Escolar Documentos
Profissional Documentos
Cultura Documentos
2 Persistent fault
A persistent fault does not disappear when power is disconnected. Faults in underground power cables are most
often persistent due to mechanical damage to the cable,
but are sometimes transient in nature due to lightning.[1]
3 Symmetric fault
Transient fault
5 Bolted fault
lightning strike
conductor clashing
One extreme is where the fault has zero impedance, giving the maximum prospective short-circuit current. Notionally, all the conductors are considered connected to
ground as if by a metallic conductor; this is called a
bolted fault. It would be unusual in a well-designed
power system to have a metallic short circuit to ground
but such faults can occur by mischance. In one type of
transmission line protection, a bolted fault is delibrately
introduced to speed up operation of protective devices.
8 ANALYSIS
Realistic faults
Analysis
First, some simplifying assumptions are made. It is assumed that all electrical generators in the system are in
phase, and operating at the nominal voltage of the system. Electric motors can also be considered to be generators, because when a fault occurs, they usually supply Analysis of the prospective short-circuit current is rerather than draw power. The voltages and currents are quired for selection of protective devices such as fuses
then calculated for this base case.
and circuit breakers. If a circuit is to be properly protected,
the fault current must be high enough to operate
Next, the location of the fault is considered to be supthe
protective
device within as short a time as possible;
plied with a negative voltage source, equal to the voltage
also
the
protective
device must be able to withstand the
at that location in the base case, while all other sources
fault
current
and
extinguish
any resulting arcs without itare set to zero. This method makes use of the principle
self
being
destroyed
or
sustaining
the arc for any signiof superposition.
cant length of time.
To obtain a more accurate result, these calculations should
be performed separately for three separate time ranges: The magnitude of fault currents dier widely depending
on the type of earthing system used, the installations supply type and earthing system, and its proximity to the sup subtransient is rst, and is associated with the largest ply. For example, for a domestic UK 230 V, 60 A TN-S
currents
or USA 120 V/240 V supply, fault currents may be a few
3
thousand amperes. Large low-voltage networks with multiple sources may have fault levels of 300,000 amperes.
A high-resistance-grounded system may restrict line to
ground fault current to only 5 amperes. Prior to selecting protective devices, prospective fault current must be
measured reliably at the origin of the installation and at
the furthest point of each circuit, and this information applied properly to the application of the circuits.
10 Batteries
The prospective fault current of larger batteries, such as
deep-cycle batteries used in stand-alone power systems,
is often given by the manufacturer.
In Australia, when this information is not given, the
prospective fault current in amperes should be considered to be 6 times the nominal battery capacity at the C 120
Ah rate, according to AS 4086 part 2 (Appendix H).
11 See also
Fault (technology)
12 References
[1] http://www.lightning.ece.ufl.edu/PDF/01516222.pdf
[2] Grainger, John J. (2003). Power System Analysis. Tata
McGraw-Hill. p. 380. ISBN 978-0-07-058515-7.
[3] Murari Mohan Saha, Jan Izykowski, Eugeniusz
Rosolowski Fault Location on Power Networks Springer,
2009 ISBN 1-84882-885-3, page 339
[4] Smth,Paul, Furse, Cynthia and Gunther, Jacob. Analysis of Spread Spectrum Time Domain Reectometry for
Wire Fault Location. IEEE Sensors Journal. December,
2005.
[5] Edward J. Tyler, 2005 National Electrical Estimator ,
Craftsman Book Company, 2004 ISBN 1-57218-143-5
page 90
13
13
13.1
13.2
Images
13.3
Content license