Escolar Documentos
Profissional Documentos
Cultura Documentos
INTRODUCTION
1.1 AN OVERVIEW OF R.S.E.B.
Rajasthan State Electricity Board started working form 1 July, 1957. When India
becomes independent its overall installed capacity was hardly 1900 mw. During first year plan
(1951-1956) this capacity was only 2300 MW. The contribution of Rajasthan state was negligible
during 1&2 year plans the emphases was on industrialization for that end it was considered to
make the system of the country reliable. Therefore Rajasthan state electricity board came into
existence in July 1957.
In 1957 RSEB (Rajasthan State Electric Board) is comes in to existence and it satisfactorily work
from 1 july1957 at that time energy level in Rajasthan is very low . The 1 st survey for energy
capacity in Rajasthan is held in 1989 at that time the total electric energy capacity of Rajasthan is
20116 MW. At that time the main aim of RSEB is to supply electricity to entire Rajasthan in the
most economical way.
And the RSEB comes under northern zone. During the 1 st survey there are few GSS in Rajasthan
and the Alwar GSS is one of them. The Alwar GSS is 2km away from the Railway station Alwar
and located near the Govt. polytechnic college Alwar.
The aim of RSEB is to supply electricity to entire Rajasthan state in the most economical way.
Government of Rajasthan on 19th July 2000, issued a gazette notification unbundling Rajasthan
State Electricity Board into Rajasthan Rajya Vidyut Utpadan Nigam Ltd (RRVUNL), the
generation Company; Rajasthan Rajya Vidyut Prasaran Nigam Ltd, (RRVPNL), the transmission
Company and the three regional distribution companies namely Jaipur Vidyut Vitran Nigam Ltd,
(JVVNL) Ajmer Vidyut Vitran Nigam Ltd (AVVNL) and Jodhpur Vidyut Vitran Nigam Ltd
(JVVNL).
Chapter-2
GRID SUBSTATION
1.1 AN OVERVIEW OF GSS.
A substation is an assembly of apparatus, which transform the characteristics of electrical energy
from one form to another say from one voltage level to another level. Hence a sub-station is an
intermediate link between the generating station and for economic transmission the voltage
should be high so it is necessary to step up the generated voltage for transmission and step down
transmitted voltage for distribution. For this purpose substations are installed.
Description:-
5. Disconnect switch
6. Circuit breaker
7. Current transformer
8. Lightning arrester
9. Main transformer
10. Control building
11. Security fence
12. Secondary power lines
220V FEEDER :
1. 220 KV Heerapura (Jaipur)
2. 220 KV MIA (Badarpur)
3. 220 KV Dousa
4. 220 KV Bhiwadi
5. 220 KV Kishangarh Bass
6. 220 KV Kotputli
132 KV FEEDERS:
1. 132 KV GSS Alwar
2. 132 KV LCAL
3. 132 KV Kishangarh Bass
4. 132 KV Mundawar
5. 132 KV M.I.A.
6. 132 KV Ramgarh
7. 132 KV Malakhera
8. 132 KV Bansur
In this substation there are two yards
a. 220KV Yard.
b. 132 KV YARD
There are four bus bars in 132 KV yard and five bus-bars in 220KV yard. The incoming feeders
are connected to bus-bar through circuit breakers, Isolators, lighting arrestors, currenttransformers etc the bus-bars are to have an arrangement of auxiliary bus So that when some
repairing work is to be done an main bus the whole load can be transferred to the auxiliary bus
6
through bus-coupler. In this 220KV GSS the incoming 220KV supply is stepped down to 132KV
with the help of t220KV GSS has a large layout consisting of 3 no. of 100MVA transformers,
2nos of 20/25MVA transformers and 1 X-mer of 40/50MVA and one X-mer of 16/20MVA
having voltage ratio respectively 220/132, 132/11Kv in addition to these transformers .
Transformers which is further supplied to different sub-station according to the load.
Chapter-3
8
Name of Equipment
Specification
Qty.
132 KV P T
Make C G E
Type V C M 138
Ratio- 132/110V
Sr No -615259
132 KV C T
Make BHEL
Ratio 480/240/120
Sr No -1227
132 KV Isolator
Make HIVELM
Volts-220
Sr
No
1052,1049,
1041,502,506,974,1074
132/11 KV
Transformer
Make NGEF
Capacity-16/20MVA
Ratio-132/11 KV
Sr No -28000,30346
Yr of manafacture-1978
Currentrating-87 SA,105 A
132/33 KV
Make EMCO
Transformer
Capacity-16/20MVA
Currentrating-10373/10856
6
132 KV,ABCB
Make HBB
33 KV Isolators
Make E M G
Capacity-400A
33 KV O C B
Make BHEL
Capacity-400 A
(ii)Type M E I 7377A
33 KV P T
Sr No HEO 700
10
33 KV C T
Ratio-3X33000X110V
10
(i)Make A E
Ratio-120/60/5/5
(iii)Make-Crompton
Ratio-240/120/5/5
11
33 Bank Capacitor
Capacity-800A,4190KVR
Type-HPRC 307 F
12
Sr no 69/21/7344051
Station Service
Make-E E
Transformer
Capacity-100KVA
Sr No -250/4
13
11 KV O C B
Make MEI
Type: ACI
Capacity-800A
Sr
No
-68/025,67/262,
68/024,67/261,67/264,
11
70/85,70/067
14
11 KV P T
Make A E
Ratio-11000/11 OV
Sr No -4124A
15
D C Rectifier
& Battery Charger
Sr No -74877381/21
Type-CP
Ratio-110/No
DC output 115-118V/10A
Make HIMD
Rectifier Standard
16
L T Panel
Make Jyoti
17
Compressors
Sr No -205/66
Type- LTLT-5
550 V-34,4 Wire
12
Type-30
Size-3X11/4X2 3/4
Sr no 8100212,81oo198
Table 3.1: Equipments used in 132KV GSS
The switch house building of the G.S.S. has following parts:1. Load Dispatch Unit (L.D.U.)
2. Power Line Carrier Communication (P.L.C.C.)
3. Battery Room
4. Control Room
5. Compressor Room
3.2. DIFFERENT EQUIPMENTS USED IN G.S.S.:
These equipments are used in the G.S.S. for successful Operational Breaker & a half scheme two
buses, they are:
1.
Lighting Arrester
2. CVT
3. Line isolator
4. Wave Trap
5. Circuit Breaker
6. Current Transformer
7. Bus Bars
8. Power Transformer
13
Chapter-4
LIGHTNING ARRESTER
4.1. Introduction
Lighting arrestor is a device, which protects the overhead lines and other electrical apparatus
vise, transformer from overhead voltages and lighting
produce negative charge on the overhead line by electrostatic induction then the negative charge
is however presented right under the cloud and portion of the line away from the cloud becomes
positively charged This charge on the line does not flow
Every instrument must be protected from the damage of lighting stroke. The three protection sin
a substation is essential:
Effective protection of equipment against direct strokes requires a shield to prevent lighting from
striking the electrical conductor together with adequate drainage facilities over insulated
structure
4.2. Description
The Thyrite Alugard lightning arrester consists of a stack of one or more units connected in
series depending on the voltage and the operating condition of the circuit three single pole
arresters are required for 3-phase installation. The arresters are single pole design and they are
suitable for indoor and out-door service.
Each arrester unit consists essentially of permanently sealed Porcelain housing equipped with
pressure relief and containing a number of thyrite value-element dieses and exclusive lumate
gaps shunted by Thyrite resistors metal fitting cemented of the housing provide means for
bolting arrester units into a stack. Each arrester unit is shipped assembled. No charging or testing
operation is required before placing them in service.
14
Installation Location:Install arrester electrically as close as possible to the apparatus being protected Line and ground
connections should be short and direct
Grounding:The arrester ground should be connected to the apparatus grounds and the main station ground
utilizing a reliable common ground network of low resistance. The efficient operation of the
lightning arrester requires permanent low resistance grounds. Station class arresters should be
provided with a ground of a value not exceeding five ohms.
Clearances: - These are given on the drawings. These are the maximum recommended. The term
clearance means the actual distance between any part of the arrester or disconnecting device at
line potential, and any object at ground potential or other phase potential.
Arrester voltage: The thvrite station-class arrester is designed to limit the surge voltages to a safe value by
discharging the surge current to ground; and to interrupt the small power frequency follow
current before the first current zero. The arrester rating is a define limit of its ability to interrupt
power follow current. It is important, therefore, to assure that the system power frequency
voltage from line to ground under any condition switching, fault, overvoltage, never exceeds the
arresters rating.
Fig.4.1
Lighting arrester
15
Lighting arrester:It consist of a isolator in series and connected in such a way that long isolator is in upward and
short isolator is in downward so that initially large potential up to earth is decreased to zero
An ideal arrestor must therefore have the following properties:
1. It should be able to drain the surge energy from the line in a minimum time
2. Should offer high resistance to the flow of power current
3. Performance of the arresters should be such that no system disturbances are introduced
by its operation
4. Should be always in perfect from to perform the function assigned to it
5. After allowing the surge to pass, it should close up so as not to permit power current to
flow to ground .
16
WORKING:Lightning, is a form of visible discharge of electricity between rain clouds or between a rain
cloud and the earth The electric discharge is seen in the form of a brilliant arc, sometimes
several kilometers long, stretching between the discharge points How thunderclouds become
charged is not fully understood, but most thunderclouds are negatively charged at the base
and positively charged at the top However formed, the negative charge at the base of the
cloud induces a positive charge on the earth beneath it, which acts as the second plate of a
huge capacitor. When the electrical potential between two clouds or between a cloud and the
earth reaches a sufficiently high value (about 10,000 V per cm or about 25,000 V per in), the
air becomes ionized along a narrow path and a lightning flash results Many meteorologists
believe that this is how a negative charge is carried to the ground and the total negative
charge of the surface of the Earth is maintained.The possibility of discharge is high on tall
trees and buildings rather than to ground Buildings are protected from lightning by metallic
lightning rods extending to the ground from a point above the highest part of the roof The
conductor has a pointed edge on one side and the other side is connected to a long thick
copper strip which runs down the building.The lower end of the strip is properly earthed
When lightning strikes it hits the rod and current flows down through the copper strip These
rods form a low-resistance path for the lightning discharge and prevent it from travelling
through the structure itself .
17
Chapter-5
POWER TRANSFORMER
5.1. Introduction:
A transformer is a device that transfers electrical energy from one circuit to another through
inductively coupled conductor -the transformer's coils A varying current in the first or primary
winding creates a varying magnetic flux in the transformer's core and thus a varying magnetic
field through the secondary winding This varying magnetic field induces a varying electromotive force, or voltage in the secondary winding This effect is called mutual induction.
If a load is connected to the secondary, an electric current will flow in the secondary winding and
electrical energy will be transferred from the primary circuit through the transformer to the load
In an ideal transformer, the induced voltage in the secondary winding (Vs) is in proportion to the
primary voltage (Vp), and is given by the ratio of the number of turns in the secondary (Ns) to the
number of turns in the primary (Np) as follows:
By appropriate selection of the ratio of turns, a transformer thus allows an alternating current
voltage to be "stepped up" by making Ns greater than Np, or "stepped down" by making Ns
less than Np
1) CORE
2) WINDING
3) OIL
Now we describe the three major parts of transformer
5.2. Core:Core is the main part of the transformer It is subjected to magnetic flux For efficient operation,
it is essential that the core of transformer must be constructed from laminated magnetic material
of low hysteresis loss and high permeability Transformers for use at power or audio frequencies
typically have cores made of high permeability silicon The steel has permeability many times
that of space and the core thus serves to greatly reduce the magnetizing current, and confine the
flux to a path which closely couples the windings Early transformer developers soon realized
that cores constructed from solid iron resulted in prohibitive eddy-current losses, and their
designs mitigated this effect with cores consisting of bundles of insulated iron wires Later
designs constructed the core by stacking layers of thin steel laminations, a principle that has
remained in use Each lamination is insulated from its neighbors by a thin non-conducting layer
of insulation The universal transformer equation indicates a minimum cross-sectional area for
the core to avoid saturation.
The effect of laminations is to confine eddy currents to highly
elliptical paths that enclose little flux, and so reduce their magnitude Thinner laminations reduce
losses, but are more laborious and expensive to construct Thin laminations are generally used on
high frequency transformers, with some types of very thin steel laminations able to operate up to
10 kHz.
A steel core's permanence means that it retains a static magnetic field when power is
removed When power is then reapplied, the residual field will cause a high inrush current until
the effect of the remaining magnetism is reduced, usually after a few cycles of the applied
alternating current Over current protection devices such as fuses must be selected to allow this
harmless inrush to passion transformers connected to long, overhead power transmission lines,
19
induced currents due to geomagnetic disturbances during solar storms can cause saturation of the
core and operation of transformer protection devices.
5.3. Winding:-
20
current rating
2.
3.
temperature rise
4.
impedance
5.
surge voltage
6.
transportation facilities
The winding used for core type transformers are of following types
1.
Cylindrical type
2.
Helical type
3.
4.
5.
6.
7.
It is found that the magnetic properties of transformer sheet steel vary in accordance with the
direction of the grain oriented by rolling, sheet are cut as far as possible along the grain which is
the direction in which the material has a higher permeability It must be made In building the
core, considerable pressure is used to minimize air gaps between the plates, which would
constitute avoiding loosed of area and might contribute to noisy operation The reduction of core
sectional area due to presence of insulating material is of the order of 10%.
The winding is layered
type and used either rectangular or round conductors. In a cylindrical winding. Using rectangular
conductor, the conductors are wound on the flat side with three-layer side parallel to the core
axis. The winding using rectangular conductors may be simultaneously wound from or more
parallel conductors.
22
23
24
The oil must not contain any impurity such as sulphur and its compounds. Sulphur when
presents, caused corrosion of metal parts and accelerates the production of degree.C
(6)SLUDGING:
This is the most important characteristic .Sludging means, the slow formation semi solid
hydrocarbons, sometime of an acidic nature. Which are deposited on winding and tank walls.
The formation of sludge is due to heat and oxidation .In its turns. It makes the whole transformer
hotter thus aggravating the trouble, which may proceed until the cooling ducts are blocked.
Experiences show that sludge is formed more quickly in the presence of bright cotter surface.
The chief remedy available is to use oil, which remains without sludge formation even it is
heated in the presence of oxygen, and to employ expansion chambers to restrict the contact of
hot oil with the surrounding air. Among the products of oxidation of transformer oil are volatile,
water soluble, organic acids and water. These in combination can attack and corrode iron and
other metals. The provision the breathers not only prevent the moisture produced by oxidation of
the oil.
Conservators are desirable to avoid the condensation of the water soluble acids on the under
surface of the tank lid from which acidic drop leads may fall back into the oil
NEW ISI FOR TRANSFORMERN OIL:Transformer oil has been a product of up gradation in our country. The first specification,
adopted by our country, was IS:335/1963.This was based on the British standard 148 through
B.S. has now undergone changes in 1984 I.S. has been changed 3-4 times during the last three
decades. The amendment made in July 1987 and feb.1988, make the transformer oil specification
most crudical in comparison to other World standard. The state electricity board now insists upon
this specification for transformer oil while accepting new transformers and tapping up running
transformer. This specification is to ensure proper quality and performance in the field.
The elaboration covers eleven points listed here under. These underline the importance of various
factors and their influence on the improvement of quality.
25
Central power research institute has conducted a lot of equipment on indigenous paraffin
commercial oil and imported hepatic oils. Indian Oil Corporation limited supplies special
based oil for experimentation. Oil produced from this base oil was tested, as per ASTM
aging test method no.D1934 for its electrical and chemical aging. This method appears
appendix in IS:335.The resistivity and power, factor after 96 hours of aging indicate the
parameters are fixed and only best quality oil pass through this test.
5) Dielectric strength:
The electric strength and water contains are specified as follows.
BDVWATER CONTENTSOIL ISI 35 30 KV
50PPM
26
50 kV
The transformer oil after filtration is expected to give minimum 60 kV breakdown voltage
(BDV)
6) Dissolved gases: The analysis of gases that dissolved in oil can help in obtaining
Valuable information about faults such as partial discharge, arcing, local overheating, and core
bolted failure ETC. A refined oil or an over refined oil will show the analysis harmful to the
performance of the equipment. A balance of aromatics should be maintained to absorb the
hydrogen etc. gases during operation.
7) Power factor
The power factor has been changed as under;
OLD
is335
0.005(MAX) 90C
NEW
IS335
0.005(MAX) 90C
An accelerated aging test under simulative conditions for 164 hours is fine indication of the life
of the iol. The sludge and acidity specified for transformer oil is revised IS:
OLD
NEW
IS335
IS335
ACIDITY
0.4(MAX)
SLUDGE
0.1(MAX)
ACIDITY
0.4(MAX)
SLUDGE
0.1(MAX)
MVA- 25/50
27
Vector symbol
Frequency
HV/LV-440
- 50 Hz
HV
LV
KV (No Load)
220
132
Amperes
262.4437.4
Phases
3-3
Type of cooling
Make
Sr No
- 24062
Type
- Star-Star(Y-Y)
HV
LV
28
The LV line end bushings are also mounted on the cover. The bushings are rated for 36 KV and
are of the solid porcelain type, confirming to be 3347 the line bushings have single gap arcing
horns with fixed gaps.
The HV line and neutral bushings are also mounted on the cover. The line end bushing is rated
for 145 kV system voltage, and are outdoor oil filled condenser type bushings confirming to
IEC- 137/IS: 2099.
The paper is wound directly ob to the metallic central tube. Single piece and brown glazed, are
pressed on to the central tube by means of springs in the head. The space between the insulating
core and the porcelain shells is filled with transformer oil. The oil expansion chamber, located in
the head is hermetically sealed slight glass in the head permits the oil level to checked.
The bushings are provided with adjustable gap arcing horns. The hv neutral is connected to an
outdoor type, solid porcelain bushing rated for 36kv peak system. The bushing confirms to be:
3347/part Vth/sec.2.But with arcing horns removed. The bushing is mounted directly on the tank
cover.
Two terminals from tertiary winding are brought out at the tank cover by means of 12/175 kV
solid porcelain type bushings confirming to IS:3347/part III, but without arcing horns. The two
terminals, when shorted, complete the delta connection of the tertiary. A link arrangement is
provided for this purpose. The terminals should be connected to earth under operating conditions.
Winding temperature indicator
Winding temperature indicator consists essentially of a current transformer and a thermal unit
comprising a heating coil and a thermometric device. The thermal unit, which is designed to have
a thermal performance similar to that of the win windings of the power transformer, is influenced
by two factors:
(1) The temperature of the surrounding oil, and
(2) The current flowing through the heater coil, which will raise the temperature of the unit
above that of the surrounding oil.
29
The CT secondary current is chosen to the max hot spot winding gradient occurring in either
HV or LV windings of the power transformer. Thus the thermal units capable of simulating the
hottest-spot temperature of the transformer windings under al conditions.
THERMAL DEVICE
The bulb of a capillary type dial thermometer is screwed into a blind pocket, which is fitted
inside the heating coil. This type of pocket enables the dial thermometer to be removed from the
transformer without having to lower the oil level. The heating coil with its blind type pocket
fitted inside is supported independently under the cover of the transformer; hence it is always in
the hottest oil. The dial thermometer is provided with one or more sets of contacts for alarm or
trip circuit and at time for controlling cooking equipment when forced cooling is called for.
OIL TEMPERATURE INDICATOR:An oil temperature indicator has been provided for measuring the transformer top oil
temperature. The heat sensitive device of the thermometer is placed in an oil pocket mounted at
the transformer cover; the thermometer has two adjustable mercury contacts and a maximum
reading pointer. The contact may be used to close circuit for alarm and tripping device. The
mercury switches are accessible by removing the top cover of the instrument and are adjustable
for different temperature ratings by location of the mount a repeater dial is for remote indication
of the oil temperature in the control room. The thermometer is housed in the marshalling box.
OIL SURGE REALY FOR OLTC GEAR:An oil- operated relay having one set of contracts is designed to trip the transformer between the
oil conservator. The relay is designed to trip the transformer on the occurrence of violent oil
surges arising out of any malfunction in the OLTC operation. The conservator for the OLTC gear
is separate from the main transformer conservator forms the conservator forms the conservator
for the OLTC .The terminals from the relay are wired to the terminal block located in the
marshalling box.
MARSHALLING BOX:-
30
The marshalling box is of sheet steel, weatherproof construction, mounted on the side of the
transformer. It is provided with a hinged door and pad lock, and housed the following instrument
and terminal block:(a) Win ding temperature indicator
(b) Oil temperature indicator
(c) Terminal block for alarm and contacts of bucholz relay
(d) Terminal block for oil legal alarm and contacts of Magnetic oil level Gauge.
(f) Heater with switch
(g) Magnetic oil leel gauge
The oil level gauge is mounted on the flate end of the con servitor. The indicator reads the oil
level inside the conservator and initiates an alarm by closing the mercury contacts swith when
the oil level is below the predetermined minimum. The contacts from the oil level gauge are
wired to the terminal block located in the marshalling box.
(h) Cooling equipment
The transformer having mixed cooling ONAF and ONAF is provided with detachable radiators
foxed to the tank wall through valves. The ONAF cooling equipment comprises of four 457 mm
dia fans, each blowing 3600 cu.ft. Of air per minute on the radiator element directed in such a
way that the no longer effective they turn pink. At the bottom of the breather a cup containing the
transformer oil is screwed this oil acts as a seal, preventing the crystals from absorbing moisture
except when breathing is taking place.
(g) Cooling plant
Oil cooling is normally achieved by heat exchange to the surrounding air. Sometimes a water
jacket acts as the secondary cooling medium. Fans may be mounted directly onto the radiators
and it is customary to use a number of separate fans rather than one or two large fans. Oil pumps
for OFAF cooling are mounted in the return pipe at the bottom of the radiators. The motors
driving the pumps often use the transformer oil as their cooling medium.
31
With ODAF cooling, the oil-to-air coolers tend to be compact and use relatively large fan
blowers. With this arrangement the cooling effectiveness is very dependent on proper operation
of the fans and oil pumps since the small amount of
Cooling surface area gives relatively poor cooling by natural convection alone. Water cooling
(ODWF) has similar characteristics to the ODAF cooling described above and is sometimes
found in power station situations where ample and well-maintained supplies of cooling water are
available. Cooling effectiveness is dependent upon the flow of cooling water and therefore on
proper operation of the water pumps. Natural cooling with the out-of-service water pumps is
very limited. Operational experience has not always been good, with corrosion and leakage
problems, and the complexity of water pumps, pipes, valves and flow monitoring equipment. The
ODAF arrangement is probably favorable as a replacement for the ODWF designs. Double wall
cooler pipes give added protection against water leakage. The inner tube carries the water and
any leakage into the outer tube is detected and causes an alarm. This more secure arrangement is
at the expense of slightly reduced heat transfer for a given pipe size. Normal practice with
cooling plant is to duplicate systems so that a failure of one need not directly affect operation of
the transformer. Two separate radiators or radiator banks and duplicate oil pumps may be
specified. In the larger ODAF cooling designs there may be four independent unit coolers giving
a degree of redundancy. The transformer may be rated for full output with three out of the four
coolers in service. Dry type transformers will normally be naturally air-cooled (classification
AN) or incorporate fans (classification AF).
5.6 TAPPINGS AND TAP CHANGER
The transformer has an on load tap changer to cater for a variation of +5% to -15% in the HV
voltage in 14 equal steps of 1.43% each for a constant power output. The tapping from the HV
tapping winding are connected to a 15 position f66KV Crompton greaves make high-speed
resistor transition on load tap-changer. The tap-changer may be either manually operated or
motor driven.
The motor driving mechanism is also described in the leaflet and is arranged for the following
types of control.
Tap changer is used to change the HV voltage. We use tap changer in HV side only because in
HV side current is less hence it is easy to handle lower amount of current. Tap changers are of
two types.
33
34
5.1.2 Application:
1) Capacitive voltage transformer can be effectively as potential sources for measuring, metering
protection, carrier communication and other vital functions of an electrical n/w
2) Capacitive voltage transformers are constructed
magnetic unit transformers this voltage, both in magnitude and to convenient levels suitable for
measuring phase metering, protection etc. all W.S.I.capacitor units has metallic bellows to
compensate the volumetric expansion of oil inside the porcelain. In the multiunit stack, all the
potential point are electrically tied and suitably shielded to overcome the effects of corona, RIV
etc.
2) Capacitive voltage transformers are available for system voltage of 33kv to 420kv.
35
22/ 3KV
500VA
Output maximum:
1000VA at 50C
Operating Voltage:
400/ 3KV
420/ 3KVmax
Voltage Factor:
15sec
30sec
36
Potential Transformer is designed for monitoring single-phase and three-phase power line voltages in power
metering applications.
A current
transformer also isolates the measuring instruments from what may be very high.
Current transformer is a instrument transformer which is mainly used for measuring currents where very high
currents are flowing.
According to the construction of the current transformer the primary
winding of transformer is in series with high current carrying line & measuring instrument is
connected to the secondary.
38
39
directly located under the main cover in the oil. On the larger X-mers the various connections
may be brought up to terminals in the main the cover for external linkage.
Rated frequency :
50 Hz
420 KV
Weight of oil :
750 Kg
Total weight :
2450 Kg
BIL :
630/1425 KV
Table 5.3.1 Rating of CT used in GSS
CURRENT RATIO
2000-1000/1
2000-1000-500/1
40
Turns Ratio
2000-1000
2000-1000-500
Core No.
1&2
4&5
Output(VA)
40
Accuracy Class
P.s.
0.5
p.s.
ISF/ALF
10
Chapter-6
PROTECTION OF TRANSFORMERS
6.1 MERZ-PRICE PROTECTION RELAY
Merz-Price voltage balance system for the protection of 3-phse line. Identical current
transformers are placed in each phase at both ends of the line. The pair of CTs in each line is
connected in series with a relay in such a way that under normal conditions, their secondary
voltages are equal and in opposition i.e. they balance each other.
Under healthy conditions, current
entering the line at one-end is equal to that leaving it at the other end. Therefore equal and
opposite voltages are induced in the secondary of the CTs at the two ends of the line. The result
is that no current flows through the relays. When a fault occurs at point F on the line as shown in
Fig 6. It will cause a greater current to flow through CT 1 than through CT2. Consequently, their
secondary voltages become unequal and circulating current flows through the pilot wires and
relays. The circuit breakers at both ends of the line will trip out and the faulty line will be
isolated.
41
Emulsifier system
This fire protection system is used to protect the transformers in the yard by extinguish
the fire. This system consists of water tanks. Jacky pumps, D.G. sets, air compressor and two
pipelines having different colors one (red) is used to circulate the water and other (yellow) is for
air. This network of pipelines covered all the area of transformer jockey pumps are used to
maintain the pressure of water at 7 kg/cm2.
A quarterized solenoid plastic valve is used with yellow pipeline near the base of
transformer. On being fired around the transformer this plastic valve contains alcohol, which
expands and due to this valve will burst. A dilute valve is erected near the transformer, which
consists of two gates these gates are blocked due to the pressure of air. A water line is connected
to this valve whenever the air releases and pressure goes down the gate is opened and a stream of
42
water having 7Kg-cm2 pressure is flow through the pipe and a shower of water is started around
the transformer to check the air to come inside and hence this way. It extinguishes the fire.
1.
Hydrant system
This protection system is used to protect the yard and office dept from fire. A network of
Halon system
2)
3)
Miscellaneous system
Chapter-7
RELAY
7.1. Introduction:
A relay is an electrically operated switch Current flowing through the coil of the relay creates a
magnetic field which attracts a lever and changes the switch contacts The coil current can be on
or off so relays have two switch positions and they are double throw (changeover) switches.
Relays
allow one circuit to switch a second circuit which can be completely separate from the first For
example a low voltage battery circuit can use a relay to switch a 230V AC mains circuit There is
no electrical connection inside the relay between the two circuits, the link is magnetic and
mechanical.
The coil of a relay passes a relatively large current, typically 30mA for a 12V relay,
but it can be as much as 100mA for relays designed to operate from lower voltages Most ICs
(chips) cannot provide this current and a transistor is usually used to amplify the small IC current
43
to the larger value required for the relay coil The maximum output current for the popular 555
timer IC is 200mA so these devices can supply relay coils directly without amplification.
Relays
are usually SPDT or DPDT but they can have many more sets of switch contacts, for example
relays with 4 sets of changeover contacts are readily available For further information about
switch contacts and the terms used to describe them please see the page on switches.
7.2. Types of Relays:
These are called normally opened, normally closed in GSS control room there is panel in which
the relays are set and there are many types of relays
1. Over voltage relays
2. Over current relays
3. I D M T fault relay
4. Earth fault relay
5. Bucholzs relay
6. Differential relay
7.2.1 OVER VOLTAGE RELAY:
This protection is required to avoid damage of system in case line becomes open circuited at one
end These fault would trip the local circuit breaker thus block the local and remote ends This
relay is operated i e , energized by CVT connected to lines.
7.2.2 OVER CURRENT RELAY:
This relay has the upper electromagnet of non-directional relay connected in series with lower
non-directional electromagnet When the fault current flow through relay current coil which
produces flux in lower magnet of directional element Thus the directional relay has the winding
over the electromagnets of non-directional element and produces a flux in lower magnet and thus
over current operates.
44
ii.
iii.
Static type
7.3 BUCHHOLZS RELAY: - It is the protective device of the transformer When any fault
occurs in the transformer then it indicates about fault and we disconnect the transformer from the
circuit It is used in the power transformer It is connected between the tank and conservator It
has two floats on which two mercury switch are attached One float is used for the bell indication
and other float is used for the tripping In the normal position the relay is filled with the oil and
contacts of the mercury switch are opened When the earth fault occurs in the transformer then it
45
increases the temperature of oil and oil flows into the conservator through relay On the way it
makes the contacts of the tripping circuit short So in the we can say that this relay works as
circuit breaker
Chapter-8
INSULATORS
In order to avoid current leakage to the Earth, through the supporting structure provide to the
conductor of overhead transmission lines, insulators are used. The conductors are secured to the
supporting structures by means of insulating feature, which do not allow current to flow through
these support and hence finally to the earth . Bus support insulators are porcelain or fiberglass
insulators that serve to the bus bar switches and other support structures and to prevent leakage
current from flowing through the structure or to ground. These insulators are similar in function
to other insulator used in substations and transmission poles and towers.
An Insulator should have following characteristic:1. High Insulation resistance.
2. High mechanical strength
46
47
EARTHING
Earthing is the provision of a surface under the substation, which has a uniform potential as
nearly as zero or equal to Absolute Earth potential. The provision of an earthing system for an
electric system is necessary by the following reason.
48
1. In the event of over voltage on the system due to lighting discharge or other system fault.
These parts of equipment which are normally dead as for as voltage, are concerned do not attain
dangerously high potential.
2. In a three phase, circuit the neutral of the system is earthed in order to stabilize the potential of
circuit with respect to earth
The resistance of earthing system is depending on shape and material of earth electrode used.
The earthing is of two principal types:1. Neutral Earthing
2. equipment Body Earthing
Neutral Earthing:Neutral Earthing also known as System Neutral Earthing (or Grounding) means connecting the
neutral point i.e. the star point of generator, transformer etc. to earth. In rotating machines,
generator, transformer circuit etc., the neutral point is always connected to earth either directly or
through a reactance. The neutral point is usually available at every voltage level from generator
or transformer neutral. If neutral point is not available, then the most common method used is
using a Zigzag transformer. Such a transformer has no secondary. Each phase of primary has two
equal parts. There are 3 limbs and each limb has two winding, providing flux density under
normal condition. Since the fluxes are opposite, the transformer takes very small magnetizing
current under normal conditions. During fault, the circuit is primary side,
Which provides very less impedance to the current? The grounding transformers are short time
rating. Their size is almost one tenth as compared to power transformer.
Electrical Earthing:Electrical Earthing is different from neutral earthing. During fault condition, the metallic parts of
an electrical installation which do not carry current under normal conditions, may attain high
potential with respect to ground. As human body can tolerate only I=0.165A/T current for a
given time t so to ensure safety we connect such metallic parts to earth by means of Earthing
49
system ,which comprises of electrical conductor to send fault current to earth. The conductor
used is generally in the form of rods, plates, pipes etc.
Earthing system ensures safety in following ways :1. The potential of earthen body does not reach dangerously high value about earth, since it
is connected to earth.
2.
Earth fault current flows through earthing and readily causes the operation of fuse or an
earth relay.
Apparatus
Path to be connected
1.
Base plate
2.
3.
Isolator
4.
Potential transformer
Transformer tank LV
5.
Power transformer
Core tank
6. Improved service reliability due to limitation of arcing ground and improved of unnecessary
fringing of CB.
At GSS the neutral point of power transformer is connected solidly to earth generally the earth
connection are provided which leads reliability.
Chapter-10
networking (PLN), is a system for carrying data on a conductor also used for electric power
transmission. Broadband over Power Lines (BPL) uses PLC by sending and receiving
information bearing signals over power lines.
Electrical power is transmitted over high voltage transmission lines, distributed over medium
voltage, and used inside buildings at lower voltages. Power line communications can be applied
at each stage. Most PLC technologies limit themselves to one set of wires (for example, premises
wiring), but some can cross between two levels (for example, both the distribution network and
premises wiring). Typically the transformer prevents propagating the signal so multiple PLC
technologies are bridged to form very large networks.
All power line communications systems operate by impressing a modulated carrier signal on the
wiring system. Different types of power line communications use different frequency bands,
depending on the signal transmission characteristics of the power wiring used. Since the power
wiring system was originally intended for transmission of AC power, in conventional use, the
power wire circuits have only a limited ability to carry higher frequencies. The propagation
problem is a limiting factor for each type of power line communications. A new discovery called
E-Line that allows a single power conductor on an overhead power line to operate as a
waveguide to provide low attenuation propagation of RF through microwave energy lines while
providing information rate of multiple Gbps is an exception to this limitation.
Data rates over a power line communication system vary widely. Low-frequency (about 100200 k Hz) carriers impressed on high-voltage transmission lines may carry one or two analog
voice circuits, or telemetry and control circuits with an equivalent data rate of a few hundred bits
per second; however, these circuits may be many miles long. Higher data rates generally imply
shorter ranges; a local area network operating at millions of bits per second may only cover one
floor of an office building, but eliminates installation of dedicated network cabling.
damaging the carrier equipment. Once the signal is on the power line it must be directed in the
proper direction in order for it to be received at the remote line terminal.
53
designed capacitors connected in parallel with the choke coils so as to resonate at carrier
frequencies and thus offers even high impedance to the flow of RF currents.
10.4.2. Transmitter:
The transmitter consists of an oscillator and a amplifier. The oscillator generates a frequency
signal within 50 to 500 HZ frequency bands the transmitter is provided so that it modulates the
carrier with protective signal. The modulation process usually involves taking one half cycle of
50 HZ signal and using this to create block to carrier.
10.4.3. Receivers:55
The receivers usually consist of an alternate matching transformer band pass filter and amplifier
detector.
The amplifier detector converts a small incoming signal in to a signal capable of operating a
relatively intensive carrier receiver relay. The transmitter and receiver at the two ends of
protected each corresponds to local as far as transmitting.
The carrier energy on the transmission line must be directed toward the remote line terminal and
not toward the station bus, and it must be isolated from bus impedance variations. This task is
performed by the line trap. The line trap is usually a form of a parallel resonant circuit which is
tuned to the carrier energy frequency. A parallel resonant circuit has high impedance at its tuned
frequency, and it then causes most of the carrier energy to flow toward the remote line terminal.
The coil of the line trap provides a low impedance path for the flow of the power frequency
energy. Since the power flow is rather large at times, the coil used in a line trap must be large in
terms of physical size.
56
57
No separate wires are needed for communication purposes as the power lines themselves
carry power as well as the communication signals. Hence the cost of constructing
separate telephone lines is saved.
When compared with ordinary lines the power lines have appreciably higher mechanical
strength. They would normally remain unaffected under the condition which might
seriously damage telephone lines.
Power lines usually provide the shortest route between the power stations.
4 Power lines have large cross-sectional area resulting in very low resisntanc3 per unit
length. Consequently the carrier signal suffers lesser attenuation than when travel on
usual telephone lines of equal lengths.
5. Power lines are well insulated to provide negligible leakage between conductors and
ground even in adverse weather conditions.
6. Largest spacing between conductors reduces capacitance which results in smaller
attenuation at high frequencies. The large spacing also reduces the cross talk to a considerable
extent.
DISADVANTAGES
1
Proper care has to be taken to guard carrier equipment and persons using them against
high voltage and currents on the line.
Reflections are produced on spur lines connected to high voltage lines. This increases
attenuation and create other problems.
High voltage lines have transformer connections, which attenuate carrier currents. Substation equipments adversely affect the carrier currents.
Noise introduced by power lines is much more than in case of telephone lines. This due to
the noise generated by discharge across insulators, corona and switching processes.
59
Interference: Interference from nearby systems can cause signal degradation as the
modem may not be able to determine a specific frequency among many signals in the
same bandwidth.
Signal Attenuation by Active Devices: Devices such as relays, transistors, and rectifiers
create noise in their respective systems, increasing the likelihood of signal degradation.
Chapter-11
CONTROL ROOM
60
To remote control of power switch gear requires the provision of suitable control plates located
at a suitable point remote from immediate vicinity of CBs and other equipments.
At "GSS ALWAR" the separate control room provided for remote protection of 220KV switch
yards transformer incoming feeder, outing feeders. Bus bar has their own control plant in their
control rooms. The control panel carrier the appropriate relays. Necessary meters indicating lamp
control switches and fuses. There are meters for reading purpose. A circuit concerning the panel
is shown on the panel with standard co lour.
On each panel a control switch is provided for remote operation of circuit breaker. There are two
indicators which show that weather circuit breaker is closed or open. A control switch for each
insulator is also provided. The position indicator of isolator is also done with the help of single
lamp and indicator. The color of signal lamps are as follows:RED:- For circuit breaker or isolator is close option
Green - For circuit breaker is in open position.
Amber - Indicates abnormal condition requiring action.
In addition to used indication an alarm is also providing for indicating abnormal condition when
any protective relay or tripping relay has operated. Its constants energies on auxiliary alarm
.Relay which on operation completes the alarm belt circuit.
Synchronizing:There is a hinged Synchronizing panel mounted at the end of control panel .Before coupling any
incoming feeders to the bus-bar. It just be Synchronized with switches. When the synchronous
copy shows zero we close the circuit breaker.
Synchronoscope is used to determine the correct instant of closing the switch which connect the
new supply to bus bar. The correct instant of synchronizing when bus bar incoming voltage.
1. Are in phase
2. Are equal in magnitude
61
ENERGY METER: - These are fitted on different panel to record transmitted energy and
recorded in energy hours .For this purpose MWH meter have been provided.
62
WATT METER: - This is mounted on each feeder panel to record import or export power.
FREQUENCY POWER: - Provided to each feeder to measure frequency which analog or
digital.
LT METER:-Provided on each panel or the purpose of indication of voltage.
AMMETER:-These are used to indication the line current.
MVAR METER:-Provided for indicating power factor of import and export.
MAXIMUM INDICATOR DEMAND:-
Chief requirement of these indicators to record the minimum power factor taken by feeder during
a particular period. This record the average power successive predetermined period.
Chapter-12
BATTERY ROOM
To remote control of power switch gear requires the provision of suitable control plates located at
a suitable point remote from immediate vicinity of CBs and other equipments.
There is a battery room which has 55 batteries of 2 volt each for 132KV section and 110 batteries
for 220KV section. Therefore D.C. power available is for functioning of the control panels. A
battery charger to charge the battery.
1. Various parts of lead acid batteries:1. Plates
2. Separators
3. Electrolyte
4. Container
5. Terminal port
6. Vent plugs
64
peroxide, whereas the ve plates will converted to spongy lead. Also in a fully charged battery
the electrolyte specific gravity will be at its highest venue or 1.2 and its terminal voltage will be
24 volts
65
Chapter-13
CAPACITOR BANK
Capacitor banks are used to improve the quality of the electrical supply and the efficient
operation of the power system. Studies show that a flat voltage profile on the system can
significantly reduce line losses. Capacitor banks are relatively inexpensive and can be easily
installed anywhere on the network.
66
1 unit of 4 MVAR
67
CONCLUSION
The training at grid substation was very helpful. It has improved my theoretical concepts of electrical
power transmission and distribution.
Protection of various apparatus was a great thing. Maintenance of transformer, circuit breaker, isolator,
insulator, bus bar etc was observable.
68
I had a chance to see the remote control of the equipments from control room itself, which was very
interesting.
References
1.
2.
3.
4.
5.
6.
7.
70