Você está na página 1de 42

Energy Division

Project Name:

BKT WELLHEAD PLATFORM

TECHNICAL PROPOSAL
REF NO.:
PACKAGE:

E-0971
HV Switchgear, Distribution Transformer, MCC, EMCC
and Distribution Panels

Our ref.
Project name
Date

: E-0971
: BKT WELLHEAD PLATFORM
: October 06, 2014

TABLE OF CONTENTS
1.

BASIS OF THE OFFER ...................................................................................................................................... 3

2.

SCOPE OF SUPPLY .......................................................................................................................................... 4

3.

SPARE PARTS ................................................................................................................................................... 5

4.

PROPOSED MAKE OF ...................................................................................................................................... 6

5.

PROJECT MANAGEMENT, ENGINEERING, TESTING & COMISSIONING, TRAINING ................................ 7

6.

FAT, WITNESS TEST ........................................................................................................................................ 9

7.

PROJECT ORGANIZATION CHART ............................................................................................................... 10

8.

DEVIATION AND CLARIFICATION LIST......................................................................................................... 11

9.

22kV RING MAIN UNIT RM6 ........................................................................................................................ 12

10.

0.4KV OKKEN SWITCHGEAR ..................................................................................................................... 20

11.

DISTRIBUTION BOARDS ............................................................................................................................ 37

12.

DRY TRANSFORMER ................................................................................................................................. 40

Package: HV Switchgear, Distribution Transformer, MCC, EMCC and Distribution Panels


BKT WELLHEAD PLATFORM

Page | 2/42

Our ref.
Project name
Date

: E-0971
: BKT WELLHEAD PLATFORM
: October 06, 2014

1. BASIS OF THE OFFER


1.1

GENERAL

Our Techno-Commercial offer is based on your BID invitation below:


Request for proposal ref. BKT-001-TS-ES2-RQ-01
Purchase requisition for HV Switchgear, Distribution Transformer, MCC, EMCC and Distribution Panels.
Schneider Electric has long experience and ability to provide a complete offer including engineering, material
supply, implementation management and commissioning services for your project.
In section 2, we proposed scope of work is detailed in scope of work table. Any further discussion with your team
will be highly appreciated so as to adjust the offer in line with your needs completely.
Other details can be found in other sections, such as section 3 comment & deviation, section 6 project
management etc.

1.2

STANDARD

Electrical equipment and system which provided will conform to the relevant standards as below:

1.3

Installed equipment

IEC standard

System study

IEC standard

Installation &implementation

IEC standard

Site safety

IEC standard and local government authority required

NORMAL OPERATING CONDITION

All offered equipments are designed and selected base on relevant standards (IEC) but in normal condition and
non- hazardous. Offered electrical panel will be suitable for installation in condition specified in project datasheet.
Assume site conditions (indoor) are listed below:

1.3.1 Ambient air temperature


0

Less than or equal to 40 C


0

Less than or equal to 35 C on average over a 24-hour period


0

Greater than or equal to 5 C

1.3.2 Temperature require for electrical room


0

Less than or equal to 25 C on average over a 24-hour period


0

Maximum 40 C

1.3.3 Altitude
Less than or equal to 1000m

1.3.4 Atmosphere
Ambient air not significantly polluted by dust, smoke, corrosive or inflammable gas and vapour, or salt.

1.3.5 Humidity
Average relative humidity over 24-hour period 95%
Average relative humidity over a month period 95%

Package: HV Switchgear, Distribution Transformer, MCC, EMCC and Distribution Panels


BKT WELLHEAD PLATFORM

Page | 3/42

Our ref.
Project name
Date

: E-0971
: BKT WELLHEAD PLATFORM
: October 06, 2014

2. SCOPE OF SUPPLY
This Technical Specification contain the proposed design, engineering, procurement, manufacture, inspection,
testing, packaging for shipment and delivery of the equipments of Electrical equipment which comprise of :
MV Switchgear (tag name HVS-RMU)
Distribution Transformer (tag name MP-T)
Low Voltage Motor Control Center - (tag name MCC)
Low Voltage Emergency Motor Control Center (tag name EMCC)
Distribution Boards (tag name MP-SDB-1, ML-SDB-1 & ML-SDB-2, EP-SDB-1, HT-SDB-1, EL-SDB-1)

Package: HV Switchgear, Distribution Transformer, MCC, EMCC and Distribution Panels


BKT WELLHEAD PLATFORM

Page | 4/42

Our ref.
Project name
Date

: E-0971
: BKT WELLHEAD PLATFORM
: October 06, 2014

3. SPARE PARTS
3.1

START-UP & COMMISSIONING SPARE PARTS

No
MV Switchboard
1
VPIS 24kV
LV Switchboards
1
FUSE 10*38-SP-GI- 10A
Distribution Boards
Not Applicable
Dry Transformer
Not Applicable

3.2

Description

Unit

Qty.

pcs

set

10

Unit

Qty.

pcs

2 YEARS SPARE PARTS

No

Description

MV Switchboard
Charging motor 230VAC, 50Hz for
1
2

Pressure switch

set

VPIS 24kV

set

set

LV Switchboards
MCB 2P 4A C
1
2

AUX.SW C/O CONT OF/SDE/SDV

set

COIL LX1F TO 230VAC AT40+400HZ

set

BLOC LAD-N22

set

CONTACTOR 3P LC1D 38A

set

CONTACTOR LC1D80P7

set

FUSE 10*38-SP-GI- 10A

set

20

Control fuse holder 1P

set

set
set

1
1

Distribution Boards
Not Applicable
Dry Transformer
1
PT100
2
Digital Thermometer

Package: HV Switchgear, Distribution Transformer, MCC, EMCC and Distribution Panels


BKT WELLHEAD PLATFORM

Page | 5/42

Our ref.
Project name
Date

: E-0971
: BKT WELLHEAD PLATFORM
: October 06, 2014

4. PROPOSED MAKE OF
Item

Description

Model

Brand

Country of origin

24kV switchboard

RM6

Schneider Electric

France

1.1

Circuit Breaker

SF6

Schneider Electric

France

1.2

CT,VT

Schneider Electric

France

1.3

Relay

Sepam

Schneider Electric

France

24kV switchboard
(Option)

FBX

Schneider Electric

France

2.1

Circuit Breaker

Vacuum

Schneider Electric

France

2.2

CT,VT

Schneider Electric

France

2.3

Relay

Sepam

Schneider Electric

France

Dry Transformer

Trihal

Schneider Electric

France

LV switchboard

Okken

Schneider Electric

Indonesia

3.1

Air Circuit Breaker

Masterpact

Schneider Electric

France

3.2

MCCB

Compact

Schneider Electric

France

3.3

Main contactor

Tesys

Schneider Electric

Czech Republic

3.4

Main relay

Sepam

Schneider Electric

France

3.4

VFD panel

ATV

Schneider Electric

Austria

Distribution Boards

Wall mounting

Schneider Electric

Indonesia

Package: HV Switchgear, Distribution Transformer, MCC, EMCC and Distribution Panels


BKT WELLHEAD PLATFORM

Page | 6/42

Our ref.
Project name
Date

: E-0971
: BKT WELLHEAD PLATFORM
: October 06, 2014

5. PROJECT MANAGEMENT, ENGINEERING, TESTING &


COMISSIONING, TRAINING
5.1

PROJECT MANAGEMENT

The management of projects requires knowledge of modern management. This project has a specific set of
objectives and constraints such as a required time frame for completion. While the relevant technology,
institutional arrangements or processes will differ, the management of such projects has much in common with the
management of similar types of projects in other specialty or technology domains.

5.2

PROJECT MANAGER

The project manager is the most important person for the success or failure of a project. Schneiders skilled
project manager will receives authority from the management of the organization to mobilize the necessary
resources to complete a project.
Our project manager will be able to exert interpersonal influence in order to lead the project team and has long
experiences for electrical in this type of project.
The project manager will be given the responsibility and authority to resolve various conflicts such that the
established project policy and quality standards will not be jeopardized. When contending issues of a more
fundamental nature are developed, they must be brought to the attention of a high level in the management and
be resolved expeditiously.
The purpose of this role is to ensure the management of projects to meet contractual obligations, project
milestones and deadlines.
As a Project Manager he will be responsible for:
Construct, develop & implement plans of action to meet clients needs.
Identify assumptions made in the contract scope & assess the risk associated with these assumptions,
inform the client accordingly & take action to minimize these risks.
Coordinate between construction, engineering & procurement throughout the project cycle & ensure that
project activities are in-line with the overall project schedule.
Liaison with technical, environmental, procurement and legal departments; who are all involved with the
project life cycle
Decision making on project
Assist the Project Teams when requested in the execution of their responsibilities and duties.
To manage all phases of the project from the award of the contract through to eventual client acceptance. The
Project Manager will be responsible for all aspects of design, procurement, and construction, supervision and
hands on commissioning of all electrical, instruments and control systems

5.3

ELECTRICAL PROJECT ENGINEER

Schneider will delegate Electrical engineer to take the leading role in ensuring the scope of work are identified,
studied, recommendations made and documented for the selected options, including:
Responsibilities:
Manage Electrical equipment specification and selection.
Generate/Lead/Implement execution strategies for scope of work.
Provide/facilitate resolution of issues arising from issues.
To provide progress and other reports as required.
Reviews and approves Studies, conceptual designs, detailed design, material/equipment specifications
and drawings.
To attend Factory Acceptance Tests (FAT).
Supervises all electrical work during the design, construction and commissioning of the Project.
Full co-operation with every aspect of the Health and Safety Management System.
Package: HV Switchgear, Distribution Transformer, MCC, EMCC and Distribution Panels
BKT WELLHEAD PLATFORM

Page | 7/42

Our ref.
Project name
Date

: E-0971
: BKT WELLHEAD PLATFORM
: October 06, 2014

To ensure that tests and inspection of works are carried out as stated in the specifications.

Package: HV Switchgear, Distribution Transformer, MCC, EMCC and Distribution Panels


BKT WELLHEAD PLATFORM

Page | 8/42

Our ref.
Project name
Date

: E-0971
: BKT WELLHEAD PLATFORM
: October 06, 2014

6. FAT, WITNESS TEST


6.1

FAT & WITNESS TEST

Witness test will be provided for each product which supplied.


expenses of owner are excluded in the proposal.

All travel, accommodation, allowances etc,

FAT for Transformer shall be scheduled in our site Schneider Electric / Regional Equipment Factory,
Metz, France
FAT for LV switchgear shall be scheduled in our site Schneider Electric / Regional Equipment Factory,
Cikarang, Indonesia

Package: HV Switchgear, Distribution Transformer, MCC, EMCC and Distribution Panels


BKT WELLHEAD PLATFORM

Page | 9/42

Our ref.
Project name
Date

: E-0971
: BKT WELLHEAD PLATFORM
: October 06, 2014

7. PROJECT ORGANIZATION CHART

Project Manager

Purchasing/ Delivery

Project Engineer

Finance

Schneider
MV Switchgear Factory
(France)

Schneider
LV switchboard, DB Factory
(Indonesia)

Package: HV Switchgear, Distribution Transformer, MCC, EMCC and Distribution Panels


BKT WELLHEAD PLATFORM

Schneider
Dry Transformer Factory
(France)

Page | 10/42

Our ref.
Project name
Date

: E-0971
: BKT WELLHEAD PLATFORM
: October 06, 2014

8. DEVIATION AND CLARIFICATION LIST


See in separate Technical Deviation / Clarification list.

Package: HV Switchgear, Distribution Transformer, MCC, EMCC and Distribution Panels


BKT WELLHEAD PLATFORM

Page | 11/42

Our ref.
Project name
Date

: E-0971
: BKT WELLHEAD PLATFORM
: October 06, 2014

9. 22kV RING MAIN UNIT RM6

Package: HV Switchgear, Distribution Transformer, MCC, EMCC and Distribution Panels


BKT WELLHEAD PLATFORM

Page | 12/42

Our ref.
Project name
Date

9.1

: E-0971
: BKT WELLHEAD PLATFORM
: October 06, 2014

GENERAL CONDITIONS

These specifications apply to factory-built, RMU type, metal-enclosed indoor switchgears.


The equipment to be supplied shall come in the form of a compact switchboard and shall meet the following
requirements:
Easy to install
Safe and easy to operate
Compact
Low maintenance
The supplier shall be capable of proving that he has a broad experience in the area of MV switchgears and shall
provide proof that he has already supplied equipment of the equivalent type and brand which has been in
operation for at least three years.
Upon the request, units shall be available either in standard compact range or in extensible versions. Details for
extensibility design shall be provided including the basic principle and operations. Extensibility shall be easily
possible on site by the customer, without SF6 handling , without any particular floor preparation and specific tools.
When assembled, extensible units shall respect integral insulation and insensitivity to environment.

9.2

STANDARDS

In order to be accepted, the switchgear shall comply with the requirements stated in the latest editions of the
following recommendations, standard and specifications:
IEC 60694 common clauses for MV switchgear standards,
IEC 62271-200 MV metal-enclosed switchgear, (replacing IEC 60298)
IEC 60265-1 MV switches,
IEC 62271-102 AC disconnectors and earthing switches, (replacing IEC 60129)
IEC 62271-100 MV AC circuit breakers, (replacing IEC 60056)
IEC 60529 degrees of protection procured by enclosures (IP code).

9.3

SERVICE CONDITIONS

The RMU shall be suitable for operations at a height of less than 1000 meters above sea level.
The RMU shall be capable of operating normally within the following temperature range:
Maximum air temperature : + 40 C
Minimum air temperature : - 25 C
Manufacturer shall declare whether RMU is able to operate in air temperature higher than + 40 C and if
current derating is necessary.
The RMU shall be capable of being operated in electrically exposed locations.
The RMU shall be capable of being exposed to high relative humidity and ambient air pollution.
The RMU shall be capable of being installed in either concrete indoor substations or in compact metal substations
and kiosks with an IP54 rating. Manufacturer shall give all details regarding its solution for free-standing outdoor
installations when requested.

9.4

GENERAL DESCRIPTION OF RM6

The RMU shall meet the criteria for compact, metal-enclosed indoor switchgear in accordance with IEC 62271200:
Switchgear classification : PM class
Loss of service continuity class : LSC2A
It shall include, within the same metal enclosure, the number of MV functional units required for connection, power
supply and protection of transformers

9.4.1 Switchboards
The switchgear and busbar shall all be contained in a stainless steel enclosure filled with SF6 at 0.2 bar (200 hPa)
relative pressure to ensure the insulation and breaking functions. Sealed for life, the enclosure shall meet the
Package: HV Switchgear, Distribution Transformer, MCC, EMCC and Distribution Panels
BKT WELLHEAD PLATFORM

Page | 13/42

Our ref.
Project name
Date

: E-0971
: BKT WELLHEAD PLATFORM
: October 06, 2014

"sealed pressure system" criterion in accordance with the IEC 60694 standard ( 3.6.5.4) : "a volume for which no
further gas processing is required during its entire expected life3. In addition, manufacturer shall confirm that
maximum leakage rate is lower than 0,1 % / year.
It shall provide full insulation, making the switchgear insensitive to the environment (temporary flooding, high
humidity...), IPX7 degrees of protection in accordance with recommendation IEC 60529 14.2.7.
Thus assembled, the active parts of the switchgear shall be maintenance-free and the switchboard shall be lowmaintenance.
The switchboards shall have an IP3X protection index.
The tank shall be made of at least 2 mm AISI 304 unpainted stainless steel and be able to withstand an accidental
internal overpressure of at least 3 bars (3000 hPA)
The colour shall be RAL 9002 for the enclosure and RAL9005 for the mimic panel.
The switchboards shall be suitable for mounting on a trench, utilities space or base.
Each switchboard shall be identified by an appropriately sized label which clearly indicates the functional units and
their electrical characteristics.
The switchgear and switchboards shall be designed so that the position of the different devices is visible to the
operator on the front of the switchboard and operations are visible as well.
In accordance with the standards in effect, the switchboards shall be designed so as to prevent access to all live
parts during operation without the use of tools.

9.4.2 Dielectric medium


SF6 gas is the preferred dielectric medium for MV RMUs. Oil filled switchgear will not be considered. SF6 gas
used for the filling of the RMU shall be in accordance with IEC 60376.
It is preferable to fit an absorption material in the tank to absorb the moisture from the SF6 gas and to regenerate
the SF6 gas following arc interruption.

9.4.3 Earthing of metallic parts


There shall be continuity between the metallic parts of the switchboard and cables so that there is no electric field
pattern in the surrounding air, thereby ensuring the safety of people.
The substation frames shall be connected to the main earth busbar without dismantling any busbars.

9.4.4 Earthing of the main circuit


The cables shall be earthed by an earthing switch with short-circuit making capacity, in compliance with IEC
60129 standard. The earthing switch can only be operated when the switch is open.
The earthing switch shall be fitted with its own operating mechanism and manual closing shall be driven by a fastacting mechanism, independent of operator action.
The moving contacts of the earthing switch shall be visible in the closed position through transparent covers.
Mechanical interlocking systems shall prevent access to the operating shaft to avoid all operator errors such as
closing the earthing switch when the switch is closed.

9.4.5 RMU bushings and Cable terminations


Bushing
It is preferable to have all bushings accessible from the front of the RMU. Bushing along the sides or the rear of
the RMU are not acceptable.
The bushing should be conveniently located for working with cables specified and allow for the termination of
these cables in accordance with the instructions supplied for the MV 400 series, 400 A plug-in or 630 A M16
bolted connectors on line switch and for the MV 200 series 200 A plug-in connectors on transformer protection
feeder.
The profiles of the cable connection bushings shall be in compliance with IEC-60137 standard.
Cable clamps
A non ferro-magnetic cable clamp arrangement must be provided for all network cables terminated on the RMU

9.4.6 Padlocking facilities


Circuit breakers, switches and earthing switches can be locked in the open or closed position by 1 to 3 locks.
Package: HV Switchgear, Distribution Transformer, MCC, EMCC and Distribution Panels
BKT WELLHEAD PLATFORM

Page | 14/42

Our ref.
Project name
Date

: E-0971
: BKT WELLHEAD PLATFORM
: October 06, 2014

9.4.7 Voltage indicators and phase comparators


Each function shall be equipped with a voltage indicator box on the front of the device to indicate whether or not
there is voltage in the cables. The capacitive dividers will supply low voltage power to the lamps.
Three inlets can be used to check the synchronisation of phases.
This device shall be in compliance with IEC 61958 standard.

9.4.8 Fault Passage Indicators


Load break switch functions shall be equipped with a fault passage indicator (FPI), in order to detect and localise
easily the faulty part of the network.
The latter FPI shall segregate the short circuit and earth faults, shall indicate permanently the phase-per-phase
load currents, and shall easily actuate a remote indication lamp.
The FPI fault detection core function shall be self-powered without help external power supply or built-in batteries.

9.4.9 Safety of people


Any accidental overpressure inside the sealed chamber will be limited by the opening of a pressure limiting device
in the lower part of the enclosure. Gas will be released to the rear of the switchboard away from the operator.
Manufacturer shall provide type test report to prove compliance with IEC 62271-200 Annex A, Internal arc
classification class AFL with 16kA for 1 s.

9.4.10 Operating lever


An anti-reflex mechanism on the operating lever shall prevent any attempts to reopen immediately after closing of
the switch or earthing switch.
All manual operations will be carried out on the front of the switchboard.
The effort exerted on the lever by the operator should not be more than 250 N for the switch and 250 N for the
circuit breaker.

9.4.11 Front plate


The front plate shall have an IP3X degree of protection. The front shall include a clear mimic diagram which
indicates the different functions.
The position indicators shall give a true reflection of the position of the main contacts. They shall be clearly visible
to the operator.
The lever operating direction shall be clearly indicated in the mimic diagram.
The manufacturer's plate shall include the switchboard's main electrical characteristics.

9.4.12 Finishing
The device shall be fully designed for use in a hot, humid atmosphere and shall be low-maintenance.
Manufacturer shall provide type test report to prove salt fog withstand for at least 200 hours on operating
mechanism according to IEC 68-2-2 standard.
All metallic parts shall have rust protection.
Two lifting rings shall be installed on the top of the switchboards for handling.

9.5

TEST

The routine tests carried out by the manufacturer shall be backed by test reports signed by the factory's quality
control department. They shall include the following:
Conformity with drawings and diagrams,
Measurement of closing and opening speeds,
Measurement of operating torque,
Checking of filling pressure,
Checking of gas-tightness,
Checking of partial discharges on individual components,
Dielectric testing and main circuit resistance measurement.

Package: HV Switchgear, Distribution Transformer, MCC, EMCC and Distribution Panels


BKT WELLHEAD PLATFORM

Page | 15/42

Our ref.
Project name
Date

9.6

: E-0971
: BKT WELLHEAD PLATFORM
: October 06, 2014

DETAILED SCOPE OF SUPPLY

9.6.1 Description of supply


Substation Description by
Compact Unit
HVS-RMU

22kV
DE-B

22kV
DE-Mt

22kV
DE-BB

9.6.2 Description of Functional Units


Each Feeder 630A circuit breaker (FUNCTION B) includes:
A 3-pole 3-position switch, insulated in SF6, may be in one of the three positions : open, closed or earthed,
representing a natural interlocking system that prevents incorrect operation. Moving-contact rotation is driven by a
fast-acting mechanism that is independent of the action of the operator. To improve safety, the earthing switch
placed in the SF6 has a short circuit making capacity which is 2.5 times the short-time current withstand.
Each function B includes :
4 auxiliary contacts for switch position (2 NF + 2 NO). (option)
1 auxiliary contact for earth switch position indication. (option).
A fast-acting operating manual mechanism, independent of operator action, released by:
either a push-button placed in front of the switchgear.
or a MITOP type low energy release incorporated in the protection unit.
or a release coil. (option)
A protection unit which requires no auxiliary power and includes:
3 current sensors incorporated in the transformer tee-off bushings.
1 MITOP type low energy release.
1 electronic relay.
Mechanical position indication system with mimic diagram.
Mechanical operating shafts of the switch and the earthing switch
Voltage presence indicator (option)
Network connecting bushings protected in a protective compartment.

Package: HV Switchgear, Distribution Transformer, MCC, EMCC and Distribution Panels


BKT WELLHEAD PLATFORM

Page | 16/42

Our ref.
Project name
Date

: E-0971
: BKT WELLHEAD PLATFORM
: October 06, 2014

9.7 TECHNICAL DETAIL


9.7.1 COMPACT UNIT 22kV
The type DE-B is a double extensible switchgear with 1 functional unit D
The type DE-Mt is a double extensible switchgear with 1 functional unit Mt
The type LE-BB is a left extensible switchgear with 2 functional unit D

General characteristics:
SELF- CONTAINED UNIT
Degree of protection
-RM6 Tank

IP67

-Enclosure and operating mechanism

IP3X (std)

Paint
-RM6 Tank

unpainted

- Enclosure

RAL 9002

- Front plate

RAL 7016

Electrical characteristics:
ELECTRICAL CHARACTERISTICS
Rated voltage

kV rms

24

Service voltage

kV rms

22

Hz

50

Rated withstand voltage at industrial frequency: 50 Hz/1min

kV rms

50

Rated impulse withstand voltage: 1,2/50ms

kV peak

125

630

Short-circuit withstand current

kA rms /1 sec

20

Short-circuit breaking capacity of the circuit breaker

kA rms /1 sec

20

kA peak

50

Frequency

Rated current

Making capacity of the circuit breaker


Compact unit:
COMPACT UNIT
Pressure switch

Yes

Cable fault creepage way


Fixing to the ground

no
the RM6s plinth has got 4 anchoring points which permit
direct fixing to the ground

Package: HV Switchgear, Distribution Transformer, MCC, EMCC and Distribution Panels


BKT WELLHEAD PLATFORM

Page | 17/42

Our ref.
Project name
Date

: E-0971
: BKT WELLHEAD PLATFORM
: October 06, 2014

Functional unit DE-B 22kV:


FUNCTIONAL UNIT
Bushing type
Interlocking of the access to the bushing
compartment
Height of the cable connectors
Cable box
Type of cables

DE-B
(Incoming)
C = plug in 630A (Disconnectable M16)
Bolted
703 mm (std)
standard
three cores, dry type

Additional earth busbar in cable


compartment

Yes

Voltage indicator

VPIS

Motorisation

Yes

Auxiliary contacts

Protection relay

Type of ring CTs

CRa

Voltage transformer

/
/

Homopolar sensor for SEPAM

Communication of SEPAM S10

Yes

Motor disabled when CB trips

(1 A.C.)
Trip coil

Included

Undervoltage coil
Interlocking

/
Yes

Functional Unit DE-Mt 22kV:


FUNCTIONAL UNIT
VT number and configuration

DE-Mt
(for RC6)
3 Phase to Earth VTs

VT protection

Without MV fuses

VTs position

Fitted left of CT

CTs number

3 Current Transformers

VT ratio

22kV:3 / 110V:3
30VA cl0.5

CT ratio

100-200/5-5A
5VA cl0.5
5VA 5P20

Key locking

LV Box

Yes

Others

Sepam S42 (for incoming)

Package: HV Switchgear, Distribution Transformer, MCC, EMCC and Distribution Panels


BKT WELLHEAD PLATFORM

Page | 18/42

Our ref.
Project name
Date

: E-0971
: BKT WELLHEAD PLATFORM
: October 06, 2014

Functional unit LE-BB 22kV:


FUNCTIONAL UNIT

LE-DD (for RC3 and RC7)


B unit (to Transformer)

B unit (Spare)

C = plug in 630A
(Disconnectable M16)

C = plug in 630A
(Disconnectable M16)

Bolted

Bolted

703 mm (std)

703 mm (std)

standard

standard

three cores, dry type

three cores, dry type

Additional earth busbar in cable compartment

Yes

Yes

Voltage indicator

VPIS

VPIS

Motorisation

Yes

Yes

Protection relay

SEPAM series 10

SEPAM series 10

Type of ring CTs

CRa

CRa

Homopolar sensor for SEPAM

CSH200

CSH200

Communication of SEPAM S10

Yes

Yes

Included

Included

Undervoltage coil

Interlocking

Bushing type
Interlocking of the access to the bushing
compartment
Height of the cable connectors
Cable box
Type of cables

Auxiliary contacts

Motor disabled when CB trips (1 A.C.)


Trip coil

Package: HV Switchgear, Distribution Transformer, MCC, EMCC and Distribution Panels


BKT WELLHEAD PLATFORM

Page | 19/42

Our ref.
Project name
Date

: E-0971
: BKT WELLHEAD PLATFORM
: October 06, 2014

10. 0.4KV OKKEN SWITCHGEAR

Package: HV Switchgear, Distribution Transformer, MCC, EMCC and Distribution Panels


BKT WELLHEAD PLATFORM

Page | 20/42

Our ref.
Project name
Date

: E-0971
: BKT WELLHEAD PLATFORM
: October 06, 2014

10.1 GENERAL DESCRIPTION OF EQUIPMENT


10.1.1 Okken: the "large site" low voltage switchboard
Okken is the Schneider Electric high dependability low voltage switchboard for electrical distribution and motor
control.
It is type tested assembly (TTA) complying with standard IEC 60439-1.
To answer all your needs
Motor supplying
Standard starters
Variable speed drives
Soft starters

Withdrawable

Disconnectable

Fixed

Electrical distribution
4000 6300A (Masterpact NW)
800 4000A (Masterpact NW)
800 1600A (Masterpact NT)
800 1600A (Compact NS)
400 630A (Compact NS)
100 250A (Compact NS)
< 100A (C60)

Withdrawable
(device)
(device)
(device)
(device)

Disconnectable

Power factor correction and


harmonic filtering

Withdrawable

Disconnectable

Fixed

Fixed

Highly polluted network


Polluted network
Slightly polluted network

Multi-purpose:
Distribution and motor control feeders
Feeders with different installation modes

Package: HV Switchgear, Distribution Transformer, MCC, EMCC and Distribution Panels


BKT WELLHEAD PLATFORM

Page | 21/42

Our ref.
Project name
Date

: E-0971
: BKT WELLHEAD PLATFORM
: October 06, 2014

With a four volumes architecture

Front side
With all types of connection:
Powering by busbar trunking (Canalis) and/or cables
Cable incoming from the top and/or bottom
Several cable compartment widths and depths for front and rear connection

Top direct connection

Bottom direct connection

Front (or side) connection

Rear connection

With a metal parts surface treatment


The external panels are made of steel sheet covered with epoxy paint. color RAL 1000.
The upper and lower grids are made of steel sheet covered with epoxy paint. color RAL 7016
Inside equipment (mounting
ing plates. partitions ) are made of galvanized steel sheet.

Package: HV Switchgear, Distribution Transformer, MCC, EMCC and Distribution Panels


BKT WELLHEAD PLATFORM

Page | 22/42

Our ref.
Project name
Date

: E-0971
: BKT WELLHEAD PLATFORM
: October 06, 2014

10.1.2 Okken: a wide range of solutions


For Electrical Distribution Functional Units > 800A
Withdrawable device on chassis: Masterpact NW (800 to
6300A). Masterpact NT and Compact NS (800 to 1600A)
Solution recommended for:
Quick replacements
All types of connection. front or rear. by busbar trunking or cables
Technical data
Power circuit:

withdrawable upstream / downstream

Auxiliary circuit:

withdrawable

Withdrawability level:

WWW

Service rating:

332

Fixed device: Masterpact NT (800 to 1600A)


Solution recommended for:
Installation with a minimum of evolution
All types of connection. front or rear. by cables. not powered.
Technical data
Power circuit:

fixed upstream / downstream

Auxiliary circuit:

fixed

Withdrawability level:

FFF

Service rating:

211

For Electrical Distribution Functional Units < 630A


Device on fixed mounting plate
Solution recommended for :
Non-priority functional units. stabilized in time
All type of connection. front or rear. by cables
Technical data: fixed type circuit-breaker
Power circuit:

fixed upstream / downstream

Auxiliary circuit:

fixed

Withdrawability level:

FFF

Service rating:

211

Technical data: plug-in type circuit-breaker


Power circuit:

withdrawable upstream / downstream

Auxiliary circuit:

withdrawable

Withdrawability level:

WWW

Service rating:

232

Package: HV Switchgear, Distribution Transformer, MCC, EMCC and Distribution Panels


BKT WELLHEAD PLATFORM

Page | 23/42

Our ref.
Project name
Date

: E-0971
: BKT WELLHEAD PLATFORM
: October 06, 2014

Disconnectable Polyfast
Solution recommended for:
Economical adaptation by qualified personnel. with operation on
downstream connections
Front connection. by cables
Technical data
Power circuit:

withdrawable upstream / fixed


withdrawabl
downstream

Auxiliary circuit:

withdrawable

Withdrawability level:

WFW

Service rating

223

Plug-in Polyfast
Solution recommended for:
Easy. quick replacements
All types of connection. front or rear. by cables
Technical data
Power circuit:

withdrawable upstream / downstream

Auxiliary circuit:

withdrawable

Withdrawability level:

WWW

Service rating:

233

Polyfast drawer
Solution recommended for:
Extremely short replacement times
Auxiliary circuit testing. disconnected from power (TEST position
of the drawer)
All types of connection. front or rear. by cables
Security position: withdrawn / padlocked
Technical data
Power circuit:

withdrawable upstream / downstream

Auxiliary circuit:

withdrawable

Withdrawability level:

WWW

Service rating:

333

C60 disconnectable mounting plate


Solution recommended for:
Replacement and adaptation flexibility

Package: HV Switchgear, Distribution Transformer, MCC, EMCC and Distribution Panels


BKT WELLHEAD PLATFORM

Page | 24/42

Our ref.
Project name
Date

: E-0971
: BKT WELLHEAD PLATFORM
: October 06, 2014

Front connection by cables


Technical data
Power circuit:

withdrawable upstream / fixed


downstream

Auxiliary circuit:

fixed

Withdrawability level:

WFF

Service rating:

223

For Motor Control Center Functional Units up to 300kW 690V


Disconnectable mounting plate (up to 40 kW 415V)
Motor control solution. recommended for:
Economical adaptations by qualified personnel. with operation on
downstream connections
Front connection by cables
Technical data
Power circuit:

withdrawable upstream / fixed


downstream

Auxiliary circuit:

disconnectab
disconnectable

Withdrawability level:

WFD

Service rating:

223

Withdrawable drawer (up to 300 kW 690V)


(from 3 to 24 modules of 25mm high including 3 and 6
modules half width drawers)
Motor control solution. recommended for :
Extremely short replacement times
Auxiliary circuit testing. disconnected from power (TEST position
of the drawer)
Optimization of switchboard dimensions
All types of connection. front or rear. by cables
Security position: withdrawn / padlocked
Technical data
Power circuit:

withdrawabl upstream / downstream


withdrawable

Auxiliary circuit:

withdrawable

Withdrawability level:

WWW

Service rating:

333

10.1.3 Okken: the ease of installation

Package: HV Switchgear, Distribution Transformer, MCC, EMCC and Distribution Panels


BKT WELLHEAD PLATFORM

Page | 25/42

Our ref.
Project name
Date

: E-0971
: BKT WELLHEAD PLATFORM
: October 06, 2014

Easy to transport and install


Built-in handling plinth
Handling by pallet truck or lifting device
Simplified alignment of columns

Easy fishplating of bars


Pre-mounted sliding fishplates
Easy access to the fishplating area

Easy to connect
Movable framework girders and cross-members
cross
Wide choice of connection compartments
Quick-mounting
mounting junction block for busbar trunking

Package: HV Switchgear, Distribution Transformer, MCC, EMCC and Distribution Panels


BKT WELLHEAD PLATFORM

Page | 26/42

Our ref.
Project name
Date

: E-0971
: BKT WELLHEAD PLATFORM
: October 06, 2014

Okken: the safety


Okken switchboards are type tested assemblies (TTA). complying
with IEC 60439-1 standard.
Only equipment produced according to this switchboard
specifications standard guarantee installation safety and reliability.
IEC 60439-1 standard defines ten compulsory tests guaranteeing
conformity of the electrical switchboard:
7 type tests (manufacturer)
3 routine tests (panelbuilder)

For Okken. all tests were carried out in the most unfavorable conditions.
Partitions
Okken switchboards. respect protection of persons by the choice of functional unit partitions required by the IEC
60439-1 standard:
incomers:

forms 3b. 4b

feeders:

forms 2b. 3b. 4a. 4b

Identification of potentially dangerous areas


The red color is used to mark out elements protecting removable live parts.
Striker system
A mechanical striker forbids the on-load withdrawal of a Compact
NS or NSX 100 to 630 installed on a POLYFAST.

Standard
OKKEN meets the main national and international standards for TTA equipment (Type Tested Assemblies):
IEC 60439-1

relating to construction of low voltage switchgear and controlgear assemblies.

IEC 60529

defining the degrees of protection provided by enclosures.

IEC 60068-2-11

defining resistance to salt mist

IEC 60068-2-2

defining resistance to dry heating

IEC 60068-2-30

defining resistance to damp heating

IEC 60068-2-1

defining resistance to low temperatures

Other European standards:


VDE 0660 Part 5

IEC 61641

NBN C 63439

IBC 2003

BS 5486

IEC 60721-2-6

CEI 542

IEC 68-3-3

GOST

EDF HN20E53 (with adaptation)

Package: HV Switchgear, Distribution Transformer, MCC, EMCC and Distribution Panels


BKT WELLHEAD PLATFORM

Page | 27/42

Our ref.
Project name
Date

: E-0971
: BKT WELLHEAD PLATFORM
: October 06, 2014

10.2 GENERAL CHARACTERISTICS


10.2.1 SWITCHBOARD: MCC
10.2.1.1 Environmental conditions
Altitude :

<= 2000 M

Ambient atmosphere :

STANDARD

Average ambient air temperature over a period of 24H:

40 C

Climate :

STANDARD

10.2.1.2 Electrical data


Power circuit
Rated service voltage :

400 V

Rated frequency :

50 Hz

Rated short-time current (kA rms/1s) :

15 kA

Neutral system :

TNS

Neutral section :

= PHASE

Auxiliary circuit
Control voltage :

230 V AC Internal

10.2.1.3 Mechanical data


Type of section used

OKKEN 70-2 & 70-M

Degree of protection :

54

Form according IEC 439-1 :

3B

Painting

RAL 7032

Degree of withdrawability (F, D, W) according to IEC


439-1 :

WWW

Type of full doors

Plain

Cable connection
Connexion access :

Front

Incoming Power cable entry:

BOTTOM

Outgoing Power cable entry :

TOP

Busbar
Rating of main busbar :

800 A - CONSTANT

Coating :

TINNED+EPOXY

Package: HV Switchgear, Distribution Transformer, MCC, EMCC and Distribution Panels


BKT WELLHEAD PLATFORM

Page | 28/42

Our ref.
Project name
Date

: E-0971
: BKT WELLHEAD PLATFORM
: October 06, 2014

10.2.2 SWITCHBOARD: EMCC


10.2.2.1 Environmental conditions
Altitude :

<= 2000 M

Ambient atmosphere :

STANDARD

Average ambient air temperature over a period of 24H:

40 C

Climate :

STANDARD

10.2.2.2 Electrical data


Power circuit
Rated service voltage :

400 V

Rated frequency :

50 Hz

Rated short-time current (kA rms/1s) :

15 kA

Neutral system :

TNS

Neutral section :

= PHASE

Auxiliary circuit
Control voltage :

230 V AC Internal

10.2.2.3 Mechanical data


Type of section used

OKKEN 70-2 & 70-M

Form according IEC 439-1 :

54
31 (VSD Panel)
3B

Painting

RAL 7032

Degree of withdrawability (F, D, W) according to IEC


439-1 :

WWW

Type of full doors

Plain

Degree of protection :

Cable connection
Connexion access :

Front

Incoming Power cable entry:

BOTTOM

Outgoing Power cable entry :

TOP

Busbar
Rating of main busbar :

800 A - CONSTANT

Coating :

TINNED+EPOXY

Package: HV Switchgear, Distribution Transformer, MCC, EMCC and Distribution Panels


BKT WELLHEAD PLATFORM

Page | 29/42

Our ref.
Project name
Date

: E-0971
: BKT WELLHEAD PLATFORM
: October 06, 2014

10.3 FUNCTIONAL DESCRIPTION


INCOMER ACB TRANSFORMER/1 - 630 A : > (WITHDRAWABLE CHASSIS)
equipped with
1 ACB Switch Masterpact NT06HA 4P
1 Power supply module (AD)
1 Motor mechanism
1 "Test" position contact
1 Pushbutton locking device
1 "Disconnected" position locking device
1 "OFF" position locking device
1 Transparent cover (IP54)
1 Operation counter
1 "Connected" position contact
1 "Disconnected" position contact
4 Auxiliary Miniature Circuit Breaker C60N 2P
3 Control Fuse 1Ph
1 Potential transformer
4 Direct signal lamp with led bulb
2 Push button
2 Selector switch 2 positions 1 contact
1 Protection relay SEPAM T81
1 Communication module for SEPAM
1 Advanced UMI module for SEPAM
1 Optional Synchrocheck relay (25) for SEPAM
1 Current test box
1 Voltage test box
5 Instantaneous auxiliary relay
1 K&N LOCKOUT RELAY
1 LSHF CABLE
4 RS ISOLSEC, 600/5A, 5P20
2 K&N SEL.SWITCH
2 PWS 230V/24V 240W ABL8RPS24100
INCOMER ACB GENERATOR/1 - 630 A : > (WITHDRAWABLE CHASSIS)
equipped with
1 ACB Switch Masterpact NT06HA 4P
1 Power supply module (AD)
1 Motor mechanism
1 Transparent cover (IP54)
1 Operation counter
1 "OFF" position locking device
1 "Disconnected" position locking device
1 "Disconnected" position contact
Package: HV Switchgear, Distribution Transformer, MCC, EMCC and Distribution Panels
BKT WELLHEAD PLATFORM

Page | 30/42

Our ref.
Project name
Date

: E-0971
: BKT WELLHEAD PLATFORM
: October 06, 2014

1 "Test" position contact


1 Pushbutton locking device
1 "Connected" position contact
1 Auxiliary Miniature Circuit Breaker C60N 2P
3 Control Fuse 1Ph
1 Potential transformer
4 Direct signal lamp with led bulb
2 Push button
2 Selector switch 2 positions 1 contact
1 Protection relay SEPAM G40
1 Communication module for SEPAM
1 Advanced UMI module for SEPAM
1 Current test box
1 Voltage test box
5 Instantaneous auxiliary relay
1 Voltage transformer single phase 3000 VA
1 LSHF CABLE
4 RS ISOLSEC, 600/5A, 5P20
1 K&N LOCKOUT RELAY
2 PWS 230V/24V 240W ABL8RPS24100
ACB TO/FROM EMCC/1 - 630 A : > (WITHDRAWABLE CHASSIS)
equipped with
1 ACB Switch Masterpact NT06HA 4P
1 Power supply module (AD)
1 Motor mechanism
1 Pushbutton locking device
1 "OFF" position locking device
1 "Disconnected" position contact
1 "Disconnected" position locking device
1 "Connected" position contact
1 "Test" position contact
1 Operation counter
1 Transparent cover (IP54)
4 Auxiliary Miniature Circuit Breaker C60N 2P
3 Control Fuse 1Ph
1 Potential transformer
4 Direct signal lamp with led bulb
2 Push button
3 Selector switch 2 positions 1 contact
1 Protection relay SEPAM S40
1 Communication module for SEPAM
1 Advanced UMI module for SEPAM
1 Current test box
1 Voltage test box

Package: HV Switchgear, Distribution Transformer, MCC, EMCC and Distribution Panels


BKT WELLHEAD PLATFORM

Page | 31/42

Our ref.
Project name
Date

: E-0971
: BKT WELLHEAD PLATFORM
: October 06, 2014

5 Instantaneous auxiliary relay


1 K&N LOCKOUT RELAY
1 LSHF CABLE
4 RS ISOLSEC, 600/5A, 5P20
2 PWS 230V/24V 240W ABL8RPS24100
DOL < 11kW/1 - 7.5 kW : > (WITHDRAWABLE UNIVERSAL)
equipped with
1 CB GV2-L20

18A

1 Rotary Handle on individual door


1 Multi-function control unit TeSysT - ModBus
1 CONTACTOR 3P LC1D 38A
1 Aux Relay
2 Direct signal lamp with led bulb
2 Push button
1 LSHF CABLE
11kW < DOL > 30kW/1 - 18.5 kW : > (WITHDRAWABLE UNIVERSAL)
equipped with
1 3P NSX100F
1 3P3D MA50 TRIP UNIT
1 Rotary handle on individual door
1 Multi-function control unit TeSysT - ModBus
1 CONTACTOR LC1D80P7
1 LTMCU DISPLAY TERMINAL
1 CORDON POUR DEPORT - L 3 M
1 Instantenous Aux Contactor
3 Instantaneous auxiliary relay
4 Direct signal lamp with led bulb
1 Auxiliary Miniature Circuit Breaker C60N 2P
1 Emergency push button
1 24VDC LTMEV40BD
DIST. FEEDER HALF DRAWER/1 - NSX100 : > (WITHDRAWABLE UNIVERSAL)
equipped with
1 4P NSX100F
1 Control unit Micrologic 6.2E
1 Rotary handle on individual door
1 ModBus SL communication interface module
1 Switchboard front display module FDM121
1 NSX Cord L 1.30m
2 SHORT TERMINAL SHIELD 4P
1 RJ45 link
1 Shunt trip coil
1 MODULE COM MODBUS BSCM
Package: HV Switchgear, Distribution Transformer, MCC, EMCC and Distribution Panels
BKT WELLHEAD PLATFORM

Page | 32/42

Our ref.
Project name
Date

: E-0971
: BKT WELLHEAD PLATFORM
: October 06, 2014

1 Auxiliary Miniature Circuit Breaker C60N 2P


1 Instantaneous auxiliary relay
1 LSHF CABLE
DIST. FEEDER/1 - NSX100 : > (WITHDRAWABLE UNIVERSAL)
equipped with
1 4P NSX100F
1 Control unit Micrologic 6.2E
1 Rotary handle on individual door
1 ModBus SL communication interface module
1 Switchboard front display module FDM121
1 NSX Cord L 1.30m
2 SHORT TERMINAL SHIELD 4P
1 RJ45 link
1 Shunt trip coil
1 MODULE COM MODBUS BSCM
1 Auxiliary Miniature Circuit Breaker C60N 2P
2 Direct signal lamp with led bulb
1 Instantaneous auxiliary relay
1 LSHF CABLE
VSD/1 - 110 kW : > (WITHDRAWABLE UNIVERSAL)
equipped with
1 Kit de deport pour Terminal Graphique
4 Instantaneous auxiliary relay
4 Direct signal lamp with led bulb
2 Auxiliary Miniature Circuit Breaker C60N 2P
1 ALTIVAR 71 132 KW 380-480 V
1 RS485 connection kit
1 Passive Filter
1 CONNECTION RS485
1 CORDON POUR DEPORT - L 3 M
1 Kit de deport pour Terminal Graphique
5 Single terminal block
4 Instantaneous auxiliary relay
4 Direct signal lamp with led bulb
2 Auxiliary Miniature Circuit Breaker C60N 2P
1 LSHF CABLE
FEEDER VSD/1 - NSX250 : > (WITHDRAWABLE UNIVERSAL)
equipped with
1 3P NSX250F
1 Control unit Micrologic 2.2
1 Rotary handle on individual door
2 6 INTERPHASE BARRIERS
Package: HV Switchgear, Distribution Transformer, MCC, EMCC and Distribution Panels
BKT WELLHEAD PLATFORM

Page | 33/42

Our ref.
Project name
Date

: E-0971
: BKT WELLHEAD PLATFORM
: October 06, 2014

1 Rotary handle on individual door


1 Breaker status and control module BSCM
1 ModBus SL communication interface module
1 NSX Cord L 1.30m
1 Auxiliary Miniature Circuit Breaker C60N 2P
2 Direct signal lamp with led bulb
1 Instantaneous auxiliary relay
2 Push button
1 CONT. S/BOB 3POL LC1-F185 (FG)
1 COIL LX1F TO 230VAC AT50HZ
1 LSHF CABLE
3 Current transformer LT6CT
1 TESYST 8A 24VCC LTMR08MBD
1 MOD.EXTENSION 24VDC LTMEV40BD
DOL < 11kW/1 - 15 kW : > (WITHDRAWABLE UNIVERSAL)
equipped with
1 CB GV2-L32

32A

1 Rotary Handle on individual door


1 Multi-function control unit TeSysT - ModBus
1 CONTACTOR 3P LC1D 38A
1 LTMCU DISPLAY TERMINAL
1 CORDON POUR DEPORT - L 3 M
1 Instantaneous contact block LA1DN22
3 Direct signal lamp with led bulb
1 Auxiliary Miniature Circuit Breaker C60N 2P
2 Push button
1 LSHF CABLE
1 24VDC LTMEV40BD
DIST. FEEDER/1 - NSX400 : > (WITHDRAWABLE POLYFAST)
equipped with
1 MCCB NSX400F 4P
1 Control unit Micrologic 6.3E
1 ModBus SL communication interface module
1 Switchboard front display module FDM121
1 NSX Cord L 1.30m
1 RJ45 link
1 Rotary handle on individual door
1 Shunt trip coil
1 MODULE COM MODBUS BSCM
1 Auxiliary Miniature Circuit Breaker C60N 2P
2 Direct signal lamp with led bulb
1 Instantaneous auxiliary relay
1 LSHF CABLE

Package: HV Switchgear, Distribution Transformer, MCC, EMCC and Distribution Panels


BKT WELLHEAD PLATFORM

Page | 34/42

Our ref.
Project name
Date

: E-0971
: BKT WELLHEAD PLATFORM
: October 06, 2014

10.4 QUANTITY OF FUNCTIONAL UNIT


SWITCHBOARD : MCC
FRONT FACE LABEL

FUNCTIONAL UNIT LABEL

SECTION

MODULE

APP./ RAW QUANTITY

INCOMER ACB TRANSFORMER/1 - 630 A

>

OKKEN

18/72

INCOMER ACB GENERATOR/1 - 630 A

>

OKKEN

18/72

ACB TO/FROM EMCC/1 - 630 A

>

OKKEN

18/72

11kW < DOL > 30kW/1 - 18.5 kW

>

OKKEN

8/72

DIST. FEEDER HALF DRAWER/1 - NSX100

>

OKKEN

8/72

DIST. FEEDER/1 - NSX100

>

OKKEN

8/72

DOL < 11kW/1 - 15 kW

>

OKKEN

4/72

DIST. FEEDER/1 - NSX400

>

OKKEN

12/72

Package: HV Switchgear, Distribution Transformer, MCC, EMCC and Distribution Panels


BKT WELLHEAD PLATFORM

Page | 35/42

Our ref.
Project name
Date

: E-0971
: BKT WELLHEAD PLATFORM
: October 06, 2014

SWITCHBOARD : EMCC
As per limited space Emergency Room, the EMCC Switchboard will be separated into 2 parallel switchboards:
SIDE A and SIDE B
FRONT FACE LABEL

FUNCTIONAL UNIT LABEL

SECTION

MODULE

APP./ RAW QUANTITY

SIDE A
INCOMER ACB GENERATOR/1 - 630 A

>

OKKEN

18/72

ACB TO/FROM EMCC/1 - 630 A

>

OKKEN

18/72

DOL < 11kW/1 - 7.5 kW

>

OKKEN

4/72

DIST. FEEDER HALF DRAWER/1 - NSX100

>

OKKEN

8/72

14

DIST. FEEDER/1 - NSX100

>

OKKEN

8/72

DIST. FEEDER/1 - NSX100

>

OKKEN

8/72

FEEDER VSD/1 - NSX250

>

OKKEN

20/72

DOL < 11kW/1 - 15 kW

>

OKKEN

4/72

>

OKKEN

72/72

SIDE B
VSD/1 - 90 kW

Package: HV Switchgear, Distribution Transformer, MCC, EMCC and Distribution Panels


BKT WELLHEAD PLATFORM

Page | 36/42

Our ref.
Project name
Date

: E-0971
: BKT WELLHEAD PLATFORM
: October 06, 2014

11. DISTRIBUTION BOARDS


11.1 GENERAL SPECIFICATION
Standard Manufacturing

IEC 439 - 1, IEC 529

Design System

Wall mounted

Type Panel

Indoor

Design Ambient Air Temperature

Between -5 C up to 40 C maximum ( Average of 24 hours


maximum 35 C ).

Altitude

Up to 2000 m

Relative Humidity
o

At Max Temp. +400 C

Less than 50 %

Lower Temp. + 200 C

Less than 90 %

Anti Arc

No

Environment

Standard, non corrosive (SO2/H2S)

Colour

RAL 7032

Electrical Characteristic
Rated Insulation Voltage

1000 VAC

Rated Operational Voltage

AC 400V, 3P 4W

Rated Short Time Withstand Current

6kA 1s

Rated Current :
- Main Bus bars

referring to customer's SLD

Frequency

50Hz

Communication Facilities

NO

Mechanical Characteristic
Withdrawabily

Fix

Form

Form 1 Plus Transparent Cover

Degrees of Protection

IP32

Cable Connection

Top/Bottom

Access

Front

Material
Enclosures

Stainless Steel

Control Cable

Std PVC, 105C


Flame Retardant
Halogen Free
Tinned Cable
Epoxy Polyester Powder

Painting
Mimic Diagram

NO

Name Plate

Gravoply

:YES
:YES
:YES
:NO

Packaging Seaworthy (9mm wood)


Fumigation

NO

Package: HV Switchgear, Distribution Transformer, MCC, EMCC and Distribution Panels


BKT WELLHEAD PLATFORM

Page | 37/42

Our ref.
Project name
Date

: E-0971
: BKT WELLHEAD PLATFORM
: October 06, 2014

11.2 MATERIAL DETAIL


Functional Name
MP-SDB-1

Detail Material and Qty

Remark

1
1
1
1
3
3
13
8
1
1
1
1
3
3
8
3

NSX100F 4P
OF+SD
Voltmeter + Selector Switch
Ammeter + Selector Switch
CT 50/5A, Cl1
Pilot Lamps
MCB Acti9 2P
Vigi C60H 30mA
NSX100F 4P
OF+SD
Voltmeter + Selector Switch
Ammeter + Selector Switch
CT 50/5A, Cl1
Pilot Lamps
MCB Acti9 2P
Vigi C60H 30mA

ML-SDB-2

1
1
1
1
3
3
19

NSX100F 4P
OF+SD
Voltmeter + Selector Switch
Ammeter + Selector Switch
CT 50/5A, Cl1
Pilot Lamps
MCB Acti9 2P

Dimension 600x400x700 (WxDxH)

EP-SDB-1

1
1
1
1
3
3
18
1
6
6

NSX100F 4P
OF+SD
Voltmeter + Selector Switch
Ammeter + Selector Switch
CT 50/5A, Cl1
Pilot Lamps
MCB Acti9 2P
Vigi C60H 30mA
MX coil MCB
Aux relay

Dimension 600x400x700 (WxDxH)

HT-SDB-1

1
1
1
1
3
3
12
12

NSX100F 4P Toggle
OF+SD
Voltmeter + Selector Switch
Ammeter + Selector Switch
CT 75/5A, Cl1
Pilot Lamps
MCB Acti9 2P
Vigi C60H 30mA

Dimension 600x400x700 (WxDxH)

ML-SDB-1

Dimension 600x400x600 (WxDxH)

Dimension 600x400x700 (WxDxH)

Package: HV Switchgear, Distribution Transformer, MCC, EMCC and Distribution Panels


BKT WELLHEAD PLATFORM

Page | 38/42

Our ref.
Project name
Date

EL-SDB-1

: E-0971
: BKT WELLHEAD PLATFORM
: October 06, 2014

1
1
1
1
3
3
21
1

NSX100F 4P Toggle
OF +SD
Voltmeter + Selector Switch
Ammeter + Selector Switch
CT 50/5A, Cl1
Pilot Lamps
MCB Active9 2P
Vigi C60 30mA

Dimension 600x400x700 (WxDxH)

Package: HV Switchgear, Distribution Transformer, MCC, EMCC and Distribution Panels


BKT WELLHEAD PLATFORM

Page | 39/42

Our ref.
Project name
Date

: E-0971
: BKT WELLHEAD PLATFORM
: October 06, 2014

12. DRY TRANSFORMER

Package: HV Switchgear, Distribution Transformer, MCC, EMCC and Distribution Panels


BKT WELLHEAD PLATFORM

Page | 40/42

Our ref.
Project name
Date

: E-0971
: BKT WELLHEAD PLATFORM
: October 06, 2014

12.1 TRIHAL - 400 KVA - 22000 V / 400 V - D YN11


Cast resin transformer Three phases - Type Indoor use - Enclosure IP23 IK7 - According to CEI 60076-1
or 60076-11 Certified C3*, E3, F1 (*) C2 Thermal shock test carried out at -50C
Rated power AN : ............................................ 400 kVA
Operation : .................................................. Step-down
Rated high voltage 1 : .............................. 22000 V

Frequency : ........................................................50 Hz
Vector group : ...................................................D yn11
Windings HV/LV : ............................. Copper imposed
Rated low voltage 1 : .............. 420 V (At no-load)

Rated high voltage insulation level : .....................24kV Rated low voltage insulation level : ................... 1.1 kV
Applied voltage to industrial frequency : ..............50 kV Applied voltage to industrial frequency : ............ 10 kV
B.I.L. (1,2 / 50s) : .............................................125 kV B.I.L. (1,2 / 50s) : ................................................. N/A
HV tapping (off-circuit) : ..... +-2,5 +-5,0 % (Connecting
links)
High voltage connections
Low voltage connections
Connections type : ....... Fixed plug-in bush. HN 52S61 Connections type : ............. LV upward pointing risers
Cables incoming : ...................................................Top Cables incoming : .................................................. Top
Connections location : .............................................Top Connections location : ................... Top LV connection
Current rated of the plug in bushings : ................ 250 A Secondary arrival : .............................................Cable
Connections marking : ............................................ IEC Number of connections : ........................................... 4
Number of connections : .............................................. 3
Plug in bushings location : ...................... On the cover
Locking device on plug in bushings : .... Stainless steel
without lock
Electrical characteristics
Site conditions
No load losses : ................................................ 1375 W
Load losses (AN) at 120C : ............................ 4862 W
Impedance voltage (AN) at 120C : .....................6.6 %
Tolerances : ............................ IEC 60076-1 Tolerance
Thermal characteristics

Altitude : ....................................................... 1000 m


Maximum ambient temperature : ....................... 45 C
Minimum ambient temperature : ........................ -25 C
Daily average temperature : ............................... 35 C
Yearly average temperature : ............................ 25 C
Electrostatic screen : .............................................. No
Rectifier supply : ..................................................... No

Thermal insulation class : .................................Class F


Windings temperature rise : .................................. 80 K
Protective enclosure characteristics
Dimensions & weights (transformer with metal
enclosure)
Enclosure type : ............................. Enclosure IP23 IK7 Length (approximate non contractual) : .... 1800 mm
Final colour : .............. RAL 9002 Pearl-grey (standard) Width (approximate non contractual) : ...... 1000 mm
Height (approximate non contractual) : ..... 2000 mm
Weight (approximate non contractual) : ......2200 Kg
Basic equipments
Routine tests according to IEC 60076 standard
Flat bi-directional rollers ( 125 mm) : ........................ 4
Lifting lugs : ................................................................. 4
Haulage holes on base : ...............................................
Earthing locations : ..................................................... 2
Rating plate fixed on HV side (Aluminium) : ............... 1
Electrical hazard warning labels (T10 warning) : ...... 2
Off-circuit tappings links,
acting on highest voltage : ......................................Yes
Multilingual installation manual : ................................. 1
Additional requested accessories
Anti vibration pads
3 PT100 sensors
T Digital thermometer (with RS 232 output connection)
Box for relay installed

Induced voltage dielectric test : ............................. Yes


Applied voltage dielectric test : ............................. Yes
Measurement of the no load
loasses and current : ............................................. Yes
Measurment of the HV and LV resistances : ....... Yes
Measurement of the load losses and Uk : ............. Yes
Measurement of the transformer
ratio & vector group : ............................................ Yes
Measurement of the partial discharge level : ......... Yes
Test report (in English) : ............................................ 1
Factory acceptance tests with customer : .............. No

Package: HV Switchgear, Distribution Transformer, MCC, EMCC and Distribution Panels


BKT WELLHEAD PLATFORM

Page | 41/42

Our ref.
Project name
Date

: E-0971
: BKT WELLHEAD PLATFORM
: October 06, 2014

Packing characteristics
Packing type : ........................................ Packing SEI4c
Wood quality : .................................................... normal

Dimensions & weights (packed transformer)


Length (approximate non contractual) : .... 2100 mm
Width (approximate non contractual) : ...... 1300 mm
Height (approximate non contractual) : ..... 2300 mm
Weight (approximate non contractual) : ......2516 Kg

Package: HV Switchgear, Distribution Transformer, MCC, EMCC and Distribution Panels


BKT WELLHEAD PLATFORM

Page | 42/42

Você também pode gostar