Você está na página 1de 134

PRIME Series

Indoor Unit

Outdoor Unit
GC 7A RC R410A

PRIME 7

GC 7A R410A
GC RELAX 7 RC R22
GCN 9 RC R410A (class A)
GCN 9 R410A (class A)
ODU WAP 9 RC R410A (class C)

PRIME 9

ODU WAP 9 R410A (class C)


ODU WAP 9 RC R22
ODU WAP 9 R22

PRIME 12 (A) R410A


PRIME 12 (C) R410A
PRIME 12 R22

GCN 12 RC R410A (class A)


GCN 12 R410A (class A)
ODU WAP 12 RC R410A (class C)
ODU WAP 12 R410A (class C)
ODU WAP 12 RC R22
ODU WAP 12 R22
GCN 17N RC R410A

PRIME 18

GCN 17N R410A


GC RELAX 18N RC R22
GC RELAX 18N R22

REFRIGERANT

COOLING ONLY

R22

HEAT PUMP

R410A

4.13*.&"(#

JULY 2008

LIST OF EFFECTIVE PAGES


LIST OF EFFECTIVE PAGES
Note: Changes in the pages are indicated by a Revision# in the footer of each effected page
(when none indicates no changes in the relevant page). All pages in the following list represent
effected/ non effected pages divided by chapters.
Dates of issue for original and changed pages are:
Original ....... 0 ........ March 2007
Total number of pages in this publication is 137 consisting of the following:

Page
No.

Revision
No. #

Page
No.

Revision
No. #

Page
No.

Revision
No. #

Title ....................... 0
A ........................... 0
i ............................. 0
1-1 - 1-3 ................ 0
2-1 - 2-6 ................ 0
3-1 ........................ 0
4-1 - 4-2 ................ 0
5-1 - 5-24 .............. 0
6-1 - 6-6 ................ 0
7-1 ........................ 0
8-1 - 8-2 ................ 0
9-1 ........................ 0
10-1-10-2 .............. 0
11-1 ....................... 0
12-1-12-31 ............ 0
13-1-13-2 .............. 0
14-1-14-22 ............ 0
Appendix -A ...........0

Zero in this column indicates an original page.

*Due to constant improvements please note that the data on this service manual can be modied with out notice.
**Photos are not contractual

SM PRIME 1- A.1 GB

TABLE OF CONTENTS

Table of Contents
1.

INTRODUCTION ...................................................................................................1-1

2.

PRODUCT DATA SHEET ......................................................................................2-1

3.

RATING CONDITIONS ..........................................................................................3-1

4.

OUTLINE DIMENSIONS .......................................................................................4-1

5.

PERFORMANCE DATA & PRESSURE CURVES ................................................5-1

6.

SOUND LEVEL CHARACTERISTICS ..................................................................6-1

7.

ELECTRICAL DATA ..............................................................................................7-1

8.

WIRING DIAGRAMS .............................................................................................8-1

9.

ELECTRICAL CONNECTIONS .............................................................................9-1

10. REFRIGERATION DIAGRAMS .............................................................................10-1


11.

TUBING CONNECTIONS......................................................................................11-1

12. CONTROL SYSTEM .............................................................................................12-1


13. TROUBLESHOOTING ..........................................................................................13-1
14. EXPLODED VIEWS AND SPARE PARTS LISTS .................................................14-1
15. APPENDIX A .........................................................................................................15-1

SM PRIME 1- A.1 GB

INTRODUCTION

1.

INTRODUCTION

1.1

General
The new PRIME Series wall mounted comprise the ST (cooling only) and RC (heat
pump) models, as follows:

Indoor Units

RC R410A
Outdoor Units

PRIME 7

GC 7ARC R410A

PRIME 9

GCN 9 RC R410A (class A)

PRIME 9

ODU WAP 9 RC R410A (class C)

PRIME 12 (A) R410A

GCN 12 RC R410A (class A)

PRIME 12 (C) R410A

ODU WAP 12 RC R410A (class C)

PRIME 18

GCN 17 NRC R410A

Indoor Units

ST R410A
Outdoor Units

PRIME 7

GC 7ARC R410A

PRIME 9

GCN 9 RC R410A (class A)

PRIME 9

ODU WAP 9 RC R410A (class C)

PRIME 12 (A) R410A

GCN 12 RC R410A (class A)

PRIME 12 (C) R410A

ODU WAP 12 RC R410A (class C)

PRIME 18

GCN 17 NRC R410A

Indoor Units

RC R22
Outdoor Units

PRIME 7

GC RELAX 7 RC R22

PRIME 9

OUD WAP 9RC R22

PRIME 12 R22

ODU WAP 12RC R22

PRIME 18

GC RELAX 18 NRC R22

Indoor Units

ST R22
Outdoor Units

PRIME 9

OUD WAP 9 R22

PRIME 12 R22

ODU WAP 12 R22

PRIME 18

GC RELAX 18 N R22

.
The indoor PRIME Series units are available as LED display types, featuring esthetic
design, compact dimensions, and low noise operation.

1.2

Main Features
The Prime Series benets from the most advanced technological innovations, namely:
R410A/R22 models.
Microprocessor control

SM PRIME 1- A.1 GB

1-1

INTRODUCTION

1.3

Infrared remote control with liquid crystal display.

Indoor large diameter cross ow fan, allowing low noise level operation.

Bended indoor coil with treated aluminum ns and coating for improved efciency.

Easy access to the interconnecting tubing and wiring connections, so that removing
the front grill or casing is not necessary.

Refrigerant pipes can be connected to the indoor unit from 5 different optional
directions.

Automatic treated air sweep.

Low indoor and outdoor noise levels.

Easy installation and service.

Indoor Unit
The indoor unit is a wall mounted, and can be easily tted to many types of residential
and commercials applications.

1.4

Filtration

1.5

Easily accessible, and re-usable pre-lters (mesh)

Control
The microprocessor indoor controller, and an infrared remote control, supplied as
standard, provide complete operating function and programming. For further details
please refer to the Operation Manual, Appendix A.

1.6

Outdoor Unit
The PRIME Series outdoor units can be installed as oor or wall mounted units by using
a wall supporting bracket. For further information please refer to the Product Data Sheet,
Chapter 2.
The rotary compressor driven by outdoor unit provides optimum performance and noise
levels. A Bluen hydrophilic treatment promotes the ow of condensates, and offers
corrosion protection to maintain performance levels and increasing the service life. On
the other hand, the anticorrosion treatment with a high density powder paint coating
ensures high resistance whatever the operating conditions.

1.7

Tubing Connections
Flare type interconnecting tubing to be produced on site.
For further details please refer to the Installation Manual, Outdoor Chapter 3.

1.8

Inbox Documentation
Each unit is supplied with its own installation and operation manuals.

1-2

SM PRIME 1- A.1 GB

INTRODUCTION

1.9

Matching Table

1.9.1

R410A
INDOOR UNITS

OUTDOOR UNITS

MODEL

Prime7

GC7

Prime9

Prime12
(class A)

Prime12
(class C)

CON9

CON12

GCN9

GCN12

ONG3-17

1.9.2

Prime18

R22
INDOOR UNITS

OUTDOOR UNITS

MODEL

Prime7
CON7
CSP9
CSP12

ONG3-17

SM PRIME 1- A.1 GB

Prime9

Prime12

Prime18\

1-3

PRODUCT DATA SHEET

2.

PRODUCT DATA SHEET

2.1

PRIME 7 (Alpha 7 DF) / GC RELAX 7 (CON 7 R22)

Model Indoor Unit


Model Outdoor Unit
Installation Method of Pipe
Characteristics

Units
Btu/hr
kW
kW
W/W

Capacity (4)
Power input (4)
EER (Cooling) or COP(Heating) (4)
Energy efciency class

V
Ph
Hz
A

Power supply

OUTDOOR

INDOOR

Rated current
Power factor
Prated (IDU)
Prated (IDU+ODU)
Starting current
Circuit breaker rating
Fan type & quantity
Fan speeds
Air ow (1)
External static pressure
Sound power level (2)
Sound pressure level(3)
Moisture removal
Condenstate drain tube I.D
Dimensions
Net Weight
Package dimensions
Packaged weight
Units per pallet
Stacking height
Refrigerant control
Compressor type,model
Fan type & quantity
Fan speeds
Air ow
Sound power level
Sound pressure level(3)
Dimensions
Net Weight
Package dimensions
Packaged weight
Units per pallet
Stacking height
Refrigerant type
Standard charge
Additional charge
Connections between
units
Operation control type
Heating elements (Option)
Others

W
W
A
A
H/M/L
H/M/L
Min
H/M/L
H/M/L

WxHxD
WxHxD

H
H
H
H
WxHxD
WxHxD

RPM
m3/hr
Pa
dB(A)
dB(A)
l/hr
mm
mm
kg
mm
kg
units
units

RPM
m3/hr
dB(A)
dB(A)
mm
kg
mm
kg
Units
units
kg(4m)

Liquid line
Suction line
Max.tubing length
Max.height
difference

In.(mm)
In.(mm)
m.

PRIME 7(Alpha 7 DF)


GC RELAX 7 (CON 7 R22)
Flared
Cooling only
Cooling
Heating
7230
7230
7340
2.12
2.12
2.15
0.75
0.75
0.67
2.83
2.83
3.21
C
C
C
220-240
1
50
3.4
3.4
3.1
0.96
0.96
0.94
25
830
16
10
Crossow x 1
1150/ - /950
400/ - /320
0
50/ - /45
37/ - /31
0.7
16
680x250x180
7
740x310x248
9.5
32
8levels
Capillary tube
Rotary,HITACHI SD134CV-H6AU
Propeller(direct) x 1
850
1200
61
62
51
52
610x520x240
23
24
725x550x355
26
27
12
4 levels
R22
0.5
4m<Lin8m:+5g/m 8m<Lin10m:+9g/m
1/4"(6.35)
3/8"(9.53)
Max.10

m.

Max.7
Remote control

kW

(1)Airow in ducted units;at nominal external static pressure.


(2)Sound power in ducted units is measured at air discharge.
(3)Sound pressure level measured at 1-meter distance from unit.
(4)Rating conditions in accordance to ISO 5151 and ISO 13253 (for ducted units)

SM PRIME 1- A.1 GB

2-1

PRODUCT DATA SHEET

2.2

PRIME 7 (Alpha 7 DF) / GC 7A (CON 7 R410A)

Model Indoor Unit


Model Outdoor Unit
Installation Method of Pipe
Characteristics
Capacity (4)
Power input (4)
EER (Cooling) or COP(Heating) (4)
Energy efciency class
Power supply

OUTDOOR

INDOOR

Rated current
Power factor
Starting current
Circuit breaker rating
Fan type & quantity
Fan speeds
H/M/L
Air ow (1)
H/M/L
External static
Min-Max
pressure
Sound power level (2)
H/M/L
Sound pressure
H/M/L
level(3)
Moisture removal
Condenstate drain tube I.D
Dimensions
WxHxD
Weight
Package dimensions
WxHxD
Packaged weight
Units per pallet
Stacking height
Refrigerant control
Compressor type,model
Fan type & quantity
Fan speeds
H/L
Air ow
H/L
Sound power level
H/L
Sound pressure
H/L
level(3)
Dimensions
WxHxD
Weight
Package dimensions
WxHxD
Packaged weight
Units per pallet
Stacking height
Refrigerant type
Refrigerant chargless distance
Additional charge
Liquid line
Suction line
Connections between
Max.tubing length
units
Max.height
difference
Operation control type
Heating elements
Others

Units
Btu/hr
kW
kW
W/W
V
Ph
Hz
A
A
A
RPM
m3/hr

PRIME 7 (Alpha 7 DF)


GC 7A (CON 7 R410A)
Flared
Cooling Only
Cooling
7400
7400
2.17
2.17
0.66
0.66
3.29
3.29
A
A
220-240
1
50
2.9
2.9
0.99
0.99
15
10
Crossow x 1
1150/850
390/320

Pa

dB(A)

50/44

dB(A)

37/32

l/hr
mm
mm
kg
mm
kg
units
units

Heating
7540
2.21
0.63
3.51
B

2.8
0.98

RPM
m3/hr
dB(A)

0.8
16
680x180x250
7
740x250x310
9.5
36
9 levels
Capillary tube
Rotary,TOSHIBA,PA82X1C-4DZDE
Propeller(direct) x 1
850
1200
61
62

dB(A)

52

mm
kg
mm
kg
Units
units
kg/m
In.(mm)
In.(mm)
m.

53
610x240x520

27.5
720x360x550
30/33.5(with kit)
30.5/34(with kit)
12
4 levels
R410A
0.72kg/7.5m
4mLength10m: +0g; 10mLength15m: +80g
1/4"(6.35)
3/8"(9.53)
Max.15

m.

27

Max.7
Remote control

kW

(1)Airow in ducted units;at nominal external static pressure.


(2)Sound power in ducted units is measured at air discharge.
(3)Sound pressure level measured at 1-meter distance from unit.
(4)Rating conditions in accordance to ISO 5151 and ISO 13253 (for ducted units)

2-2

SM PRIME 1- A.1 GB

PRODUCT DATA SHEET

2.3

PRIME 9 (ASP 9 DF) / ODU WAP 9RC (CSP 9 RC R22)

Model Indoor Unit


Model Outdoor Unit
Installation Method of Pipe
Characteristics
Capacity (4)
Power input (4)
EER (Cooling) or COP(Heating) (4)
Energy efciency class
Power supply

OUTDOOR

INDOOR

Rated current
Power factor
Prated (IDU)
Prated (IDU+ODU)
Starting current
Circuit breaker rating
Fan type & quantity
Fan speeds
H/M/L
Air ow (1)
H/M/L
External static
Min
pressure
Sound power level (2)
H/M/L
Sound pressure
H/M/L
level(3)
Moisture removal
Condenstate drain tube I.D
Dimensions
WxHxD
Net Weight
Package dimensions
WxHxD
Packaged weight
Units per pallet
Stacking height
Refrigerant control
Compressor type,model
Fan type & quantity
Fan speeds
H
Air ow
H
Sound power level
H
Sound pressure
H
level(3)
Dimensions
WxHxD
Net Weight
Package dimensions
WxHxD
Packaged weight
Units per pallet
Stacking height
Refrigerant type
Refrigerant chargless distance
Additional charge
Liquid line
Suction line
Connections between
Max.tubing length
units
Max.height
difference
Operation control type
Heating elements (Option)
Others

RPM
m3/hr

PRIME 9 (ASP 9 DF)


ODU WAP 9RC (CSP 9 RC R22)
Flared
Cooling Only
Cooling
Heating
8770
9050
9870
2.57
2.65
2.89
0.94
0.94
0.85
2.73
2.82
3.41
D
C
B
220-230
1
50
4.4
4.4
4.0
0.95
0.95
0.95
30
1090
26
10
Crossow x 1
1310/-/1100
450/-/350

Pa

dB(A)

53/-/49

dB(A)

41/-/35

l/hr
mm
mm
kg
mm
kg
units
units

RPM
m3/hr
dB(A)

1
16
680x180x250
6
740x310x248
8.5
32
8levels
Capillary tube
Rotary,TOSHIBA PH170X1C-4DZDE3
Propeller(direct) x 1
900
1265
62
63

dB(A)

52

Units
Btu/hr
kW
kW
W/W
V
Ph
Hz
A
W
W
A
A

mm
kg
mm
kg
Units
units
kg(4m)
In.(mm)
In.(mm)
m.
m.

53
610x520x240

26

26.5
725x550x355

29

29.5
12
4 levels
R22
0.63
4m<Length8m:+5g/m; 8m<Lin15m:+15g/m
1/4"(6.35)
3/8"(9.53)
Max.15
Max.7
Remote control

kW

(1)Airow in ducted units;at nominal external static pressure.


(2)Sound power in ducted units is measured at air discharge.
(3)Sound pressure level measured at 1-meter distance from unit.
(4)Rating conditions in accordance to ISO 5151 and ISO 13253 (for ducted units)

SM PRIME 1- A.1 GB

2-3

PRODUCT DATA SHEET

2.4

PRIME 9 (Alpha 9 R410A DF) / GCN 9A RC (GCN 9 RC R410)

Model Indoor Unit


Model Outdoor Unit
Installation Method of Pipe
Characteristics
Capacity (4)
Power input (4)
EER (Cooling) or COP(Heating) (4)
Energy efciency class
Power supply

OUTDOOR

INDOOR

Rated current
Power factor
Starting current
Circuit breaker rating
Fan type & quantity
Fan speeds
H/M/L
Air ow (1)
H/M/L
External static
Min-Max
pressure
Sound power level (2)
H/M/L
Sound pressure
H/M/L
level(3)
Moisture removal
Condenstate drain tube I.D
Dimensions
WxHxD
Weight
Package dimensions
WxHxD
Packaged weight
Units per pallet
Stacking height
Refrigerant control
Compressor type,model
Fan type & quantity
Fan speeds
H/L
Air ow
H/L
Sound power level
H/L
Sound pressure
H/L
level(3)
Dimensions
WxHxD
Weight
Package dimensions
WxHxD
Packaged weight
Units per pallet
Stacking height
Refrigerant type
Refrigerant chargless distance

Units
Btu/hr
kW
kW
W/W
V
Ph
Hz
A
A
A
RPM
m3/hr
Pa

dB(A)

53/49

dB(A)

41/35

l/hr
mm
mm
kg
mm
kg
units
units

RPM
m3/hr
dB(A)

1.2
16
680x180x250
7
740x250x310
9.5
36
9 levels
Capillary tube
Rotary,TOSHIBA,PA108X1C-4FZDE
Propeller(direct) x 1
750
1370
59
61

dB(A)

49

mm
kg
mm
kg
Units
units
kg/m

Operation control type


Heating elements
Others

Liquid line
Suction line
Max.tubing length
Max.height
difference

Heating
10510
3.08
0.90
3.42
B

4.0
0.98

51
830x245x545

32.5
35/38.5(with kit)

0.85kg/7.5m

33.5
880x310x610
36/39.5(with kit)
9
3 levels
R410A
0.90kg/7.5m

4mLength10m: +0g;
10mLength15m: +80g

Additional charge

Connections between
units

PRIME 9 (ALPHA 9 R410A DF)


GCN 9A RC (GCN 9 RC R410A)
Flared
Cooling Only
Cooling
9420
9420
2.76
2.76
0.84
0.84
3.29
3.29
A
A
220-240
1
50
3.7
3.7
0.99
0.99
21.7
10
Crossow x 1
1310/1100
450/360

In.(mm)
In.(mm)
m.
m.

4mLength10m: +0g;
10mLength15m: +80g
1/4"(6.35)
3/8"(9.53)
Max.15
Max.7

Remote control
kW

(1)Airow in ducted units;at nominal external static pressure.


(2)Sound power in ducted units is measured at air discharge.
(3)Sound pressure level measured at 1-meter distance from unit.
(4)Rating conditions in accordance to ISO 5151 and ISO 13253 (for ducted units)

2-4

SM PRIME 1- A.1 GB

PRODUCT DATA SHEET

2.5

PRIME 9 (ASP 9 R410A DF)/ODU WAP 9RC R410 (CSP 9R410A)

Model Indoor Unit


Model Outdoor Unit
Installation Method of Pipe
Characteristics
Capacity (4)
Power input (4)
EER (Cooling) or COP(Heating) (4)
Energy efciency class
Power supply

OUTDOOR

INDOOR

Rated current
Power factor
Prated(IDU)
Prated(IDU+ODU)
Starting current
Circuit breaker rating
Fan type & quantity
Fan speeds
H/M/L
Air ow (1)
H/M/L
External static
Min
pressure
Sound power level (2)
H/M/L
Sound pressure
H/M/L
level(3)
Moisture removal
Condenstate drain tube I.D
Dimensions
WxHxD
Net Weight
Package dimensions
WxHxD
Packaged weight
Units per pallet
Stacking height
Refrigerant control
Compressor type,model
Fan type & quantity
Fan speeds
H
Air ow
H
Sound power level
H
Sound pressure
H
level(3)
Dimensions
WxHxD
Net Weight
Package dimensions
WxHxD
Packaged weight
Units per pallet
Stacking height
Refrigerant type
Standard charge
Additional charge
Liquid line
Suction line
Connections between
Max.tubing length
units
Max.height
difference
Operation control type
Heating elements
Others

Units
Btu/hr
kW
kW
W/W
V
Ph
Hz
A
W
W
W
A
A
RPM
m3/hr

PRIME 9 (ASP 9 R410A DF)


ODU WAP 9RC R410 (CSP 9 R410A )
Flared
Cooling Only
Cooling
Heating
8700
8700
9040
2.55
2.55
2.65
0.89
0.89
0.82
2.84
2.84
3.22
C
C
C
220-230
1
50
4.0
4.0
3.7
0.97
0.97
0.97
30
1072
1072
16.5
10
Crossow x 1
1310/-/1100
450/-/360

Pa

dB(A)

53/-/49

dB(A)

41/-/35

l/hr
mm
mm
kg
mm
kg
units
units

RPM
m3/hr
dB(A)

0.9
16
680x250x180
6
740x310x248
8.5
36
9 levels
Capillary tube
Rotary,Sanyo(Hua Run),C-1RV107
Propeller(direct) x 1
900
1200
62
62

dB(A)

51

mm
kg
mm
kg
Units
units

51
610x520x240

23.5

24
725x550x355

In.(mm)
In.(mm)
m.

26.5
12
4 levels
R410A
0.58kg
4mLength10m: +0g; 10mLength15m: +50g
1/4"(6.35)
3/8"(9.53)
Max.15

m.

Max.7

kW

Remote control
Remote control(RC-5)

kg(7.5m)

26

(1)Airow in ducted units;at nominal external static pressure.


(2)Sound power in ducted units is measured at air discharge.
(3)Sound pressure level measured at 1-meter distance from unit.
(4)Rating conditions in accordance to ISO 5151 and ISO 13253 (for ducted units)

SM PRIME 1- A.1 GB

2-5

PRODUCT DATA SHEET

2.6

PRIME 12 (ASP 12 DF) / ODU WAP 12RC R22 (CSP 12RC R22)

Model Indoor Unit


Model Outdoor Unit
Installation Method of Pipe
Characteristics
Capacity (4)
Power input (4)
EER (Cooling) or COP(Heating) (4)
Energy efciency class
Power supply

OUTDOOR

INDOOR

Rated current
Power factor
Prated (IDU)
Prated (IDU+ODU)
Starting current
Circuit breaker rating
Fan type & quantity
Fan speeds
H/M/L
Air ow (1)
H/M/L
External static
Min
pressure
Sound power level
H/M/L
(2)
Sound pressure
H/M/L
level(3)
Moisture removal
Condenstate drain tube I.D
Dimensions
WxHxD
Net Weight
Package dimensions
WxHxD
Packaged weight
Units per pallet
Stacking height
Refrigerant control
Compressor type,model
Fan type & quantity
Fan speeds
H
Air ow
H
Sound power level
H
Sound pressure
H
level(3)
Dimensions
WxHxD
Net Weight
Package dimensions
WxHxD
Packaged weight
Units per pallet
Stacking height
Refrigerant type
Refrigerant chargless distance
Additional charge
Liquid line
Connections between Suction line
Max.tubing length
units
Max.height
difference
Operation control type
Heating elements
Others

RPM
m3/hr

PRIME 12 (ASP 12 DF)


ODU WAP 12RC R22 (CSP 12 RC R22 )
Flared
Cooling Only
Cooling
Heating
11260
11260
12800
3.30
3.30
3.75
1.17
1.17
1.06
2.81
2.81
3.54
C
C
B
220-230
1
50
5.2
5.2
4.8
0.95
0.95
0.95
30
1425
1446
28
10
Crossow x 1
1250/-/1000
650/-/500

Pa

dB(A)

55/-/49

dB(A)

41/-/34

l/hr
mm
mm
kg
mm
kg
units
units

1.1
16
840x250x180
7
900x310x248
9.5
32
8evels
Capillary tube
Rotary,Sanyo,C-RV212H51BA
Propeller(direct) x 1
900
1200
65

Units
Btu/hr
kW
kW
W/W
V
Ph
Hz
A
W
W
A
A

RPM
m3/hr
dB(A)

63

dB(A)

52

mm
kg
mm
kg
Units
units

54
610x520x240

29.5

30
725x550x355

In.(mm)
In.(mm)
m.

32
12
4 levels
R22
0.88
4mLength10m: +0g; 10mLength15m: +100g
1/4"(6.35)
1/2"(12.7)
Max.15

m.

Max.7

kg(7.5m)

31.5

Remote control
kW

(1)Airow in ducted units;at nominal external static pressure.


(2)Sound power in ducted units is measured at air discharge.
(3)Sound pressure level measured at 1-meter distance from unit.
(4)Rating conditions in accordance to ISO 5151 and ISO 13253 (for ducted units)

2-6

SM PRIME 1- A.1 GB

PRODUCT DATA SHEET

2.7

PRIME 12A (ALPHA 12 R410A DF) / GCN12A RC R410A / GCN 12


RC R410A

Model Indoor Unit


Model Outdoor Unit
Installation Method of Pipe
Characteristics
Capacity (4)
Power input (4)
EER (Cooling) or COP(Heating) (4)
Energy efciency class
Power supply

OUTDOOR

INDOOR

Rated current
Power factor
Starting current
Circuit breaker rating
Fan type & quantity
Fan speeds
H/M/L
Air ow (1)
H/M/L
External static
Min-Max
pressure
Sound power level (2)
H/M/L
Sound pressure
H/M/L
level(3)
Moisture removal
Condenstate drain tube I.D
Dimensions
WxHxD
Weight
Package dimensions
WxHxD
Packaged weight
Units per pallet
Stacking height
Refrigerant control
Compressor type,model
Fan type & quantity
Fan speeds
H/L
Air ow
H/L
Sound power level
H/L
Sound pressure
H/L
level(3)
Dimensions
WxHxD
Weight
Package dimensions
WxHxD
Packaged weight
Units per pallet
Stacking height
Refrigerant type
Refrigerant chargless distance
Additional charge
Liquid line
Suction line
Connections between
Max.tubing length
units
Max.height
difference
Operation control type
Heating elements
Others

Units
Btu/hr
kW
kW
W/W
V
Ph
Hz
A
A
A
RPM
m3/hr

PRIME 12A (ALPHA 12 R410A DF)


GCN12 A RC 410A (GCN 12 RC R410A)
Flared
Cooling Only
Cooling
Heating
12280
12280
13030
3.60
3.60
3.82
1.12
1.12
1.11
3.21
3.21
3.44
A
A
B
220-240
1
50
4.9
4.9
4.9
0.99
0.99
0.98
31.5
10
Crossow x 1
1210/950
620/460

Pa

dB(A)

53/47

dB(A)

40/33

l/hr
mm
mm
kg
mm
kg
units
units

RPM
m3/hr
dB(A)

1.5
16
840x180x250
8
930x250x310
10.5
36
9 levels
Capillary tube
Rotary,TOSHIBA,PA145X2C-4FT
Propeller(direct) x 1
830
1450
65
65

dB(A)

54

mm
kg
mm
kg
Units
units
kg/m
In.(mm)
In.(mm)
m.

54
830x245x545

38
880x310x610
39.5/43(with kit)
40.5/44(with kit)
9
3 levels
R410A
0.89kg/7.5m
4mLength10m: +0g; 10mLength15m: +80g
1/4"(6.35)
3/8"(9.53)
Max.15

m.

37

Max.7
Remote control

kW

(1)Airow in ducted units;at nominal external static pressure.


(2)Sound power in ducted units is measured at air discharge.
(3)Sound pressure level measured at 1-meter distance from unit.
(4)Rating conditions in accordance to ISO 5151 and ISO 13253 (for ducted units)

SM PRIME 1- A.1 GB

2-7

PRODUCT DATA SHEET

2.8

PRIME 12C (ASP 12 R410A DF) / ODU WAP 12RC R410A (CSP
12 R410A)

Model Indoor Unit


Model Outdoor Unit
Installation Method of Pipe
Characteristics
Capacity (4)
Power input (4)
EER (Cooling) or COP(Heating) (4)
Energy efciency class
Power supply

OUTDOOR

INDOOR

Rated current
Power factor
Prated(IDU)
Prated(IDU+ODU)
Starting current
Circuit breaker rating
Fan type & quantity
Fan speeds
H/M/L
Air ow (1)
H/M/L
External static
Min
pressure
Sound power level (2)
H/M/L
Sound pressure
H/M/L
level(3)
Moisture removal
Condenstate drain tube I.D
Dimensions
WxHxD
Net Weight
Package dimensions
WxHxD
Packaged weight
Units per pallet
Stacking height
Refrigerant control
Compressor type,model
Fan type & quantity
Fan speeds
H
Air ow
H
Sound power level
H
Sound pressure
H
level(3)
Dimensions
WxHxD
Net Weight
Package dimensions
WxHxD
Packaged weight
Units per pallet
Stacking height
Refrigerant type
Standard charge
Additional charge
Liquid line
Suction line
Connections between
Max.tubing length
units
Max.height
difference
Operation control type
Heating elements
Others

Units
Btu/hr
kW
kW
W/W
V
Ph
Hz
A
W
W
A
A
RPM
m3/hr

PRIME 12C (ASP 12 R410A DF)


ODU WAP 12RC R410 (CSP 12 R410A )
Flared
Cooling Only
Cooling
Heating
11260
11260
11600
3.30
3.30
3.40
1.16
1.16
1.05
2.84
2.84
3.22
C
C
C
220-230
1
50
5.13
5.13
4.65
0.98
0.98
0.98
30
1295
1440
28
10
Crossow x 1
1250/-/1000
650/-/500

Pa

dB(A)

55/-/49

dB(A)

41-/34

l/hr
mm
mm
kg
mm
kg
units
units

RPM
m3/hr
dB(A)

1.1
16
840x250x180
7
900x310x248
9.5
36
9 levels
Capillary tube
Rotary,Sanyo(Hua Run),C-RV133H1D
Propeller(direct) x 1
900
1200
63
64

dB(A)

53

mm
kg
mm
kg
Units
units
kg(7.5m)
In.(mm)
In.(mm)
m.

55
610x520x240

29

30
725x550x355

31

32
12
4 levels
R410A
0.89kg
4mLength10m: +0g; 10mLength15m: +50g
1/4"(6.35)
3/8"(9.53)
Max.15

m.

Max.7

kW

Remote control
Remote control(RC-5)

(1)Airow in ducted units;at nominal external static pressure.


(2)Sound power in ducted units is measured at air discharge.
(3)Sound pressure level measured at 1-meter distance from unit.
(4)Rating conditions in accordance to ISO 5151 and ISO 13253 (for ducted units)

2-8

SM PRIME 1- A.1 GB

PRODUCT DATA SHEET

2.9

PRIME 18 (COMPACT-17) / GC RELAX 18N / ONG17 RC R22

Model Indoor Unit


Model Outdoor Unit
Installation Method of Pipe
Characteristics
Capacity (4)
Power input (4)
EER (Cooling) or COP(Heating) (4)
Energy efciency class
Power supply

OUTDOOR

INDOOR

Rated current
Power factor
Prated (IDU)
Prated (IDU+ODU)
Starting current
Circuit breaker rating
Fan type & quantity
Fan speeds
H/M/L
Air ow (1)
H/M/L
External static
Min
pressure
Sound power level
H/M/L
(2)
Sound pressure
H/M/L
level(3)
Moisture removal
Condenstate drain tube I.D
Dimensions
WxHxD
Net Weight
Package dimensions
WxHxD
Packaged weight
Units per pallet
Stacking height
Refrigerant control
Compressor type,model
Fan type & quantity
Fan speeds
H
Air ow
H
Sound power level
H
Sound pressure
H
level(3)
Dimensions
WxHxD
Net Weight
Package dimensions
WxHxD
Packaged weight
Units per pallet
Stacking height
Refrigerant type
Standard charge
Additional charge
Liquid line
Connections between Suction line
Max.tubing length
units
Max.height
difference
Operation control type
Heating elements (Option)
Others

Units
Btu/hr
kW
kW
W/W
V
Ph
Hz
A
W
W
A
A
RPM
m3/hr

PRIME 18 /COMPACT-17
GC RELAX 18 N / (ONG-17 RC R22 )
Flared
Cooling only
Cooling
Heating
18120
18150
19110
5.31
5.32
5.60
1.81
1.86
1.79
2.93
2.86
3.13
C
C
D
220-240
1
50
8.5
8.4
8.2
0.32
0.33
0.32
40
2350
36.8
15
Crossow x 1
1200/ - /1000
720/ - /590

Pa

dB(A)

55/ - /50

dB(A)

43/ - /37

l/hr
mm
mm
kg
mm
kg
units
units

RPM
m3/hr
dB(A)

2.4
16
900x295x200
11
955x360x270
14
21
7
Capillary tube
Rotary,TOSHIBA PH330X2CS-4KT4
Propeller(direct) x 1
920
2160
65
65

dB(A)

53

mm
kg
mm
kg
Units
units
kg(7.5m)

54
795x610x290

43

44
970x650x394

46

47
9
3 Levels
R22

In.(mm)
In.(mm)
m.

1.12
1.40
4mLin10m:0g; 10m<Lin15m:+100g
1/4"(6.35)
1/2"(12.7)
Max.15

m.

Max.7
Remote control

kW

(1)Airow in ducted units;at nominal external static pressure.


(2)Sound power in ducted units is measured at air discharge.
(3)Sound pressure level measured at 1-meter distance from unit.
(4)Rating conditions in accordance to ISO 5151 and ISO 13253 (for ducted units)

SM PRIME 1- A.1 GB

2-9

PRODUCT DATA SHEET

2.10

PRIME 18 (ALPHA 17 R410A DF) / GCN 17 NRC / ONG17 RC


R410A

Model Indoor Unit


Model Outdoor Unit
Installation Method of Pipe

H/M/L
H/M/L

RPM
m3/hr

PRIME 18 ( ALPHA 17 R410A DF)


GCN 17 NRC (ONG 17 RC R410A)
Flared
Cooling
Cooling
Heating
Only
18770
18770
19450
5.50
5.50
5.70
1.66
1.66
1.67
3.31
3.31
3.41
A
A
B
220-240
1
50
7.6
7.6
7.7
0.95
0.95
0.95
40
2150
32
15
Cross ow*1
1200/ - /1000
720/ - /590

Min

Pa

H/M/L

dB(A)

55/ - /50

H/M/L

dB(A)

43/ - /37

l/hr
mm
mm
kg
mm
kg
units
units

Characteristics

Units
Btu/hr
kW
kW
W/W

Capacity (4)
Power input (4)
EER (Cooling) or COP(Heating) (4)
Energy efciency class

V
Ph
Hz
A

Power supply

OUTDOOR

INDOOR

Rated current
Power factor
Prated (IDU)
Prated (IDU+ODU)
Starting current
Circuit breaker rating
Fan type & quantity
Fan speeds
Air ow (1)
External static
pressure
Sound power level
(2)
Sound pressure
level(3)
Moisture removal
Condenstate drain tube I.D
Dimensions
Net Weight
Package dimensions
Packaged weight
Units per pallet
Stacking height
Refrigerant control
Compressor type,model
Fan type & quantity
Fan speeds
Air ow
Sound power level
Sound pressure
level(3)
Dimensions
Net Weight
Package dimensions

W
W
A
A

H
H
H

RPM
m3/hr
dB(A)

2.2
16
900x295x200
11
955x360x270
14
24
8
Capillary tube
Rotary,TOSHIBA PA200X2CS-4KT1
Propeller(direct) x 1
910
2160
64
65

dB(A)

53

54

WxHxD

mm
kg
mm

42

795x610x290
43
970x650x394

Packaged weight

kg

45/49(with
kit)

Units per pallet


Stacking height
Refrigerant type
Standard charge
Additional charge

Units
units

Connections
between units
Operation control type
Heating elements (Option)
Others

WxHxD
WxHxD

WxHxD

In.(mm)
In.(mm)
m.

9
3
R410A
1.28
4mL10m: +0g;10mL15m: +100g
1/4"(6.35)
1/2"(12.7)
15

m.

kg(7.5m)
Liquid line
Suction line
Max.tubing length
Max.height
difference

46/50(with kit)

Remote control
kW
All season kit Factory option

(1)Airow in ducted units;at nominal external static pressure.


(2)Sound power in ducted units is measured at air discharge.
(3)Sound pressure level measured at 1-meter distance from unit.
(4)Rating conditions in accordance to ISO 5151 and ISO 13253 (for ducted units)

2-10

SM PRIME 1- A.1 GB

RATING CONDITIONS

3.

RATING CONDITIONS
Standard conditions in accordance with ISO 5151, ISO 13253 (for ducted units)
and EN 14511.
Cooling:
Indoor:
27oC DB 19oC WB
Outdoor: 35 oC DB
Heating:
Indoor:
20oC DB
Outdoor: 7oC DB 6oC WB

3.1

Operating Limits

3.1.1

R410A
Indoor
Cooling
Heating

Upper limit

32oC DB 23oC WB

46oC DB

Lower limit

21oC DB 15oC WB

10oC DB

Upper limit

27oC DB

24oC DB 18oC WB

Lower limit

10oC DB

-9oC DB -10oC WB

Voltage

3.1.2

Outdoor

198 264 V

R22
Indoor
Cooling
Heating

Upper limit

32oC DB 23oC WB

46oC DB

Lower limit

21oC DB 15oC WB

10oC DB

Upper limit

27oC DB

24oC DB 18oC WB

Lower limit

10oC DB

-5oC DB -10oC WB

Voltage

SM PRIME 1- A.1 GB

Outdoor

198 264 V

3-1

OUTLINE DIMENSIONS

4.

OUTLINE DIMENSIONS

4.1

PRIME 7, 9
 
 
 





 ! 







 








 


 
 

 
 

 

4.2

PRIME 12

SM PRIME 1- A.1 GB

4-1

OUTLINE DIMENSIONS

4.3

PRIME 18

4.4

GC7, WAP9_12

4-2

SM PRIME 1- A.1 GB

OUTLINE DIMENSIONS

4.3

GCN9, 12

AIR INTAKE

AIR OUTLET

4.4

GC18, GCN18

SM PRIME 1- A.1 GB

4-3

PERFORMANCE DATA & PRESSURE CURVES

5.

PERFORMANCE DATA & PRESSURE CURVES

5.1

Prime 7 / GC7 R410A

5.1.1

Cooling Mode at 7.5m Tubing Connection.


230V : Indoor Fan at High Speed.

Entering Air DB
OD Coil(oC)

Data
TC
SC
PI
TC
SC
PI
TC
SC
PI
TC
SC
PI
TC
SC
PI
TC
SC
PI
TC
SC
PI

15

20

25

30

35

40

46

Entering Air WB/DB ID Coil(oC)


15/21
2.29
1.58
0.47
2.21
1.55
0.51
2.09
1.51
0.55
1.96
1.46
0.59
1.81
1.39
0.64
1.65
1.31
0.69
1.43
1.20
0.75

17/24
2.37
1.64
0.47
2.33
1.63
0.51
2.26
1.60
0.55
2.13
1.55
0.60
1.97
1.49
0.65
1.79
1.41
0.70
1.56
1.29
0.76

19/27
2.43
1.71
0.47
2.41
1.70
0.51
2.38
1.69
0.56
2.30
1.65
0.61
2.17
1.61
0.66
1.96
1.52
0.71
1.72
1.39
0.78

21/29
2.48
1.75
0.47
2.46
1.75
0.51
2.45
1.73
0.56
2.39
1.70
0.61
2.28
1.66
0.67
2.14
1.57
0.72
1.90
1.44
0.79

23/32
2.52
1.78
0.47
2.52
1.78
0.52
2.51
1.77
0.56
2.46
1.73
0.62
2.39
1.69
0.67
2.25
1.60
0.73
2.05
1.47
0.80

LEGEND
TC
SC
PI
WB
DB
ID
OD

Total Cooling Capacity, kW


Sensible Capacity, kW
Power Input, kW
Wet Bulb Temp., (oC)
Dry Bulb Temp., (oC)
Indoor
Outdoor

(1) Marked area is below standard operating limits. For operating in low ambient
conditions, an A.S.K Kit is required.

SM PRIME 1- A.1 GB

5-1

PERFORMANCE DATA & PRESSURE CURVES


5.1.2

Heating
ENTERING AIR DB ID COIL(OC)
15

20

25

ENTERING WB
OD COIL(oC)

TH

Pl

TH

Pl

TH

Pl

-10

1.16

0.50

1.12

0.54

1.07

0.56

-7

1.25

0.52

1.20

0.55

1.16

0.57

-2

1.33

0.52

1.28

0.55

1.24

0.59

1.61

0.55

1.55

0.58

1.48

0.62

2.28

0.59

2.21

0.63

2.13

0.67

10

2.48

0.62

2.41

0.66

2.34

0.71

15

2.67

0.65

2.61

0.70

2.54

0.74

20

2.82

0.67

2.75

0.72

2.67

0.78

LEGEND
TH
PI
WB
DB
ID
OD

5-2

Total Heating Capacity, kW


Power Input, kW
Wet Bulb Temp., (oC)
Dry Bulb Temp., (oC)
Indoor
Outdoor

SM PRIME 1- A.1 GB

PERFORMANCE DATA & PRESSURE CURVES

5.2

Model: Prime 7 / GC7 R410A

5.2.1

Cooling

Discharge Pressure (Bar[g])

Discharge Pressure VS.Outdoor Temp


40
38
36
34
32
30
28
26
24
22
20
18
16
14
12
10

 :%'%|& 
 :%'%|&
 :%'%|&
 :%'%|&
 :%'%|&

15

20

25

30

35

Outdoor Temp.(DB oC )

40

46

40

46

Suction Pressure VS.Outdoor Temp

Suction Pressure (Bar[g])

13.0
 :%'%|&
 :%'%|&
 :%'%|&
 :%'%|&
 :%'%|&

12.0
11.0
10.0
9.0
8.0
7.0
6.0
15

20

25

30

35

Outdoor Temp.(DB oC )

SM PRIME 1- A.1 GB

5-3

PERFORMANCE DATA & PRESSURE CURVES


5.2.2

Heating

Discharge Pressure(Bar[g])

Discharge Pressure VS.Outdoor Temp


34
32
30
28
26
24

'% |& 
'% |& 
'% |& 

22
20
18
16
-10

-5

10

Outdoor Temp.( WB oC )

15

20

Suction Pressure VS.Outdoor Temp


Suction Pressure(Bar[g])

11.0
10.0
9.0
8.0
7.0

'% |&
'% |&
'% |&

6.0
5.0
4.0
3.0
-10

5-4

-5

10

Outdoor Temp.( WB oC )

15

20

SM PRIME 1- A.1 GB

PERFORMANCE DATA & PRESSURE CURVES

5.3

Prime 7 / GC Relax7 R22

5.3.1

Cooling Mode at 7.5m Tubing Connection.


230V : Indoor Fan at High Speed.

Entering Air DB
OD Coil(oC)
15

20

25

30

35

40

46

Data

Entering Air WB/DB ID Coil(oC)

TC
SC
PI
TC
SC
PI
TC
SC
PI
TC
SC
PI

15/21
2.23
1.53
0.53
2.16
1.50
0.58
2.05
1.46
0.62
1.91
1.41
0.67

17/24
2.31
1.59
0.53
2.28
1.58
0.58
2.21
1.55
0.63
2.08
1.50
0.68

19/27
2.37
1.66
0.53
2.35
1.65
0.58
2.32
1.63
0.63
2.25
1.60
0.69

21/29
2.43
1.70
0.54
2.41
1.69
0.58
2.39
1.68
0.64
2.33
1.64
0.69

23/32
2.46
1.73
0.54
2.46
1.72
0.59
2.45
1.71
0.64
2.40
1.67
0.70

TC
SC
PI
TC
SC
PI
TC
SC
PI

1.77
1.34
0.73
1.61
1.27
0.78
1.40
1.17
0.86

1.92
1.44
0.74
1.75
1.36
0.80
1.53
1.25
0.87

2.12
1.56
0.75
1.91
1.48
0.81
1.68
1.35
0.89

2.23
1.61
0.76
2.09
1.52
0.82
1.86
1.39
0.90

2.33
1.64
0.76
2.20
1.55
0.83
2.00
1.42
0.91

LEGEND
TC
SC
PI
WB
DB
ID
OD

Total Cooling Capacity, kW


Sensible Capacity, kW
Power Input, kW
Wet Bulb Temp., (oC)
Dry Bulb Temp., (oC)
Indoor
Outdoor

(1) Marked area is below standard operating limits. For operating in low ambient
conditions, an A.S.K Kit is required.

SM PRIME 1- A.1 GB

5-5

PERFORMANCE DATA & PRESSURE CURVES


5.3.2

Heating
ENTERING AIR DB ID COIL(OC)
15

20

25

ENTERING WB
OD COIL(oC)

TH

Pl

TH

Pl

TH

Pl

-10

1.13

0.54

1.09

0.57

1.04

0.60

-7

1.21

0.55

1.17

0.58

1.13

0.61

-2

1.29

0.56

1.25

0.59

1.20

0.62

1.57

0.58

1.51

0.62

1.44

0.66

2.21

0.63

2.15

0.67

2.07

0.71

10

2.41

0.66

2.34

0.71

2.28

0.76

15

2.60

0.69

2.54

0.74

2.47

0.79

20

2.74

0.71

2.68

0.77

2.60

0.83

LEGEND
TH
PI
WB
DB
ID
OD

5-6

Total Heating Capacity, kW


Power Input, kW
Wet Bulb Temp., (oC)w
Dry Bulb Temp., (oC)
Indoor
Outdoor

SM PRIME 1- A.1 GB

PERFORMANCE DATA & PRESSURE CURVES

5.4

Prime 7 / GC Relax7 R22

5.4.1

Cooling
Discharge Pressure VS.Outdoor Temp

Discharge Pressure (Bar[g])

30

 :%'%|& 
 :%'%|&
 :%'%|&
 :%'%|&
 :%'%|&

28
26
24
22
20
18
16
14
12
10
15

20

25

30

35

Outdoor Temp.(DB oC )

40

46

40

46

Suction Pressure VS.Outdoor Temp

Suction Pressure (Bar[g])

8.0

 :%'%|&
 :%'%|&
 :%'%|&
 :%'%|&
 :%'%|&

7.0
6.0
5.0
4.0
3.0
2.0
15

20

25

30

35

Outdoor Temp.(DB oC )

SM PRIME 1- A.1 GB

5-7

PERFORMANCE DATA & PRESSURE CURVES


5.4.2

Heating

Discharge Pressure(Bar[g])

Discharge Pressure VS.Outdoor Temp


22
20
18
16
14

'% |& 
'% |& 
'% |& 

12
10
8
-10

-5

10

15

20

Outdoor Temp.( WB oC )

Suction Pressure VS.Outdoor Temp


Suction Pressure(Bar[g])

6.0
5.0
4.0
3.0

'% |&
'% |&

2.0

'% |&

1.0
-10

-5

10

15

20

Outdoor Temp.( WB oC )

5-8

SM PRIME 1- A.1 GB

PERFORMANCE DATA & PRESSURE CURVES

5.5

Prime 9 / GCN9 R410A

5.5.1

Cooling Mode at 7.5m Tubing Connection.


230V : Indoor Fan at High Speed.

Entering Air DB
OD Coil(oC)
15

20

25

30

35

40

46

Data

Entering Air WB/DB ID Coil(oC)

TC
SC
PI
TC
SC
PI
TC
SC
PI
TC
SC
PI

15/21
2.91
1.91
0.60
2.81
1.87
0.65
2.66
1.82
0.70
2.49
1.77
0.75

17/24
3.01
1.99
0.60
2.97
1.97
0.65
2.88
1.94
0.70
2.71
1.88
0.76

19/27
3.08
2.07
0.60
3.06
2.06
0.65
3.02
2.04
0.71
2.93
2.00
0.77

21/29
3.16
2.12
0.60
3.13
2.12
0.65
3.11
2.10
0.71
3.03
2.05
0.78

23/32
3.21
2.16
0.60
3.20
2.15
0.66
3.19
2.14
0.72
3.12
2.09
0.78

TC
SC
PI
TC
SC
PI
TC
SC
PI

2.31
1.68
0.81
2.10
1.58
0.88
1.82
1.46
0.96

2.50
1.80
0.83
2.28
1.70
0.89
1.99
1.56
0.97

2.76
1.95
0.84
2.49
1.84
0.91
2.19
1.68
0.99

2.90
2.01
0.85
2.72
1.90
0.92
2.42
1.74
1.01

3.04
2.05
0.85
2.86
1.94
0.93
2.60
1.78
1.02

LEGEND
TC
SC
PI
WB
DB
ID
OD

Total Cooling Capacity, kW


Sensible Capacity, kW
Power Input, kW
Wet Bulb Temp., (oC)
Dry Bulb Temp., (oC)
Indoor
Outdoor

(1) Marked area is below standard operating limits. For operating in low ambient
conditions, an A.S.K Kit is required

SM PRIME 1- A.1 GB

5-9

PERFORMANCE DATA & PRESSURE CURVES


5.5.2

Heating
ENTERING AIR DB ID COIL(OC)
15

20

25

ENTERING WB
OD COIL(oC)

TH

Pl

TH

Pl

TH

Pl

-10

1.62

0.72

1.56

0.77

1.49

0.81

-7

1.74

0.74

1.68

0.78

1.62

0.82

-2

1.85

0.75

1.79

0.79

1.72

0.84

2.25

0.78

2.16

0.83

2.06

0.88

3.17

0.84

3.08

0.90

2.97

0.96

10

3.45

0.89

3.36

0.95

3.26

1.02

15

3.73

0.93

3.63

1.00

3.54

1.06

20

3.93

0.95

3.83

1.04

3.73

1.12

LEGEND
TH
PI
WB
DB
ID
OD

5-10

Total Heating Capacity, kW


Power Input, kW
Wet Bulb Temp., (oC)
Dry Bulb Temp., (oC)
Indoor
Outdoor

SM PRIME 1- A.1 GB

PERFORMANCE DATA & PRESSURE CURVES

5.6

Model: Prime 9 / GCN9 R410A

5.6.1

Cooling

Discharge Pressure (Bar[g])

Discharge Pressure VS.Outdoor Temp


40
38
36
34
32
30
28
26
24
22
20
18
16
14
12
10

 :%'%|& 
 :%'%|&
 :%'%|&
 :%'%|&
 :%'%|&

15

20

25

30

35

Outdoor Temp.(DB oC )

40

46

40

46

Suction Pressure VS.Outdoor Temp

Suction Pressure (Bar[g])

13.0

 :%'%|&
 :%'%|&
 :%'%|&
 :%'%|&
 :%'%|&

12.0
11.0
10.0
9.0
8.0
7.0
6.0
15

20

25

30

35
o

Outdoor Temp.(DB C )

SM PRIME 1- A.1 GB

5-11

PERFORMANCE DATA & PRESSURE CURVES


5.6.2

Heating

Discharge Pressure(Bar[g])

Discharge Pressure VS.Outdoor Temp


42
40
38
36
34
32
30
28
26
24
22
20
18
16

'% |& 
'% |& 
'% |& 

-10

-5

10

Outdoor Temp.( WB oC )

15

20

Suction Pressure VS.Outdoor Temp


Suction Pressure(Bar[g])

11.0
10.0
9.0
8.0
7.0
'% |&
'% |&
'% |&

6.0
5.0
4.0
3.0
-10

5-12

-5

10

Outdoor Temp.( WB oC )

15

20

SM PRIME 1- A.1 GB

PERFORMANCE DATA & PRESSURE CURVES

5.7

Model: Prime 9 / WAP9 R410A

5.7.1

Cooling Mode at 7.5m Tubing Connection.


230V : Indoor Fan at High Speed.

Entering Air DB
OD Coil(oC)

Data
TC
SC
PI
TC
SC
PI
TC
SC
PI
TC
SC
PI
TC
SC
PI
TC
SC
PI
TC
SC
PI

15

20

25

30

35

40

46

Entering Air WB/DB ID Coil(oC)


15/21
2.69
1.90
0.63
2.60
1.86
0.69
2.46
1.81
0.74
2.30
1.76
0.80
2.13
1.67
0.86
1.94
1.57
0.93
1.68
1.45
1.02

17/24
2.78
1.98
0.63
2.74
1.96
0.69
2.66
1.93
0.75
2.51
1.87
0.81
2.31
1.79
0.88
2.11
1.70
0.94
1.84
1.55
1.03

19/27
2.85
2.06
0.63
2.83
2.05
0.69
2.79
2.03
0.75
2.71
1.99
0.82
2.55
1.94
0.89
2.30
1.84
0.96
2.02
1.67
1.05

21/29
2.92
2.11
0.63
2.89
2.10
0.69
2.88
2.09
0.76
2.80
2.04
0.82
2.68
2.00
0.90
2.52
1.89
0.97
2.23
1.73
1.07

23/32
2.96
2.15
0.64
2.96
2.14
0.69
2.95
2.13
0.76
2.89
2.08
0.83
2.80
2.04
0.90
2.65
1.93
0.98
2.41
1.77
1.08

LEGEND
TC
SC
PI
WB
DB
ID
OD

Total Cooling Capacity, kWv


Sensible Capacity, kW
Power Input, kW
Wet Bulb Temp., (oC)
Dry Bulb Temp., (oC)
Indoor
Outdoor

(1) Marked area is below standard operating limits. For operating in low ambient
conditions, refer to Optional Accessories (Chapter 15).

SM PRIME 1- A.1 GB

5-13

PERFORMANCE DATA & PRESSURE CURVES


5.7.2

Heating
ENTERING AIR DB ID COIL(OC)
15

20

25

ENTERING WB
OD COIL(oC)

TH

Pl

TH

Pl

TH

Pl

-10

1.39

0.66

1.34

0.70

1.29

0.73

-7

1.50

0.67

1.44

0.71

1.39

0.75

-2

1.59

0.68

1.54

0.72

1.48

0.76

1.93

0.71

1.86

0.76

1.78

0.80

2.73

0.77

2.65

0.82

2.56

0.87

10

2.97

0.81

2.89

0.87

2.81

0.93

15

3.21

0.84

3.13

0.91

3.05

0.97

20

3.38

0.87

3.30

0.94

3.21

1.02

LEGEND
TH
PI
WB
DB
ID
OU

5-14

Total Heating Capacity, kW


Power Input, kW
Wet Bulb Temp., (oC)
Dry Bulb Temp., (oC)
Indoor
Outdoor

SM PRIME 1- A.1 GB

PERFORMANCE DATA & PRESSURE CURVES

5.8.

Model: Prime 9 / WAP9 R410A

5.8.1

Cooling

Discharge Pressure (Bar[g])

Discharge Pressure VS.Outdoor Temp


40
38
36
34
32
30
28
26
24
22
20
18
16
14
12
10

 :%'%|& 
 :%'%|&
 :%'%|&
 :%'%|&
 :%'%|&

15

20

25

30

35

Outdoor Temp.(DB oC )

40

46

40

46

Suction Pressure VS.Outdoor Temp

Suction Pressure (Bar[g])

13.0
 :%'%|&
 :%'%|&
 :%'%|&
 :%'%|&
 :%'%|&

12.0
11.0
10.0
9.0
8.0
7.0
6.0
15

20

25

30

35

Outdoor Temp.(DB oC )

SM PRIME 1- A.1 GB

5-15

PERFORMANCE DATA & PRESSURE CURVES


5.8.2

Heating.

Discharge Pressure(Bar[g])

Discharge Pressure VS.Outdoor Temp


34
32
30
28
26
24
'% |& 
'% |& 
'% |& 

22
20
18
16
-10

-5

10

Outdoor Temp.( WB oC )

15

20

Suction Pressure VS.Outdoor Temp


Suction Pressure(Bar[g])

10.0
9.0
8.0
7.0
6.0

'% |&
'% |&
'% |&

5.0
4.0
3.0
-10

5-16

-5

10

Outdoor Temp.( WB oC )

15

20

SM PRIME 1- A.1 GB

PERFORMANCE DATA & PRESSURE CURVES

5.9

Model: Prime 9 / WAP9 R22

5.9.1

Cooling Mode at 7.5m Tubing Connection.


230V : Indoor Fan at High Speed.

Entering Air DB
OD Coil(oC)
15

20

25

30

35

40

46

Data

Entering Air WB/DB ID Coil(oC)

TC
SC
PI
TC
SC
PI
TC
SC
PI
TC
SC
PI

15/21
2.79
1.87
0.67
2.70
1.83
0.72
2.56
1.79
0.78
2.39
1.73
0.84

17/24
2.89
1.95
0.67
2.85
1.93
0.73
2.76
1.90
0.79
2.60
1.84
0.86

19/27
2.96
2.03
0.67
2.94
2.01
0.73
2.90
2.00
0.79
2.81
1.96
0.86

21/29
3.03
2.08
0.67
3.01
2.07
0.73
2.99
2.06
0.80
2.91
2.01
0.87

23/32
3.08
2.12
0.67
3.07
2.11
0.73
3.06
2.09
0.80
3.00
2.05
0.88

TC
SC
PI
TC
SC
PI
TC
SC
PI

2.21
1.65
0.91
2.01
1.55
0.98
1.75
1.43
1.07

2.40
1.76
0.93
2.19
1.67
1.00
1.91
1.53
1.09

2.65
1.91
0.94
2.39
1.81
1.01
2.10
1.65
1.11

2.78
1.97
0.95
2.61
1.86
1.03
2.32
1.70
1.13

2.91
2.00
0.95
2.75
1.90
1.04
2.50
1.74
1.14

LEGEND
TC
SC
PI
WB
DB
ID
OD

Total Cooling Capacity, kWv


Sensible Capacity, kW
Power Input, kW
Wet Bulb Temp., (oC)
Dry Bulb Temp., (oC)
Indoor
Outdoor

(1) Marked area is below standard operating limits. For operating in low ambient
conditions, refer to Optional Accessories (Chapter 15).

SM PRIME 1- A.1 GB

5-17

PERFORMANCE DATA & PRESSURE CURVES


5.9.2

Heating
ENTERING AIR DB ID COIL(OC)
15

20

25

ENTERING WB
OD COIL(oC)

TH

Pl

TH

Pl

TH

Pl

-10

1.52

0.68

1.46

0.72

1.40

0.76

-7

1.63

0.70

1.58

0.74

1.52

0.78

-2

1.73

0.71

1.68

0.75

1.62

0.79

2.11

0.74

2.02

0.79

1.94

0.83

2.98

0.79

2.89

0.85

2.79

0.90

10

3.24

0.84

3.15

0.90

3.06

0.96

15

3.50

0.88

3.41

0.94

3.32

1.00

20

3.68

0.90

3.60

0.98

3.50

1.05

LEGEND
TH
PI
WB
DB
ID
OU

5-18

Total Heating Capacity, kW


Power Input, kW
Wet Bulb Temp., (oC)
Dry Bulb Temp., (oC)
Indoor
Outdoor

SM PRIME 1- A.1 GB

PERFORMANCE DATA & PRESSURE CURVES

5.10.

Model: Prime 9 / WAP9 R22

5.10.1

Cooling

Discharge Pressure VS.Outdoor Temp

Discharge Pressure (Bar[g])

30
 :%'%|& 
 :%'%|&
 :%'%|&
 :%'%|&
 :%'%|&

28
26
24
22
20
18
16
14
12
10
15

20

25

30

35

Outdoor Temp.(DB oC )

40

46

40

46

Suction Pressure VS.Outdoor Temp

Suction Pressure (Bar[g])

8.0
 :%'%|&
 :%'%|&
 :%'%|&
 :%'%|&
 :%'%|&

7.0
6.0
5.0
4.0
3.0
2.0
15

20

25

30

35

Outdoor Temp.(DB oC )

SM PRIME 1- A.1 GB

5-19

PERFORMANCE DATA & PRESSURE CURVES


5.10.2

Heating.

Discharge Pressure(Bar[g])

Discharge Pressure VS.Outdoor Temp


24
22
20
18
16
14

'% |& 
'% |& 
'% |& 

12
10
8
-10

-5

10

15

20

Outdoor Temp.( WB oC )

Suction Pressure VS.Outdoor Temp


Suction Pressure(Bar[g])

6.0
5.0
4.0
3.0

'% |&
'% |&
'% |&

2.0
1.0
-10

-5

10

15

20

Outdoor Temp.( WB oC )

5-20

SM PRIME 1- A.1 GB

PERFORMANCE DATA & PRESSURE CURVES

5.11

Model: Prime 12 / GCN12 R410A

5.11.1

Cooling Mode at 7.5m Tubing Connection.


230V : Indoor Fan at High Speed.

Entering Air DB
OD Coil(oC)

Data
TC
SC
PI
TC
SC
PI
TC
SC
PI
TC
SC
PI
TC
SC
PI
TC
SC
PI
TC
SC
PI

15

20

25

30

35

40

46

Entering Air WB/DB ID Coil(oC)


15/21
3.79
2.47
0.79
3.67
2.42
0.86
3.47
2.36
0.93
3.25
2.28
1.01
3.01
2.17
1.08
2.73
2.05
1.17
2.37
1.88
1.28

17/24
3.93
2.57
0.80
3.87
2.55
0.87
3.75
2.50
0.94
3.54
2.43
1.02
3.26
2.33
1.10
2.98
2.20
1.19
2.59
2.02
1.30

19/27
4.02
2.67
0.80
3.99
2.66
0.87
3.94
2.64
0.94
3.82
2.58
1.03
3.60
2.52
1.12
3.25
2.38
1.21
2.85
2.17
1.33

21/29
4.12
2.74
0.80
4.09
2.73
0.87
4.06
2.71
0.95
3.96
2.66
1.04
3.78
2.59
1.13
3.55
2.46
1.22
3.15
2.25
1.35

23/32
4.18
2.79
0.80
4.17
2.78
0.87
4.16
2.76
0.96
4.07
2.71
1.05
3.96
2.64
1.13
3.74
2.51
1.23
3.40
2.30
1.36

LEGEND
TC
SC
PI
WB
DB
ID
OD

Total Cooling Capacity, kWv


Sensible Capacity, kW
Power Input, kW
Wet Bulb Temp., (oC)
Dry Bulb Temp., (oC)
Indoor
Outdoor

(1) Marked area is below standard operating limits. For operating in low ambient
conditions, refer to Optional Accessories (Chapter 15).

SM PRIME 1- A.1 GB

5-21

PERFORMANCE DATA & PRESSURE CURVES


5.11.2

Heating
ENTERING AIR DB ID COIL(OC)
15

20

25

ENTERING WB
OD COIL(oC)

TH

Pl

TH

Pl

TH

Pl

-10

2.01

0.89

1.93

0.95

1.85

0.99

-7

2.16

0.91

2.08

0.96

2.01

1.01

-2

2.29

0.92

2.22

0.98

2.14

1.03

2.79

0.97

2.67

1.03

2.56

1.09

3.93

1.04

3.82

1.11

3.69

1.18

10

4.28

1.10

4.16

1.17

4.05

1.25

15

4.62

1.14

4.51

1.23

4.39

1.31

20

4.87

1.18

4.76

1.28

4.62

1.38

LEGEND
TH
PI
WB
DB
ID
OU

5-22

Total Heating Capacity, kW


Power Input, kW
Wet Bulb Temp., (oC)
Dry Bulb Temp., (oC)
Indoor
Outdoor

SM PRIME 1- A.1 GB

PERFORMANCE DATA & PRESSURE CURVES

5.12.

Model: Prime 12 / GCN12 R410A

5.12.1

Cooling

Discharge Pressure (Bar[g])

Discharge Pressure VS.Outdoor Temp


40
38
36
34
32
30
28
26
24
22
20
18
16
14
12
10

 :%'%|& 
 :%'%|&
 :%'%|&
 :%'%|&
 :%'%|&

15

20

25

30

35

Outdoor Temp.(DB oC )

40

46

40

46

Suction Pressure VS.Outdoor Temp

Suction Pressure (Bar[g])

13.0
 :%'%|&
 :%'%|&
 :%'%|&
 :%'%|&
 :%'%|&

12.0
11.0
10.0
9.0
8.0
7.0
6.0
15

20

25

30

35
o

Outdoor Temp.(DB C )

SM PRIME 1- A.1 GB

5-23

PERFORMANCE DATA & PRESSURE CURVES


5.12.2

Heating.

Discharge Pressure(Bar[g])

Discharge Pressure VS.Outdoor Temp


38
36
34
32
30
28
26
24
22
20
18
16

'% |& 
'% |& 
'% |& 

-10

-5

10

Outdoor Temp.( WB oC )

15

20

Suction Pressure VS.Outdoor Temp

Suction Pressure(Bar[g])

11.0
10.0
9.0
8.0
7.0
'% |&
'% |&
'% |&

6.0
5.0
4.0
3.0
-10

5-24

-5

10

Outdoor Temp.( WB oC )

15

20

SM PRIME 1- A.1 GB

PERFORMANCE DATA & PRESSURE CURVES

5.13

Prime 12 / WAP12 R410

5.13.1.

Cooling Mode at 7.5m Tubing Connection


230V : Indoor Fan at High Speed.

Entering Air DB
OD Coil(oC)

Data
TC
SC
PI
TC
SC
PI
TC
SC
PI
TC
SC
PI
TC
SC
PI
TC
SC
PI
TC
SC
PI

15

20

25

30

35

40

46

Entering Air WB/DB ID Coil(oC)


15/21
3.48
2.53
0.82
3.37
2.48
0.89
3.18
2.41
0.97
2.98
2.34
1.04
2.76
2.22
1.12
2.51
2.09
1.21
2.18
1.93
1.32

17/24
3.60
2.64
0.82
3.55
2.61
0.90
3.44
2.56
0.97
3.24
2.48
1.06
2.99
2.38
1.14
2.73
2.25
1.23
2.38
2.07
1.34

19/27
3.69
2.74
0.83
3.66
2.72
0.90
3.61
2.70
0.98
3.50
2.64
1.07
3.30
2.58
1.16
2.98
2.44
1.25
2.62
2.23
1.37

21/29
3.77
2.81
0.83
3.75
2.80
0.90
3.72
2.78
0.98
3.63
2.72
1.07
3.47
2.65
1.17
3.26
2.52
1.27
2.89
2.30
1.39

23/32
3.83
2.86
0.83
3.83
2.85
0.91
3.81
2.83
0.99
3.73
2.77
1.08
3.63
2.71
1.18
3.42
2.57
1.28
3.11
2.35
1.41

LEGEND
TC
SC
PI
WB
DB
ID
OD

Total Cooling Capacity, kWv


Sensible Capacity, kW
Power Input, kW
Wet Bulb Temp., (oC)
Dry Bulb Temp., (oC)
Indoor
Outdoor

(1) Marked area is below standard operating limits. For operating in low ambient
conditions, refer to Optional Accessories (Chapter 15

SM PRIME 1- A.1 GB

5-25

PERFORMANCE DATA & PRESSURE CURVES


5.13.2

Heating.

ENTERING AIR DB ID COIL(OC)


15

20

25

ENTERING WB
OD COIL(oC)

TH

Pl

TH

Pl

TH

Pl

-10

1.79

0.84

1.72

0.89

1.65

0.94

-7

1.92

0.86

1.85

0.91

1.79

0.96

-2

2.04

0.87

1.97

0.92

1.90

0.98

2.48

0.91

2.38

0.97

2.28

1.03

3.50

0.98

3.40

1.05

3.28

1.12

10

3.81

1.04

3.71

1.11

3.60

1.18

15

4.11

1.08

4.01

1.17

3.91

1.24

20

4.34

1.11

4.23

1.21

4.11

1.30

LEGEND
TH
PI
WB
DB
ID
OU

5-26

Total Heating Capacity, kW


Power Input, kW
Wet Bulb Temp., (oC)
Dry Bulb Temp., (oC)
Indoor
Outdoor

SM PRIME 1- A.1 GB

PERFORMANCE DATA & PRESSURE CURVES

5.14

Prime 12 / WAP12 R410.

5.14.1

Cooling

Discharge Pressure (Bar[g])

Discharge Pressure VS.Outdoor Temp


40
38
36
34
32
30
28
26
24
22
20
18
16
14
12
10

 :%'%|& 
 :%'%|&
 :%'%|&
 :%'%|&
 :%'%|&

15

20

25

30

35

Outdoor Temp.(DB oC )

40

46

40

46

Suction Pressure VS.Outdoor Temp

Suction Pressure (Bar[g])

13.0
 :%'%|&
 :%'%|&
 :%'%|&
 :%'%|&
 :%'%|&

12.0
11.0
10.0
9.0
8.0
7.0
6.0
15

20

25

30

35

Outdoor Temp.(DB oC )

SM PRIME 1- A.1 GB

5-27

PERFORMANCE DATA & PRESSURE CURVES


5.14.2

Heating.

Discharge Pressure VS.Outdoor Temp


Discharge Pressure(Bar[g])

36
34
32
30
28
26
24

'% |& 
'% |& 
'% |& 

22
20
18
16
-10

-5

10

Outdoor Temp.( WB oC )

15

20

Suction Pressure VS.Outdoor Temp


Suction Pressure(Bar[g])

10.0
9.0
8.0
7.0
6.0

'% |&
'% |&
'% |&

5.0
4.0
3.0
-10

5-28

-5

10

Outdoor Temp.( WB oC )

15

20

SM PRIME 1- A.1 GB

PERFORMANCE DATA & PRESSURE CURVES

5.15

Model: Prime 12 / WAP12 R22.

5.15.1

Cooling Mode at 7.5m Tubing Connection


230V : Indoor Fan at High Speed

Entering Air DB
OD Coil(oC)

Data
TC
SC
PI
TC
SC
PI
TC
SC
PI
TC
SC
PI
TC
SC
PI
TC
SC
PI
TC
SC
PI

15

20

25

30

35

40

46

Entering Air WB/DB ID Coil(oC)


15/21
3.48
2.18
0.83
3.37
2.14
0.90
3.18
2.09
0.97
2.98
2.02
1.05
2.76
1.92
1.13
2.51
1.81
1.22
2.18
1.67
1.33

17/24
3.60
2.28
0.83
3.55
2.26
0.90
3.44
2.21
0.98
3.24
2.15
1.07
2.99
2.06
1.15
2.73
1.95
1.24
2.38
1.79
1.35

19/27
3.69
2.37
0.83
3.66
2.35
0.91
3.61
2.33
0.99
3.50
2.28
1.07
3.30
2.23
1.17
2.98
2.11
1.26
2.62
1.92
1.39

21/29
3.77
2.43
0.83
3.75
2.42
0.91
3.72
2.40
0.99
3.63
2.35
1.08
3.47
2.29
1.18
3.26
2.18
1.28
2.89
1.99
1.41

23/32
3.83
2.47
0.84
3.83
2.46
0.91
3.81
2.45
1.00
3.73
2.39
1.09
3.63
2.34
1.19
3.42
2.22
1.29
3.11
2.04
1.42

LEGEND
TC
SC
PI
WB
DB
ID
OD

Total Cooling Capacity, kWv


Sensible Capacity, kW
Power Input, kW
Wet Bulb Temp., (oC)
Dry Bulb Temp., (oC)
Indoor
Outdoor

(1) Marked area is below standard operating limits. For operating in low ambient
conditions, refer to Optional Accessories (Chapter 15

SM PRIME 1- A.1 GB

5-29

PERFORMANCE DATA & PRESSURE CURVES


5.15.2

Heating.
ENTERING AIR DB ID COIL(OC)
15

20

25

ENTERING WB
OD COIL(oC)

TH

Pl

TH

Pl

TH

Pl

-10

1.97

0.84

1.89

0.89

1.82

0.94

-7

2.12

0.86

2.04

0.91

1.97

0.96

-2

2.25

0.87

2.18

0.92

2.10

0.98

2.74

0.91

2.63

0.97

2.51

1.03

3.86

0.98

3.75

1.05

3.62

1.12

10

4.20

1.04

4.09

1.11

3.98

1.18

15

4.54

1.08

4.43

1.17

4.31

1.24

20

4.78

1.11

4.67

1.21

4.54

1.30

LEGEND
TH
PI
WB
DB
ID
OU

5-30

Total Heating Capacity, kW


Power Input, kW
Wet Bulb Temp., (oC)
Dry Bulb Temp., (oC)
Indoor
Outdoor

SM PRIME 1- A.1 GB

PERFORMANCE DATA & PRESSURE CURVES

5.16

Model: Prime 12 / WAP12 R22.

5.16.1

Cooling

Discharge Pressure VS.Outdoor Temp

Discharge Pressure (Bar[g])

30
 :%'%|& 
 :%'%|&
 :%'%|&
 :%'%|&
 :%'%|&

28
26
24
22
20
18
16
14
12
10
15

20

25

30

35

Outdoor Temp.(DB oC )

40

46

40

46

Suction Pressure VS.Outdoor Temp

Suction Pressure (Bar[g])

8.0
 :%'%|&
 :%'%|&
 :%'%|&
 :%'%|&
 :%'%|&

7.0
6.0
5.0
4.0
3.0
2.0
15

20

25

30

35

Outdoor Temp.(DB oC )

SM PRIME 1- A.1 GB

5-31

PERFORMANCE DATA & PRESSURE CURVES


5.16.2

Heating.

Discharge Pressure(Bar[g])

Discharge Pressure VS.Outdoor Temp


26
24
22
20
18
16
'% |& 
'% |& 
'% |& 

14
12
10
8
-10

-5

10

Outdoor Temp.( WB oC )

15

20

Suction Pressure VS.Outdoor Temp


Suction Pressure(Bar[g])

6.0
5.0
4.0
3.0

'% |&
'% |&
'% |&

2.0
1.0
-10

-5

10

15

20

Outdoor Temp.( WB C )

5-32

SM PRIME 1- A.1 GB

PERFORMANCE DATA & PRESSURE CURVES

5.17

Model: Prime 18 / GCN17 NRC R410

5.17.1

Cooling Mode at 7.5m Tubing Connection


230V : Indoor Fan at High Speed

Entering Air DB
OD Coil(oC)
15

20

25

30

35

40

46

Data

Entering Air WB/DB ID Coil(oC)

TC
SC
PI
TC
SC
PI
TC
SC
PI
TC
SC
PI

15/21
5.80
3.81
1.18
5.61
3.73
1.28
5.31
3.64
1.38
4.96
3.52
1.49

17/24
6.00
3.97
1.18
5.91
3.94
1.28
5.73
3.86
1.39
5.40
3.75
1.51

19/27
6.15
4.13
1.18
6.10
4.10
1.29
6.02
4.07
1.40
5.84
3.98
1.52

21/29
6.29
4.23
1.18
6.24
4.22
1.29
6.21
4.19
1.41
6.05
4.10
1.54

23/32
6.39
4.31
1.19
6.38
4.30
1.30
6.36
4.27
1.42
6.22
4.18
1.55

TC
SC
PI
TC
SC
PI
TC
SC
PI

4.59
3.35
1.61
4.18
3.16
1.73
3.63
2.91
1.89

4.99
3.59
1.63
4.55
3.40
1.76
3.96
3.12
1.92

5.50
3.89
1.66
4.96
3.68
1.79
4.36
3.36
1.97

5.78
4.00
1.67
5.43
3.80
1.81
4.82
3.47
1.99

6.05
4.08
1.68
5.71
3.87
1.83
5.19
3.55
2.02

LEGEND
TC
SC
PI
WB
DB
ID
OD

Total Cooling Capacity, kWv


Sensible Capacity, kW
Power Input, kW
Wet Bulb Temp., (oC)
Dry Bulb Temp., (oC)
Indoor
Outdoor

(1) Marked area is below standard operating limits. For operating in low ambient
conditions, refer to Optional Accessories (Chapter 15).

SM PRIME 1- A.1 GB

5-33

PERFORMANCE DATA & PRESSURE CURVES


5.17.2

Heating.
ENTERING AIR DB ID COIL(OC)
15

20

25

ENTERING WB
OD COIL(oC)

TH

Pl

TH

Pl

TH

Pl

-10

2.99

1.34

2.88

1.42

2.76

1.49

-7

3.22

1.37

3.11

1.44

2.99

1.52

-2

3.42

1.39

3.31

1.47

3.19

1.55

4.16

1.45

3.99

1.54

3.82

1.64

5.87

1.56

5.70

1.67

5.50

1.77

10

6.38

1.65

6.21

1.76

6.04

1.88

15

6.90

1.72

6.73

1.85

6.56

1.97

20

7.27

1.77

7.10

1.92

6.90

2.07

LEGEND
TH
PI
WB
DB
ID
OU

5-34

Total Heating Capacity, kW


Power Input, kW
Wet Bulb Temp., (oC)
Dry Bulb Temp., (oC)
Indoor
Outdoor

SM PRIME 1- A.1 GB

PERFORMANCE DATA & PRESSURE CURVES

5.18

Model: Prime 18 / GCN17 NRC R410

5.18.1

Cooling

Discharge Pressure (Bar[g])

Discharge Pressure VS.Outdoor Temp


40
38
36
34
32
30
28
26
24
22
20
18
16
14
12
10

 :%'%|& 
 :%'%|&
 :%'%|&
 :%'%|&
 :%'%|&

15

20

25

30

35

Outdoor Temp.(DB oC )

40

46

40

46

Suction Pressure VS.Outdoor Temp

Suction Pressure (Bar[g])

13.0
 :%'%|&
 :%'%|&
 :%'%|&
 :%'%|&
 :%'%|&

12.0
11.0
10.0
9.0
8.0
7.0
6.0
15

20

25

30

35

Outdoor Temp.(DB oC )

SM PRIME 1- A.1 GB

5-35

PERFORMANCE DATA & PRESSURE CURVES


5.18.2

Heating.

Discharge Pressure(Bar[g])

Discharge Pressure VS.Outdoor Temp


38
36
34
32
30
28
26
24
22
20
18
16

'% |& 
'% |& 
'% |& 

-10

-5

10

Outdoor Temp.( WB oC )

15

20

Suction Pressure VS.Outdoor Temp


Suction Pressure(Bar[g])

11.0
10.0
9.0
8.0
7.0
'% |&
'% |&
'% |&

6.0
5.0
4.0
3.0
-10

5-36

-5

10

Outdoor Temp.( WB oC )

15

20

SM PRIME 1- A.1 GB

PERFORMANCE DATA & PRESSURE CURVES

5.19

Model: Prime18 / RELAX17 NRC R22.

5.19.1

Cooling Mode at 7.5m Tubing Connection


230V : Indoor Fan at High Speed

Entering Air DB
OD Coil(oC)
15

20

25

30

35

40

46

TC
SC
PI
WB
DB
ID
OD

Data

Entering Air WB/DB ID Coil(oC)

TC
SC
PI
TC
SC
PI
TC
SC
PI
TC
SC
PI

15/21
5.61
3.50
1.32
5.43
3.43
1.43
5.13
3.34
1.55
4.80
3.23
1.67

17/24
5.81
3.65
1.32
5.72
3.61
1.44
5.54
3.54
1.56
5.23
3.44
1.69

19/27
5.95
3.79
1.32
5.90
3.77
1.44
5.83
3.74
1.57
5.65
3.65
1.71

21/29
6.09
3.88
1.33
6.04
3.87
1.45
6.00
3.84
1.58
5.85
3.76
1.72

23/32
6.18
3.95
1.33
6.17
3.94
1.45
6.15
3.91
1.59
6.02
3.83
1.74

TC
SC
PI
TC
SC
PI
TC
SC
PI

4.44
3.07
1.80
4.04
2.90
1.94
3.51
2.67
2.12

4.82
3.30
1.83
4.40
3.12
1.97
3.83
2.86
2.15

5.32
3.57
1.86
4.80
3.38
2.01
4.22
3.08
2.20

5.59
3.67
1.87
5.25
3.48
2.03
4.66
3.19
2.23

5.85
3.75
1.88
5.52
3.56
2.05
5.02
3.26
2.26

Total Cooling Capacity, kWv


Sensible Capacity, kW
Power Input, kW
Wet Bulb Temp., (oC)
Dry Bulb Temp., (oC)
Indoor
Outdoor

(1) Marked area is below standard operating limits. For operating in low ambient
conditions, refer to Optional Accessories (Chapter 15).

SM PRIME 1- A.1 GB

5-37

PERFORMANCE DATA & PRESSURE CURVES


5.19.2

Heating
ENTERING AIR DB ID COIL(OC)
15

20

25

ENTERING WB
OD COIL(oC)

TH

Pl

TH

Pl

TH

Pl

-10

2.94

1.43

2.83

1.53

2.72

1.60

-7

3.16

1.47

3.05

1.55

2.94

1.63

-2

3.36

1.49

3.25

1.58

3.14

1.66

4.09

1.56

3.92

1.66

3.75

1.75

5.77

1.67

5.60

1.79

5.40

1.90

10

6.27

1.77

6.10

1.89

5.94

2.02

15

6.78

1.84

6.61

1.99

6.44

2.11

20

7.14

1.90

6.97

2.06

6.78

2.22

LEGEND
TH
PI
WB
DB
ID
OU

5-38

Total Heating Capacity, kW


Power Input, kW
Wet Bulb Temp., (oC)
Dry Bulb Temp., (oC)
Indoor
Outdoor

SM PRIME 1- A.1 GB

PERFORMANCE DATA & PRESSURE CURVES

5.20

Model: Prime18 / RELAX17 NRC R22

5.20.1

Cooling

Discharge Pressure VS.Outdoor Temp

Discharge Pressure (Bar[g])

30
 :%'%|& 
 :%'%|&
 :%'%|&
 :%'%|&
 :%'%|&

28
26
24
22
20
18
16
14
12
10
15

20

25

30

35

Outdoor Temp.(DB oC )

40

46

40

46

Suction Pressure VS.Outdoor Temp

Suction Pressure (Bar[g])

8.0
 :%'%|&
 :%'%|&
 :%'%|&
 :%'%|&
 :%'%|&

7.0
6.0
5.0
4.0
3.0
2.0
15

20

25

30

35
o

Outdoor Temp.(DB C )

SM PRIME 1- A.1 GB

5-39

PERFORMANCE DATA & PRESSURE CURVES


5.20.2

Heating.

Discharge Pressure(Bar[g])

Discharge Pressure VS.Outdoor Temp


26
24
22
20
18
16
'% |& 
'% |& 
'% |& 

14
12
10
8
-10

-5

10

15

20

Outdoor Temp.( WB oC )

Suction Pressure VS.Outdoor Temp


Suction Pressure(Bar[g])

6.0
5.0
4.0
3.0

'% |&
'% |&
'% |&

2.0
1.0
-10

-5

10

15

20

Outdoor Temp.( WB oC )

5-40

SM PRIME 1- A.1 GB

SOUND LEVEL CHARACTERISTICS

6.

SOUND LEVEL CHARACTERISTICS

6.1

Sound Pressure Level

Unit
1m

Wall

0.8m

Mic.
Figure 1

6.2

Soud Pressure Level Spectrum (Measured as Figure 1)


PRIME 9

NC-70

NC-60

NC-50

NC-40

NC-30
APPROXIMATE
THRESHOLD OF
HEARING FOR
CONTINUOUS
NOISE

NC-20

BAND CENTER FREQUENCIES, Hz

 

OCTAVE BAND SOUND PRESSURE LEVEL, dB re 0.002 MICRO BAR

OCTAVE BAND SOUND PRESSURE LEVEL, dB re 0.002 MICRO BAR

PRIME 7

NC-70

NC-60

NC-50

NC-40

NC-30
APPROXIMATE
THRESHOLD OF
HEARING FOR
CONTINUOUS
NOISE

NC-20

BAND CENTER FREQUENCIES, Hz







SM PRIME 1- A.1 GB

6-1

SOUND LEVEL CHARACTERISTICS

6.2

Sound Pressure Level


PRIME 18

NC-70

NC-60

NC-50

NC-40

NC-30
APPROXIMATE
THRESHOLD OF
HEARING FOR
CONTINUOUS
NOISE

NC-20

BAND CENTER FREQUENCIES, Hz

 

OCTAVE BAND SOUND PRESSURE LEVEL, dB re 0.002 MICRO BAR

OCTAVE BAND SOUND PRESSURE LEVEL, dB re 0.002 MICRO BAR

PRIME 12

NC-70

NC-60

NC-50

NC-40

NC-30
APPROXIMATE
THRESHOLD OF
HEARING FOR
CONTINUOUS
NOISE

NC-20

BAND CENTER FREQUENCIES, Hz







6-2

SM PRIME 1- A.1 GB

SOUND LEVEL CHARACTERISTICS

6.3

Outdoor units

Unit

1m
Mic.

Ground
Figure 2

6.4

Sound Pressure Level Spectrum (Measured as Figure 2)


GC7 Heating

NC-70

NC-60

NC-50

NC-40

NC-30
APPROXIMATE
THRESHOLD OF
HEARING FOR
CONTINUOUS
NOISE

NC-20

OCTAVE BAND SOUND PRESSURE LEVEL, dB re 0.002 MICRO BAR

OCTAVE BAND SOUND PRESSURE LEVEL, dB re 0.002 MICRO BAR

GC7 Cooling

NC-70

NC-60

NC-50

NC-40

NC-30
APPROXIMATE
THRESHOLD OF
HEARING FOR
CONTINUOUS
NOISE

BAND CENTER FREQUENCIES, Hz

BAND CENTER FREQUENCIES, Hz

GCN9 (class A) Heating

NC-70

NC-60

NC-50

NC-40

NC-30

NC-20

BAND CENTER FREQUENCIES, Hz

SM PRIME 1- A.1 GB

OCTAVE BAND SOUND PRESSURE LEVEL, dB re 0.002 MICRO BAR

OCTAVE BAND SOUND PRESSURE LEVEL, dB re 0.002 MICRO BAR

GCN9 (class A) Cooling

APPROXIMATE
THRESHOLD OF
HEARING FOR
CONTINUOUS
NOISE

NC-20

NC-70

NC-60

NC-50

NC-40

NC-30
APPROXIMATE
THRESHOLD OF
HEARING FOR
CONTINUOUS
NOISE

NC-20

BAND CENTER FREQUENCIES, Hz

6-3

SOUND LEVEL CHARACTERISTICS


GCN12 (class A) Heating

NC-70

NC-60

NC-50

NC-40

NC-30
APPROXIMATE
THRESHOLD OF
HEARING FOR
CONTINUOUS
NOISE

NC-20

OCTAVE BAND SOUND PRESSURE LEVEL, dB re 0.002 MICRO BAR

OCTAVE BAND SOUND PRESSURE LEVEL, dB re 0.002 MICRO BAR

GCN12 (class A) Cooling

NC-70

NC-60

NC-50

NC-40

NC-30
APPROXIMATE
THRESHOLD OF
HEARING FOR
CONTINUOUS
NOISE

BAND CENTER FREQUENCIES, Hz

BAND CENTER FREQUENCIES, Hz

CSP9 (class C) Heating

 











"$  "


#!  

 

"$  #  !!#  $    

"$  #  !!#  $    

CSP9 (class C) Cooling



  

 



NC-20

 











  

 





"$  "


#!  







6-4

SM PRIME 1- A.1 GB

SOUND LEVEL CHARACTERISTICS

CON12 (class C) Heating

 











  

 



"$  #  !!#  $    

"$  #  !!#  $    

CON12 (class C) Cooling

 











  

 





"$  "


#!  

"$  "


#!  

CON17 Heating

NC-70

NC-60

NC-50

NC-40

NC-30

NC-20

BAND CENTER FREQUENCIES, Hz

SM PRIME 1- A.1 GB

OCTAVE BAND SOUND PRESSURE LEVEL, dB re 0.002 MICRO BAR

OCTAVE BAND SOUND PRESSURE LEVEL, dB re 0.002 MICRO BAR

CON17 Cooling

APPROXIMATE
THRESHOLD OF
HEARING FOR
CONTINUOUS
NOISE



NC-70

NC-60

NC-50

NC-40

NC-30
APPROXIMATE
THRESHOLD OF
HEARING FOR
CONTINUOUS
NOISE

NC-20

BAND CENTER FREQUENCIES, Hz

6-5

SOUND LEVEL CHARACTERISTICS

6-6

CSP12 RC R22 Cooling

CSP12 RC R22 Heating

ONG3-17 RC R22 Cooling

ONG3-17 RC R22 Heating

SM PRIME 1- A.1 GB

ELECTRICAL DATA

7.

ELECTRICAL DATA

7.1

Single Phase Units


MODEL
Power Supply
Max Current, A
Circuit Breaker,A
Power Supply Wiring No. X
Cross Section mm2
Interconnecting Cable RC
Model No. X Cross Section mm2
Interconnecting Cable ST
Model No. X Cross Section mm2

MODEL
Power Supply
Max Current, A
Circuit Breaker,A
Power Supply Wiring No. X
Cross Section mm2
Interconnecting Cable RC
Model No. X Cross Section mm2
Interconnecting Cable ST
Model No. X Cross Section mm2

Prime 7

Prime 9

To indoor
1PH-230V-50Hz
4.1
10

To indoor
1PH-230V-50Hz
6.5
10

3x1.0 mm2

3x1.0 mm2

5x1.0 mm2 +2x0.5 mm2 (OCT senser)

5x1.0 mm2 +2x0.5 mm2 (OCT senser)

4x1.0 mm2

4x1.0 mm2

Prime 12

Prime 18

To indoor
1PH-230V-50Hz
7.7
10

To indoor
1PH-230V-50Hz
10.4
15

3x1.0 mm2

3x1.5 mm2

5x1.0 mm2 +2x0.5 mm2 (OCT senser)

5x1.5 mm2 +2x0.5 mm2 (OCT senser)

4x1.0 mm2

4x1.5 mm2

NOTE
Power wiring cord should comply with local lows and electrical
regulations requirements.

SM PRIME 1- A.1 GB

7-1

WIRING DIAGRAMS

8.

WIRING DIAGRAMS

8.1

Indoor Unit : Prime 7, 9, 12, 18

SM PRIME 1- A.1 GB

8-1

WIRING DIAGRAMS

8.2

Outdoor Unit: CON 7 R22/R410A / CSP 9, 12 R22/R410A


WIRING DIAGRAM
LEGEND:
BU-Blue BN-Brown
BK-Black GR-Green
RD-Red YE-Yellow
GN/YE-Yellow/Green
CAP.--Capacitor
COMP.--Compressor

DEICER TEMP.
SENSOR RT3

XT3
BK

OPTIONAL:
4-WAY VALVE ONLY FOR HEAT PUMP
UNIT
DEICER TEMP SENSOR ONLY FOR HEAT
PUMP UNIT
OVER LOAD PROTECTOR IS OPTION
ALL SEASON KIT IS OPTION

RD

ASK

BU
Compressor CAP

4-WAY VALVE
4

BU
BN
GR
BN

BU

BU RD

BU

RD

over load
protector

BU

YE
S

R
Fan Motor CAP

GN/YE

~
M

~
M

GN/YE
GN/YE

FAN MOTOR

COMP

O.U.TERMINAL

453244800/01

8.3

Outdoor Unit: GCN 9, 12 R410A


!  




 
! #  # 
# 

  
 

"



*2'/-4,
*$%)/'',
'&##'**-4
##'**-4/'',
 $.$%(1-/
-+./'00-/




! #  

-+./'00-/ 














 

-3'/*-$&
./-1'%1-/


#

#


$,-1-/ 

5


#

5


#
 



 



8-2

SM PRIME 1- A.1 GB

WIRING DIAGRAMS

8.4

Outdoor Unit: ONG3-17 R22/R410A

SM PRIME 1- A.1 GB

8-3

ELECTRICAL CONNECTIONS

9.

ELECTRICAL CONNECTIONS

9.1

ASP9, 12 / CSP9, 12

SM PRIME 1- A.1 GB

9-1

REFRIGERATION DIAGRAMS

10.

REFRIGERATION DIAGRAMS

10.1

Heat Pump Models

10.1.1

Prime7, 9, 12, 18 RC R410A(class A) / Prime12, 18 R22


 

 

(,!
'&(*

&$'())&(

%)&(

,()
,#,

'!##(.
*+
+*&&(&!#

*(!%(

%)&(

#,)

#(
&%%*!&%

'!##(.
*+

%&&(&!#

"
,#,


 

 

(,!
'&(*

&$'())&(

%)&(

,()
,#,

%)&(

#,)

#(
&%%*!&%

'!##(.
*+

'!##(.
*+
+*&&(&!#

*(!%(

%&&(&!#

"
,#,

 

SM PRIME 1- A.1 GB

10-1

REFRIGERATION DIAGRAMS
10.1.2

Prime7, 9 RC R22 / Prime9, 12 RC R410A(class C)


  

  

"





"
""



"


 

#
!
! 



 


 
  

  

"





"
""



"

#
!
! 


 



 

  

10-2

Service Manual - PRIME Series

REFRIGERATION DIAGRAMS
10.1.3

COOLING ONLY
All Model
OUTDOOR UNIT

INDOOR UNIT

Compressor

Service
port

Capillary
tube
Outdoor coil

SM PRIME 1- A.1 GB

Sensor

Valves

Flared
connection

Indoor coil

Strainer

10-3

TUBING CONNECTIONS

11.

TUBING CONNECTIONS

TUBE (Inch)

11-13
13-20
11-13

40-45
13-20
11-13

60-65
18-25
11-13

70-75
18-25
11-13

80-85
40-50
11-13

TORQUE (Nm)

Flare Nuts
Valve Cap
Service Port Cap
1.
2.
3.
4.
5.
6.
7.
8.

Valve Protection Cap-end


Refrigerant Valve Port (use Allen wrench to open/close)
Valve Protection Cap
Refrigerant Valve
Service Port Cap
Flare Nut
Unit Back Side
Copper Tube

When the outdoor unit is installed above the indoor unit an oil trap is required every 5m along
the suction line at the lowest point of the riser. Incase the indoor unit is installed above the
outdoor, no trap is required.

SM PRIME 1- A.1 GB

11-1

CONTROL SYSTEM

12.

CONTROL SYSTEM PRIME 7, 9, 12, 17

12.1

Electronic Control

12.1.1

Introduction
The electronic control information is designed for service applications, and is common
to the following groups of air-conditioners:
ST/ RC group -Cooling only / cooling and heating by heat pump.
SH group
-Cooling and heating by heat pump and supplementary
heater.
RH group
-Cooling, heating by heaters only.

12.1.2

Jumpers Settings
GROUP

J6 Setting

J2 Setting

ST / RC

Open

Open

SH

Closed

Open

RH

Closed

Closed

SM PRIME 1- A.1 GB

12-1

CONTROL SYSTEM

12.2

Legend

AC

- Alternate Current

A/C
ANY
CLOCK
COMP
CPU
ELUM
EPROM, EEP
HE
HPC
H/W
ICP
ICT
IF, IFAN
IR
LEVEL1
LEVEL2/3
LEVEL4
Max
Min
min
NA
OCP
OCT
OF, OFAN
OPER
Para.
RAT
RC
R/C
RCT
RH
RT
RV
SB, STBY
sec
Sect
SH
SPT
ST
S/W
TEMP
W/O

- Air-Conditioner
- ON or OFF status
- ON/OFF Operation Input, (dry contact)
- Compressor
- Central Processing Unit
- Extended Louver Upward Movement (Software Jumper)
- Erase Enable Programmable Read Only Memory
- Heating Element
- High Pressure Control
- Hardware
- Indoor Condensation Pump
- Indoor Coil Temperature (RT2) sensor
- Indoor Fan
- Infra Red
- Normal Water Level
- Medium/High Water Level
- Overow Level
- Maximum
- Minimum
- Minute (time)
- Not Applicable
- Outdoor Condensation Pump
- Outdoor Coil Temperature (RT3) sensor
- Outdoor Fan
- Operate
- Paragraph
- Return Air Temperature (RT1) sensor
- Reverse Cycle (Heat Pump)
- Remote Control
- Remote Control Temperature
- Resistance Heater
- Room Temperature (i.e. RCT in IFEEL mode, RAT otherwise)
- Reversing Valve
- Stand-By
- Second (time)
- Section
- Supplementary Heater
- Set Point Temperature
- Standard (a Model with Cooling Only)
- Software
- Temperature
- Without

WVL
T

- Water Valve
- The difference between SPT and RT.
in Heat Mode:T = SPT-RT
in Cool/Dry/Fan Mode: T = RT-SPT

12-2

SM PRIME 1- A.1 GB

CONTROL SYSTEM

12.3

General functions

12.3.1

COMP operation
For each Mode including POWER OFF & SB, a Min time delay of 3 min
before COMP restarting, excluding DEICING Mode
The Min operation time of COMP under different operating conditions is

12.3.2

Operation Mode

Min operation time of


COMP

Heat, Cool or Auto Modes


Fan, Dry, Overow, Protection modes, or mode change

3 min.
ignored

IFAN operation

Min time interval between IFAN speed change in AUTOFAN Mode, is 30 sec.

Min time interval between IFAN speed change in H/M/L Mode is 1 sec.

IFAN speed in Heat/Cool Autofan Mode is determined according to the following table:
T
T 2
2 T 1
1 T

where

IFAN Speed
HIGH
MED
LOW

in Heat Mode:T = SPT-RT


in Cool Mode:T = RT-SPT

Note:

In Heat Mode, the rules in section 4.0.3 have the higher priority.
The table above can be represent by a hysteresis curve which
will minimize the switching of the IFAN relay and will minimize the
change in IFAN speed:
IFAN speed
H

12.3.3

12.3.4

T [oc]

OFAN operation

Min time interval between OFAN ON/OFF state change is 30 sec.

In general, OFAN starts together with COMP.

HE operation

Minimum Heaters ON or OFF time is 30 sec.

Heaters can be activated only if IFAN is on.

SM PRIME 1- A.1 GB

12-3

CONTROL SYSTEM
12.3.5

Protections

12.3.6

High pressure protection is applicable to all operating modes.

Deicing control is valid in Heat and Auto Heat Mode only.

Defrosting control is valid in Dry, Cool, Heat and Auto Modes.

No reset after protection modes.

Thermistors operation

12.3.6.1

12-4

Return air Temp. is detected by RAT (RT1) in normal Mode, or by RCT (R/C sensor)
in I-FEEL Mode.

Indoor Coil Temp. is detected by ICT (RT2).


Denition of thermistor faults:

a.

Thermistor is disconnected The thermistor reading is below -30oc.

b.

Thermistor is shorted The thermistor reading is over 75oc.

c.

Thermistor Temp reading doesnt change (irrelevant for RT1) (i) This test is performed only once after a unit is switched from
OFF/STBY to operation. At the rst occurrence of 10 min
continuous COMP operation, the current ICT & OCT are
compared with those when the COMP was switched from OFF
to ON 10 min before. If the T is less than 3oc, the thermistor is
regarded as defective.
(ii) The ICT and OCT no-change error can be disabled together by
connecting a4.7 kohm resistor (5%) to the OCT connector. These
resistors are equivalent to a thermistor at 43+/-1oc and 48+/-1oc
respectively.
(iii) Connecting a 4.7k resistor to the ICT connector will disable the
ICT no-change error only.

SM PRIME 1- A.1 GB

CONTROL SYSTEM
12.3.6.2

i.

Handling the thermistor faults in a COMP unit

ICT/OCT thermistor is disconnected or shorted The invalid thermistor temperature is replaced by 43oc, so that the unit
can continue the normal operation. All protections related to that faulty
thermistor will be disabled. For example, in case of any ICT fault, the ICT
high pressure protection in Heat Mode and ICT defrost protection in Cool
Mode will not operate anymore. The same is also applied to the OCT fault.

ii.

RAT thermistor is disconnected or shorted


The RAT will be derived from the ICT by using the equations :
Heat Mode: RAT=ICT/2.3
Cool Mode
RAT=ICT*4
Notes:
In case of any thermistor failure, the STBY LED will be blinking until the
fault condition is corrected.
User can use the system diagnostics function to nd out the nature of
the thermistor faults.
i.

RAT thermistor is disconnected or shorted


System will operate continuously in the last IFAN & WVL status when
turned ON.

Notes:
As in the COMP unit, the STBY LED will be blinking to indicate a
thermistor fault. And, the user can use the system diagnostics function
to nd out the nature of the fault.

SM PRIME 1- A.1 GB

12-5

CONTROL SYSTEM

12.4
1)

2)

Cooling Mode - General


Room Temperature, RT, is detected by
RAT in normal operation, or
RCT (R/C sensor) in I-FEEL mode.
The resolution of RT is 1oc.
RT is activating COMP/WVL if (RT > SPT), and
RT is stopping COMP/WVL if (RT =< SPT).

3)

Indoor Coil Temp is detected by ICT (RT2).

4)

Outdoor Coil Temp is detected by OCT (RT3).

5)

OFAN OPERATIONS
OFAN starts together with COMP in general.

12-6

SM PRIME 1- A.1 GB

CONTROL SYSTEM
12.4.1

Cooling
Mode:
Temp:
Fan:
Timer:
I Feel:

Cool, Auto (at Cooling)


Selected desired temperature.
HIGH, MED, LOW
Any
On or Off

Control function
Maintains room temp at desired level by comparing RT and SPT.

(RT - SPT) [ oc]

+3

+2

+1

-1

-2

ON

COMP
(WVL) OFF

ON

OFAN

OFF

USER FAN SPEED

IFAN

ON

RV

OFF

Note:
1) IFAN is always running at High, Medium or Low speed selected by user.
2) In IFEEL mode, the Room Temperature (RT) is the RCT from a R/C. Otherwise, the
RT is the RAT from the Room Thermistor.

SM PRIME 1- A.1 GB

12-7

CONTROL SYSTEM
12.4.2

Cooling with Autofan


Mode:
Temp:
Fan:
Timer:
I Feel:

Cool, Auto (at cooling)


Selected desired temperature
Auto
Any
On or Off

Control function
Maintains room temp at desired level and controls the IFAN speed for optimal comfort.

(RT - SPT) [ oc]

+3

+2

+1

-1

-2

ON

COMP
(WVL)

OFF

ON

OFAN

OFF

IFAN

M
L

ON

RV

12-8

OFF

SM PRIME 1- A.1 GB

CONTROL SYSTEM

12.5

Heating Mode

12.5.1

Heating Mode - General

In heating Mode, temp. compensation schedule will be activated for wall mounted
units.
Add to SPT

SPT [oc]

I-FEEL ON
0 oc
0 oc

18 SPT 27
27 < SPT 30

I-FEEL OFF
+2 oc
+3 oc

Notes :
No compensation will be activated in Forced operation modes

12.5.2

IF operating rules

As a general rule for RC and SH groups, when COMP is ON, excluding


protection modes, IFAN will be switched ON if
ICT > 35oc or
at the IFTC 30 sec after the COMP is switched ON. In
this case,IFAN
theSpeed
IFAN will be started at low speed.

EMD/ELD
Any

Low
EMD/ELD
Stop

General :
For WAX :

30
15

35
20

40
25

ICT [oc]

Notes :
1) In SH or RC group, if HE is set to OFF due to low ICT, IFAN will be
switched to LOW and will be turned OFF after 30 sec.
2) An exception to this rule (4.0.3.a) is the Back-up mode for SH.
In RC and SH groups, whenever COMP & HE are both
OFF, excluding protection modes, IFAN operation will be according
to the following:
In other models IFAN will operate in low speed for 30 sec and then stop. If
COMP is OFF for more than 3 minutes and IFEEL Mode is inactive, IFAN will
operate in low speed according to the following graph:

IFAN (Low Speed)

ON

OFF
SPT+4
SM PRIME 1- A.1 GB

SPT+6

ICT [oc]
12-9

CONTROL SYSTEM
12.5.3

HE operation

For all Groups, HE can be ON only when IFAN is ON.

For all Groups, HE switches to OFF when ICT > 50 oc, and is activated
again when ICT 45oc.

In SH or RC group, HE operation is limited by the following graph:

HE

ON

OFF

General :
For WAX :

30
15

35
20

40

45

50

ICT [oc]

Back-up mode for SH group


After COMP has been working for 5 minutes, HE & IFAN are activated even
if the ICT is still below 35oc. This situation is called Back-up Mode. Both
HE & IFAN will work in Back-up Mode until the ICT reaches 35oc. Then, the
operation goes on in the usual mode .

12-10

SM PRIME 1- A.1 GB

CONTROL SYSTEM
12.5.4

Heating, RC or SH Group
Mode:
Temp:
Fan:
Timer:
I Feel:

Heat, Auto (at heating)


Selected desired temperature
HIGH, MED, LOW
Any
On or Off

Control function
Maintains room temp. at desired level by comparing RAT or RCT to SPT.
(RT - SPT) [ oc]
+2

+1

-1

-2

-3

ON

COMP
(WVL)

OFF

ON

HE1

OFF

ON

HE2

OFF

H/M/L

IFAN

L
OFF

Note 1

Note 2

ON

RV

OFF

SM PRIME 1- A.1 GB

12-11

CONTROL SYSTEM
12.5.5

Heating, RC or SH Group with Autofan


Mode:
Temp:
Fan:
Timer:
I Feel:

Heat, Auto (at heating)


Selected desired temperature
Auto
Any
On or Off

Control function
Maintains room temp at desired level by controlling COMP, IFAN and OFAN.
(RT - SPT) [ oc]
+2

+1

-1

-2

-3

ON

COMP
(WVL)

OFF

ON

HE1

OFF

ON

HE2

OFF

H
M

IFAN

L
OFF

Note 1

Note 2

ON

RV

12-12

OFF

SM PRIME 1- A.1 GB

CONTROL SYSTEM
12.5.6

OFAN operation is controlled by the graph below when


1. (RAT SPT 2oc), AND
2. (ICT 45oc), AND
3. (COMP is ON)
Otherwise, OFAN runs together with COMP.

OCT [oc]

+3

+2

+1

-1

ON

OFAN

OFF

SM PRIME 1- A.1 GB

12-13

CONTROL SYSTEM

12.6

Automatic Cooling or Heating

12.6.1

Automatic Cooling or Heating - General


Switching-temperature between Cooling and Heating is SPT 3oc.
Autofan in Automatic Cooling and Heating Mode will activate Cooling
with Autofan Mode and Heating with Autofan Mode respectively.
When the Auto Mode is started with SPT +/-0oc, the unit will not select
Auto Heat or Auto Cool mode immediately. Instead, the unit will be in
a temporary Fan Mode with IFAN operating at low speed.
The proper Auto Heat mode or Auto Cool will be started whenever the RT
reaches SPT-1oc or SPT+1oc respectively.
For RC & SH units, Mode change between Auto Heat & Auto Cool
Modes is possible only after the COMP has been OFF during the
last T minutes.

12-14

Mode Change

time, T

Auto Cool to Auto Heat

3 min

Auto Heat to Auto Cool

4 min

When unit is changed form Cool/Dry mode to Auto Mode, the unit
will continue to operate at (Auto) Cool Mode until the conditions for
switching from Auto Cool to Auto Heat are satised.
Similarly, when unit is changed from Heat Mode to Auto Mode, the
unit will continue to operate at (Auto) Heat Mode until the conditions
for switching from Auto Heat to Auto Cool are satised.

SM PRIME 1- A.1 GB

CONTROL SYSTEM

12.6.2

Auto Cooling or Heating, RC or SH Groups

Mode:
Temp:
Fan:
Timer:
I Feel:

Auto
Selected desired temperature
Any
Any
On or Off

Control function
Maintains room temp at desired level by selecting between cooling and heating modes.
(RT - SPT) [ oc]
+3
+2
+1
0
-1
-2
-3

Auto Cool Mode

Auto Heat Mode

ON

COMP
& OFAN

Auto Heat Mode

> 4 min

> 3 min

(3)

(3)

OFF

ON

HE1

OFF
(5)
ON

HE2

OFF

H/M/L/OFF

IFAN

H/M/L/OFF
L/OFF

USER FAN SPEED

L/OFF

> 3 min
ON

RV

H/M/L/OFF

L/OFF
> 2 min
(4)
(4)

OFF

SM PRIME 1- A.1 GB

12-15

CONTROL SYSTEM

12.7 Dry Mode


12.7.1

Dry, ST or RC group
Mode: Dry
Temp: Selected desired temp
Fan: Low (automatically selected by software)
Timer: Any
I FEEL:
Any

Control function
Reduce room humidity with minimum temp. uctuations by operating in Cool Mode with
low speed IFAN.
(RT - SPT) [ oc]

+2

+1

0
10

20

40

30

50

Time [min]

-1

-2

DRY-ON

DRY

DRY-OFF

LOW

IFAN

OFF
5 minutes COMP
ON time

ON

COMP
& OFAN

OFF
Max 15 minutes

ON

HE1
& HE2

3.5
min
Note1

Max 15 minutes

6 min
Note 2

OFF

ON

RV

OFF

Notes :
When Dry is ON, the COMP is forced OFF for 3.5 min (longer than the
3 min Min COMP-Off time) after every 15 min of continuous COMP
operation.
When Dry is OFF, the COMP is forced ON for 6 min (longer than the 3
min Min COMP-On time) after every 15 min of continuous COMP OFF
time.
When Dry is changed from ON to OFF or vice versa, the limits
mentioned in (1) & (2) are ignored. The COMP operation is only
controlled by the 3 min Min OFF time and 1 min Min ON time.
In Dry Mode, IFAN is LOW when COMP is ON, and is OFF when
COMP is OFF.

12-16

SM PRIME 1- A.1 GB

CONTROL SYSTEM

12.8

Protection

12.8.1

Cooling Mode Protections


Indoor Coil Defrost
Mode:
Temp:
Fan:
Timer:
I Feel:

Cooling, Dry, Auto


Selected desired temp.
Any
Any
On or Off

Control Function
Protect the indoor coil from ice formation at low ambient temperature.
ICT [oc]
+14

+5

+2
+1
0
-1

-6

t1

t2

t3

t1

t1

ON

OFAN

OFF

ON

COMP

OFF

ON

IFAN

OFF

J7 OPEN

J7 CLOSED

t1 = 5 min minimum for each COMP starting


t2 = OFAN cycling (alternate between ON and OFF every 30 sec) for 20 min
maximum
t3 = COMP and OFAN stop for 10 min minimum

Notes:

When J7 is closed (connected), OFAN cycling is cancelled and the


set temperature for COMP & OFAN cut-out and cut-in are changed.
COMP & OFAN are forced OFF when ICT =< -6oc, and are kept OFF
until ICT > 14oc.
For WAX model, the defrost processes is simpler. When J7 is open,
COMP & OFAN are forced OFF when ICT =< -1oc, and are kept OFF
until ICT > 5oc. When J7 is closed, the WAX defrosting process is the
same as that of the other models (R.H.S. of the graph above). In both
cases, the ICT checking in t2 and t3 are not applied.

SM PRIME 1- A.1 GB

12-17

CONTROL SYSTEM
12.8.2

High Pressure Protection


Mode:
Temp:
Fan:
Timer:
I Feel:

(Auto) Cooling or Dry


Selected desired temp.
Any
Any
On or Off

Control Function
To protect the COMP from the high pressure built-up in the outdoor coil during normal
cooling operation, by switching OFF the IFAN and COMP.

OCT [oc]

For all models except WAX & P2000

For WAX & P2000 models

68
66

61

55
52

Any

COMP OFF

COMP is forced OFF

COMP is forced OFF

OFAN is forced ON

OFAN is forced ON

Any

OFAN

ON

OFAN follow operation of


COMP

Any

IFAN

IFAN forced
to LOW

ON

OPER
LED

Blink

Note:
The ICT is also monitored during Cool and Dry mode, in case the RV control circuit
is faulty. Whenever ICT reaches 70oc, which indicates a high pressure in the indoor
coil, the COMP will be forced off automatically. The COMP can be turned on again only
after the ICT is under 70oc again and after the 3 min COMP ON delay time. The OPER
LED will not blink in this case.

12-18

SM PRIME 1- A.1 GB

CONTROL SYSTEM
12.8.3

Heating Mode Protections


Outdoor coil Deicing (excluding RH Group)
Mode: Heating, Auto (at heating)
Temp: Selected desired Temp
Fan: Any
Timer: Any
I FEEL:
Any
Control function
Protects the Outdoor coil from ice formation by controlling COMP & RV operation.
Scope

This new deicer is designed to operate at extreme temp conditions. The deicing cycle
could be triggered from:
1. OCT temp and time between two consecutive deicing cycles.
2. Detection of ice forming by change of the OCT temp.
Both algorithms adjust the time between deicing cycles to optimize the A/C
performance. The algorithm will automatically increase the time between deicing cycles
and reduce the deicing cycle as needed.
The algorithm uses EEPROM data to operate.

SM PRIME 1- A.1 GB

12-19

CONTROL SYSTEM
Deicing procedure

OCT [oc]
12

0
DOC

DST
(DDT)
3 min

3 min

36s

max 12 min.

36s

ON

COMP

OFF
DI (note 1)

DI (note 2)

ON

OFAN

OFF
30s

30s

ON

RV

DT

OFF

RC or WAX units

all SH units
except WAX

ANY

IFAN

IFAN is forced to Low Speed

ON

HE

ANY

HEs are forced ON

ANY

IFAN

OFF

Note 3

ANY

HE

OFF

HEs are forced OFF

ON

OPER
LED

BLINK

Notes :
At the rst COMP activation after SB or OFF, if (OCT < 0oc), then DI = 10
min, else DI = 40 min.
In the following Deicing cycles, the time interval between two Deicing
cycles activation is between 30 to 80 min (refer to the ow chart).
For RC group, HEs are forced OFF. IFAN operation is as in Heat
Mode, Sect 4.0.3.a, i.e. IFAN will be set to OFF when ICT<30oc.
For WAX, the IFAN is simply forced OFF.
For SH group, HEs are forced ON and IFAN is forced to operate in Low
speed, regardless of the ICT and difference between RAT & SPT.

12-20

SM PRIME 1- A.1 GB

CONTROL SYSTEM
12.8.4

High pressure protection (excluding RH Group)


Mode:
Fan:
Timer:
I Feel:

(Auto) Heating
Any
Any
On or Off

Control Function
Protect the Compressor from high pressure by switching OFF the OFAN and COMP.

ICT [oc]

For all models except WAX

For WAX model

67
66

61

55
52

Any

COMP Off

COMP is forced OFF

COMP is forced OFF

Any

OFAN

Off

OFAN is force
Off

ON

OPER
LED

BLINK

Notes:

IFAN, HE1 and HE2 will be activated according to the relevant


Heating Mode Sect.

In case of any malfunction in the relay control circuit, the OCT is also
monitored during heating mode. Whenever OCT reaches 70oc, which indicates
a high pressure in the outdoor coil, the COMP will be forced off automatically.
The COMP can be turned on again only after the 3 min COMP ON delay and the
OCT is under 70oc. The OPER LED will not blink in this case.

SM PRIME 1- A.1 GB

12-21

CONTROL SYSTEM

12.9

Timer
Mode:
Temp.
Fan:
Timer:
I Feel:

Any
Selected desired temp
Any
Timer On, Timer Off
On or Off

Control function

Starts or stops the unit operation after pre-set time. If RC-1 is used,
the timer setting will be (0.5 - 24 Hr) from the moment the timer is set.
The minimum resolution is 30 minutes.
If RC-2 or later version of remote controls is used, the timer
setting will be (0:00 - 23:50) real time with 10 minutes resolution.

After power failure, all pre-set timers are cleared. The system is
forced to STBY mode and the Timer LED indicator is blinked to
indicate the situation. The LED keeps blinking until the timer settings
can be reloaded from a R/C message.
Note: If all timers are inactive, the system will not be forced
OFF after the power failure. The last OPER/STBY status will
be loaded from the EEP instead.

When the A/C receives any valid message from a R/C, the current
ON/OFF timer settings will be replaced by the new timer settings in
the R/C message.
Note: The following timer related operations will not affect the
A/C operating mode (Heat/Cool/Auto/Dry/Fan) setting.
Set ON/OFF timer
Clear ON/OFF timer
R/C ON Timer is time-up
R/C OFF Timer is time-up

E.g.

12-22

When a STBY A/C unit (with Cool Mode setting in its EEP) is
turned on by the ON-TIMER of a R/C with heat mode setting,
the A/C will start in Cool Mode.

SM PRIME 1- A.1 GB

CONTROL SYSTEM

12.10

Forced Operation

Forced operation allows units to start, stop and operate in Cooling or Heating in pre-set
temperature according to the following table:
Pre-set Temp for :

Forced operation
mode

WMZ, WMF,WNG models

Cooling

22C

Heating

28C

Note:

While under the forced operation, the temperature compensation


schedule.
The forced operation is activated when the mode button on the
Display Board is used to switch the unit to Cool or Heat mode.
The IFAN is always set to Autofan Speed in forced operation.

SM PRIME 1- A.1 GB

12-23

CONTROL SYSTEM

12.11

Sleep Mode
Mode:
Temp:
Fan:
Timer:
I Feel:

Any
Set desired temperature selected
Any
Interact with Sleep Timer as described in sect 12.2
On or Off

The Sleep mode is activated by using the sleep button on the R/C. In Sleep Mode,
the unit will automatically adjust the SPT to turn up/down the room temperature (RT)
gradually to provide maximum comfort to the user in sleep.
Sleep is treated as TIMER function. Therefore, the TIMER LED is activated similar to
TIMER function.

12.11.1

Adjustment in Sleep Mode

1. in cool, auto cool or dry modes, the SPT adjustment is positive (from 0 to +3oc).
2. In heat or auto heat modes, the SPT adjustment is negative (from 0 to -3oc).
3. In other modes, there is no SPT adjustment.
4. The SPT adjustment is cancelled when the Sleep mode is cancelled.

RT
7 Hours Sleep operation
for Normal Sleep Mode

Unit is turned to SB
after Sleep

SPT+3

Cool, Dry modes


SPT+2
SPT+1

SPT
SPT-1
SPT-2

Heat mode
SPT-3

Start
Sleep

Time [Hr]

Note: If Off-timer is active, the unit may go to SB before or after 7 hours of


sleep operation.

12-24

SM PRIME 1- A.1 GB

CONTROL SYSTEM
12.11.2

Time adjustment in Sleep Mode

The user can make use of the Off-Timer to extend the Sleep Time from 7 hours to 12
hour (max). The operation of the new Extended Sleep Mode is illustrated by the
graphs below.
Case 1 is the Standard Sleep Mode, which is the only sleep mode in previous version
of MCU. The A/C unit simply works for 7 hours, then goes to SB.
Case 2 is the new Extended Sleep Mode. If an active Off-Timer is set to turn off the
A/C between 7-12 hour, relative to the starting of Sleep, the Sleep time is extended.
And, instead of going to SB at the 7th hour, the A/C will work until reaching the Off-time.
Case 3 is an exception to case 2. The Sleep Mode will not be extended to the Off-Time
when the Off-Timer is preceded by an On-Timer, which is also between 7-12 hour.
Case 1 : Standard Sleep Mode
Condition : Off-timer is not set or is beyond 12 hour.

Oper

SB
Start
Sleep

10

10

12

Time [Hr]

12

Time [Hr]

12

Time [Hr]

Case 2 : Extended Sleep Mode


Condition : Off-timer is set at 7-12 hour.

Oper

SB
Start
Sleep

Off-timer

Case 3 : Exception to Case 2


Condition : Off-timer is set at 7-12 hour
On-timer is set at 7-12 hour and before Off-timer

Oper

SB
Start
Sleep

SM PRIME 1- A.1 GB

10
On-timer

Off-timer

12-25

CONTROL SYSTEM

12.12 Controller Self-Test Procedure


12.12.1

By Shorting Test Jumper J1


SELF-TEST FLOW CHART
FOR CONTROLLER (VERSION 4V5 OR HIGHER)

Step 1

SHORT JUMPER
J1
(CONTROL PCB)

RC/ST TEST

MODEL
CONFIGURATION
TEST

Step 2

PRESS ON
POWER
BUTTON

STEP MOTOR TEST

FREQUENCY
TEST

Step 3

PRESS ON
MODE BUTTON

STANDBY

LEDS OFF
OPERATE
LEDS ON TEST

TIMER

AUTO RELAY
TEST

COOL

HEAT
INDOOR FAN
SPEED TEST

COMPRESSOR

OUTDOOR FAN

Step 4

PRESS ON RESET
BUTTON

BUZZER TEST
(ONE BEEP SOUND)

Step 5

PRESS ON FAN
BUTTON ON THE
REMOTE CONTROL

REMOTE CONTROL
TO CPU COMUNICATION
(TWO BEEPS SOUNDS)

R.V.

LOW

MEDIUM

Step 6

PRESS ON MODE
BUTTON

THERMISTOR ANALOG
VOLTAGE CHECKING

Step 7

PRESS ON MODE
BUTTON

EEPROM MEMORY
TEST

Step 8

DISCONNECT
JUMPER
J1

END OF SELF
TEST

12-26

HIGH

SM PRIME 1- A.1 GB

CONTROL SYSTEM
12.12.2

By Remote Control Settings:


a.

1: TURNING ON THE POWER.


Turn ON the power, make sure that the unit is in operation.

b.

STEP 2 : ENABLE SELF-TEST MODE

c.

Use the remote control to send the rst settings to display / indoor unit
HEAT mode, HIGH IFAN, set temperature to 16 C, no I-FEEL Sleep or
any other timer settings are needed.

Cover the IR transmitter components in the remote control so that it will


not transmit the signals to the indoor unit display.

Use the remote control to send the second settings to display / indoor unit
COOL mode, LOW IFAN, no I-FEEL Sleep or any other timer settings.

Uncover the remote control IR transmitter and change the temperature


settings. If the display/indoor unit receive the settings properly the
following steps will start:

STEP 3: MODEL SETTING CONFIRMATION

The STAND-BY and COOL LEDS will indicate the operation mode as
follows:

OPERATION MODE

STAND-BY LED

COOL LED

ST

ON

OFF

RC

OFF

OFF

SH

OFF

ON

RH

ON

ON

MODEL
WNG
WMZ
WMN4
WMN2/WHX
WMN3

Testing the Model conguration. Selected by the COMP, STAND-BY,


TIMER LEDS and FILTER will indicate the model conguration as follows
(the relevant line for this manual is highlighted):
COMP
ON
ON
OFF
OFF
OFF

OPERATE LED
OFF
ON
OFF
ON
ON

TIMER LED
OFF
OFF
ON
OFF
ON

FILTER LED
OFF
ON
OFF
ON
ON

In this term the step motor will turn to HOME POSITION.

SM PRIME 1- A.1 GB

12-27

CONTROL SYSTEM
d.

STEP 4 : AUTO LED WALK TEST.

All the LEDS will turn OFF.

All the LEDS will turn ON for 1 second one by one in the following
sequence:
STAND-BY  OPERATE  TIMER  FILTER  COOL 

e.

HEAT.

In PRX all the LEDS will turn ON for 1 second one by one in the following
sequence : 18 c  20 c  22 c  24 c  26 c  28 c  30 c 
High IFAN  Auto IFAN  Med IFAN  Low IFAN  STAND-BY
TIMER  FILTER COOL HEAT.

STEP 5: AUTO REALY WALK TEST:

All relays will energize one by one in the following sequence:

COMPRESSOR  OUTDOOR FANR. V.  HEATER 1  HEATER 2


 INDOOR WATER PUMP  SWING or OUTDOOR WATER PUMP 
INDOOR FAN: LOW  MID  HIGH.

f.

STEP 6: FREQUENCY TESTING:

g.

When the relay walk test is completed, the next test will start
automatically.

If the frequency measuring process fails the COOL LED will turn ON.
In order to move to the next step, press ON/OFF button on the remote
control.

STEP 7: INPUT TEST.

The test purpose is to check the analog real time indicators (thermistors,
LEVEL and clock) according to the table below.

LED Indicator
STBY LED
OPER LED
TIMER LED
FILTER LED
COOL LED
HEAT LED

h.

Condition for LED to be ON


Room thermistor 25c
Indoor coil thermistor 25c
Outdoor coil thermistor 25c
Clock
LEVEL 2&3
LEVEL 4

STEP 8: TIMING RESET TEST (WATCH DOG).

The test purpose is to verify that the CPU rise time after power failure
is between 1 to 3 sec, test results are indicated on the LEDS : STANDBY,OPER, TIMER and FILTER turning ON one by one.

The results of the test are coded as follows:


Pass condition:
1 sec - STAND-BY and OPER are turned ON
2 sec - STAND-BY, OPER and TIMER are turned ON

12-28

SM PRIME 1- A.1 GB

CONTROL SYSTEM
Fail condition:
0 sec - STAND-BY is turned ON
3 sec - STAND-BY, OPER, TIMER and FILTER are turned ON

i.

When the timing reset test is completed, the next test will start
automatically.

STEP 9: MEMORY TEST (EEPROM)

The test purpose is to check if the memory is functioning correctly. The test
result is reported by using the STAND-BY and FILTER LEDS:

LED Indicator

Condition for LED to be ON

STAND-BY LED
FILTER LED

Test passed
Test failed

AT THIS POINT THE SELF-TEST IS COMPLETED.


In order to terminate Self-Test mode the User can change the unit setting from COOL
Mode, LOW FAN to COOL Mode, MED FAN or to wait without using the remote control
for 60 sec.
Values of Sensors Temperature VS. Voltage (DC)
Temp. (*C) Voltage (V) Temp. (*C) Voltage (V) Temp. (*C) Voltage (V) Temp. (*C) Voltage (V)
-20

4.554

3.744

24

2.555

46

1.487

-19

4.529

3.695

25

2.5

47

1.447

-18

4.502

3.646

26

2.445

48

1.409

-17

4.475

3.595

27

2.391

49

1.371

-16

4.446

3.544

28

2.338

50

1.334

-15

4.417

3.492

29

2.284

51

1.298

-14

4.386

3.439

30

2.232

52

1.263

-13

4.354

3.386

31

2.18

53

1.228

-12

4.322

10

3.332

32

2.128

54

1.195

-11

4.287

11

3.278

33

2.077

55

1.162

-10

4.252

12

3.223

34

2.027

56

1.13

4.216

13

3.168

35

1.978

57

1.099

-8

4.178

14

3.113

36

1.929

58

1.069

-7

4.14

15

3.058

37

1.881

59

1.04

-6

4.1

16

3.002

38

1.834

60

1.011

-5

4.059

17

2.946

39

1.798

61

0.983

-4

4.017

18

2.89

40

1.742

62

0.956

-3

3.974

19

2.833

41

1.698

63

0.929

-2

3.93

20

2.777

42

1.654

64

0.904

-1

3.885

21

2.722

43

1.611

65

0.879

3.839

22

2.666

44

1.569

66

0.854

3.792

23

2.61

45

1.527

67

0.831

SM PRIME 1- A.1 GB

12-29

CONTROL SYSTEM

12.13 On Unit Indicators and Controls

STAND BY
INDICATOR

OPERATION
INDICATOR

Lights up when the Air Conditioner is connected to power and


ready to receive the R/C commands
Blinks continuously in case of any thermistor failure.

Lights up during operation.


Blinks for 300 ms, to announce that a R/C infrared signal has
been received and stored.
Blinks continuously during
OCT High Pressure Protection Mode
ICT High Pressure Protection Mode
Deicing in Heating Mode
Water Over Flow in ECC Model

MODE BUTTON
(Cool, Heat, SB)

12-30

Use to cycle the operation mode of the A/C unit among COOL,
HEAT and SB modes, without using the R/C.
Every time this switch is pressed, the next operation mode is
selected, in this order :
SB  Cool Mode  Heat Mode  SB  ...
Press this button continuously for 5 sec or more to start the
Diagnostic Mode.

SM PRIME 1- A.1 GB

CONTROL SYSTEM

12.14

Clock Random Delay From 0 to 2.5 seconds


0=
1=

Clock Switch Open


Clock Switch close

The Clock is activate according to the following table:


A/C STATE
CLOCK STATE
CLOCK ACTION
(before clock is changed) (before clock is changed) (clock is changed)

A/C NEW STATE


(after clock is changed)

ON

OFF

OFF

ON

OFF by
interrupt (1)

OFF

ON by
interrupt (1)

ON

Notes :
1.
Clock can be interrupted by :
R/C - POWER ON/OFF Push-button.
R/C - TIMER.
R/C - SLEEP.
A/C - MODE SWITCH.
2. Any change in the CLOCK level during the rst 6 sec after the system
Reset is ignored.

SM PRIME 1- A.1 GB

12-31

TROUBLESHOOTING

13.

TROUBLESHOOTING

NO

SYMPTON

1.

The stand-by
indicator (red led)
on the central
control display
panel doesnt light
up.

PROBABLE CAUSE
There is no correct voltage
between the line and neutral
terminals on main P.C.B

CORRECTIVE ACTION
-If the voltage is low repair power
supply.
-If there is no voltage repair
general wiring.
-If there is correct voltage replace
main or display P.C.BS

2.

The operation
indicator (green
led) on the central
control display
panel does not
light up.

The remote control batteries


are discharged

-Replace batteries of the remote


control.

3.

The operation
indicator (green
led) does not light
up when starting
from unit.

Check main P.C.B and display


P.C.B

-Replace P.C.B if necessary.

4.

The indoor fan


does not function
correctly.

Check the voltage between


indoor fan terminals on the
main P.C.B

-If there is voltage replace


capacitor or motor.

5.

The outdoor fan


does not function
correctly.

Check the voltage between out


door fan terminals on the main
P.C.B

-If there is no voltage replace main


P.C.B

There is voltage between


outdoor fan terminals on the
outdoor unit.

-Replace capacitor or motor.

There is no voltage between


outdoor fan terminals on the
outdoor unit.
Check voltage on compressor
terminals on the outdoor unit.
(with ammeter)

-Check and repair electrical wiring


between indoor and outdoor units.

Check if there is correct voltage


between compressor terminals
on the outdoor unit.

-If the voltage correct replace


capacitor or compressor.

6.

The compressor
does not start up.

-If no voltage replace main P.C.B


-If low voltage repair power supply.

-If there is no voltage repair


electrical wiring between indoor
and outdoor units.
7.

The refrigeration
system does not
function correctly.

SM PRIME 1- A.1 GB

Check for leaks or restrictions.


With ammeter. Pressure gauge
or surface thermometer.

-Repair refrigeration system and


charge refrigerant if necessary.

13-1

TROUBLESHOOTING

NO

SYMPTON

PROBABLE CAUSE

CORRECTIVE ACTION

No cooling or
heating only
indoor fan works.

Outdoor fan motor faulty or


other fault caused, compressor
overload protection cut out.

-Replace P.C.B.
-Outdoor fan blocked remove
obstructions.

9.

Only indoor fan


and compressor
working.
Only indoor fan
working.

Outdoor fan blocked.

-Remove obstructions.

-Run capacitor of outdoor fan


motor faulty.
-Windings of outdoor fan are
shorted.
-Overload safety device on
compressor is cut out (low
voltage or high temperature).

-Replace capacitor.

-Compressor runs capacitor


faulty.

-Replace compressor capacitor.

10.

11.

No cooling or
heating takes
place, indoor fans
working.

-Replace motor.
-Check for proper voltage, switch
off power and try again after one
hour.

-Replace compressor.

12.

No air supply
at indoor unit,
compressor
operates.

13.

Partial, limited air


supply at indoor
unit.

14.

Water
accumulates
and over ow
from indoor unit
section.
Water dripping
from outdoor unit
base, (in heating
mode).
Freeze-up of
outdoor coil in
heating mode,
poor heating effect
in room, indoor fan
operates.

15.

16.

17.

13-2

Unit is in heat
mode but
operating in
cooling.

-Compressor windings are


shorted.
-Indoor fan motor is blocked or
turns slowly.
-Indoor fan run capacitor faulty.
-Motor windings are shorted.
Lack of refrigerant (will
accompanied by whistling
noise) cause ice formation on
indoor unit coil in cooling mode.
Drain tube or spout of drain pan
clogged.

-Check voltage, repair wiring if


necessary.
-Check fan wheel if it is tight
enough on motor shaft, tighten if
necessary.
-charge the unit after localizing
leak.

-Disassemble plastic drain tube


from spout of indoor unit drain pan.

Water drain outlet is clogged.

-Open outdoor unit cover clean out


water outlet clean the base inside
thoroughly.

-Faulty outdoor thermistor.

-Replace thermistor.

-Faulty control cable.

-Repair control cable.

-Outdoor temperature is below


design conditions.

-Shut unit off, it cannot work


properly.

-Outdoor unit air outlet is


blocked.
-Faulty RV coil.

-Remove obstructions.

-RV coil is ok valve is stuck


position.

-Replace the reversing valve.

-Replace RV coil.

SM PRIME 1- A.1 GB

EXPLODED VIEWS AND SPARE PARTS LISTS

14.

EXPLODED VIEWS AND SPARE PARTS LISTS

14.1

Indoor Unit: Prime 7, 9, 12, 18

SM PRIME 1- A.1 GB

14-1

EXPLODED VIEWS AND SPARE PARTS LISTS

14.2

14-2

Indoor Unit Prime 9 R22 / R410A


No.

Item Code

Item Description

Quantity

465100013

Grill /Alpha 7,9 F

453036500

Filter for DELTA 7/9

465720055

Front Frame Assy./ AIRWELL Delta 9 x R

4525987

SCREW COVER

4523860

Coil ASSY

452784400

IOD-7,9 Air outlet Assy. (no

4523693

DRAIN HOSE

4525991

LOUVER

10

4525992

VER. FLAP A

10

4525993

VER. FLAP B

11

4523526

BERAING ASSY FAN

12

453264200

Impeller Fan

13

4526659

REAR PANEL ASSY

14

464220008

Mount Bracket./Low Cost ALPHA 9

15

4526000

TUBE CLIP

16

4527112R

Motor Compact 12

17

4525998

MOTEOR COVER

18

4523507

Step motor

19

455013301R

EUR EURPowerCord/3G/1.0/2100(187)

20

4525988

CABLE LOCKER

21

453089600R

Display assy. for DELTA EHK:936A034-00

22

4516263

SENSOR BASE

23

467300198R

Controller/Delta 7/9/12 S/W:10V14

24

438082

Thermistor Indoor

25

467400024

( 320mm) Indoor Air Inlet Temperature Se

26

453027000

Terminal Cover

28

4520416

Defrost cable EXPORT UNITS

29

436670R

R/C RC4

32

465440009

Frame Left Crank

32

465440010

Frame Right Crank

SM PRIME 1- A.1 GB

EXPLODED VIEWS AND SPARE PARTS LISTS

14.3

Indoor Unit Prime 12 R22


No.

Item Code

Item Descrption

465100014

Grill /Alpha 12 F

453082900

Filter for DELTA 12

465720056

Front Frame Assy./ AIRWELL Delta 12 x

4525987

SCREW COVER

462350047

Evaporator Assy./CON 12 R22

4527506

Air Outlet

4523693

DRAIN HOSE

4527509

Horizontal Flap

10

4525992

VER. FLAP A

10

4527510

Vertical Flap B

11

4523526

BERAING ASSY FAN

12

4527111

FAN ASSY PLASTIC

13

4527186

IOD-12 REAR PANEL ASSY

14

464220007

Mount Bracket./Low Cost ALPHA 12

15

4527512

Tube Clip

16

4527112R

Motor Compact 12

17

4525998

MOTEOR COVER

18

4523507

Step motor

19

455013301R

EUR EURPowerCord/3G/1.0/2100(187)

20

4525988

CABLE LOCKER

21

453089600R

Display assy. for DELTA EHK:936A034-00

22

4516263

SENSOR BASE

23

467300198R

Controller/Delta 7/9/12 S/W:10V14

24

438082

Thermistor Indoor

25

467400024

( 320mm) Indoor Air Inlet Temperature Se

26

453027000

Terminal Cover

28

4520416

Defrost cable EXPORT UNITS

29

436670R

R/C RC4

32

465440009

Frame Left Crank

32

465440010

SM PRIME 1- A.1 GB

Quantity

14-3

EXPLODED VIEWS AND SPARE PARTS LISTS

14.4

14-4

Indoor Unit: Prime 12 (class A) R410A


No.

Item Code

Item Description

Quantity

465100014

Grill /Alpha 12 F

453082900

Filter for DELTA 12

465720056

Front Frame Assy./ AIRWELL Delta 12 x

4525987

SCREW COVER

453058200

Evap. System Assy./Alfa12

4527506

Air Outlet

4523693

DRAIN HOSE

4527509

Horizontal Flap

10

4525992

VER. FLAP A

10

4527510

Vertical Flap B

11

4523526

BERAING ASSY FAN

12

4527111

FAN ASSY PLASTIC

13

4527186

IOD-12 REAR PANEL ASSY

14

464220007

Mount Bracket./Low Cost ALPHA 12

15

4527512

Tube Clip

16

4527112R

Motor Compact 12

17

4525998

MOTEOR COVER

18

4523507

Step motor

19

455013301R

EUR EURPowerCord/3G/1.0/2100(187)

20

4525988

CABLE LOCKER

21

453089600R

Display assy. for DELTA EHK:936A034-00

22

4516263

SENSOR BASE

23

467300198R

Controller/Delta 7/9/12 S/W:10V14

24

438082

Thermistor Indoor

25

467400024

( 320mm) Indoor Air Inlet Temperature Se

26

453027000

Terminal Cover

28

4520416

Defrost cable EXPORT UNITS

29

436670R

R/C RC4

32

465440009

Frame Left Crank

32

465440010

Frame Right Crank

SM PRIME 1- A.1 GB

EXPLODED VIEWS AND SPARE PARTS LISTS

14.5

Indoor Unit: Prime 12 (class C) R410A


No.

Item Code

Item Desc

465100014

Grill /Alpha 12 F

453082900

Filter for DELTA 12

465720056

Front Frame Assy./ AIRWELL Delta 12 x

4525987

SCREW COVER

470680012

Evaporator List/Low Cost ALPHA 12 R410A

4527506

Air Outlet

4523693

DRAIN HOSE

4527509

Horizontal Flap

10

4525992

VER. FLAP A

10

4527510

Vertical Flap B

11

4523526

BERAING ASSY FAN

12

4527111

FAN ASSY PLASTIC

13

4527186

IOD-12 REAR PANEL ASSY

14

464220007

Mount Bracket./Low Cost ALPHA 12

15

4527512

Tube Clip

16

4527112R

Motor Compact 12

17

4525998

MOTEOR COVER

18

4523507

Step motor

19

467000000R

Power Cord Without Plug 3*1.0mm2 L=2100

20

4525988

CABLE LOCKER

21

453089600R

Display assy. for DELTA EHK:936A034-00

22

4516263

SENSOR BASE

23

467300198R

Controller/Delta 7/9/12 S/W:10V14

24

438082

Thermistor Indoor

25

467400024

( 320mm) Indoor Air Inlet Temperature Se

26

453027000

Terminal Cover

28

4520416

Defrost cable EXPORT UNITS

29

436670R

R/C RC4

32

465440009

Frame Left Crank

32

465440010

Frame Right Crank

SM PRIME 1- A.1 GB

Quantity

14-5

EXPLODED VIEWS AND SPARE PARTS LISTS

14.6

14-6

Indoor Unit:Prime 18 R22 / R410A


No.

Item Code

Item Description

Quantity

465100015

Grill /Alpha 17 F

453080800

Filter

470500003

FilterAssy.

465720123

Front Frame Assy./Delta 17 Fixed RPM/Air

453081000

Screw Cover

453102200

Evaporator Assy.

453081100

Air Outlet Frame

4518664

Drain hose

4527509

Horizontal Flap

10

453081400

Vertical Flap A

11

10

453081500

Vertical Flap B

11

4518662

Bearing assy fan

12

453082400

Impeller Fan

13

453101400

Unit Housing Assy./ALPHA-17

14

453081900

Mount Bracket Assy.

15

4526000

TUBE CLIP

16

453102100R

ResinMotor/18W/1200rpm1000rpm

17

452918800

Cover/motor

18

4523507

Step motor

19

455013700R

PowerCordWithoutPlug/3G/1.5/2100(187)

20

4525988

CABLE LOCKER

21

467300007R

Display Board Assy./DELTA EHK: 936A035-0

22

4516263

SENSOR BASE

23

467300199R

Controller/Delta 17/22 S/W:10V14

24

438082

Thermistor Indoor

25

467400024

( 320mm) Indoor Air Inlet Temperature Se

26

453027000

Terminal Cover

28

4520416

Defrost cable EXPORT UNITS

29

436670R

R/C RC4

32

465440001

Grill Left Crank

32

465440002

Grill Right Crank

SM PRIME 1- A.1 GB

EXPLODED VIEWS AND SPARE PARTS LISTS

14.7

Outdoor Unit: CSP 9, 12 RC R410A (class C)

SM PRIME 1- A.1 GB

14-7

EXPLODED VIEWS AND SPARE PARTS LISTS

14.8

Outdoor Unit: CSP 9, RC R410A (class C)


No. P/N

14-8

Description

Quan.

4526481

CON Outdoor Grille

464660013

Front panel Painting assy/CON 9/12

464600046

Base Plate Painting assy/CON 9 R410A

455000108

Double patch Capacitor for fan motor 2uF

464160019

Partition plate/CON 9/12

4510679

Nut M6 GB6187-86

455000503

Compressor Capacitor With Screw 30uF (CBB65)

10

461010020

Gas Valve 3/8 R410A

11

461000011

Liquid Valve 1/4 R410A

12

4523707

AXIAL FAN

14

204107

Cable clip Nylon

15

464180011

Capacitor Support/CON 9/12

16

466100017R

Metal Motor 20W 900rpm/Outdoor Unit

17

453045000

Motor support

18

463600026

Capillary Assy. 2.6x1.4x1200

19

201019

Nut M8

20

391498

Wire assy

21

460090002R

Compressor Assy./SANYO C-1RV107H1C

22

469100003

Insulation Felt/ Compressor

24

4516637

Out sensor Black

25

461600034

4-Way Valve Assy./CON 9 R410A

26

4520071

4-W valve coil for R410A

27

4518951

4-W valve SHF-4H for R410A

28

4526668

R lifter

29

464630010

Side Plate Painting Assy./Right/CON 9/12

30

4514588

5 Poles terminal block

31

236179

2 Poles terminal block

34

464800008

Guard Net Painting Assy. /CON

35

462300038

Condenser Assy/CON 9

36

4526675

TOP COVER PAINTING

37

436358

L. lifter

38

4526143

LINKER OF MOTOR SUPPORT ASSY

SM PRIME 1- A.1 GB

EXPLODED VIEWS AND SPARE PARTS LISTS

14.9

Outdoor Unit: CSP 12 RC R410A (class C)


NO.

P/N

Description

4526481

CON Outdoor Grille

464660013

Front panel Painting assy/CON 9/12

464600040

Base Painting assy/ CON 12 R410A

455000108

Double patch Capacitor for fan motor 2uF

464160019

Partition plate/CON 9/12

4510679

Nut M6 GB6187-86

455000502

Compressor Capacitor With Screw 25uF (CBB65)

10

461010020

Gas Valve 3/8 R410A

11

461000011

Liquid Valve 1/4 R410A

12

4523707

AXIAL FAN

14

204107

Cable clip Nylon

15

464180011

Capacitor Support/CON 9/12

16

466100017R Metal Motor 20W 900rpm/Outdoor Unit

17

453045000

Motor support

18

463600028

Capillary Assy.

19

201019

Nut M8

20

391498

Wire assy

21

460090000R Compressor Assy./SANYO C-RV133H1D

22

469100003

Insulation Felt/ Compressor

24

4516637

Out sensor Black

25

461600031

4-Way Valve System Assy./ CON 12 R410A

26

4520071

4-W valve coil for R410A

27

4518951

4-W valve SHF-4H for R410A

28

4526668

R lifter

29

464630010

Side Plate Painting Assy./Right/CON 9/12

30

4514588

5 Poles terminal block

31

236179

2 Poles terminal block

34

464800008

Guard Net Painting Assy. /CON

35

462300039

Condenser Assy/CON 12 For EU

36

4526675

TOP COVER PAINTING

37

436358

L. lifter

38

4526143

LINKER OF MOTOR SUPPORT ASSY

SM PRIME 1- A.1 GB

Quan.

14-9

EXPLODED VIEWS AND SPARE PARTS LISTS

14.10

14-10

Outdoor Unit: CSP 9, 12 ST R410A (class C)

SM PRIME 1- A.1 GB

EXPLODED VIEWS AND SPARE PARTS LISTS

14.11

Outdoor Unit: CSP 9 ST R410A (class C)


NO.

P/N

Description

4526481

CON Outdoor Grille

464660013

Front panel Painting assy/CON 9/12

464600046

Base Plate Painting assy/CON 9 R410A

455000108

Double patch Capacitor for fan motor 2uF

464160019

Partition plate/CON 9/12

4510679

Nut M6 GB6187-86

455000503

Compressor Capacitor With Screw 30uF (CBB65)

10

461010020

Gas Valve 3/8 R410A

11

461000011

Liquid Valve 1/4 R410A

12

4523707

AXIAL FAN

14

204107

Cable clip Nylon

15

464180011

Capacitor Support/CON 9/12

16

466100017R

Metal Motor 20W 900rpm/Outdoor Unit

17

453045000

Motor support

18

463600026

Capillary Assy. 2.6x1.4x1200

19

201019

Nut M8

20

391498

Wire assy

21

460090002R

Compressor Assy./SANYO C-1RV107H1C

22

469100003

Insulation Felt/ Compressor

26

463300375

Discharge Pipe TP2M 7.94*0.8/CON 9 ST R410A

27

463300377

Scution Pipe TP2M 9.53*0.8/CON 9 ST R410A

28

4526668

R lifter

29

464630010

Side Plate Painting Assy./Right/CON 9/12

31

236179

2 2 Poles terminal block

34

464800008

Guard Net Painting Assy. /CON

35

462300042

Condenser Assy/CON 9 ST

36

4526675

TOP COVER PAINTING

37

436358

L. lifter

38

4526143

LINKER OF MOTOR SUPPORT ASSY

SM PRIME 1- A.1 GB

Quan.

14-11

EXPLODED VIEWS AND SPARE PARTS LISTS


14.12

Outdoor Unit: CSP 12 ST R410A (class C)


No.

14-12

P/N

Description

Quan.

4526481

CON Outdoor Grille

464660013

Front panel Painting assy/CON 9/12

464600040

Base Painting assy/ CON 12 R410A

455000108

Double patch Capacitor for fan motor 2uF

464160019

Partition plate/CON 9/12

4510679

Nut M6 GB6187-86

455000502

Compressor Capacitor With Screw 25uF (CBB65)

10

461010020

Gas Valve 3/8 R410A

11

461000011

Liquid Valve 1/4 R410A

12

4523707

AXIAL FAN

14

204107

Cable clip Nylon

15

464180011

Capacitor Support/CON 9/12

16

466100017R

Metal Motor 20W 900rpm/Outdoor Unit

17

453045000

Motor support

18

463600028

Capillary Assy.

19

201019

Nut M8

20

391498

Wire assy

21

460090000R

Compressor Assy./SANYO C-RV133H1D

22

469100003

Insulation Felt/ Compressor

26

463300376

Discharge Pipe TP2M 7.94*0.8/CON 12 ST R410A

27

463300378

Scution Pipe TP2M 9.53*0.8/CON 12 ST R410A

28

4526668

R lifter

29

464630010

Side Plate Painting Assy./Right/CON 9/12

30

4514588

5 Poles terminal block

34

464800008

Guard Net Painting Assy. /CON

35

462300043

Condenser Assy/CON 12 ST

36

4526675

TOP COVER PAINTING

37

436358

L. lifter

38

4526143

LINKER OF MOTOR SUPPORT ASSY

SM PRIME 1- A.1 GB

EXPLODED VIEWS AND SPARE PARTS LISTS

14.13

Outdoor Unit: CSP 9, 12 RC R22

SM PRIME 1- A.1 GB

14-13

EXPLODED VIEWS AND SPARE PARTS LISTS

14.14

Outdoor Unit CSP 9 RC R22


No.

14-14

Item

Description

Quan.

4526481

CON Outdoor Grille

464660013

Front panel Painting assy/CON 9/12

464600056

Base Plate Painting Assy./CON SP 9 R22

455000108

Double patch Capacitor for fan motor 2uF

4526141

PARTITION PLATE

4510679

Nut M6 GB6187-86

455000401

Compressor Capacitor 30uF (CBB65)

10

4523587

GAS VALVE

11

4523533

Liqiud Valve

12

4523707

AXIAL FAN

13

4518839

Comp. Capacitor Clip

14

204107

Cable clip Nylon

15

453044500

Pedestal/Control

16

466100017R

Metal Motor 20W 900rpm/Outdoor Unit

17

4526146

MOTOR SUPPORT ASSY

18

4523913

Capillary assy

19

201019

Nut M8

20

391498

Wire assy

21

452982000

Compressor assy PH170X1C-4DZDE3

22

469100003

Insulation Felt/ Compressor

24

4516637

Out sensor Black

25

4526875

4-W vavle welding assy

26

4514005

4-W valve coil

27

224213

4-W valve

28

4526668

R lifter

29

4526669

SIDE PANEL PAINTING

30

4514588

5 Poles terminal block

31

236179

2 Poles terminal block

34

464800008

Guard Net Painting Assy. /CON

35

4526651

Cond. Assy

36

4526675

TOP COVER PAINTING

37

436358

L. lifter

38

4526143

LINKER OF MOTOR SUPPORT ASSY

SM PRIME 1- A.1 GB

EXPLODED VIEWS AND SPARE PARTS LISTS

14.15

Outdoor Unit: CSP 12 RC R22


No.

Item

Description

4526481

CON Outdoor Grille

464660013

Front panel Painting assy/CON 9/12

464600040

Base Painting assy/ CON 12 R410A

455000108

Double patch Capacitor for fan motor 2uF

464160019

Partition plate/CON 9/12

4510679

Nut M6 GB6187-86

455000502

Compressor Capacitor With Screw 25uF (CBB65)

10

461010021

Gas Valve 1/2 R22

11

461000013

Liquid Valve 1/4 R22

12

4523707

AXIAL FAN

14

204107

Cable clip Nylon

15

464180011

Capacitor Support/CON 9/12

16

466100017R

Metal Motor 20W 900rpm/Outdoor Unit

17

453045000

Motor support

18

463600030

Capillary Assy. (OD2.6xID1.6x800+450)

19

201019

Nut M8

20

391498

Wire assy

21

460030002R

Compressor Assy/ SANYO C-RV212H51BA

22

469100003

Insulation Felt/ Compressor

24

4516637

Out sensor Black

25

461600038

4-Way Valve Assy./CON12 R22

26

4514005

4-W valve coil

27

224213

4-W valve

28

4526668

R lifter

29

464630010

Side Plate Painting Assy./Right/CON 9/12

30

4514588

5 Poles terminal block

31

236179

2 Poles terminal block

34

464800008

Guard Net Painting Assy. /CON

35

462300046

Condenser Assy/CON 12 R22

36

4526675

TOP COVER PAINTING

37

436358

L. lifter

38

4526143

LINKER OF MOTOR SUPPORT ASSY

SM PRIME 1- A.1 GB

Quan.

14-15

EXPLODED VIEWS AND SPARE PARTS LISTS


14.16

14-16

Outdoor Unit: GCN9, 12 RC R410A (class A)

SM PRIME 1- A.1 GB

EXPLODED VIEWS AND SPARE PARTS LISTS


14.17
No.

Outdoor Unit: GCN9 RC R410A (class A)


Item Code

Description

4516158

Cover panel Painting assy

4522551

Grille A of GCN

436358

L. lifter

4523441

Front panel A Painting assy

4516907

PAINTING BASE ASSY.

453086200

Side Plate Painting Assy.

4516857

BIG SIDE COVER

204107

Cable clip Nylon

453070800

Rubber gromet/base plate

10

236332

6 Poles terminal block

11

236179

2 Poles terminal block

12

253046

Clip set PVC

13

4518022

Cap. Clip

14

201130

Nut M4

15

203008

Washer

16

455000108

Double patch Capacitor for fan

17

455000502

Compressor Capacitor 35uF With Screw

18

453090300

Compressor Assy. PA108X1C-4FZ

19

452795300

Nut With Flange M6

20

391498

Wire assy

21

453047000

Low pressure stop valve for R410A

22

453046900

High pressure stop valve for R410A

23

453091500

4 Way Valve System Assy.

24

4520071

4-W valve coil for R410A

25

4518951

4-W valve SHF-4H for R410A

26

453091600

Single Valve Assy.

27

4516156

Rear panel Painting assy

28

4516637

Out sensor Black

29

453090700

Condenser System Assy.

30

464160018

Partition plate/GCZ 9/12

31

464860032

Motor Support Assy.

32

4522765R

Motor of outdoor (670/750rpm)

33

4519251

Axial Fan OD=400

34

4519300

Nut M5 L

35

453121500

Install. Accessory

SM PRIME 1- A.1 GB

Quantity

14-17

EXPLODED VIEWS AND SPARE PARTS LISTS

Outdoor Unit: GCN12 RC R410A (class A)

14.18
No.

14-18

Item Code

Description

Quantity

4516158

Cover panel Painting assy

4522551

Grille A of GCN

436358

L. lifter

4523441

Front panel A Painting assy

4523862

Base Painting assy

453086200

Side Plate Painting Assy.

4516857

BIG SIDE COVER

204107

Cable clip Nylon

453070800

Rubber gromet/base plate

10

236332

6 Poles terminal block

11

236179

2 Poles terminal block

12

253046

Clip set PVC

13

4518022

Cap. Clip

14

201130

Nut M4

15

203008

Washer

16

455000108

Double patch Capacitor for fan

17

455000504

Compressor Capacitor With Screw

18

4526452

Comp. Assy GMCC PA145X2C-4FT

19

4510677

Nut With Flange M8 -D=24

20

391498

Wire assy

21

453047000

Low pressure stop valve for R410A

22

453046900

High pressure stop valve for R410A

23

453092700

4-Way Valve System Assy.

24

4520071

4-W valve coil for R410A

25

4518952

4-W valve SHF-7H for R410A

26

453092800

Single Valve Assy. 2.6X1.6

27

4516156

Rear panel Painting assy

28

4516637

Out sensor Black

29

453092100

Condenser System Assy.

30

464160018

Partition plate/GCZ 9/12

31

464860032

Motor Support Assy.

32

4522766R

Motor of outdoor (830rpm)

33

4519251

Axial Fan OD=400

34

4519300

Nut M5 L

35

453121500

Install. Accessory

SM PRIME 1- A.1 GB

EXPLODED VIEWS AND SPARE PARTS LISTS


14.19

Outdoor Unit: GCN9,12 ST R410A (class A)

SM PRIME 1- A.1 GB

14-19

EXPLODED VIEWS AND SPARE PARTS LISTS

Outdoor Unit: GCN9 ST R410A (class A)

14.20
No.

14-20

Item Code

Description

Quantity

4516158

Cover panel Painting assy

4522551

Grille A of GCN

436358

L. lifter

4523441

Front panel A Painting assy

4516907

PAINTING BASE ASSY.

453086200

Side Plate Painting Assy.

4516857

BIG SIDE COVER

204107

Cable clip Nylon

453070800

Rubber gromet/base plate

10

236332

6 Poles terminal block

12

253046

Clip set PVC

13

4518022

Cap. Clip

14

201019

Nut M8

15

203008

Washer

16

455000108

Double patch Capacitor for fan

17

455000502

Compressor Capacitor 35uF With Screw

18

453090300

Compressor Assy. PA108X1C-4FZ

19

452795300

Nut With Flange M6

20

391498

Wire assy

21

453047000

Low pressure stop valve for R410A

22

453046900

High pressure stop valve for R410A

23

453086900

Scution Pipe

24

453087000

Discharge Pipe 1

25

4526865

Mufer

26

453091300

Discharge Pipe 2

27

453121700

Capillary 2.6*1.4*900

28

464770001

Rear Plate/Left Painting Assy

28

464770007

Rear Plate/Right Painting Assy/GCZ 9/12

28

464800000

Guard Net/ODU Painting Assy

29

453090700

Condenser System Assy.

30

464160018

Partition plate/GCZ 9/12

31

464860002

Motor Support Assy.

32

4522765R

Motor of outdoor (670/750rpm)

33

4519251

Axial Fan OD=400

34

4519300

Nut M5 L

35

453166600

Install. Accessory

SM PRIME 1- A.1 GB

EXPLODED VIEWS AND SPARE PARTS LISTS

Outdoor Unit: GCN12 ST R410A (class A)

14.21
No.

Item Code

Description

4516158

Cover panel Painting assy

4522551

Grille A of GCN

436358

L. lifter

4523441

Front panel A Painting assy

4523862

Base Painting assy

453086200

Side Plate Painting Assy.

4516857

BIG SIDE COVER

204107

Cable clip Nylon

453070800

Rubber gromet/base plate

10

236332

6 Poles terminal block

11

236179

2 Poles terminal block

12

253046

Clip set PVC

13

4518022

Cap. Clip

14

201130

Nut M4

15

203008

Washer

16

455000108

Double patch Capacitor for fan

17

455000504

Compressor Capacitor With Screw

18

4526452

Comp. Assy GMCC PA145X2C-4FT

19

4510677

Nut With Flange M8 -D=24

20

391498

Wire assy

21

453047000

Low pressure stop valve for R410A

22

453046900

High pressure stop valve for R410A

23

453087500

Scution Pipe

24

453087600

Discharge Pipe 1

25

453091000

Mufer

26

453092500

Discharge Pipe 2

27

453121600

Capillary 2.6*1.6*900

28

4516156

Rear panel Painting assy

29

453092100

Condenser System Assy.

30

464160018

Partition plate/GCZ 9/12

31

464860032

Motor Support Assy.

32

4522766R

Motor of outdoor (830rpm)

33

4519251

Axial Fan OD=400

34

4519300

Nut M5 L

35

453166600

Install. Accessory

SM PRIME 1- A.1 GB

Quantity

14-21

EXPLODED VIEWS AND SPARE PARTS LISTS


14.22

14-22

Outdoor Unit: ONG3-17 RC R410A

SM PRIME 1- A.1 GB

EXPLODED VIEWS AND SPARE PARTS LISTS

Outdoor Unit: ONG3-17 RC R410A

14.23
No.

Item Code

Item Desc

Quantity

433218

Front Panel A

433221

Air Inlet Ring-420

464860054

Painting Insulation Plate Assy/ONG

4519251

Axial Fan OD=400

4520171R

Fan Motor (910rpm)

4527203

Motor Support

464600001

Base Plate Painting Assy.

4527202

Partition Plate

455000506

Compressor Capacitor With Screw

10

453012700

Electric Panel

11

4524176

1/4 Liqiud Valve(R410A)

12

4524595

1/2 Gas Valve for ONG R410A

13

455000001

single patch Capacitor for fan

14

4514588

5 Poles terminal block

15

204107

Cable clip Nylon

16

236179

2 Poles terminal block

17

4516637

Out sensor Black

18

463600000

Capillary Assy

19

469270002

Insulation Rub+Felt/Compress

20

463230014

Way Strainer

21

4510677

Nut With Flange M8 -D=24

22

4519987

Wire assy

23

460000000

Compressor Assy./ GMCC PA200X

24

433229

Valve Cover

26

4519606

Right side panel (painting plate)

27

461600001

4-Way Valve Assy.

28

4518952

4-W valve SHF-7H for R410A

29

4520071

4-W valve coil for R410A

30

433228

Back Side Net

31

4526298

Bridge

32

462300003

Condenser Assy.

33

4519614

Painting Top Cover

34

4519300

Nut M5 L

35

433225

Handle

36

4519607

Left Side Panel Painting Plate

37

470120001

Rubber Cushion /Base Plate

38

453121300

Install. Accessory

SM PRIME 1- A.1 GB

14-23

EXPLODED VIEWS AND SPARE PARTS LISTS


14.24

14-24

Outdoor Unit: ONG3-17 RC R22

SM PRIME 1- A.1 GB

EXPLODED VIEWS AND SPARE PARTS LISTS


14.25

Outdoor Unit: ONG3-17 RC R22


No.

Item Code

Description

Quantity

433218

Front Panel A

433221

Air Inlet Ring-420

464860054

Painting Insulation Plate Assy/ONG

4519251

Axial Fan OD=400

4520171R

Fan Motor (910rpm)

4527203

Motor Support

4520060

Base Painting Assy.

255015

Washer

436632

Drain Connector

10

4519609

Drain Jam

11

433217

Partition Plate

12

455000507

Compressor Capacitor With Screw

13

203008

Washer

14

201019

Nut M8

15

453012700

Electric Panel

16

4519265

Liquid Valve OD=6.35

17

4519266

GAS VALVE OD=12.7

18

455000108

Double patch Capacitor for fan

19

4514588

5 Poles terminal block

20

236179

2 Poles terminal block

21

204107

Cable clip Nylon

22

4516637

Out sensor Black

24

4519898

Capillary Welding Assy.

25

4510463

Charge tube T2M ?6.35x0.7

26

452987500

Comp. Jacket

27

461600007

4-Way Valve Assy.

28

4514005

4-W valve coil

29

4519987

Wire assy

30

224136

4-W valve

31

460000002

CompressorAssy./PH330X2CS-4KT4

32

4510677

Nut With Flange M8 -D=24

33

433229

Valve Cover

34

452892900

Wire Clip

35

4519606

Right side panel (painting plate)

36

433228

Back Side Net

37

4526298

Bridge

38

452813200

coil stopper

39

4519620

Cond. ONG-14,18RC Not Assembley!

40

4519614

Painting Top Cover

41

4519300

Nut M5 L

42

433225

Handle

43

4519607

Left Side Panel Painting Plate

SM PRIME 1- A.1 GB

14-25

APPENDIX A

APPENDIX A
INSTALLATION AND OPERATION MANUAL

INSTALLATION MANUAL PRIME SERIES

OPERATION MANUAL PRIME SERIES

OPERATION MANUAL RC3

OPERATION MANUAL RC4

SM PRIME 1- A.1 GB

15-1