INPUT PARAMETERS
Fuel Spill Volume (V)
Fuel Spill Area or Dike Area (Adike)
Mass Burning Rate of Fuel (m")
Effective Heat of Combustion of Fuel (Hc,eff)
5.00 gallons
0.0189 m3
9.00 ft2
0.051 kg/m2-sec
0.836 m2
43500 kJ/kg
760 kg/m3
3.6 m-1
Fuel Density ()
Empirical Constant (k)
Ambient Air Temperature (Ta)
77.00 F
25.00 C
298.00 K
9.81 m/sec2
1.18 kg/m3
Calculate
Note: Air density will automatically correct with Ambient Air Temperature (Ta) Input
Density
m" (kg/m2-sec)
(kg/m3)
km
Methanol
0.017
20,000
796
100
Ethanol
Butane
Benzene
Hexane
Heptane
Xylene
Acetone
Dioxane
Diethy Ether
Benzine
Gasoline
Kerosine
Diesel
JP-4
JP-5
Transformer Oil, Hydrocarbon
561 Silicon Transformer Fluid
Fuel Oil, Heavy
Crude Oil
Lube Oil
User Specified Value
0.015
0.078
0.085
0.074
0.101
0.09
0.041
0.018
0.085
0.048
0.055
0.039
0.045
0.051
0.054
0.039
0.005
0.035
0.0335
0.039
Enter Value
26,800
45,700
40,100
44,700
44,600
40,800
25,800
26,200
34,200
44,700
43,700
43,200
44,400
43,500
43,000
46,000
28,100
39,700
42,600
46,000
Enter Value
794
573
874
650
675
870
791
1035
714
740
740
820
918
760
810
760
960
970
855
760
Enter Value
100
2.7
2.7
1.9
1.1
1.4
1.9
5.4
0.7
3.6
2.1
3.5
2.1
3.6
1.6
0.7
100
1.7
2.8
0.7
Enter Value
Fuel
Reference: SFPE Handbook of Fire Protection Engineering, 3rd Edition, 2002, Page 3-26.
D = (4Adike/)
D=
1.032
(Liquids with relatively high flash point, like transformer oil, require
localized heating to achieve ignition)
1809.75 kW
1715.31 Btu/sec
Answer
tb = 4V / D2
Where
337.33 sec
5.62 minutes
Note that a liquid pool fire with a given amount of fuel can burn for long periods of time over small area or for
Answer
Answer
1
Hf =
3.67 m
Answer
12.04 ft
METHOD OF THOMAS
Reference: SFPE Handbook of Fire Protection Engineering, 2nd Edition, 1995, Page 3-204.
Hf = 42 D (m"a (g D))0.61
Where
3.14 m
Answer
10.30 ft
ESTIMATING POOL FIRE RESULTS FOR RANDOM SIZE SPILLS USING INPUT PARAMETERS
Area (ft2)
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
20
25
50
75
100
Area (m2)
0.09
0.19
0.28
0.37
0.46
0.56
0.65
0.74
0.84
0.93
1.02
1.11
1.21
1.30
1.39
1.86
2.32
4.65
6.97
9.29
Diameter (m)
0.34
0.49
0.60
0.69
0.77
0.84
0.91
0.97
1.03
1.09
1.14
1.19
1.24
1.29
1.33
1.54
1.72
2.43
2.98
3.44
Q (kW)
201.08
402.17
603.25
804.33
1005.41
1206.50
1407.58
1608.66
1809.75
2010.83
2211.91
2412.99
2614.08
2815.16
3016.24
4021.66
5027.07
10054.14
15081.21
20108.28
tb (sec)
Hf (ft) (Heskestad)
Hf (ft) (Thomas)
3035.96
1517.98
1011.99
758.99
607.19
505.99
433.71
379.50
337.33
303.60
276.00
253.00
233.54
216.85
202.40
151.80
121.44
60.72
40.48
30.36
5.28
6.86
7.99
8.90
9.67
10.35
10.97
11.52
12.04
12.52
12.97
13.39
13.80
14.18
14.55
16.17
17.56
22.62
26.21
29.08
4.80
6.11
7.03
7.77
8.40
8.95
9.44
9.89
10.30
10.69
11.05
11.39
11.71
12.01
12.30
13.60
14.69
18.70
21.53
23.79
Caution! The purpose of this random spill size chart is to aid the user in evaluating the
hazard of random sized spills. Please note that the calculation doe not take into account
the viscosity or volatility of the liquid, or the absorptivity of the surface. The results
generated for small volume spills over large areas should be used with extreme caution.
NOTE
The above calculations are based on principles developed in the SFPE Handbook of Fire
Protection Engineering, 2nd Edition, 1995.
Calculations are based on certain assumptions and have inherent limitations. The results
of such calculations may or may not have reasonable predictive capabilities for a given
situation, and should only be interpreted by an informed user.
Although each calculation in the spreadsheet has been verified with the results of hand
calculation, there is no absolute guarantee of the accuracy of these calculations.
Any questions, comments, concerns, and suggestions, or to report an error(s) in the
spreadsheets, please send an email to nxi@nrc.gov or mxs3@nrc.gov.
Prepared by:
Date
Organization
Checked by:
Date
Organization
Additional Information
Revision Log
1805.0
Description of Revision
Original issue with final text.
Date
January 2005