Você está na página 1de 3

EAPL

Model M2-8
INSTRUCTION MANUAL

Connection Diagram

M2-8 PROGRAMMABLE FAULT ANNUNCIATOR


www.eaplindia.com

DIMENSION

DOC NO: OD RN YN 02007 0 REV NO: 07 DATE: 21/01/2015

Page 1 of 3

FUNCTION
M2-8 is a Programmable fault Annunciator having features like programming
input fault for window annunciating w.r.t NO or NC, output relay for either TRIP or
ALARM function.
Terminals Details:
A1, A2

: Source voltage

Testing of windows for working condition


1) Apply source voltage between A1 & A2
2) Remove the short between P1 & P2 to operate in RUN mode.
3) Slide the RUN/PGM switch to PGM mode.
Press
4) Test Button - All windows starts flashing and relay switches on.(Trip /
Alarm)
5)

Mute Button - Relay switches OFF (Trip / Alarm)

PGM ENABLE : Short -Program Enable


Open- Program Disable

6)

ACK Button - Flashing window becomes steady to acknowledge the


fault

COM

7)

RST Button - Window switches OFF indicating fault is rectified.

: Common fault terminal

MUTE, ACK, RST, TEST : For External push buttons,


Remote operations and cascading facility. Connect WRT COM(No Volt)

Sequence of operation:
F1 to F8: Individual fault I/P terminals for respective window Connect WRT
COM(No Volt)
Fault

Switch
Operation

Window

Relay

No

--------

OFF

OFF

Yes

--------

Flashing

ON

MUTE : To mute the relay during fault conditions in


RUN mode

Yes

Mute

Flashing

OFF

Yes

Ack.

Steady ON

OFF

NC/NO : Select NC or NO as input sensing in PGM


Mode

Yes

Reset

Steady ON

OFF

Rectified

Reset

OFF

OFF

Front Panel Switches.


SEL

: To select the window for programming in


PGM mode

ACK

: To Acknowledge the fault during fault


conditions in RUN Mode

RST

: To reset the fault, once fault is rectified in


RUN mode

T/NT

: Select Trip Relay or Alarm Relay in PGM


mode

TEST

: To test healthy condition of all windows in


RUN mode

DOC NO: OD RN YN 02007 0 DATE: 21/01/2015

Page 2 of 3

CAUTION

PROGRAMMING
Short PGM ENABLE terminals at the rear using wire jumper. Slide the
RUN / PGM switch to PGM Mode.
Press SEL button, window 1 will glow. By pressing NC/NO button, the Red
LED can be toggled from ON to OFF and vice versa. If the RED LED
glows. Normally open is a healthy condition & fault sensing is closed type.
If RED LED is OFF Normally closed is a healthy condition & fault sensing is
open type.
By pressing T/NT button, the GREEN LED can be toggled from ON to OFF
and vice versa. If the GREEN LED glows the output is programmed for
ALARM RELAY and if the GREEN LED is OFF the output programmed is
for TRIP RELAY.
Press SEL button, now the second window shall glow and by pressing the
NC/NO and T/NT buttons required fault input sensing and relay output can
be programmed. Follow the above procedure for the rest of the windows.
Once the programming of all the windows is over, remove short at PGM
ENABLE terminals, to save the program Slide the RUN / PROG switch to
RUN Mode.

HINTS ON CORRECT USAGE


 Use proper gauge wires for connections.
 Ensure all terminals are tightly screwed.
 Source Voltage should not exceed specified limits. It will damage the
unit beyond repair.

CONTACT

 Applying power to PGM ENABLE,


MUTE, ACK, RST, TEST & F1-F8
shall
damage
the
product
permanently.

Electronic Automation Pvt. Ltd


#20, KHB Industrial area
Yelahanka
Bangalore -64

 Blinking of unit indicates over


voltage. Switch off the unit for 20Sec
to reset the resetable fuse & switch
on.
Applicable for Aux supply 85 to 270V
AC/DC only

Ph:+91-80-28567561/2/42802345
Email : info@eaplindiamail.com
www.eaplindia.com

DISPOSITION
 Once the product life is over, you
may send back the unit to EAPL
for disposition.

TROUBLE ANALYSIS
 Pilot LED not blinking.
Check power supply (Rated
supply should be applied).
 Fault not sensing.
Check for proper connection
between Common & fault
terminals (F1-F8).

DOC NO: OD RN YN 02007 0 Dtd: 21/01/2015