STANDARD FEATURES
Casing Flatform
The casing is built on a framework of extruded Aluminum profiles assembled by
means of insertion joints sturdy nylon corner pieces. This makes assembly much
easier and allows to place the air handling units in locations that could not be
considered before.
Slope design for drain pan with galvanized sheet to prevent standing water and
minimize microbial growth can meet challenging indoor air quality (IAQ), controls, and
acoustic (sound sensitive) projects.

AIR HANDLING
2,500 m3/hr ...
65,000 m3/hr

Panels
3
25 mm double wall high density (45 kg/m ) panels manufactured by injecting
polyurethane foam between two metal sheet. Exterior wall shall be fabricated from
0.5 mm pre-painted galvanized sheet and factory applied protection film.
Panels assembled with mechanical fasteners such that each panel is individually
removable. Access door are completed constructed with the same material as casing
panels shall permit a complete 180o swing at nylon reinforced door hinge.

Fans
All units equipped with High Performance double inlet centrifugal fans with scaling in
accordance to AMCA Standard for maximum performance.
The following fan types are available :
3
3
Forward Curved blade Fans : Volume flow from 200 m /h to 140,000 m /h
Total pressure up to 1,000 Pa
Backward Curved blade Fans : Volume flow from 200 m3/h to 110,000 m3/h
Total pressure up to 2,000 Pa
Electric Motor
Factory furnished and installed 3-phase Asynchronous Induction Motor fan motors
shall be mounted inside the unit. The Motors are totally enclosed fan cooled (TEFC)
type with 380Volts, 3 Phase, 50 Hz electrical supply, class F Insulation and IP 54
Degree of Protection. Other specification motors are available on Request.
Fan and Motor Base are made of painted heavy gauge galvanized steel to ensure
proper installation.

FE
M

ADE IN

Coils
Designed, manufactured and tested by AICOOL. Chilled Water Coil are aluminum
finned copper tube that have galvanized steel casing end plate, copper tubes header
with male threaded connections. Mechanically expanded copper tubes on aluminum
fin construction with die-formed spacer collars for uniform spacing and leak tested to
a minimum 450 psig air pressure under water. Completed with manual air vent plug
for all water coils.
Evaporator (DX) coils and heating coils are an options.

Chilled Water or Direct Expansion

DO

BEST
PERFORMANCE

NES

Every Cooling Solution... We Have It

AICOOL

reserves the right to change in specifications without prior notice

SPECIFICATION DATA
AIR HANDLING UNIT
FE 01

FE 02

FE 03

FE 04

FE 05

FE 06

FE 07

FE 08

FE 09

FE 10

@2.0 m/s CMH


(400 FPM) CFM

2,925

4,175

5,427

10,791

16,304

18,115

21,181

27,525

30,784

46,246

1,722

2,458

3,196

6,354

9,600

10,667

12,467

16,207

18,127

27,231

@2.3 m/s CMH


(450 FPM) CFM

3,291

4,697

6,106

12,140

18,341

20,379

23,829

30,965

34,632

52,027

1,938

2,766

3,595

7,148

10,800

12,000

14,026

18,233

20,392

30,635

@2.5 m/s CMH


(500 FPM) CFM

3,656

5,219

6,784

13,489

20,379

22,644

26,477

34,406

38,480

57,807

2,153

3,073

3,995

7,943

12,000

13,333

15,584

20,259

22,658

34,039

@2.8 m/s CMH


(550 FPM) CFM

4,022

5,741

7,463

14,838

22,417

24,908

29,124

37,846

42,328

63,588

2,368

3,380

4,394

8,737

13,200

14,667

17,142

22,285

24,924

37,443

kW

15

29

42

80

125

138

165

216

246

MBtu/h

52

99

144

275

427

471

564

739

839

333
1,135

kW

23

36

51

98

143

160

187

246

270

MBtu/h

77

123

172

335

489

546

640

840

920

384
1,311

kW

27

41

57

108

165

184

209

271

MBtu/h

90

141

194

369

565

629

712

925

307
1,048

467
1,594

kW

32

48

64

124

189

205

241

MBtu/h

109

163

219

422

644

700

824

315
1,075

353
1,205

519
1,771

Length

mm

1,131

1,131

1,131

1,477

1,477

1,824

2,211

2,211

2,558

2,558

Width
Height

mm

1,090

1,284

1,477

1,824

2,252

2,252

2,599

2,599

2,904

3,679

mm

654

854

1,054

1,160

1,384

1,577

1,577

1,924

1,924

2,352

MODEL

Airflow

4 Rows

Cooling Coil
Capacity*

5 Rows
6 Rows
8 Rows

Basic Unit
Dimension

GUIDE SPECIFICATIONS
* Indoor mounted central station
air handling unit designed to
provide air to a conditioned space
as required to meet specified
performance requirements for
ventilation, heating, cooling and
air distribution.
* Unit shall be assembled for
draw thru application and shall
be arranged to discharge
conditioned air horizontally.
* Unit with a direct expansion
cooling coil shall have capability
to be used in a refrigerant circuit
in conjunction with a field supplied
and matched condensing unit.

*) Nominal Cooling Capacity Conditions: Evaporator Air Inlet Temp. 26.7C / 50%, Airflow @2.5 m/s velocity, Chilled Water Inlet Temp. 6 C; Outlet Temp. 12 C, Fin spacing 2mm (12FPI)
We improve our products continuously, therefore we reserve the right to make modifications without prior notice.

DUCT CONNECTION DATA

Unit
Fan Type

FE 01

FE 02

FE 03

FE 04

FE 05

FE 06

FE 07

FE 08

FE 09

FE 10

225/250

280/315

355/400

450/500

500/560

630

710

800

900

1000

Supply Fan 1

288 x288

361 x361

453 x453

569 x569

638 x638

801 x801

898 x898

Supply Fan 2

322 x322

404 x404

507 x507

638 x638

715 x715

Return

500 x1000

700 x1200

900 x1400 900 x1700 1200 x2100 1400 x2100 1400 x2500 1600 x2500 1600 x2800 2100 x3500

1007 x1007 1130 x1130 1267 x1267


-

The FE series are designed with wide range option functions : Reheat Coil, Higher Class Filter, Integrated Heater, in simple modular form