise over 50C ambient temp


a) In winding (measured by Resistance method)
b) Core and other adjacent parts of winding
c) Core and other parts not adjacent of windings

90C
90C
Within safe limit of core and
adjacent materials

Bushing mounted CTs


17

CT in LV Neutral bushing for standby E/F protection

Ratio : 500/5 A
Class : 10P15

18

Tap changer
a)Range
b) Total tap positions
c) Taps above nominal voltage
d) Taps below nominal voltage
e) Voltage per step variation
f) Tap change controls

OCTC
5%
5
2
2
2.50%
Manual

19

Impulse test withstand voltage

As per IS 2026, Part III 1981

power frequency voltage withstand


a) primary
b) Secondary

Induced over voltage withstand


a) primary
b) Secondary

Full wave lighting impulse withstand voltage


a) primary
b) Secondary

a) 60 KVp b) N/A

Short circuit withstand capacity at Terminal


a) For 1 sec
b) For 3 sec
c) For 5 sec

40 ka for 3 Seconds

20
21
22

Short circuit level on HV side


Short circuit level on LV side
Auxiliary supply voltage

40 kA for 3 Seconds
50 kA for 3 Sec
240 AC

23

Parallel operation

24
25
26
27

Overload capacity
Magnetizing current
Paint
Paint shade

28

Current Density

2.5 A/mm2 Max

29

Mandatory Spares

Bidder to Include

30

Special tools & tackles & commissioning


spares

Bidder to Include

31

Current rating - Primary/Secondary (amp)

32

Separate Neutral Bushing terminal for earthing

a) 20 KV b) 3 KV
Shall withstand double voltage &
double frequency for 60 Secs.

Suitable for parallel operation


with transformers of similar
ratings
As per IS 6600 1972
0.3% of rated current
Epoxy
Shade 632 as per IS 5

87.48 Amps. At HV side &


398.17 in LV1 & 398.17 in
LV
2
Required

33

Neutral terminal to be brought down to accessible


level

34

Regulation at full load and at 75degC


a) At UPF
b) At 0.8 PF

35

Loss & Efficiency

36

No load loss
a) At 100% voltage
b) At 110%voltage

37

Excitation loss at flux density 1.7 Wb/Sqm

38

Load loss at 75 degC


a) At full load
b) At half load

39

Efficiency at 75degC for UPF at


a) full load
b) 3/4 th load
c) 1/2 load

a) 98.853 b) 99.012 c) 99.098

40

Efficiency at 75degC for 0.8lag PF at


a) full load
b) 3/4th load
c) 1/2 load

a) 98.571 b) 98.767 c) 98.875

41
42
43
44
45
46

Max efficiency
Load at which max. efficiency occurs

99.099
48%

47

Winding Conductor material

48
49
50
51
52
53
54

Insulating Material
Between Turns
Between Core & winding
Between Winding
Of core laminations

Material & Type


Core material /grade
Flux density at rated voltage & at normal tap
Flux density at 110% rated voltage at normal tap

Bushing
Make

55

Bushing Type / Voltage rating / rated current


a) primary
b) Secondary

56

Bushing insulation level (KV) :


a) Impulse withstand HV/LV bushing
b) Dry withstand HV/LV bushing
c) wet withsatnd HV/LV bushing
d) Flashover withstand HV/LV bushings

57

Total creepage distance of HV/LV bushings

Required
a) 1.131 b) 4.555

a) 2.2 KW ( Sub IS Tol ) b) 3.3


KW ( Approx )
1.0 watt/kg
a) 9.4 KW ( Sub to IS Tol ) b) 2.35
KW ( Sub to IS Tol

CRGO Silicon Steel


1.7 Tesla
Bidder to specify
Electrolytic Annealed Copper
conductor
Fiber Glass
Expoxy + Air
Expoxy + Air
Carlite
Bidder to Specify
a) 12 KV, 250 Amps, b) 1KV,
1000 Amps.

IEC standard ( 1.5 x Full wave)

25 mm/KV

58
59
60

Arcing Horn gap

Bidder to specify

Current Transformer
CT make for REF/Earth fault protection

Bidder to specify

61

CT type/Qty/Ratio/Burden/Accuracy

62

Fitting & accessories(Transformer protection relay)

63

Power Cable Box Included with


a) weather protection
b) Door lock Switch
c) Space heater & illumination lamp
d) Space terminals in case of control terminals
e)
Glands
Marshalling
/ Control box Included with

64

65

a) weather protection
b) Door lock Switch
c) Space heater & illumination lamp
d) Space terminals in case of control terminals
e) Glands
weight & dimensions

i)

Weight of
a) Core
b) Winding
c) Overall Weight

iii)

Minimum clear height required to lift core & Winding

44

Tests to be performed

to be decided during detail engg.


Bidder to Include as per
specification

Bidder to specify

Bidder to specify

Core & Winding- 3010 Kgs. Over


all weight :- 3850 Kgs.
Bidder to Include mm
Bidder to Include

i)

Type tests
a) heat run test
b) Impulse test
c) Vacum test

ii)

Routine Tests

All routine test as PER IS 2026


shall be conducted at our unit.

45
46
47
a
b
c

GA Drawing
QAP

Bidder to Include
Bidder to Include

Approximate Overall dimension (in mm)


Overall Length
Overall breadth
Overall Height

2550 mm ( Approx )
2550 mm ( Approx )
2375 mm ( Approx )

48

Approximate Weight of Heaviest package (KG)

3850 Kgs ( Approx )

49

Approximate transport dimensions of largest


package LxBxH (mm)

( 2550x2550x2375 ) mm Approx

Required
Not Required
Required
(for one transformer of identical
rating)

50
51
52
53

Fitting & Accessories as per specification


Reference standard

Schedule of components & Accessories indicating


ratings,types,makes etc.
Compliance with Technical Specification and
Technical Procurement Specification

YES
IS 2026/11171
Bidder to Include
Bidder to Include

KIRLOSKAR
IS 2026,
Part I 1977
Part II - 1977
Part III 1981
Part IV 1977
IS11171-1985
Three phase, core type, cast
resin dry type
Input transformer to VFD
for Motor
Indoor, installed in room
IP 23
6.6 / 0.725 kV
50 Hz
3
1000/500-500 KVA
Copper
Class H or Better
Air Natural
Delta / Star
Dyn11d0
Effectively earthed
HV-Unearthed
LV-Effectively earthed
6.25%
HV- Cable end box suitable
for termination of XLPE
aluminium cables, with air
insulated disconnecting
chamber
LV- Cable end box suitable
for termination of XLPE
aluminium cables, with air
insulated disconnecting
chamber

90C
90C
Within safe limit of core and
adjacent materials

Ratio : 500/5 A
Class : 10P15
OCTC
5%
5
2
2
2.50%
Manual
As per IS 2026, Part III
1981
a) 20 KV b) 3 KV
Shall withstand double
voltage & double frequency
for 60 Secs.
a) 60 KVp b) N/A

40 ka for 3 Seconds
40 kA for 3 Seconds
50 kA for 3 Sec
240 AC
Suitable for parallel
operation with transformers
of similar ratings
As per IS 6600 1972
0.3% of rated current
Epoxy
Shade 632 as per IS 5
2.5 A/mm2 Max
Bidder to Include
Bidder to Include
87.48 Amps. At HV side &
398.17 in LV1 & 398.17 in
LV 2
Required

Required
a) 1.120 b) 3.794

a) 2 KW ( Sub IS Tol ) b) 2.2


KW ( Approx )
1.0 watt/kg
a) 10 KW ( Sub to IS Tol ) b)
2.4 KW ( Sub to IS Tol

a) 98.814 b) 98.994 c)
98.108

a) 98.522 b) 98.745 c)
98.888
99.114
45%
CRGO Silicon Steel
1.65 Tesla
Bidder to specify
Electrolytic Annealed
Copper conductor
Fiber Glass
CASTING MATERIAL
CASTING MATERIAL
Carlite
Bidder to Specify
a) 12 KV, 250 Amps, b)
1KV, 1000 Amps.

IEC standard ( 1.5 x Full


wave)
25 mm/KV

Bidder to specify
Bidder to specify
to be decided during detail
engg.
Bidder to Include as per
specification

Bidder to specify

Bidder to specify

Core & Winding- 3200 Kgs.


Over all weight :- 4200 Kgs.
Bidder to Include mm

ok noted

ok noted
Bidder to Include
Bidder to Include
2400 mm ( Approx )
2775 mm ( Approx )
2525 mm ( Approx )
4200 Kgs ( Approx )
( 2400x2775x2525 ) mm Approx

ok noted
IS 2026/11171
Bidder to Include
Bidder to Include

Você também pode gostar