Você está na página 1de 5

Date

2/1/2013

2/1/2013

2/1/2013

Water Proprietary and Confidential


WTR-FM-EN-1841, Rev. 1, 2/1/2013

Page 1 of 5

CONTROLLED when read online


Printed copy is UNCONTROLLED

Revision
Edited calculation for effective depth "d" in cells K78 and M78 to increase clear distance between
rebar layers from 2.0 inches to 2.5 inches. Also edited language in J78 description. This also
required an edit to H130 and H131 where the skin reinforcing spacing is calculated.
Edited cells K83 and M83 so that the tension controlled outcome is set to "NO" if the rebar grade is
above 60 ksi. The ACI 318 code is unclear about the tension control limit for bars above Grade 60.
All bars 60 ksi and below are valid for this template. Edited language in J78 description. Also
edited J43 and J53 to give no value for Et if rebar is higher than 60 ksi yield.
Edited cells K109, M109, K110, M110 so that Sd will not give an error if both the service and
ultimate moments are entered as zero. Likewise for cells F122, F123 related to service and
ultimate shears. Added a user note in cell P20 to explain what happens if a "DIV/0!" error appears.
If ultimate is entered with a value, but a zero is entered for service, this will produce the "DIV!0!"
error.

Water Proprietary and Confidential


WTR-FM-EN-1841, Rev. 1, 2/1/2013

Page 2 of 5

CONTROLLED when read online


Printed copy is UNCONTROLLED

South Hartford
Grit & Screening building
176810
Grit & Screening building
Beam B1 & B2

Owner
Plant
Project No.
Title

BLACK & VEATCH

Computed By
Unit

Date

File No.

Verified By

AKJ
10/19/15
NV

Date
Page

of

Concrete Beam Design per ACI 318-05, 318-08, 318-11, 350-06


INPUTS
Reinf Yield Strength (fy) =
Concrete Strength (f'c) =

60.0
4.0
2.0
2.0
24.0
48.0

Bottom Cover =
Top Cover =
Beam width (b) =
Beam depth (h) =

Service Positive Moment (Ms +) =


Service Negative Moment (Ms -) =
Factored Positive Moment (Mu +) =
Factored Negative Moment (Mu -) =
Service Shear (Vs) =
Factored Shear (Vu) =

ksi
ksi
in
in
in
in

Bottom Reinforcing =
Top Reinforcing =
Stirrup Reinforcing =
Skin (Side Face) Reinforcing =

Design Code/Exposure = ACI 318

6
6
#4
2

213 k-ft
125 k-ft
275 k-ft (not including the Sd factor)
160 k-ft (not including the Sd factor)
71.6 k
92.6 k (not including the Sd factor)
-#6
Two Layers
-#5
Two Layers
@ 12 in Single Stirrup
- # 5 EF

DESIGN SKETCH
Use 24 in. x 48 in. beam with:
6 - # 6 BOTTOM REINF,
6 - # 5 TOP REINF,
# 4 @ 12" SINGLE STIRRUPS
2 - # 5 EA FACE SIDE REINF

6 - # 5 LAYERED
# 4 @ 12 SINGLE STIRRUPS
48 "

2 - # 5 EACH FACE

(Graphic is schematic only and does


not reflect actual number of bars)

6 - # 6 LAYERED
24 "

BOTTOM REINFORCEMENT SUMMARY


As + (prov'd.) =
Moment capacity
Tension controlled section
Minimum reinforcing
Reinforcing clear spacing
Reinforcing c-c spacing (ACI 318)

Mn+ =
T actual =
(req'd.) =
actual =
actual =

504
0.056
0.0018
8.38
9.13

2.64 in^2

6 - # 6 LAYERED

Mu + =
k-ft
>=

minimum
=
>=
T
(w/o Sd factor)
<

275 k-ft
0.005
prov'd.) =

in
in

2.50 in
20.22 in

>=
<=

min =
max =

0.0025

O.K.
O.K.
O.K.
O.K.
O.K.

0.0018

O.K.
O.K.
O.K.
O.K.
O.K.

TOP REINFORCEMENT SUMMARY


As - (prov'd.) =
Moment capacity
Tension controlled section
Minimum reinforcing
Reinforcing clear spacing
Reinforcing c-c spacing (ACI 318)

Mn- =
T actual =
(req'd.) =
actual =
actual =

359
0.081
0.0010
8.56
9.19

1.86 in^2

6 - # 5 LAYERED

Mu - =
k-ft
>=

minimum
=
>=
T
(w/o Sd factor)
<

160 k-ft
0.005
prov'd.) =

in
in

2.50 in
24.64 in

>=
<=

min =
max =

SHEAR SUMMARY
Av =
Vn =
Av (min.) =
s max =

Shear capacity
Minimum stirrup area
Maximum stirrup spacing

0.40 in^2

164.0 k
0.24 in^2
21.7 in

# 4 @ 12 SINGLE STIRRUPS

>=

Vu =

>=

Av =
s=

<

92.6 k
0.40 in^2
12 in

O.K.
O.K.
O.K.

SKIN (SIDE FACE) REINFORCEMENT SUMMARY


Beam height
Maximum spacing

Water Proprietary and Confidential


WTR-FM-EN-1841, 2/1/2013

h=
actual =

48 in
12.0 in

Skin reinforcement required.


max =
20.2 in

Page 3 of 5

O.K.

CONTROLLED when read online


Printed copy is UNCONTROLLED

Owner
Plant
Project No.
Title

BLACK & VEATCH

South Hartford
Grit & Screening building
176810
Grit & Screening building
Beam B1 & B2

Computed By
Unit

Date

File No.

Verified By

AKJ
10/19/15
NV

Date
Page

of

Concrete Beam Design per ACI 318-05, 318-08, 318-11, 350-06


CALCULATION DETAILS
Modular Ratio (n) = 29,000,000/57,000*(f'c)1/2 =

Flexure

Bot
8.04
0.85

Top
8.04
0.85

Effective Depth (d) for single layer reinf = h - cover - stirrup dia - 1/2 bar dia =
in
Effective Depth (d) for double layer reinf = h - cover - stirrup dia - bar dia - 2.5"/2 =
43.42 in
Distance from compression face to centroid of extreme layer of tension steel, d t =
45.09 in
As (prov'd.) =
2.64 in^2
c = Asfy / (0.85bf'c1) =
2.28 in
T = 0.003*(dt-c)/c =
0.056
Tension controlled section for fy <= 60 ksi, (T >= 0.005)
YES
(calc) = (0.85 f'c/fy) * (1-(sqrt(1-((2*Mu*12/(.85*.9*b*d^2*f'c)))) = 0.0014
(min) =
3*(f'c)1/2/ fy = 0.0032
and
200/(fy*1000) = 0.0033
and
1.33*(calc) = 0.0018
controlling case, (req'd) = 0.00182
As (req'd) =(req'd)*b*d =
1.89 in^2
(Prov'd.) = As (Prov'd.)/(b*d) = 0.0025
Mn = 0.9*As*fy*(d-0.5*(As*fy/0.85*f'c*b))*(1/12) =
504.3 k-ft
k = ((*n)2+2**n)1/2-*n =
0.183
j = 1-k/3 =
0.939
fs = Ms/(As*j*d) =
24 ksi
Per ACI 318, fs need not be greater than 2/3*fy =
40 ksi
Per ACI 318, maximum spacing, s, = 15*(40/fs) - 2.5*cov =
20.3 in
Per ACI 318, maximum spacing, s, = 12*(40/fs) =
20.2 in
Actual bar c-c spacing, s =
9.13 in
Bar horizontal clear spacing =
8.38 in
Larger of 2.5 inches or 3*db =
2.50 in
Horizontal clear spacing not less than 2.5 inches or 3*db
YES
Bar horizontal c-c spacing adequate to meet ACI 318
YES
ACI 350, strain gradient amplification factor =
ACI 350, fs max for normal environmental exposure =
ksi
ACI 350, fs max for severe environmental exposure =
ksi
ACI 350, fs max need not exceed
ksi
ACI 350, fs max need not be less than
ksi
ACI 350 controlling case, fs max =
ksi
ACI 350 = factored moment / unfactored moment =
ACI 350 Environmental Durability Factor, Sd, = fy/fs (>= 1.0) =

43.57
45.16
1.86
1.61
0.081
YES
0.0008
0.0032
0.0033
0.0010
0.00105
1.09
0.0018
358.9
0.155
0.948
19
40
25.8
24.6
9.19
8.56
2.50
YES
YES

in
in
in
in^2
in

in^2
k-ft

ksi
ksi
in
in
in
in
in

ksi
ksi
ksi
ksi
ksi

(NA)
(NA)
(NA)
(NA)
(NA)
(NA)
(NA)
(NA)

Shear
Av =

#4 @ 12 in. Single Stirrups =


Vc = 0.75*2*(f'c)1/2*b*d =
If Vu > 0.5* Vc, Av (min.) = 0.75*(f'c)1/2*b*s / fy =
if Vu > 0.5 * Vc, Av (min.) = 50*b*s / fy =
Vs = 0.75*Av*fys*d / s =
Vs (max) = 0.75*8*(f'c)1/2*b*d =
ACI 318Vn = Vc + Vs =
ACI 350, fs for normal environmental exposure =
ACI 350, fs for severe environmental exposure =
ACI 350, = Vu / Vs =
ACI 350 Env Dur Factor, Sd, = fy/fs (>= 1.0) =
ACI 350Vn = Vc + (Vs / Sd)=

0.40
98.9
0.23
0.24
65.1
395.5
164.0

in^2
k
in^2
in^2
k
k
k
ksi
ksi

ACI 318, Vs (req'd) = (Vu-Vc)/ =


ACI 350, Vs (req'd) = Sd(Vu-Vc)/ =
Maximum stirrup spacings:
When Vu < = 0.5 * Vc =
When Vu > 0.5 * Vc , d/2 =
When Vs (req'd) > 4*(f'c)1/2*b*d, d/4 =

(NA)
(NA)
(NA)
(NA)
(NA)

ACI 350, max =


Controlling case, max =

0.0 k
k

(NA)
(NA)

21.7 in
in
in
21.7 in

(NA)
(NA)

Skin (Side Face) Reinforcement


h=
Per ACI 318, max spacing equals beam steel s max =
Per ACI 350, max spacing equals d/6, 12 inches, or 1000Ab/(d-30), ssk =
Distance from bottom face to highest bottom tension bar =
Distance from top face to lowest top tension bar =
Water Proprietary and Confidential
WTR-FM-EN-1841, 2/1/2013

Page 4 of 5

48 in
20.2 in
in
6.1 in
5.9 in

Skin reinforcement required


(NA)

CONTROLLED when read online


Printed copy is UNCONTROLLED

Owner
Plant
Project No.
Title

BLACK & VEATCH

South Hartford
Grit & Screening building
176810
Grit & Screening building
Beam B1 & B2

Computed By
Unit

Date

File No.

Verified By

AKJ
10/19/15
NV

Date
Page

of

Concrete Beam Design per ACI 318-05, 318-08, 318-11, 350-06


Skin reinforcement bars provided =
Actual skin reinforcement spacing =

Water Proprietary and Confidential


WTR-FM-EN-1841, 2/1/2013

Page 5 of 5

2 per face
12.0 in

O.K.
O.K.

CONTROLLED when read online


Printed copy is UNCONTROLLED