Once the system is heated up steam condenses due to normal radiation losses to the
surrounding air. These losses depend of course on the size and length of the pipe, on the
pressure of steam and its latent heat and mainly on the type and thickness of insulation. The
equation from which a normal regulation load can be calculated is:
F x HL ( T - t )
Q =
L
Where F = Length of Pipe (ft)
HL ( T t ) = Heat loss/foot of pipe at the temperature differential between steam and air
Above Table
L = Latent heat of steam ( BTUs/Hr. )
www.velansteamtraps.com
1-800-860-0233
sales@velansteamtraps.com
Condensate in LBS/Hr created in steam mains 1 to 24 and pressure of 600 to 2500 PSI based
on the warm up period of 1 hour and 100 feet of pipe, and based on the above assumption is
shown in tables.
For shorter or longer heating up time, multiply by 60/m where m is the warm up time in minutes.
www.velansteamtraps.com
1-800-860-0233
sales@velansteamtraps.com
Heat in
BTU/lb
Latent
Total
1017
1001
990
982
976
970
968
966
964
962
960
959
957
956
954
953
949
947
944
941
939
937
934
933
930
929
927
925
923
922
920
918
917
915
914
912
909
903
901
898
895
891
889
886
883
880
878
875
873
871
868
866
861
859
1119
1130
1137
1142
1147
1150
1151
1153
1154
1154
1155
1157
1157
1157
1159
1160
1161
1163
1164
1165
1166
1167
1167
1169
1169
1272
1273
1173
1174
1175
1176
1176
1177
1177
1178
1179
1180
1180
1183
1184
1185
1185
1187
1188
1188
1189
1190
1191
1192
1193
1193
1194
1194
1195
www.velansteamtraps.com
Specific
Volume
Cu. Ft./lb
142
73.9
51.3
39.4
31.8
26.8
25.2
23.5
22.3
21.4
20.1
19.4
18.7
18.4
17.1
16.5
15.3
14.3
13.4
12.6
11.9
11.3
10.8
10.3
9.85
9.46
9.10
8.75
8.42
8.08
7.82
7.57
7.31
7.14
6.94
6.68
6.27
5.84
5.49
5.18
4.91
4.67
4.44
4.24
4.05
3.89
3.74
3.59
3.46
3.34
3.23
3.12
2.92
2.98
1-800-860-0233
Latent
Total
857
855
853
851
849
847
845
843
841
839
837
836
834
832
830
828
827
825
823
822
820
819
817
815
814
812
811
809
808
806
805
803
802
800
799
797
796
794
793
791
790
789
788
786
785
784
783
781
780
778
777
766
751
740
728
1196
1196
1197
1197
1197
1198
1198
1198
1199
1199
1199
1200
1200
1200
1200
1200
1201
1201
1201
1202
1202
1202
1202
1202
1203
1203
1203
1203
1203
1203
1203
1203
1204
1204
1204
1204
1204
1204
1204
1204
1204
1205
1205
1205
1205
1205
1205
1205
1205
1205
1205
1205
1204
1204
1203
Specific
Volume
Cu. Ft./lb
2.74
2.68
2.60
2.54
2.47
2.41
2.34
2.29
2.29
2.19
2.14
2.09
2.05
2.00
1.96
1.92
1.89
1.85
1.81
1.78
1.75
1.72
1.69
1.66
1.63
1.60
1.57
1.55
1.53
1.49
1.47
1.45
1.43
1.41
1.38
1.36
1.34
1.33
1.31
1.29
1.28
1.26
1.24
1.22
1.20
1.19
1.18
1.16
1.14
1.13
1.12
1.00
.89
.82
.74
sales@velansteamtraps.com
Examples:
Warm up loss
Ambient Temp = 70F
Working Temp = 366F (150psig)
Warm up time = 720 minutes
1000 feet of 10 inch Schedule 40 pipe weighs = 40483
Latent heat = 857
40483 x (366-70) x .12 x 60
Q =
857 x 720
Q = 472 lbs/hr
www.velansteamtraps.com
1-800-860-0233
sales@velansteamtraps.com
Radiation loss
Ambient Temp = 70F
Working Temp = 366F (150psig)
Differential temp = 294F
Differential multiplier = .98
1000 feet 10 inch Schedule 40 uninsulated pipe
Latent heat = 857
1000 x 2600 ( .98 [factor for 296 diff] )
Q =
857
Q = 2973 lbs/hr