CALCULATION of PIPE RACK STRUCTURE #1 Doc. No.

(MR01-1 to MR01-10)
REV.
SENORO GAS DEVELOPMENT PROJECT

DATE.

SNO-S-CC-05-001

A
17-APR-13

D. DESIGN LOAD
D.1. Loading Data
Service Load
MR01 01-10

Storey
Elev. +6.000

Row 01-10
Pipe
Line <= 10 inch

Elev. +8.000

Row 01-10
Pipe
Line <= 10 inch
Pipe
16-HF-1004-6R-PP-01
Pipe
16-HF-2004-6R-PP-01

Elev. +11.000

Row 01-10
Pipe
Line <= 10 inch
Pipe
24-VH-0051-1B-01

Elev. +18.000

Row 01-10
Pipe
Pipe
Pipe
Pipe
Pipe
Pipe
Pipe

Line <= 10 inch


CPDMR01-6-HF-2104-6R-01
CPDMR01-6-HF-2107-6R-01
CPDMR01-6-HF-2106-6R-01
CPDMR01-6-HF-1104-6R-01
CPDMR01-6-HF-1107-6R-01
CPDMR01-6-HF-1106-6R-01

________________________________________________________________________________________
Attachment D Page 2 of 15

CALCULATION of PIPE RACK STRUCTURE #1 Doc. No.


(MR01-1 to MR01-10)
REV.
SENORO GAS DEVELOPMENT PROJECT

DATE.

SNO-S-CC-05-001

A
17-APR-13

D.1.1. Dead Load


All self weight of structural steel shall be calculated with STAAD Pro v8i.
D.1.1.1 Member Properties
Elevation
m
EL+0.000
to
EL+6.000

Symbol

Profile

Unit Weight
kg/m
kN/m

R1
R2
R4
R5
R7
R12
R15
R20
R21

SH
SH
SH
SH
SH
2C
2L
2L
SH

588x300x12x20
300x150x6.5x9
400x200x8x13
400x200x8x13
500x200x10x16
150x75x6.5x10
150 x 150
175 x 175
350x175x7x11

151
36.7
66
66
89.6
37.2
67.2
78.8
49.6

1.48131
0.360027
0.64746
0.64746
0.878976
0.364932
0.659232
0.773028
0.486576

Column (Row 01-10)


Longitudinal beam
Support Cantilever beam
Cantilever Beam
Main Beam
Horizontal Bracing
Vertical Bracing
Vertical Bracing
Secondary and longitudinal beam

EL+6.000
to
EL+8.000

R1
R2
R4
R5
R12
R13
R15
R16
R22

SH
SH
SH
SH
2C
SH
2L
SH
SH

588x300x12x20
300x150x6.5x9
400x200x8x13
400x200x8x13
150x75x6.5x10
400x200x8x13
150 x 150
450x200x8x15
350x175x7x11

151
36.7
66
66
37.2
66
67.2
76
49.6

1.48131
0.360027
0.64746
0.64746
0.364932
0.64746
0.659232
0.74556
0.486576

Column (Row 01-10)


Longitudinal beam
Support Cantilever beam
Cantilever Beam
Horizontal Bracing
Main Beam
Vertical Bracing
Main Beam
Secondary and longitudinal beam

EL+8.000
to
EL+11.000

R1
R2
R4
R5
R8
R12
R15
R17
R23

SH
SH
SH
SH
SH
2C
2L
SH
SH

588x300x12x20
300x150x6.5x9
400x200x8x13
400x200x8x13
400x200x8x13
150x75x6.5x10
150 x 150
450x200x8x15
350x175x7x11

151
36.7
66
66
66
37.2
67.2
76
49.6

1.48131
0.360027
0.64746
0.64746
0.64746
0.364932
0.659232
0.74556
0.486576

Column (Row 01-10)


Longitudinal beam
Support Cantilever beam
Cantilever Beam
Main Beam
Horizontal Bracing
Vertical Bracing
Main Beam
Secondary and longitudinal beam

Remarks

________________________________________________________________________________________
Attachment D Page 3 of 15

CALCULATION of PIPE RACK STRUCTURE #1 Doc. No.


(MR01-1 to MR01-10)
REV.
SENORO GAS DEVELOPMENT PROJECT
Profile

Unit Weight
kg/m
kN/m

DATE.

SNO-S-CC-05-001

A
17-APR-13

Elevation
m
EL+11.000
to
EL+15.000

Symbol
R1
R2
R4
R5
R9
R12
R15
R18

SH
SH
SH
SH
SH
2C
2L
SH

588x300x12x20
300x150x6.5x9
400x200x8x13
400x200x8x13
400x200x8x13
150x75x6.5x10
150 x 150
450x200x8x15

151 1.48131 Column (Row 01-10)


36.7 0.360027 Secondary and longitudinal beam
66 0.64746 Support Cantilever beam
66 0.64746 Cantilever Beam
66 0.64746 Main Beam
37.2 0.364932 Horizontal Bracing
67.2 0.659232 Vertical Bracing
76 0.74556 Main Beam

EL+15.000
to
EL+18.000

R1
R3
R4
R5
R6
R10
R11
R12
R14
R15
R19
R24

SH
SH
SH
SH
SH
SH
SH
SH
SH
2L
SH
SH

588x300x12x20
300x150x6.5x9
300x150x6.5x9
400x200x8x13
175x90x5x7
400x200x8x13
250x125x6x9
450x200x8x15
500x200x10x16
150 x 150
300x150x6.5x9
700x300x13x24

151
36.7
36.7
66
18.1
66
29.6
76
89.6
67.2
36.7
185

1.48131
0.360027
0.360027
0.64746
0.177561
0.64746
0.290376
0.74556
0.878976
0.659232
0.360027
1.81485

Remarks

Column (Row 01-10)


Longitudinal Beam
Support Cantilever beam
Cantilever Beam
Secondary Beam
Main beam
Secondary and longitudinal beam
Horizontal Bracing
Main beam
Vertical Bracing
Longitudinal beam
Main Beam

________________________________________________________________________________________
Attachment D Page 4 of 15

CALCULATION of PIPE RACK STRUCTURE #1 Doc. No.


(MR01-1 to MR01-10)
REV.
SENORO GAS DEVELOPMENT PROJECT

DATE.

SNO-S-CC-05-001

A
17-APR-13

D.1.1.2 Cable Tray Load


(Elect. Cable Tray)
900 F

Tray
designations
MR01-01
Electrical tray
Instrument Tray

Length
(m)

(Instr. Cable Tray)


900

P
(KN/m')

SF

F
(KN)

1.50

3.00
1.50

1.20

2.70
1.35

MR01-02-09
Electrical Tray
Instrument Tray

3.00

3.00
1.50

1.20

5.40
2.70

MR01-10
Electrical tray
Instrument Tray

1.50

3.00
1.50

1.20

2.70
1.35

________________________________________________________________________________________
Attachment D Page 5 of 15

CALCULATION of PIPE RACK STRUCTURE #1 Doc. No.


(MR01-1 to MR01-10)
REV.
SENORO GAS DEVELOPMENT PROJECT

DATE.

SNO-S-CC-05-001

A
17-APR-13

D.1.1.3 Fire Proofing Load


Refer to SNO-C-SD-100-007 Standard Drawing Fire Proofing for Structural Steel, Fire Proofing shall be
performed at column and beam which exposed to fire hazard with thickness 50 mm.
Then, the detail weight of light concrete for fire proofing is shown in below table.

Fireproofing

Fig. A.3.1 Fire Proofing of Sub Pipe Rack SPR-2C

t2 + 2t

concrete weight
fire proofing thickness (t)
Inner Height of fireproof (H')
Total width (W')
Section area1 (A1)
Section area2 (A2)
Total Section Area (A)
Wc

=
=
=
=
=
=
=
=

23.50 kN/m3
50 mm
t1 + 2t
H - 2t = H - 100
W + 2t = W + 100
H' * (t1 + 2t) = H' * (t1 + 100)
2*(W' *(t2 + 2t) = 2*W'*t2 + 200*W'
A1 + A2
A * c

W'
W
t2
t1

H'

________________________________________________________________________________________
Attachment D Page 6 of 15

CALCULATION of PIPE RACK STRUCTURE #1 Doc. No.


(MR01-1 to MR01-10)
REV.
SENORO GAS DEVELOPMENT PROJECT

Profile

H
W
t1
t2
H'
W'
mm mm mm mm mm mm

A
m2

588

300 12.0 20.0

588

300

0.18

4.15

H500X200X10

500

200 10.0 16.0

500

200

0.10

2.35

H400X200X8

400

200

8.0 13.0

400

200

0.08

1.88

H350X175X7

350

175

7.0 11.0

350

175

0.06

1.44

H300X300X10

300

150 10.0 15.0

300

150

0.05

1.06

200x100x5.5x8

200

100

200

100

0.02

0.47

8.0

A
17-APR-13

Wc
kN/m

H588X300X12

6.0

DATE.

SNO-S-CC-05-001

________________________________________________________________________________________
Attachment D Page 7 of 15

CALCULATION of PIPE RACK STRUCTURE #1 Doc. No.


(MR01-1 to MR01-10)
REV.
SENORO GAS DEVELOPMENT PROJECT

DATE.

SNO-S-CC-05-001

A
17-APR-13

D.1.2. Piping Load


PIPING LOAD (From Stress Analysis)
Piping Load in Section B.1.2 should be converted to kN unit. Piping load with contingency
can be seen in the following table.
Weight
Span
Operating
Test
Piping Number
Unit Empty
PE
PO
PT
L Unit
Elev. +6.000
Row 01-10
Line <= 10 inch

kN/m2

1.177

1.668

1.668

kN/m2

1.177
9.810
19.620
10.791
21.582

1.668
14.715
29.430
16.187
32.373

1.668
18.149
36.297
19.620
39.240

1.177
11.282
22.563

1.668
12.263
22.563

1.668
24.525
22.563

1.177
17.658
17.658
15.696
17.658
17.658
17.658

1.668
68.670
68.670
68.670
58.860
68.670
68.670

1.668
29.430
27.468
22.563
27.468
27.468
25.506

Elev. +8.000
Row 01-10
Line <= 10 inch
16-HF-1004-6R-PP-01
16-HF-2004-6R-PP-01

Elev. +11.000
Row 01-10
Line <= 10 inch
24-VH-0051-1B-01

3
6
3
6

m
m
m
m

kN
kN

kN/m2

3m
6m

kN

Elev. +18.000
Row 01-10
Line <= 10 inch
CPDMR01-6-HF-2104-6R-01
CPDMR01-6-HF-2107-6R-01
CPDMR01-6-HF-2106-6R-01
CPDMR01-6-HF-1104-6R-01
CPDMR01-6-HF-1107-6R-01
CPDMR01-6-HF-1106-6R-01

kN/m2

kN

For distance between pipes, please see Attachment B Part B.1 Piping Loading Data

________________________________________________________________________________________
Attachment D Page 8 of 15

CALCULATION of PIPE RACK STRUCTURE #1 Doc. No.


(MR01-1 to MR01-10)
REV.
SENORO GAS DEVELOPMENT PROJECT

DATE.

SNO-S-CC-05-001

A
17-APR-13

THERMAL LOAD
Thermal Load in Section B.1.2 should be converted to kN unit. Thermal load with contingency 20%
can be seen in the following table.
Longitudinal Direction (Fx)
Piping Number

Unit

01

02

Thermal load on each of row


03 04 05 06 07 08

09

10

Elev. +6.000
Section A (Row 01-10)
Line <= 10 inch
Anchor Support <= 10 inch

kN/m
kN

3.00 3.00 3.00 3.00 3.00 3.00 3.00 3.00 3.00 3.00
0.25 0.25 0.25 0.25 0.25 0.25 0.25 0.25 0.25 0.25

Elev. +8.000
Section A (Row 01-10)
Line <= 10 inch
16-HF-1004-6R-PP-01
16-HF-2004-6R-PP-01
Anchor Support <= 10 inch

kN/m
kN
kN
kN

3.00 3.00 3.00 3.00


8.83 8.83 8.83
9.71 9.71
0.25 0.25 0.25 0.25

Elev. +11.000
Section A (Row 01-10)
Line <= 10 inch
24-VH-0051-1B-01
Anchor Support <= 10 inch

kN/m
kN
kN

3.00 3.00 3.00 3.00 3.00 3.00 3.00 3.00 3.00 3.00
7.36 7.36 7.36 7.36 7.36 7.36 7.36 7.36 7.36 7.36
0.25 0.25 0.25 0.25 0.25 0.25 0.25 0.25 0.25 0.25

Elev. +18.000
Section A (Row 01-10)
Section A (Row 01-10)
Anchor Support <= 10 inch

kN/m
kN

3.00 3.00 3.00 3.00 3.00 3.00 3.00 3.00 3.00 3.00
0.25 0.25 0.25 0.25 0.25 0.25 0.25 0.25 0.25 0.25

3.00
8.83
9.71
0.25

3.00
8.83
9.71
0.25

3.00
8.83
9.71
0.25

3.00
8.83
9.71
0.25

3.00
8.83
9.71
0.25

3.00
8.83
9.71
0.25

________________________________________________________________________________________
Attachment D Page 9 of 15

CALCULATION of PIPE RACK STRUCTURE #1 Doc. No.


(MR01-1 to MR01-10)
REV.
SENORO GAS DEVELOPMENT PROJECT

SNO-S-CC-05-001

DATE.

17-APR-13

D.1.3. Wind Load


This load will be applied as joint load at each column for wind load on pipe and will be
applied as member load at beam and column for wind load on beam and column.

10

06

05

07

08

09

04
03

Wx

Wz

02
01

Fig.D.1.3.1 Wind Load Direction


Velocity Pressure :
Wind Velocity (v)
Wind Pressure (qz)
Wind Pressure (qz)
Wind Pressure (qz)
Wind Pressure (qz)
Wind Pressure (qz)

=
=
=
=
=
=

32.08
0.479
0.508
0.545
0.579
0.595

m/s Wind Data Evaluation Report


kN/m2
h=6m
kN/m2
h=8m
kN/m2
h = 11 m
kN/m2
h = 15 m
kN/m2
h = 18 m

( Ref.3 )

Velocity Pressure up to the height of 10 m above grade are shown in below. These values are derived
from:
qz = 0.613*Kz*Kzt*Kd*V^2
Where :
qz = Velocity pressure evaluated at height z above ground (kN/m2)
Kz = Velocity pressure exposure coefficient , Exposure
:
Kzt = Topographic factor
:
Kd = Wind directional factor
:
z = Height above ground level

C
1.00
0.85

________________________________________________________________________________________
Attachment D Page 10 of 15

CALCULATION of PIPE RACK STRUCTURE #1 Doc. No.


(MR01-1 to MR01-10)
REV.
SENORO GAS DEVELOPMENT PROJECT

DATE.

SNO-S-CC-05-001

A
17-APR-13

Velocity Pressure
Height (z)
feet

Kz
m

19.69

6.00 0.89

26.25

8.00 0.95

36.09

11.00 1.02

49.21

15.00 1.08

59.06

18.00 1.11

Wind Load
Platform surface wind pressure on projected area has been adjusted by the proper shape and
height factor that required by the basic design specification and applied as a horizontal force
at joint.
Wind Force shall be calculated based on :
F = qz x G x Cf x wf
where :
qz = vellocity pressure
G = Gust Effect factor
: 0.85
Cf = Pressure coeficient
: 1.80
wf = Projected width see table

Profil
MH -588
MH -588
MH -588
MH -588
MH -588
SH -350
SH -350
SH -350
SH -300
SH -300
SH -500
SH -400
SH -400
SH -400
SH -400
SH -500

z
m
6
8
11
15
18
6
8
11
15
18
6
8
11
15
18
18

wf
mm
588
588
588
588
588
350
350
350
300
300
500
400
400
400
400
500

X Direction
qz
kN/m2
0.48
0.51
0.55
0.58
0.60
0.48
0.51
0.55
0.58
0.60
0.48
0.51
0.55
0.58
0.60
0.60

F
kN/m
0.43
0.46
0.49
0.52
0.54
0.26
0.27
0.29
0.27
0.27
0.37
0.31
0.33
0.35
0.36
0.46

wf
mm
300
300
300
300
300
350
350
350
300
300
400
-

Z Direction
qz
F
kN/m2
kN/m
0.48
0.22
0.51
0.23
0.55
0.25
0.58
0.27
0.60
0.27
0.48
0.26
0.51
0.27
0.55
0.29
0.58
0.27
0.60
0.27
0.60
0.36
-

Remarks
Column El + 6
Column El + 8
Column El + 11
Column El + 15
Column El + 18
Sec. Beam El + 6
Sec. Beam El + 8
Sec. Beam El + 11
Sec. Beam El + 15
Sec. Beam El + 18
Main Beam El + 6
Main Beam El + 8
Main Beam El + 11
Main Beam El + 15
Main Beam El + 18
Main Beam El + 18

________________________________________________________________________________________
Attachment D Page 11 of 15

CALCULATION of PIPE RACK STRUCTURE #1 Doc. No.


(MR01-1 to MR01-10)
REV.
SENORO GAS DEVELOPMENT PROJECT
b.

DATE.

SNO-S-CC-05-001

A
17-APR-13

WIND LOAD ON PIPING

Wind load on piping shall be calculated based on equation in ASCE 7-10 as below:
Basic wind speed =
Velocity Pressure :
Kz :
Kzt :
Kd :

32.08 m/s
0.613 Kz Kzt Kd V^2
0.96
1
1

Velocity Pressure :

606 N/m2

Wind Load (W)


VW :

V G Cf A

G
Cf
A

:
:
:

:
606 N/m2

0.85
1.2
Projected Area, depends on pipe size diameter

Diameter (in)

Pipe Length (m)

Projected Area (m2)

W (kN)

36
24
18
16
14
12
10
8
6
4
3
2

3
3
3
3
3
3
3
3
3
3
3
3

3.29
2.19
1.65
1.46
1.28
1.10
0.91
0.73
0.55
0.37
0.27
0.18

2.03
1.36
1.02
0.90
0.79
0.68
0.56
0.45
0.34
0.23
0.17
0.11

________________________________________________________________________________________
Attachment D Page 12 of 15

CALCULATION of PIPE RACK STRUCTURE #1 Doc. No.


(MR01-1 to MR01-10)
REV.
SENORO GAS DEVELOPMENT PROJECT

SNO-S-CC-05-001

DATE.

17-APR-13

D.1.4. Earthquake Load


Base shear due to earthquake load shall be calculated based on reference 7 as below.
V
V
The
total

=
=

Fi

Wi

0.264
0.212

x Wt
x Wt

Transverse
Longitudinal

Wi x hi
(Wi x hi)
(D+Po) + 0.25 L
Vx

Ex

02

04

03

06

05

07

08

09

10

Ez

01

Fig.D.1.4.1 Seismic Load Direction


TOS El + 18.00

F5

TOS El + 15.00

F4

TOS El + 11.00

F3

TOS El + 8.00

F2

TOS El + 6.00

F1

8m

Fig.D.1.4.2 Distribution Force Seismic Load

________________________________________________________________________________________
Attachment D Page 13 of 15

CALCULATION of PIPE RACK STRUCTURE #1 Doc. No.


(MR01-1 to MR01-10)
REV.
SENORO GAS DEVELOPMENT PROJECT

DATE.

SNO-S-CC-05-001

A
17-APR-13

Seismic load

MR01-07

MR01-06

MR01-05

MR01-04

MR01-03

MR01-02

MR01-01

Elevation
(m)
6
8
11
15
18
Total
6
8
11
15
18
Total
6
8
11
15
18
Total
6
8
11
15
18
Total
6
8
11
15
Total
6
8
11
15
Total
6
8
11
15
Total

(*)
h
W
kN
m
25.20
6
87.82
8
63.49 11
46.02 15
153.82 18
376.351
6
70.37
8
171.08
113.76 11
72.56 15
403.90 18
831.67
69.43
6
183.04
8
123.60 11
84.25 15
432.26 18
892.58
34.97
6
170.60
8
120.86 11
71.37 15
143.89 18
541.69
6
34.97
170.60
8
120.87 11
97.71 15
424.15
34.97
6
8
170.60
120.87 11
97.71 15
424.15
6
34.97
170.60
8
120.87 11
97.71 15
424.148

W*h
kN.m
151.21
702.54
698.41
690.29
2,768.76
5,011.21
422.24
1,368.62
1,251.37
1,088.37
7,270.13
11,400.72
416.59
1,464.30
1,359.60
1,263.72
7,780.68
12,284.89
209.84
1,364.81
1,329.50
1,070.51
2,589.95
6,564.61
209.84
1,364.80
1,329.52
1,465.65
4,369.80
209.84
1,364.80
1,329.52
1,465.65
4,369.80
209.84
1,364.80
1,329.52
1,465.65
4,369.80

V long.

V trans.

Force (kN)

kN
79.81
79.81
79.81
79.81
79.81

kN
99.31
99.31
99.31
99.31
99.31

F1
F2
F3
F4
F5

Long.
2.41
11.19
11.12
10.99
44.09

F1
F2
F3
F4
F5

Trans.
3.00
13.92
13.84
13.68
54.87

176.36
176.36
176.36
176.36
176.36

219.47
219.47
219.47
219.47
219.47

F1
F2
F3
F4
F5

6.53
21.17
19.36
16.84
112.46

F1
F2
F3
F4
F5

8.13
26.35
24.09
20.95
139.95

189.27
189.27
189.27
189.27
189.27

235.54
235.54
235.54
235.54
235.54

F1
F2
F3
F4
F5

6.42
22.56
20.95
19.47
119.88

F1
F2
F3
F4
F5

7.99
28.08
26.07
24.23
149.18

114.87
114.87
114.87
114.87
114.87

142.95
142.95
142.95
142.95
142.95

F1
F2
F3
F4
F5

3.67
23.88
23.26
18.73
45.32

F1
F2
F3
F4
F5

4.57
29.72
28.95
23.31
56.40

89.94
89.94
89.94
89.94

111.93
111.93
111.93
111.93

F1
F2
F3
F4

4.32
28.09
27.36
30.17

F1
F2
F3
F4

5.37
34.96
34.05
37.54

89.94
89.94
89.94
89.94

111.93
111.93
111.93
111.93

F1
F2
F3
F4

4.32
28.09
27.36
30.17

F1
F2
F3
F4

5.37
34.96
34.05
37.54

89.94
89.94
89.94
89.94

111.93
111.93
111.93
111.93

F1
F2
F3
F4

4.32
28.09
27.36
30.17

F1
F2
F3
F4

5.37
34.96
34.05
37.54

________________________________________________________________________________________
Attachment D Page 14 of 15

CALCULATION of PIPE RACK STRUCTURE #1 Doc. No.


(MR01-1 to MR01-10)
REV.
SENORO GAS DEVELOPMENT PROJECT

MR01-10

MR01-09

MR01-08

Elevation
(m)
6
8
11
15
18
Total
6
8
11
15
18
Total
6
8
11
15
18
Total

(*)
h
W
kN
m
34.97
6
170.60
8
120.86 11
73.30 15
114.43 18
514.162
85.79
6
193.23
8
134.27 11
183.19 15
554.05 18
1150.526
88.06
6
208.22
8
124.68 11
188.33 15
546.60 18
1155.896

W*h
kN.m
209.84
1,364.80
1,329.50
1,099.43
2,059.74
6,063.31
514.72
1,545.85
1,477.00
2,747.79
9,972.90
16,258.26
528.37
1,665.78
1,371.51
2,825.01
9,838.71
16,229.38

V long.

DATE.

V trans.

SNO-S-CC-05-001

A
17-APR-13

Force (kN)

kN
109.03
109.03
109.03
109.03
109.03

kN
135.68
135.68
135.68
135.68
135.68

Long.
F1
F2
F3
F4
F5

3.77
24.54
23.91
19.77
37.04

F1
F2
F3
F4
F5

Trans.
4.70
30.54
29.75
24.60
46.09

243.97
243.97
243.97
243.97
243.97

303.61
303.61
303.61
303.61
303.61

F1
F2
F3
F4
F5

7.72
23.20
22.16
41.23
149.65

F1
F2
F3
F4
F5

9.61
28.87
27.58
51.31
186.24

245.11
245.11
245.11
245.11
245.11

305.03
305.03
305.03
305.03
305.03

F1
F2
F3
F4
F5

7.98
25.16
20.71
42.67
148.59

F1
F2
F3
F4
F5

9.93
31.31
25.78
53.10
184.92

________________________________________________________________________________________
Attachment D Page 15 of 15