Você está na página 1de 7

Anchor Bolts Design Calculation for Equipment Foundations of

CB-DS-CT-VT-SA & LT

1
0
Rev.

3/11/2015
22/10/2015
Date

Project:

Revised with correct loading


Issued for Approval
Description

M.M.K
M.M.K
Prepared

M. Rafique
M. Rafique
Approved By

132kV GRID STATION AT CHITRAL - GOLEN GOL HYDROPOWER PROJECT - (LOT-4)


PACKAGE-1

Project Number:

Client:

GGHP - (LOT-4) PACKAGE-1


Prepared:

Date:

M.M.Khurram
Approved By:

22/10/2015
Date:

M. Rafique
Calculation Document for Drawings:

NTT-GOL-CHT-031
NTT-GOL-CHT-032
NTT-GOL-CHT-033
NTT-GOL-CHT-034
NTT-GOL-CHT-036

Format:

Water and Power Development


Authority (WAPDA)
Consultant

22/10/2015

7
Lang.

Fichtner-PES-DMC-BAK
Project:

A4
Page

eng
Revision:

1
Issued Date

22/10/2015

GOLEN GOL

132kV AIS Chitral Grid Station

132kV GRID STATION AT CHITRAL - GOLEN GOL HYDROPOWER PROJECT


(LOT-4) PACKAGE-1

Design Loads for Anchor Bolt of Equipment Foundations


(CT-VT-SA-DS & LT)
Loads for DS-DSE for the design of Anchor Bolt
OutputCase

Global FX Global FY Global FZ


KN
KN
KN
DEAD
0.00
0.00
1.99
Live
5.00
2.00
9.00
W45
2.46
2.46
0.00
W0
1.93
0.00
0.00
EQX
1.13
0.00
0.00
EQY
0.00
1.13
0.00
Factored Load (1.2D+1.6L+0.8W)
9.97
5.17
16.79

Global MX
KN-m
0.00
1.72
1.63
0.02
0.01
0.93
4.06

Global MY
KN-m
0.00
4.46
1.72
1.23
0.96
0.00
8.51

Loads for CT - VT - SA - LT (Line Trap) for the design of Anchor Bolt


OutputCase

Global FX Global FY Global FZ


KN
KN
KN
DEAD
0.00
0.00
1.45
Live
3.00
4.00
7.60
W45
1.77
1.77
0.00
W0
1.78
0.00
0.00
EQX
0.52
0.00
0.00
EQY
0.00
0.52
0.00
Factored Load (1.2D+1.6L+0.8W)
6.21
7.81
13.90

Global MX
KN-m
0.00
3.08
0.84
0.02
0.00
0.34
5.60

Global MY
KN-m
0.00
2.69
0.97
0.97
0.38
0.00
5.07

Design Loading Maximum Taken from DS-DSE


Loading for one anchor bolt group c/c 400mm
Fz
Fx
Fy
Mx
kN
kN
kN
kN
16.79
9.97
5.17
4.06
M
VR
kN
kN
9.43
11.23

My
kN
8.51
TR
kN
16.67

NETRACON Technologies

132kV AIS Chitral Grid Station

GOLEN GOL

132kV GRID STATION AT CHITRAL - GOLEN GOL HYDROPOWER PROJECT


(LOT-4) PACKAGE-1
Design Calculations for Anchor Bolt of Equipment Foundations
(CT-VT-SA-LT & DS)
With Maximum Loading of DS
Description
1. Load on Bolt

Symbol

Tensile Load
Shear
Fu
Fy
No. of Bolt in one Pedestal
No. of Bolt in Tension
Spacing of Bolt
Dia of Bolt
Effective Length of Bolt

Nu
Vu
Fu
Fy
Nt
N

Formulae

F-1554-A36

S
db
h eff. Pro.

Value

Units

16.67
kN
11.23
kN
400
Mpa
250
Mpa
4
No.
1
No.
Due to Biaxial Bending
400
mm
30
mm
600
mm

2. Concrete Data
fc'
Fy Rebars
Pedestal Size
Edge Distance
Vertical Steel in Pedestal
Area of #6 Bar

fc'
Fy
L
W
C1
C2
d reb.
A reb.

21
280
700
700
150
150

Mpa
Mpa
mm
mm
mm
mm

284

mm2

3.14/4*(30-24.75/7)^2

550

mm2

v
T Nsa

N*t*As eff.*Fu

0.75
0.65
165

v Vsa

v*T Nsa

107.3

12 - #6

3. Calculation
3.1. Tensile Strength
Effective area of Bolt

As eff.
Thread per inch 7
T

Total Strength of Bolts in Tension

kN
>Nu Strength is Ok

3.2. Shear Strength


Total Bolt Strength in Shear
Aps

kN
>Vu Strength is Ok

3.3. Shear and Tension Interaction


0.2*T Nsa
Nu
0.2*v Vsa
Vu
0.2*T Nsa
0.2*v Vsa
Check Interaction Equation

33
kN
16.6700424
kN
21.46
kN
11.23
kN
> Nu
Full tension design is permitted
> Vu
Full Shear design is permitted
So Interaction Equation is not valid
Nu/T Nsa+Vu/v Vsa <1.2
1.03
< 1.2 Ok

NETRACON Technologies

132kV AIS Chitral Grid Station

GOLEN GOL

132kV GRID STATION AT CHITRAL - GOLEN GOL HYDROPOWER PROJECT


(LOT-4) PACKAGE-1
Design Calculations for Anchor Bolt of Equipment Foundations
(CT-VT-SA-LT & DS)
With Maximum Loading of DS
Description
3.4. Length Of Bolt
heff. Min.

Symbol

Formulae

Value

Units

h eff.
Y

12*d(fu/58 Y) ^0.5
6.89 for fu in Mpa

360.17

mm
>heff. Pro. is Ok

60
60
2893.5
486.108
364.581

mm
mm
mm2
kN
kN
>Nu Strength is Ok

3.5. Pullout Resistance of Bottom Plate


Use Plate Thickness 8mm
Bearing Area
Pullout Resistance of Bolt in tension

W
L
Abrg
Np
Np

W*L - 3.14/4*db
Y*8*Abrg*fc'*N

364.581

NETRACON Technologies

GOLEN GOL

132kV AIS Chitral Grid Station

132kV GRID STATION AT CHITRAL - GOLEN GOL HYDROPOWER


PROJECT - (LOT-4) PACKAGE-1
Design Loads for Anchor Bolt of Equipment Foundations
(CB)
Loads for CB for the design of Anchor Bolt
kN'
Self Weight of equipment per Pole
Fz

14.00

Fx
Fz

4.00
20.00

Mechanical Terminal Load

Wind Load
Wx
Wy
Global FX Global FY Global FZ
KN
KN
KN
Factored Load (1.2D+1.6L+0.8W)
8.64
1.52
48.80

2.80
1.90
VR
KN
8.77

NETRACON Technologies

132kV AIS Chitral Grid Station

GOLEN GOL

132kV GRID STATION AT CHITRAL - GOLEN GOL HYDROPOWER PROJECT


(LOT-4) PACKAGE-1
Design Calculations for Anchor Bolt of Equipment Foundations
(CB)
Description
1. Load on Bolt

Symbol

Tensile Load
Shear
Fu
Fy
No. of Bolt in one Pedestal
No. of Bolt in Tension
Spacing of Bolt
Dia of Bolt
Effective Length of Bolt

Nu
Vu
Fu
Fy
Nt
N

Formulae

F-1554-A36

S
db
h eff. Pro.

Value

Units

48.80
8.77
400
250
4
2
No Biaxial Bending
400
30
600

kN
kN
Mpa
Mpa
No.
No.
mm
mm
mm

2. Concrete Data
fc'
Fy Rebars
Pedestal Size
Edge Distance
Vertical Steel in Pedestal
Area of #6 Bar

fc'
Fy
L
W
C1
C2
d reb.
A reb.

21
280
700
700
150
150

Mpa
Mpa
mm
mm
mm
mm

284

mm2

3.14/4*(30-24.75/7)^2

550

mm2

v
T Nsa

N*t*As eff.*Fu

0.75
0.65
330

v Vsa

v*T Nsa

214.5

12 - #6

3. Calculation
3.1. Tensile Strength
Effective area of Bolt

As eff.
Thread per inch 7
T

Total Strength of Bolts in Tension

kN
>Nu Strength is Ok

3.2. Shear Strength


Total Bolt Strength in Shear
Aps

kN
>Vu Strength is Ok

3.3. Shear and Tension Interaction


0.2*T Nsa
Nu
0.2*v Vsa
Vu
0.2*T Nsa
0.2*v Vsa
Check Interaction Equation

66
kN
48.8
kN
42.9
kN
8.77
kN
> Nu
Full tension design is permitted
> Vu
Full Shear design is permitted
So Interaction Equation is not valid
Nu/T Nsa+Vu/v Vsa <1.2
0.94
< 1.2 Ok

3.4. Length Of Bolt


heff. Min.

h eff.
Y

12*d(fu/58 Y) ^0.5
6.89 for fu in Mpa

360.17

mm
>heff. Pro. is Ok

NETRACON Technologies

132kV AIS Chitral Grid Station

GOLEN GOL

132kV GRID STATION AT CHITRAL - GOLEN GOL HYDROPOWER PROJECT


(LOT-4) PACKAGE-1
Design Calculations for Anchor Bolt of Equipment Foundations
(CB)
Description
Symbol
3.5. Pullout Resistance of Bottom Plate
Use Plate Thickness 8mm
Bearing Area
Pullout Resistance of Bolt in tension

W
L
Abrg
Np
Np

Formulae

Value

Units

W*L - 3.14/4*db

60
60
2893.5
972.216
364.581

mm
mm
mm2
kN
kN
>Nu Strength is Ok

Y*8*Abrg*fc'*N

364.581

NETRACON Technologies

Você também pode gostar