Escolar Documentos
Profissional Documentos
Cultura Documentos
STANDAR
D NUMBER
TITLE
INTERNATION
AL AND
INTERNATION
ALLY
RECOGNISIED
STANDARD
IS-2026
(Part 1 to 5
)
Power Transformers IEC-60076(Part I
to 5)
CBIP Publication
No.295
Manual on Power Transformers
IS-335 Insulating oil for transformers IEC-296,BS-148.
IS18662000
Electrical maintenance and Supervision
of mineral insulating oil in equipment.
IS-2099 Bushings for alternating Voltage above
1000V.
IEC60137(2008)
IS-2312 Fans (Cooler fans)
IS-2705. Current Transformers. IEC 60044
IS-325. Three phase Induction motors. IEC-34.
IS-375 &
IS-996
Marking & arrangements for switch
gear, bus bars, main connections &
auxiliary wiring.
IS-3637. Gas & oil operated relays.
IS-10028
(Part 1to3)
Code of practice for installation and
maintenance of transformers.
IS-2147. Degree of protection provided by
enclosures for low voltage switch gear
and control.
IEC
60529,IEC60947
IS-5. Colours for ready mix paints.
IS-6272 Industrial cooling fans.
DOC.ETD16
(3703)
Draft standard by BIS for revision of IS6600 for Guide for loading of oil
immersed transformers.
IEC 60354
OLTC IEC 60214
INDIAN
STANDAR
D NUMBER
TITLE
INTERNATION
AL AND
INTERNATION
ALLY
RECOGNISIED
STANDARD
IS 5561 Terminal connectors
Short Circuit Current calculation of
effects
IEC 865(part I &
II)
IS-5553 Shunt Reactors, Neutral/Earthing
Reactor and Arc Suppression Coil
IEC 60289
IS:335 Insulating oils for transformers and
switchgears
IEC:60296,
BS:223
IS -1886 Code of practice for installation and
maintenance of transformers.
Supervision and Maintenance guide for
Mineral Insulating Oil in Electrical
Equipment
IEC 60422
Method of Sampling of Liquid dielectrics IEC 60475
Guide for the Sampling of Gases and of
Oil from Oil-filled Electrical Equipment for
the Analysis of Free and Dissolved Gases
IEC 60567
Digital Recorders and Software for High
Voltage Impulse testing
IEC 61083
Specification for radio disturbance and
immunity measuring apparatus
CISPR 16
Guidelines for conducting design reviews
Accessories and quantity of oil for first filling including wastage & 10% extra
of that quantity, total weight of core + winding after assembly and total
weight of transformer are indicated in the technical bid by the manufacturers
on tentative basis and at the time of submission of drawing, wide
variations in these quantities take place. This is not in order and it will
be obligatory on the part of the Bidder to ensure that all these details are
worked out carefully and only correct figures after proper design are offered
in the technical bid. It may be noted that at the time of submission of final
drawings, variation in these weights beyond the limits of (+) 5% shall not be
permitted.
2.5 It will also be obligatory on the part of the Bidders to furnish details
of calculations for quantity (weight & size) of core material, quantity (weight
& size) of copper material, calculations for thermal and dynamic short
circuit withstand capability of transformer, calculations for pressure relief
valve, adequacy of size of AIRCELL Bag, volume of oil for adequate
cooling with calculations of size of conservator and other details as called
for in the specification. Furnishing of these calculations along-with technical
bid is a must. All the data should be supported with calculation details. In
addition, calculations for no. of thermosyphon filter and their adequacy be
furnished.
2.6 Interconnection : The transformers are meant for service as
interconnecting transformers and shall be capable of being energized either
from 400 KV side or 220 KV side. The auto transformer shall be capable of
being loaded at rated power on the 400 KV and 220 KV sides with tertiary
winding loaded at its full rating (lagging or leading or mixed load). On Load
Tap Changer and tertiary winding shall be suitable for such operation. The
OLTC shall be suitable for bidirectional flow of power.
3.0 SERVICE CONDITIONS
3.1 Climatic Conditions : The transformers and its accessories to be
supplied against this specification shall be suitable for satisfactory
continuous operation under the following tropical conditions.
1. Location At various substations within
The Bidder shall also indicate 160% & 170% over voltage/over
fluxing withstand capability period. Over fluxing withstand characteristics up
to 170% shall be submitted along with the bid.
4.4.4 Detailed calculations for maximum flux density and magnetizing
current for core material shall be furnished to substantiate the
above requirement. The Bidder shall enclose details of Core Material with
thickness of lamination, type designation and source of raw material and its
characteristic curves. All characteristic curves of material including Voltage Vs
Flux Density and Loss per Kg Vs Flux Density are to be enclosed with Bid
clearly indicating Flux Density selected for calculation of core losses (No load
loss). On the basis of these data, for the Flux Density and core material
chosen verification of Saturation Flux Density shall be done by the
purchaser, to know the margin considered in operating Flux Density .
4.4.5 The maximum current density for design of power
transformers within specified limits of transformer losses shall not
exceed the limits of 300 amps per sq.cm.
4.4.6 All other requirement of magnetic circuit shall be as per latest issue
of CBIP Manual no 295.
4.4.7 The transformers shall be either core type or shell type
construction, oil immersed, ONAN/ONAF/OFAF with external heat
exchangers and shall be suitable for outdoor service as inter connecting
Forced)
45oC 40oC.
7.0 FREQUENCY : All the transformers shall be suitable for continuous
operation with a frequency variation of + 4% to -4% from normal 50 Hz
without exceeding the specified temperature rise.
8.0 IMPEDANCE : The percentage impedance of the power transformer
shall be 12.5%, 30% & 45% between HV-IV, IV-LV & HV-LV respectively on
its own highest MVA base i.e 315 MVA base. Bidders shall indicate the
guaranteed impedance, tolerances and also the impedance on all taps for the
offered transformers. Impedance shall include positive and zero sequence
and shall be expressed in terms of the branches of the star connected
equivalent diagrams on all the specified MVA base and the range shall be
given for each branch of the equivalent circuit turn. It may be noted that if
required the percentage impedance should be designed identical to the
existing transformer of any make in case parallel operation is desired. The
IS tolerance on all matching taps are acceptable. Confirmation
regarding requirement of parallel operation should be given in the Bid.
It may be noted by the Bidders that for the purpose of matching
impedance of transformer, included in scope of this Bid, between 400KV,
220KV & 33KV main/ tertiary windings , the Bidders are not permitted to use
reactor or reactor/capacitor assembly. The design of the main winding should
MPPTCL/TECH/PROC/01/JULY 13 Page 10 of 125
meter of digital /numeric type suitable for specified CT ratio shall be provided
on the RTCC panel. In case size of CT is large provision of separate CT with
structure shall be included within the offered price. The tertiary winding shall
be designed to carry the fault current under worst fault condition.
10.0 COOLING : The Bidder may offer ONAN/ ONAF/ OFAF type of
cooling for these Transformer. Each transformer shall be provided with two
sets of radiator banks each rated for affording 50% cooling and required
number of air blast fans and oil pumps for normal operation. Each of the two
(50% rated) radiator banks shall have stand by fans. There shall be two oil
pumps for each Bank rated for 100% duty, one of the oil pumps being stand
by for each Bank. The OFAF cooling shall be in two groups each of 50%
capacity. Adequate number of fans and one cooling pump for providing
additional 20 % cooling capacity as standby shall be provided separately duly
mounted and wired for each group/bank of coolers in line with requirement
indicated in clause 15.1 ( C ).
11.0 CONSTRUCTION DETAILS : The features and construction details
of power transformer shall be in accordance with the requirements stated
hereunder
11.1 Tank
(A) As required in CBIP specification, the tank shall be of Bell type
construction for 315 MVA transformers covered under this
specification. Top cover of Bell type construction shall be
welded to the tank body .
(B) Tank shall be of welded construction and fabricated from
tested quality low carbon steel suitable for welding & of
following minimum sheet thickness.
Tank cover - 20 mm, sides including inspection cover- 10 mm
, Base - 20 mm.
(C) All seams and those joints not required to be opened at site
shall be factory welded and wherever possible they shall
be double welded. After completion of tank construction and
before painting, 'Dye Penetration Test' shall be carried out on
welded parts of jacking bosses, lifting lugs and all load
bearing members.
(D) Tank stiffeners shall be provided for general rigidity and these
shall be designed to prevent retention of water.
(E) The tanks shall be designed to withstand the following
without permanent distortion.
(i) Mechanical shocks during transportation.
(ii) Vacuum filling of oil at 10 milli torr in transformer
with all fittings.
(iii) Continuous internal pressure of 35 kN/m2 over normal
hydrostatic pressure of oil.
(iv) Short circuit forces &
MPPTCL/TECH/PROC/01/JULY 13 Page 12 of 125
(F) Where ever possible the transformer tank and its accessories
shall be designed without pockets wherein gas may collect.
Where pockets can not be avoided, pipes shall be provided to
vent the gas into the main expansion pipes if any.
(G) The shields shall be such that no magnetic fields shall exist
outside the tank. They shall be of magnetically permeable
material. If required impermeable shields shall be provided
at the coil ends. Tank shield shall not resonate when excited at
the natural frequency of the equipment.
(H) The tank shall be provided with :
(i) Lifting lugs suitable for lifting the equipment complete
with oil.
(ii) A minimum of four jacking pads in accessible position
at 500mm height to enable the transformer complete
with oil to be raised or lowered using hydraulic or
screw jacks. The location of jacking pads shall be such
that there should not be any interference with the civil
foundation of rails in either direction i.e. longitudinal or
transverse. A typical drawing no. MPPTCL/315MVA/01 for
providing jacking pad is enclosed with the Bid
specification.
(iii) Suitable haulage holes shall be provided.
(I) (i) Inspection cover/access windows & Manholes:
Suitable man-hole with a welded flange and a properly
gasketted bolted cover having of minimum thickness of
10 mm shall be provided on the tank cover. The manhole
shall be of sufficient size to offer easy access to
the lower ends of the bushings, terminal etc. The
requirement of inspection windows and manholes have
been stipulated in Annexure-IV & Bidders have to
confirm compliance of the same in their Bid.
(ii) Space for free movement in Transformer Tank for
inspection:
Details of passage & free space provided inside the
main tank should be indicated in concerned drawing to
allow free movement of at-least two persons for
inspection of active parts etc. To be more specific it
may please be noted that minimum clearance from
outer most winding/connection leads/supports to
tank shall not be less than 300 mm. on all 4 sides
with suitable platform on bottom of the tank to
facilitate free movement of person all around inside
the tank.
MPPTCL/TECH/PROC/01/JULY 13 Page 13 of 125
(P) Suitable earthing bridge between upper and lower tank shall be
provided at least on two places each on HV & IV side and one
place on other both sides.
11.2 Tank Cover
(a) The tank cover shall be sloped to prevent retention of rain
water and shall not distort when lifted.
(b) Inspection cover/man holes shall be provided as per
Annexure-IV.
(c) The tank covers shall be fitted with pockets at the position
of maximum oil temperature of MCR (Maximum
Continuous Rating) for inserting bulbs of oil and winding
temperature indicators. It shall be possible to remove these
bulbs without lowering the oil in the tank. The thermometer
shall be fitted with a captive sensor to prevent the ingress of
water.
(d) Bushings, turrets, covers of inspection openings,
thermometer, pockets etc., shall be designed to prevent
(c) The track/rail gauge shall be 1676 mm along the longer side,
as well as along the shorter axis. However Rails shall be placed
perpendicular to the bushing line.
(d) Pulling eyes shall be provided to facilitate movement/pulling of
the transformers and these shall be suitably braced in a
vertical direction so that bending does not occur when the
pull has a vertical component.
11.4 Axles And Wheels
(a) The transformers are to be provided with flanged bidirectional
wheels and axles. These shall be so designed as
not to deflect excessively to interfere with the movement of
the transformer. Wheels shall be provided with suitable
bearings which shall be rust and corrosion resistant.
Fittings for lubrication shall also be provided.
(b) Suitable locking arrangement along-with foundation bolts
shall be provided for the wheels to prevent accidental
movement of transformer. The locking arrangement shall be
such that it can be locked with plinth of transformer. The
length of the arrangement should be adequate to cover height
of the rail. No floating type locking arrangement shall be
accepted
(c) The wheels are required to swivel and they shall be arranged
so that they can be turned through an angle of 90 degrees
when the tank is jacked up to clear of rails. Means shall be
provided for locking the swivel movements in positions
parallel to and at right angles to the longitudinal axis of the
11.7 Tank Earthing Arrangement : Two earthing pads complete with two
number tapped holes M10 bolts plain and spring washer suitable for
connection to 75x8mm GI flat shall be provided each at position close to two
diagonally opposite bottom corners of tank. Earthing strips up to the
ground level and its connection with station earth pit shall be
provided by the Bidder.
11.8 Pressure Relief Device : A minimum of 3 (three) number of
pressure relief devices of reputed make and reliable quality shall be
provided on each transformer and these shall be mounted preferably
on the tank cover above each phase winding. Bidders must submit
MPPTCL/TECH/PROC/01/JULY 13 Page 17 of 125
calculations to prove that the no and capacity of pressure relief device with
location of each PRV provided on the transformer will adequately meet our
requirement. The quantity of three numbers is on the basis that two numbers
will be required as per design calculation and one number additional PRD shall
be provided from the point of view of additional safety.
Constructional and design details of pressure relief device must be furnished
and it should be proved by calculation that the size and operating pressure
setting of pressure relief device is adequate, considering the rating of the
transformer and quantity of oil in the transformer. Furnishing of this
information is a must. These PRD's shall be of sufficient size for rapid
release of any pressure that may be generated in the tank and which may
result in damage to the equipment. The device shall operate at a static
pressure of less than the hydraulic test pressure of transformer tank. It
shall be mounted directly on the tank. One set of electrically insulated
contacts shall be provided for alarm & tripping along-with the
recommendations.
11.9 Relays
11.9.1 Buchholz Relay : A double float type Buchholz relay along with
suitable moulded type cover to avoid ingress of moisture/ rain water shall be
provided. All the gases evolved in the transformer shall collect in this relay.
The relay shall be provided with a test cock suitable for a flexible pipe
connection for checking its operation and for taking gas sample. A copper
or stainless steel tube, shall be connected from the gas collector to a
valve located about 1200mm above ground level to facilitate sampling of
gas while the transformer is in service. The device shall be provided with
two electrically independent ungrounded contacts, one for alarm on gas
accumulation and the other for tripping on sudden rise of pressure. The
contacts of relay shall be properly housed, sealed and gasketted to make the
arrangement water proof. Entry of moisture/water in the contact chamber
needs to be eliminated. Cable entry to terminal box of buchholz relay should
be made through bottom of relay.
11.9.2 Oil Surge Relay (OSR) : From our past experience, it is found
that undesired tripping of Power Transformers is occurring on oil surge relay
(OSR)and Buchholz relay operation actuating due to accumulation of water
inside relay pockets. The water accumulation takes place through entry
point of cable gland. In view of above, the design and placement of Alarm &
trip contact assembly of OSR and Buchholz Relay should be improved to
take care of the following requirements:
(a) The cable entry to terminal box of OSR should be made through
bottom of relay. Also the OSR relay should be protected from rain
water by providing proper cover on it.
(b) In order to ensure exit/drainage of accumulated water from inside the
relay, a fine hole should be made in terminal box of relay.
MPPTCL/TECH/PROC/01/JULY 13 Page 18 of 125
Note : The Bidders shall ensure that the compartments housing relay
contacts of Pressure Relief Valve , Buchholz Relay and Oil Surge Relay are
made absolutely water and vermin proof. The compartment housing
contacts of OSR,PRV and Buchholz Relay shall be tested for water proof at
the time of inspection and effectiveness of water proofing shall be
demonstrated at the time of inspection. This should be noted carefully by
the Bidder and specifically confirmed in their bid.
11.9.3 Rapid Pressure Rise Relay (RPRR) : The provision for the
same be made on the main tank to operate on rate of rise of pressure. An
electrically insulated trip contact shall be provided in RPRR relay as per
requirement of NIFPS.
11.10 Temperature Indicator
11.10.1 Oil Temperature Indicator (OTI) :Transformers shall be
provided with a 150mm dial type thermometer with maximum pointer for
top oil temperature indication. The thermometer shall have adjustable two
electrically isolated heavy duty alarm and trip contacts, maximum reading
pointer and resetting device mounted in the Fan control cubicle (FCC). A
temperature sensing element suitably located in a pocket on top oil shall be
provided. This shall be connected to the OTI by means of capillary
tubing. Accuracy class of OTI shall be plus or minus 1.0% or better. The OTI
shall be provided with anti vibration mounting .
11.10.2 Winding Temperature Indicator (WTI)
(a) WTI for measuring the winding temperature of each of the
windings (HV, IV, Tertiary) shall be provided. It shall
comprise of the following
(i) Temperature sensing element.
(ii) Image coil.
(iii) Auxiliary CTs, if required, to match the image coil, shall
be provided.
(iv) 150mm dia local indicating instrument with maximum
reading pointer mounted in FCC/marshalling box and with
four adjustable electrically isolated heavy duty contacts
(two for control of cooling equipment, one for high
winding temperature alarm and other for trip) shall be
provided. The WTI shall be provided with anti vibration
mounting.
(v) Calibration device.
(b) In addition to the (a) above, repeater dial of WTI for each
winding shall be provided for Remote winding temperature
indication. It shall be suitable for flush mounting on RTCC
panel. A precision potentiometer mounted inside the case
shall function as a transmitter to operate a repeater for
MPPTCL/TECH/PROC/01/JULY 13 Page 19 of 125
S.
N
o
Nomin
al
Syste
m
Voltag
e
Voltage
Class of
Bushing
Current
Rating
Impulse
Withstand
Voltage
(Kvp)
1 Min.
Power
Frequency/
Switching
Impulse
Voltage
Kv (Rms)
Creepage
Distance
in mm
Clearance
in mm
Ph to
Ph
Ph
to
E
1 400KV 420KV 1250A 1425 630/1050 10500 4000 3500
2 220KV 245KV 1250A 1050 460 / - 6125 2700 2400
3 33KV 72.5KV 3150A 325 140 / - 1813 700 660
The Bidders are required to confirm clearances and no change
/reduction in clearances shall be acceptable. The clearances
shall be clear distances in air after accounting for
clamps/connectors dimensions to be mounted on the stud of
bushings.
(j) Special adjustable arcing horns shall be provided for the HV &
IV bushings. For 72.5KV class bushings, arcing horns are not
required.
(k) The Bidder is requested to furnish the guaranteed withstand
voltage for the above and also furnish a calibration curve with
different settings of the coordination gap to the purchaser
to decide the actual gap setting. Bidder's
recommendations are also invited in this respect.
(l) The bushings shall be capable of withstanding without injury
the electrical, thermal and mechanical effects of external
short circuits. Bushings shall be rated for short time
thermal current rating of 63/ 40/ 31.5 KA for 3 seconds, for
400/ 220/ 33 KV respectively.
(m) All the transformers covered under this specification shall be
utilized in heavily polluted atmosphere. In view of this the
Bidders while offering prices for the transformers against
this contract may please note that the offer should be made
out based on the creepage for the bushings @ 25mm per KV
based on the voltage of 72.5KV/245KV/ 420KV. Thus in the
quoted prices of transformer cost of bushings should be
included based on a creepage distance of 25mm per KV.
(n) All O.I.P. Condenser bushings shall be provided with :
(i) Oil level gauge.
(ii) Oil filling plug and drain valve, if not hermetically sealed.
(iii) Tap for capacitance/tan delta test.
(o) When bushings have an under-oil end of reentrant form, the
pull through lead shall be fitted with a gas bubble
deflector.
MPPTCL/TECH/PROC/01/JULY 13 Page 26 of 125
(d) The OLTC motor should be capable of smooth and trouble free
operation with supply voltage variation of 0.4KV -25% &
+10%.
(e) The design of the tap changing arrangement shall be such that
there should be minimum variation of ohmic impedance of the
transformer from minimum to maximum tap. The permissible
tolerance on these ohmic values shall be plus minus 10%.
14.2 On Load Tap Changing Gear (OLTC)
(a) The details of the method of diversion of the load current
during tap changing, the mechanical construction of the gear
and the control features for OLTC gear alongwith detailed
drawings on the inner view and the arrangement of
connections shall be submitted with the Bid. Information
regarding the service experience on the gear and a list of
important users shall also be furnished. The tap changer shall
change the effective transformation ratio without producing
phase displacement.
(b) The current diverting contacts shall be housed in a separate oil
chamber not communicating with the oil in main tank of the
transformer.
(c) The contacts shall be accessible for inspection without
lowering oil level in the main tank and the contact tips shall
be replaceable.
(d) The Bidder shall indicate the safeguards employed to take care
of harmful arcing at the current diverting contacts in
the event of operation of the OLTC gear under overload
conditions ( overloading capability as per IS 6600 ) of the
transformer. Necessary tools and tackles shall be provided
diagram.
viii) Transformer load tap changer shall be equipped with a
fixed resistor network capable of providing discrete
voltage steps for input to the supervisory system. Any
other approved / established design for remote indication
of tap position shall also be acceptable.
(i) Limit switches shall be provided to prevent over-running of
the mechanism and in addition, a mechanical stop shall be
MPPTCL/TECH/PROC/01/JULY 13 Page 32 of 125
(w) The location and design of OLTC shall be such that in the
event of any repair / maintenance , it should be possible to
take out various parts from the OLTC and other accessories
in same position.
iii. Master Position : If the selector switch is in MASTER
position, it shall be possible to control the OLTC units in the
FOLLOWER mode by operating the controls of the MASTER
unit Independent operation of the units under FOLLOWER
mode shall have to be prevented. However, the units
under independent mode will be controlled independently.
iv. Follower Position : If the selector switch is in FOLLOWER
mode, control of OLTC shall be possible only from MASTER
panel.
v. Independent Position : In this position of Selector Switch,
Control of OLTC of individual unit only shall be possible.
14.6 Local OLTC Control Cubicle : The Auxiliary devices for
electrical control of the OLTC shall be housed in a weather proof cubicle . It
shall be complete with the following :
i) A circuit breaker/contactor with thermal overload devices for
controlling the AC auxiliary supply to the OLTC motor.
ii) Cubicle light with door switch.
iii) Space heaters to prevent condensation of moisture.
iv) Padlocking arrangement for hinged door of cabinet.
v) Cable terminal glands for power and control cables to the
OLTC gear.
14.7 Remote Tap Changer Control Panel (RTCC Panel) : Remote
tap changer control panel to be supplied by the Bidder shall consist of :
i) Actuating switch for electrical raise/lower control.
ii) Remote tap position indicator.(preferred digital type)
MPPTCL/TECH/PROC/01/JULY 13 Page 35 of 125
iii) Signal lamps for Tap changer in progress and Tap changer out
of step.
iv) Auxiliary devices for remote electric group control of OLTC.
v) Annunciation scheme with the following :
- Fan/pump fail (for all fans individual windows).
- AC supply fail.
- Stand by fan fail.
- Stand by fan on.
- OLTC motor over loaded.
- OLTC control supply fail.
- OLTC at extreme position i.e. lowest & highest voltage tap.
- Two spare windows.
vi) Indicating Devices : Following lamp indications shall be
provided in Remote tap changer control cubicle / panel- Fan "ON", Fan "OFF"
- Pump "ON", Pump "OFF
- Cooling system "On Automatic Control".
- Cooling system "On Manual".
- No flow/Reverse flow of oil in oil pump.
- Selector switch in auto or manual.
- 0.4 KV cooler supply auto changeover.
- Cooler supply failure for each supply.
- Oil pump failure for each pump.
- Control supply failure main and standby.
- one potential free initiating contact for all the above
indications shall be wired independently to the
terminal blocks of cooler control cabinet exclusively for
owner's use.
vii) Remote OTI with repeater unit.
viii) Separate WTI 2 nos. for HV, one no. for IV and one no. for LV
winding operated by signal transmitter.
ix) Voltmeter for indicating HV, IV and tertiary voltage.
x) Schedule of equipments for RTCC panel shall be as under:
- Name plate remote OLTC and cooler control cubicle
- Indicating lamp-OLTC control supply on ( red)
- Indicating lamp-tap change in progress ( yellow)
- Indicating lamp-OLTC out of step ( red)
- Indicating lamp-OLTC motor trip ( red)
- Cooler mode selector (auto-off-on)
- OLTC sequence selector switch.(OFF-INT-FOLL-MAST.)
- Emergency stop push button for tap change operation. (red)
- Auxiliary contactor for OLTC out of step monitoring.
MPPTCL/TECH/PROC/01/JULY 13 Page 36 of 125
d) Two (2), 100% centrifugal oil pumps (out of which one pump
shall be standby) shall be provided with each radiator bank.
Measures shall be taken to prevent mal-operation of Buchholz
relay when all oil pumps are simultaneously put into service.
The pump shall be so designed that upon failure of power
supply to the pump motor, the pump impeller will not limit the
natural circulation of oil. Under failure of main oil pump, the
changeover from main to standby oil pump shall be automatic.
e) Cooling fans and oil pump motors shall be suitable for
operation from 0.4 KV, three phase 50 HZ power supply and
shall conform to IS:325.
f) An oil flow indicator shall be provided for the confirmation of
the oil pump operating in a normal state. A provision shall be
made in the flow indicator to indicate reserve flow of oil/loss of
oil flow.
g) The exhaust air flow from cooling fan shall not be directed
towards the main tank in any case. Cooling fans for each
radiator bank shall be located so as to prevent ingress of rain
water. Each fan shall be suitably protected by galvanised wire
guard.
h) The cooler and its accessories shall preferably be hot dipped
galvanised or corrosion resistant paint shall be applied to it.
i) Each cooling fan shall be provided with starter thermal
overload and short circuit protection and also single phase
preventor.
j) Each radiator shall be provided with suitable lifting lugs and
shut off/air release/sampling valves as per Annexure-V
k) Expansion joints, one each on top and bottom cooler pipe
connections as per a above.
l) Air release device/plug and oil drain plug on oil pipe
connections.
m) The cooling Fans shall be mounted on separate
foundation. Mounting of Cooling fans directly on
Radiators or on transformer tank is not acceptable .
The radiators mounting arrangement is to be indicated
by the Bidder in his Bid.
n) Cooling fan support shall be of adequate strength to avoid
bending etc.
o) The mounting arrangement of cooling fans shall be subject to
drawing approval from MPPTCL.
MPPTCL/TECH/PROC/01/JULY 13 Page 39 of 125
16.3 A space heater and cubicle lighting with ON-OFF switch shall be
provided.
16.4 Terminal Blocks
a) The terminal blocks to be provided shall be fully enclosed
with removable covers and made of moulded, non
inflammable plastic material with block and barriers moulded
integrally .Such block shall have washer and binding screws for
external circuit wire connections, a white marking strip for
circuit identification and moulded plastic cover. All
terminals shall be clearly marked with identification
numbers or letters to facilitate connection to external wiring.
b) All internal wiring to be connected to the external equipment
shall terminate on terminal blocks, preferably vertically
mounted on the side of each panel. The terminal blocks
shall be 1100 V grade and have 10 amps continuous
rating, moulded piece, complete with insulated barriers,
non-disconnecting stud type terminals, washers, nuts
and lock nuts. Terminal block design shall include a white
fiber marking strip with clear plastic, slip-on/clip-on terminal
cover. Markings on the terminal strips shall correspond to wire
number and terminal numbers on the wiring diagrams.
c) Terminal blocks for current transformer secondary leads
shall be provided with test links and isolating facilities. Also
current transformer secondary leads shall be provided with
short circuiting and earthing facilities.
d) Unless otherwise specified, terminal blocks shall be
suitable for connecting the following conductors on each
side.
For all circuits except current transformer circuits minimum of
two nos. 2.5 mm2 copper.
For all CT circuits minimum of four nos. 4.0 mm2 copper.
e) There shall be a minimum edge to edge clearance of 250
mm between the first row of terminal blocks and the
associated cable gland plate. Also the clearance between two
rows of terminal blocks shall be a minimum of 150 mm.
f) Arrangement of the terminal block assemblies and the wiring
channel within the enclosure shall be such that a row of
20.2 Although oil for the transformer is included in the scope of supply, but
it may be noted that the transformer shall be supplied duly N 2 gas filled with
suitable arrangement to ensure that the pressure of gas is regularly
maintained during transit and upto the date of filling of oil. For this
purpose, necessary gas cylinders with regulator shall be supplied on non
returnable basis. Additional gas cylinders required recouping and
maintaining of positive Nitrogen pressure upto filling of oil should be
supplied by the manufacturer of Transformers and the offered price
should take into account this requirement.
20.3 The quality of the oil supplied with transformer shall conform to the
oil parameters specified in this clause. No inhibitors shall be used in the oil.
The oil samples of transformer will be drawn for the oil used at factory &
site as follows.
i. Prior to filling
ii. Before and after heat run test / pre-commissioning test
iii. Before energizing.
All tests as per IS:335 (latest revision) , IEC, ASTM standards shall
be conducted on oil samples.
20.4 Sufficient quantity of oil necessary for first filling of main tank, coolers,
radiators and conservators etc. upto the proper level plus anticipated
quantity of wastage of oil during first filling shall be supplied in tankers. Please
note, wastage means quantity of oil absorbed during initial filling at works for
testing. In addition to the oil needed for first filling, 10% extra quantity of oil
for topping up in future, shall be supplied in non-returnable containers
suitable for outdoor storage. Therefore, total quantity of oil required for first
filling shall be measured at works at the time of testing on unit subjected to
heat run test.
20.5 The supplier shall dispatch the transformer in an atmosphere of
pressurised Nitrogen. In this case, necessary arrangement shall be ensured
by the supplier to take care of pressure drop of nitrogen during transit and
storage till completion of oil filling during erection. A gas pressure testing
valve with necessary pressure gauge and adapter valve shall be provided.
20.6 The supplier shall warrant and confirm that oil to be used for the
transformer testing at Works & oil to be supplied for the transformer is free
from Polychlorinated Biphenyls (PVB/PCB). The transformer oil to be used
and supplied by the bidder for first filling at site shall be new oil of EHV GradeI having technical specification mentioned hereunder . Hence Oil to be used
by the manufacturers at factory for the purpose of testing at their
works shall be of similar or better quality having parameters matching
with the parameters specified in the specification. Specific approval of
oil test results of oil proposed to be used for testing of transformer in
factory shall be obtained by the manufacturer from the purchaser
before first filling in the unit. MPPTCL shall not accept any other oil for
testing purposes having lower parameters than those specified in the
Bid. Bidders should specifically confirm this requirement in their offer.
MPPTCL/TECH/PROC/01/JULY 13 Page 48 of 125
Sl.
No
Characteristics Requirement Method of Test
1. Appearance The oil shall be clear
and transparent and
free from suspended
matter or sediment
A representative
0.02 percent by
weight
IS:335 Appendix `C
13. Presence of oxidation
inhibitor
The oil shall not
contain antioxidant
inhibitors .
IS:335
Appendix `D
MPPTCL/TECH/PROC/01/JULY 13 Page 49 of 125
Sl.
No
Characteristics Requirement Method of Test
14. SK value 6% maximum IS:335
15. Water content,
maximum.
10 ppm IS:2362,IS 13567
16. Ageing characteristics
after accelerated ageing
(open Breaker method
with copper catalyst)
a) Resistivity
i. 27oc
ii. 90oc
b) Tan delta at 90oc
c) Total acidity (max)
d) Sludge content
by weight
2.5x1012 ohm.cm(min)
0.2x1012ohm.cm(min)
0.15 (max.)
0.05 mg KOH/gm
0.05% (max)
As per ASTM-D
1934, IS 12177,IEC
62021
17. Oil sample taken from
the transformer after
the completion of site
processing and tested in
approved manner shall
have the following
values before
commissioning of the
transformer.
i. Break down
strength
ii. Moisture content
iii. Resistivity at 90oc
minimum
iv. Interfacial Tension
at 27oc
v. Dielectric
dissipation factor at
90 oC
Minimum 70 KV
withstand
Maximum of 10 ppm
35x1012 ohm.cm
(min)
0.04 N/M (min)
0.002 (max.)
Tested in accordance
with IS :335
18 N-dm analysis
CA%
CN%
CP%
4 6%
40-43%
51-54%
20.7 AIR CELL: Our technical specification calls for supply of power
transformers with air cell type oil preservation system of PRONOL,
make only. It is obligatory on the part of the Bidders to clearly submit
complete constructional and technical details of sealing arrangement, duly
supported with technical details, pamphlets and dimensional drawings.
MPPTCL/TECH/PROC/01/JULY 13 Page 50 of 125
While furnishing details for the above sealing arrangement the Bidders
must confirm clearly that the size and capacity of sealing arrangement is
adequate for the transformer and for the quantity of oil required for the
transformers. Necessary calculation/documentary proof shall be furnished.
20.8 Air cell type oil preservation system included with each transformer
shall ensure as under:
(a) The air inlet of COPS (Conservator Oil preservation System) shall
be properly fitted on the conservator for leak proof arrangement to
ensure that the air does not come in contact with oil under any
circumstances.
(b) The size and capacity of the COPS (Conservator Oil preservation
System) shall be selected to suit the design of Conservator and to
ensure proper operation for the quantity of oil in the unit with the
proper allowances. The COPS shall be of reputed make, proven
design and of established performance. Details in this regard are to
be submitted with the offer by the Bidder for verification . The
Bidder is required to submit calculation with bid to prove
adequacy of air cell & its size.
(c) The Bidder shall clearly indicate in the manual the procedure
for installation of COPS and precautions to be taken at the time of
first oil filling under vacuum in the transformer.
20. 9 SPECIFICATION OF FIRE PROTECTION SYSTEM : Nitrogen
injection type fire prevention & extinguishing system with flow sensitive
conservator isolation valve shall be provided for all the transformers.
20.9.1 Nitrogen Injection Fire Protection System (NIFPS) shall be
designed to prevent explosion of transformer tank and the fire during internal
faults resulting from arc and also to extinguish the external oil fires on
transformer due to tank explosion and/or external failures like bushing fires,
OLTC fires and fire from surrounding equipments, etc. The system shall work
on the principle of Drain & stir. On activation, it shall drain a pre-determined
quantity of oil from the tank top through drain valve to reduce the tank
pressure, isolate conservator tank oil and inject nitrogen gas at high pressure
from the bottom side of the tank through inlet valves to create stirring action
and reduce the temperature of oil below flash point to extinguish the fire. The
quantity of oil removed from the tank shall be such that adequate amount of
oil shall remain to cover active part, i.e. core coil assembly even after
stoppage of oil drain. Electrical isolation of transformer shall be an essential
pre-condition for activating the system. The NIFPS shall conform to NEPA
70 standard titled Fire protection of transformers & transformer
vaults and Tariff Advisory Committee (TAC) regulations .
20.9.2 OPERATIONAL CONTROLS: The system operation shall be fully
automatic and activate from the required fire and other trip signals. In
addition to automatic operation, remote operation from control room/ remote
MPPTCL/TECH/PROC/01/JULY 13 Page 51 of 125
centre and local manual control in the fire extinguishing cubicle shall also be
provided. System shall operate on following situations.
20.9.3 PREVENTION OF TRANSFORMER EXPLOSION AND FIRE: To
prevent transformer explosion and fire in case of an internal fault, signals
given by operation of Electrical protection relays and tripping of circuit breaker
of transformer and operation of either Buchholtz relay, or pressure relief valve
(PRV) alongwith Rapid Pressure Rise Relay (RPRR) shall be used to
activate the system and logic for RPRR for system activation should
include for operation of Electrical protection relays and tripping of
circuit breaker of transformer. The exact logic for system activation shall
be finalized during detailed engineering.
20.9.4 FIRE PROTECTION: In case of fire, sensed by fire detectors, the
system shall be activated only after electrical isolation of the transformer,
confirmed by breaker trip. If the fire detection is not associated with any other
fault, the system activation shall be only manual. Manual operation switch
shall be provided in the control room/ remote control centre with a cover to
avoid accidental operation of it.
20.9.5 OPERATION OF SYSTEM: On receiving activation signal, the
following shall take place:
i. Open the quick opening drain valve to drain the top layer oil
ii. Shut off the conservator isolation valve to prevent flow of oil from the
Conservator tank to the main tank.
iii. Open the Nitrogen regulator valve to inject Nitrogen into the
transformer tank to create stirring of oil.
There shall be interlock to prevent activation of the system if the transformer
is not electrically isolated. There shall also be provision for isolating the
system during maintenance and/or testing of the transformer.
20.9.6 TECHNICAL PARTICULARS: The supplier shall be responsible for
the design of the complete system and shall submit the drawings and design
calculations for the number of fire detectors, pipe sizing of drain pipe and
Nitrogen injection pipe, Nitrogen cylinder capacity, number of injection points,
etc. and get approval from purchaser. Facility shall be provided to test the
system when the transformer is in service, without actually draining the oil
and injecting Nitrogen. The Nitrogen regulator valve shall be designed in such
a way that the Nitrogen shall not enter the transformer tank even in case of
passing/ leakage of valve. The system shall work on station DC supply.
MPPTCL shall give two distinct DC feeders in control. The control box of fire
protection system shall have facility to receive these feeders for auto change
over of supply. It shall be the contractors responsibility to further distribute
power to the required locations.
MPPTCL/TECH/PROC/01/JULY 13 Page 52 of 125
Following indications and alarms shall be provided in the cubicle as well as the
control box: Nitrogen cylinder pressure indication.
Nitrogen cylinder pressure low.
Fire in Transformer/ Reactor.
Oil drain started.
Conservator oil isolation valve closed.
Nitrogen injection started.
20.9.7 DETAILS OF SUPPLY & WORK FOR SYSTEM EQUIPMENTS AND
OTHER RELATED ACTIVITIES: The scope of supply shall include the
following items, any other items required for safe & trouble free operation of
the system and the scope of works include complete earthwork (i.e.
excavation, backfilling etc.), scope of supply also includes services to be
availed by the purchaser for erection and commissioning of NIFPS at EHV
substations
of MPPTCL in MP. , civil work with civil material for the entire open/
buried piping for the fire protection system, construction of safety wall,
construction of oil pits with provision of oil storage tank of MS and pipe
supports for open/ buried, entrenched and overground piping. The system
design shall also conform to TAC/NFPA norms.
(i) Fire extinguishing cubicle with base frame and containing at least the
following:
Nitrogen gas cylinder of sufficient capacity with pressure regulator and
manometer with sufficient number of adjustable NO contacts.
Oil Drain Assembly including oil drain pipe extension of suitable size for
connecting pipes to oil pit.
Mechanical release device for oil drain and nitrogen release.
Limit switches for monitoring of the systems.
Panel lighting.
Flanges on top of the panel for connecting oil drain and nitrogen injection
pipes for transformer.
Limit switch for pressure switch/sensor.
Pressure indicators for Nitrogen pressure in the cylinder and after
Nitrogen regulator.
(ii) Control box to be installed in the control room of the station for monitoring
system operation, automatic control and remote operation, with alarms,
indication light, switches, push buttons, audio signal, suitable for tripping
and signaling.
(iii) Conservator isolation valve which shall be flow sensitive and shut off
when the flow in the pipe is more than the flow expected in the permissible
normal operating conditions. It shall be provided with position indicator
remote alarm indication.
(iv) Required number of fire detectors to be located in strategic locations to be
finalized during detailed engineering.
(v) Flow Sensitive Conservator Isolation Valve.
MPPTCL/TECH/PROC/01/JULY 13 Page 53 of 125
(vi) All controls, alarms, panels, cables, cable trays (if required), junction
boxes, Valves etc.
20.9.8 INSTALLATION AND PRE-COMMISSIONING TEST: After
installation the system pre-commissioning tests shall be carried out jointly
with the MPPTCL representative before the system is put in service.
20.9.9 In order to restrict the supply of oil in case of a fire in transformer,
provision shall be made to isolate the conservator oil from the main tank.
20.9.10 A valve which shall be flow sensitive and shut off when the flow in
the pipe is more than the flow expected in the permissible normal operating
conditions. This valve shall be located in the piping between the conservator
and the buchholz relay and shall not affect the flow of oil from and to the
conservator in normal conditions.
20.9.11 When the flow from conservator to main tank is more than the
normal operating conditions, the valve shall shut off by itself and will have to
be reset manually. It shall be provided with valve open/close position
indicator along with alarm indication in control room during closing operation
of valve.
20.9.12 Necessary switches shall be provided in cooler control cabinet /
common marshalling box for manual open / close operation of the valve.
Bidders shall offer Transformers completely fitted with Nitrogen
Injection Fire Protection Systems, separately in their offer in schedule
of prices .
20.10 ON LINE MONITORING DEVICE FOR TRANSFORMER
20.10.1 The Bidder should offer for a suitable on line monitoring device
for regular monitoring of 3 key gases and moisture for condition
assessment and fault detection of the 400 KV 315 MVA transformer . The
device should measure 3 key dissolved gases viz. Hydrogen, Acetylene,
Carbon mono oxide with accuracy of 10%. The minimum range of
measurement of dissolved gases shall be Hydrogen :5 to 500, Acetylene : 3
to 5000, Carbon mono oxide : 10 to 5000 . The moisture content shall be
measured from 0 to 100 % RS (in ppm). The device shall have non volatile
memory storage to prevent loss of data. The device shall be provided with
user configurable at least six alarm contacts & two front panel LED arrays.
The alarm setting screen shall be available for setting alarms based on level of
3 Key gases or moisture and rates of change for Key gases. For configuring
the six alarm settings, suitable PC software shall be provided with the device.
The device shall be supplied with two separate channels for remote
communication plus local USB and Ethernet connections. The device should
support communication Protocol viz. MODBUS, DNP 3.0 and IEC-61850. It
shall be possible to configure sampling rates to hourly/ daily. The alarm &
Caution thresholds shall be user configurable. The device should support Load
monitoring by analyzing results with loading of Transformer and device shall
MPPTCL/TECH/PROC/01/JULY 13 Page 54 of 125
be provided with suitable software for graphical trending & diagnostic analysis
of results. The device shall have minimum maintenance requirements.
On line monitoring unit shall not be mounted on the body of the
transformer. A separate mounting arrangement near the transformer body
with proper protective sheds & covers for protection against sun and rains be
provided. The mounting cubical shall have provision for ventilation/cooling
and also provision for reading of parameters by operators without opening
the box. On line monitoring unit shall be complete with provision for remote
monitoring alarm and indication in RTCC panel in control room. Complete
details of offered device shall be submitted by the Bidder and explained by
suitable manual/pamphlets.
External temperature range : 0 to 55 o C
Operating Humidity : 10 to 95% RH non condensing
Enclosure : IP55
Input Power requirement : Voltage 120 to 260 V AC, Frequency 47 to
60 Hz; The power supply should be able to
withstand electrical surges & disturbances
prevalent in EHV substation.
20.10.2 Bidders shall offer Transformers completely fitted with On