(d) air break (under atmospheric pressure) CB ; (e) compressed gas (air or sulphur hexafluorid) CB. Oil circuit-breaker is used throughout the whole range of voltages and powers, but especially below 66 kV . The small-oilvolume circuit-breaker retains oil as the insulating and extinguishing medium, but the circuit-breaking compartment is separated from the link mechanism compartment . Such separation permits of reduced clearances since the carbonization of oil only occurs in the circuit-breaking compartment , the oil in the link mechanism compartment staying clean . This design of circuit-breaker has its main application in the 33 kV to 220 kV voltage range . The air-blast circuit-breaker is used over a wide range of voltage up to the highest transmission voltages, but the need for a reliable supply of compressed gas at relatively high pressure confines its use to large installations where many circuitbreakers share the same compressed air supply . It is also noisy in operation , which makes it unsuitable for outdoor use in built-up areas, although noise suppressors are now fitted to most 400 kV units . Airbreak and compressed gas-break circuit-breakers are mainly used for power station auxiliary supplies , or 1
in distribution , form 3.3 kV to 11KV or in the 40-550
volt range. Typical ratings are in the range 800-3000 amperes , with a breaking capacity of 30 MVA . Miniature circuit-breakers, widely used in building installations, are also of air-break type with magnetic blow-out of the arc . The use of compressed gas , air of SF6 , not only for circuit breaking but as an insolent, has further reduced size and weight of circuit-breakers but with the added complication of gas tightness . Pressures up to 500 Ib/in2 are used in the circuitbreaking chamber and 100 Ib/in2 for the insulation of live components . Vacuum circuit-breakers in which the arc is struck in a vacuum have been successfully made up to 132 kV , but again the necessary vacuum pumping equipment is a heavy additional cost unless it can serve a number of circuit-breakers . :Single Line Diagram And Layout of The Present 66/11 kV Substation (8.6)
Figure (8.1) presents the single line diagram of the 66/11
kV substation that feeds the residential area in out project . Figure shows that the substation consists of a sectionalized double bus bar system fed by six 66 kV cables , two incoming from the preceding substation in the 66 kV ring and two are outgoing to the next substation in the ring and remains two 66 kV feeder cells as reserve . The bus bar sections are coupled via 2
a bus coupler consisting of a circuit breaker and two isolating
switches , together with four isolating switches dividing the bus bars into four sections . Four 66/11 kV , 35 MVA transformers are fed from the bus bars , and are connected in parallel groups or each to a separate section of the bus bars. The transformer connection circuit to the bus bar , as well as the feeder connection circuit, consists of a 66 kV circuit breaker with two isolating switches towards the bus bars and one after the circuit breaker on the other side . Current and potential transformers are connected in the circuits for the objectives of protection and measuring . The transformers are connected via circuit breakers to the 11 kV sectionalized bus bar . This is cut into four sections coupled with four bus couplers . Outgoing 11 kV feeders come