Você está na página 1de 2

HINDUSTHAN URBAN INFRASTRUCTURE LIMITED

Kanchenjunga(7th Floor) 18, Barakhamba Road, New Delhi-110 001.


Tel.011 23310001(5 Lines) Fax: 011-23313707 Email: hvplndl@hindusthanvidyut.com
Website: www.hindusthanvidyut.com.
SCHEDULE-V
GUARANTEED TECHNICAL AND OTHER PARTICULARS OF ACSR ZEBRA

SL
NO.
1.

DESCRIPTION
Manufacturers Name and address

Page 1 of 2
ACSR ZEBRA
(54/3.18 mm Al. + 7/3.18 mm St.)
HINDUSTHAN VIDYUT PRODUCTS LTD.
FARIDABAD : 12/1, Delhi Mathura Road,
Faridabad (Haryana)
GWALIOR

2.
3.

4.
5.

6.
7.
8.
9.

10.
11.

12.
13.

14.

Type of industry (Small / Medium / Large scale) with their


Registration No.
Stranding and nominal wire diameter in mm
a) Aluminium
b) Steel
Nominal Aluminium area in sq mm
Sectional area in sq mm
a) Aluminium Strand
b) Steel Strand
c) Conductor
Overall diameter (approx) of conductor in mm
i) Density of hard drawn aluminium at 20C in g/cm3
ii) Density of galvanized steel wire at 20C in g/cm3
Approximate calculated breaking load of conductor in KN
Minimum breaking load in KN for:
a) Aluminium Strand
i)
Before stranding
ii)
After stranding
b) Steel Strand
i)
Before stranding
ii)
After stranding
Purity of aluminium rods
Zinc coating of steel strand (values before stranding)
a) Uniformity of coating, number and duration of dips
(Preece test)
i)
Number of dips one min.
ii)
Number of dips half min.
b) Minimum weight of coating in gms/m2
Maximum working tension in KN
Mass in Kg. per Km (Approx.)
a) Aluminium
b) Steel
c) Conductor
Resistance in ohms/Km at 20C
i) Aluminium wire
ii) Complete conductor

: Industrial area, P.O. Birla Nagar,


Gwalior.

GUWAHATI : 1C, Brahmaputra Industrial Park,


Vill. Sila Sinduri Ghopa, North
Guwahati, Dist. Kamrup, Assam.
Refer our offer

54/3.18 mm
7/3.18 mm
420 Sq mm
7.938 Sq mm
7.938 Sq mm
484.5 Sq mm
28.62 mm
2.703
7.80
130.32

1.29
1.23
10.43
9.91
99.5 % Min.

3
-250
75% of UTS
1186
435
1621
3.626
0.06868
Page 2 of 2

SL
NO.
15.

16.

17.
18.
19.
20.
21.

22.
23.
24.
25.
26.

27.
28.

DESCRIPTION
Modulus of Elasticity in GN/M2
a) Aluminium
b) Steel
c) Conductor
Co-efficient of Linear Expansion per degree centigrade of
a) Aluminium
b) Steel
c) Conductor
Percentage of carbon in steel wire rods
Standard length of each piece
Tolerance on standard length, if any.
No. of standard length in one reel
Dimensions of the reel in mm
i) Flange dia
ii) Traverse
iii) Barrel dia
Net weight of the conductor in one reel in Kg. (Approx.)
Tare weight of the reel in Kg. (Approx.)
Gross weight of the reel including weight of the conductor
(Approx.)
Standard according to which the conductor will be
manufactured and tested
Method of jointing in Aluminium wires (Only cold pressure
butt welding is permitted as per clause no. 8.1 of section
3 of our specification).
Packing details
Other particulars, if any.
i)
Short length
ii)

Note:

ACSR ZEBRA
(54/3.18 mm Al. + 7/3.18 mm St.)

Order Qty.tolerance

69
193
69
23 x 10-6
11.5 x 10-6
19.3 x 10-8
0.50 to 0.85
1100 m
5%
One
1550
710
600
1783
300
2083
IS: 398 (Part-2) 1996
Yes by cold pressure butt welding

On wooden drum as per IS: 1778


Up to 10% of order quantity, no length less then
50% of standard length
5%

These technical particulars submitted above are subjected to tolerances given in the relevant Specification as